Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
1
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
2
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
3
constant and its voltage magnitude at 1 p.u.. PV buses are as- compared to existing power flow studies that have only con-
sumed to keep its real power and voltage magnitude at its rating sidered the topology of one ac and one dc subgrid. The pro-
whereas PQ buses are assumed to always demand or supply the posed method takes into account all the unique characteristics
same amount of real and reactive power. However, islanded of an islanded hybrid microgrid: bidirectional power flow, the
microgrids do not have a single slack bus, as DGs are usually absence of slack bus, and droop-controlled DGs. Lastly, the
insufficient to act as an infinite power source [11]–[14]. algorithm is based on the well-known NR method which is
Therefore, islanded microgrids often deploy a droop mecha- efficient and easy to implement.
nism as a primary control in the load sharing among DGs [15]. The rest of the paper is organized as follows. Section II de-
Droop control adjusts the voltage and frequency reference tails the modeling of the DGs and loads whereas Section III
points depending on the real and reactive power output of the details the IC model. Section IV explains the proposed power
DGs [16]. Thus, the frequency is not constant and is one of the flow algorithm. Section V shows the implementation and val-
state variables to be solved for in the power flow. idation of the algorithm. In section VI, the proposed method’s
Although significant work has been carried out to solve the advantages, computation time, and normalized frequency and
power flow of islanded microgrids, they are usually limited to dc voltage are discussed. Section VII describes conclusions and
ac microgrids only [12]–[14], [17]–[21]. Different methods future avenues of study.
have been proposed such as a branch-based method in [17] or
the backward-forward sweep in [18] which were designed II. SYSTEM MODELING
specifically for radial, distribution-level microgrid. In [19], a The modeling of a microgrid, both ac and dc, is indispensa-
power flow method using virtual impedance that was generic ble in power flow analysis. This section discusses the modeling
enough to be applied on ac or dc subgrid was presented. To of ac microgrid line impedance as a function of frequency, ZIP
solve three-phase power flow of an unbalanced microgrid, the model of the ac loads and different dc load models, as well as
authors in [12] modelled the power balance equations as an the modeling of both ac and dc DG droop characteristics.
optimization problem to be solved using Newton-Trust-Region
(NTR). An optimization model was also deployed in [14] to A. Line Impedance Modeling
select the droop parameters. In [20], a load flow based approach For an ac network with N buses, Ybus is a 𝑁 𝑥 𝑁 nodal ad-
was proposed to achieve voltage security in ac islanded mi- mittance matrix for the network. Unlike a system with a stiff
crogrids. Modifications on the well-known Newton-Raphson grid, the frequency in islanded microgrids is not constant and
method was the basis to solve the power flow in [13] and [21]. therefore neither is the line reactance, as it is a function of
In [21], the proposed method efficiently incorporates the DGs frequency. When constructing the bus admittance matrix for the
droop control in the Jacobian matrix to keep the matrix size and calculation, this must be taken into account. Therefore, the
computation time to minimum. admittance matrix is also a function of frequency, as shown in
Only very few literatures proposed a method to solve ac/dc (1).
power flow of islanded hybrid microgrids [22], [23]. Although
jθij (ω )
∑ j ≠ i Z ij−1 (ω ) ∀i =j
ac/dc power flow is not a new topic, to date it is only discussed = Yij (ω ) Y=
ij ( ω ) e (1)
− Z ij (ω )
−1
for HVDC systems [24]–[27]. In [22], the authors performed ∀i ≠ j
the ac and dc power flow in sequence using NR whereas in where Zij(ω) = Rij + jXij(ω) is the line impedance between buses
[23], the power flows were executed simultaneously using i and j.
NTR. In both methods, there is a coupling between ac subgrid
B. Load Modeling
frequency and dc subgrid bus voltage. The coupling was in-
troduced as a way to achieve power balance between the ac and In general, an ac load can be represented using the composite
dc subgrid. When one subgrid is loaded more than the other, the load model which has both static and dynamic load character-
other subgrid can transfer its power to support the overloaded istics. Static load model expresses the instantaneous real and
subgrid. reactive powers as functions of frequency and the bus voltage
Building on the research results in [21]–[23], this paper magnitude at that instant [28]. For steady-state power flow
proposes an algorithm for islanded microgrids that solves the ac study, static model is commonly used [29]. The ZIP or poly-
and dc power flow simultaneously – which saves iteration and nomial load model represents ac loads as a combination of
computation time compared to separate or sequential methods. constant impedance, constant current and constant power by
Further, in contrast to [22] where the ac/dc coupling was set in a assigning the ZIP coefficients accordingly [30]. The sum of Zp,
way that the frequency always matches the dc voltage (thus, Ip, Pp for each load bus must equal 1 and likewise for Zq, Iq, Pq.
always achieving equal power sharing between the ac and dc The load might also be dependent on the frequency and this is
subgrids), this paper deploys a droop mechanism to control the represented by the constants kpw and kqw, ranging from 0 to 2
amount of power transferred between the subgrids through the and from -2 to 0, respectively [12], [21].
