You are on page 1of 6

BI16-R LATCHING RELAY

LATCHING TRIP RELAY WITH 16 CO FAST


CONTACTS

APPLICATIONS MAIN FEATURES


> Trip and lockout relay with very fast pickup time > 16 CO/SPDT heavy duty contacts
> Safety locking with high request in number of > Tested individually
contacts
> Wide range of temperature.
> Stable selectors with memory independent from
> Wide range of voltage variation
the auxiliary supply (AUT/MAN)
> Self-cleaning contacts for polluted
> Safety milestone in safety flows or sequences
environments.
> Safety milestone in safety flows or sequences
> High breaking capacity
> Galvanic isolation between the control system
> LDL models (low duty loads)
and the primary equipment
> Long lasting low resistance contacts.
> High galvanic isolation between contacts
> According to the most demanding test
> Critical process surveillance
standards: IEC, EN, IEEE, and bearing the CE
mark.

Substations: OPTIONS
> Transformer lockout (86). > Reset Inhibitor available upon request
> Sequencer in tap changers. > Manual reset pushbutton available upon request
> Security loops. > LDL contacts available
> Alarm signaling with recognition.

1 www.arteche.com
V1.0

LATCHING RELAYS
TECHNICAL SPECIFICATIONS

Construction Characteristics
Applications Power source independent lockout
Contacts 16 Changeover contacts

Connections

Weight (g) 1400


Dimensions (mm) 120x110x105

Electrical Characteristics
Standard voltages 24, 48, 72, 110, 125, 220 Vdc/Vac (50/60Hz)
Voltage range -20% +10% Un
Coil characteristics Pick-up / release voltage See pick-up/release voltage-temperature curves
Average consumptions in the
<108 W
changeover
Operating times Pick-up time < 10 ms
Contact material AgNi
≤ 30 mΩ
Contacts resistance
(15 m LDL range)
Distance between contacts 1,8 mm
Permanent current 10 A
Contacts
Instantaneous current 30 A 1s. 80 A 200 ms 200 A 10 ms.
Max. making capacity 40A, 0,5s, 110Vdc | 30A, 1s, 36Vdc, | 30.000 operations (1op/15s)
Breaking capacity *See figures
Max. breaking capacity 100.000 operations
Umax opened contact 250 Vdc / 400 Vac
Dielectric strength 2 kV. 50Hz. 1 min
Impulse voltage 5 kV. 0,5 J. 1,2/50 µs
Insulation resistance 500 Vdc.; > 100MW

Endurance characteristics
Mechanical endurance 1*107 operations

2 www.arteche.com
V1.0

LATCHING RELAYS
Other Standard Compliance
Vibration and 60255-21-1 Class 2
shock Stress
during operation 60255-21-2 Class 1

Vibration and 60255-21-1 Class 2


shock Stress
during transport 60255-21-2 Class 1

Common mode: 2,5kV, 1MHz and


High frequency 1MHz burst disturbance 100kHz
IEC 61000-4-18 (2006) + A1 (2010)
test
Differential mode: 1kV, 1MHz and
100kHz
Common mode: 4 kV, 5kHz, 1min
Electrical Fast transient EN 61000-4-4
Differential mode: 2 kV, 5kHz, 1min
Common mode: 2kV 1,2/50µs.
(voltage) | 8/20µs. (current)
Surge EN 61000-4-5
Differential mode: 1kV 1,2/50µs.
Emc Immunity (voltage) | 8/20µs. (current)
80-1000MHz, 10V/m, 80% AM
Radiated electromagnetic field EN 61000-4-3
(1kHz)
900±5MHz, 10V/m, 50% (200Hz) |
Digital telephones radiated
EN 61000-4-3 1.89GHz±10MHz, 10V/m, 50%
electromagnetic field
(200Hz).
Conducted disturbances induced by radio
EN 61000-4-6 0.15-80MHz, 10V, 80% AM (1kHz)
frequency fields
Electrostatic discharges EN 61000-4-2 Contact ±15 kV | Air mode ±15 kV
Magnetic fields at power frequency EN 61000-4-8 100 A/m 1min. | 1000 A/m 1s.
Cover: 30Mhz-1GHz Group 1 class
A | Power supply: 0.15-0.5 MHz,
79dB(µV) (quasi peak) /
EMC emissions Radio disturbance CISPR 11, CISPR22
66dB(average) |0.5-30 MHz,
73dB(µV) (quasi peak) / 60dB
(average)
Maximum ambient T, 10A through
Maximum temperature in the relay parts EN 61810-7 all the contacts. Time until thermal
stability
Thermal test
Maximum ambient T, Vmax, 10A
Thermal Endurance EN 61810-7 through all the contacts. 1.000
hours
Cold test EN 60068-2-1 (Test Ab) - 40˚C, 96 hours
Dry heat test EN 60068-2-2 (Test Bd) 70˚C, 96 hours
Environmental
Sudden changes of temperature EN 60068-2-14 (Test Na) TA =-40˚C; TB = +70˚C
Tests
Damp heat test (Cyclic) EN 60068-2-30 (Test Dd) 55˚C, 6 cycles
Damp heat, steady state EN 60068-2-78 (Test Cab) 40˚C, 93% Rh, 56 days
EB2: High burden models
Functional Tests Immunity to capacitive discharges ESI 48-4 (Discharge of capacitor 10µF; 120%
Vrated; no pick-up current: 50mA)
Protection Degree IP4X
Operating altitude <2000 m

3 www.arteche.com
V1.0

LATCHING RELAYS
BREAKING CAPACITY CURVES
The breaking capacity is a critical parameter on the design and the application of the relay. Its mechanical life could be
considerably reduced, depending on the value of the load (especially with heavy duty loads), the number of operations
and the environmental conditions in which the relay is operating.

48 Vdc 125Vdc
Resistive load:
L/R = 0 ms
Inductive load:
L/R = 20 ms
Highly inductive load:
L/R = 40 ms

4 www.arteche.com
V1.0

LATCHING RELAYS
PICK-UP & RELEASE VOLTAGE-TEMPERATURE CHARTS

RELAY DIMENSIONS

5 www.arteche.com
V1.0

LATCHING RELAYS
SOCKETS AND RETAINING CLIP
The dimensional and format of the sockets for the relay BI16-R are “I” type. Please refer to the document
“MU_BASES_RELES_EN” for further and more precise details.
The list of sockets & clips available for this model are:

Sockets

I DE

I TR -

I EMP TR -

Clips
This model is screwed to the socket, so does not have retaining clips
-
available

OPTIONS FOR THIS RELAY

This relay must be ordered indicating the following options


Reference Pushbutton IR option Coil Rated Voltage LDL Option
BI16-R --/P --/IR 125 Vdc --/LDL