IC droop gain. In this way, power system designers have more Vac ,i
2
V
flexibility in the control of the power transfer. It also enables =PLac ,i PLac ,i Z p ,i 0 + I p ,i ac0 ,i + Pp ,i
0
the connection of more than one ac or dc subgrids – which Vac ,i Vac ,i (2)
1 + k pw,i (ω − ω )
makes the algorithm generic, regardless of the network con- 0
figuration. This is the main advantage of the proposed method,
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
4
2
V III. INTERLINKING CONVERTER (IC) MODELING
QLac ,i = 0
QLac Z Vac ,i + I q ,i ac0 ,i + Pq ,i
,i q , i
0 (3) An interlinking converter can act as a slack bus to ac subgrid
Vac ,i Vac ,i to provide a stable frequency and voltage [2] or it may act as a
1 + k
(
qw,i ω − ω
0
) voltage source for the dc subgrid [15]. In hybrid microgrids
where neither the ac nor the dc subgrid is hierarchically higher
The dc loads can similarly be modeled with a constant re- than the other, the IC has the control over the power transferred
sistance, constant current or constant power model. Loads with between the subgrids to achieve balanced power sharing of the
constant resistance can be directly incorporated into the system system demands. In order to do so, there has to be a method
conductance matrix as shunt resistances. Most dc loads, how- correlating the loading in the ac and dc subgrids [32], [33].
ever, employ power electronic-based converters when they are
connected to the grid. These converters are normally regulated A. AC-DC Coupling
tightly, thus, the loads can be modeled as constant power loads The ac and dc subgrid can only exchange real power. As
[3], [31]. Loads with constant power and constant current are mentioned above, the ac real power is a function of frequency
modeled as follows: while the dc real power is a function of voltage. Because of the
P=
Ldc , k
0
PLdc , k + Vdc , k I dc , k
0
(4) different scales, ac frequency and dc bus voltage can be com-
When the load is not a function of voltage and frequency, it pared using the normalized values [22], [23], [32], [33]. The
draws its nominal power. For generalization purposes, every normalized ac frequency and dc bus voltage c ϵ BIC are calcu-
bus in the ac grid is assigned the term PLac,i and QLac,i or the term lated with (11) and (12). The governing equations are given
PLdc,k is utilized for the dc grid. When the bus is not connected below:
to a load, naturally these terms have zero values. ω − 0.5 (ωmax + ωmin )
ωˆ = (11)
0.5 (ωmax − ωmin )
C. Distributed Generation Modeling
In grid-connected ac microgrids, DGs are usually controlled Vdc , c − 0.5 (Vdcmax
, c + Vdc , c )
min
= Vˆdc , c , ∀c ∈ B IC (12)
as PV or PQ buses, instead of slack buses due to their relatively 0.5 (Vdcmax
, c − Vdc , c )
min
( )
ferred through the IC is inversely proportional to the droop
QGac ,i = QGac0
, i + k qac , i VGac , i − Vac , i
0
(6) gain. IC droop gain represents the sensitivity of a subgrid to the
PGdc , k =+ 0
PGdc ,k k pdc , k VGdc 0
(, k − Vdc , k (7) )
changes in the bus voltage-and-frequency deviation, or in other
words, to the overloading or under-loading condition of the
When the DGs operate in PQ mode, their power equals to their other subgrids. The difference between the normalized fre-
nominal power. quency and the dc bus voltage, Δe, can be fed to a PI controller
The droop constants of the DGs can be chosen to keep the which will always try to minimize this difference. The amount
frequency and voltage within the limits [3], [22] and are ex- of power injected by the IC is given by the output of the PI
pressed as follows: controller and governed by (13). The IC droop constant, kIC, is
max
PGac the inverse of the proportional gain. It determines the amount of
k pac ,i = ,i
(8)
ωmax − ωmin power transferred between the ac and dc side based on the
max
difference between the normalized frequency on the ac side and
QGac
kqac ,i = max ,i
(9) dc voltage on the dc side. In Fig. 1 below, when ∆e is positive
Vac ,i − Vacmin ,i � is larger than V
(ω � dc ), power is transferred from ac grid to dc
P max grid, thus the real power injected by the IC to the dc grid, PICdc,
k pdc , k = maxGdc , k min (10) is positive.
V −Vdc , k dc , k
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
5
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
6
dc grid and hence, are essential in solving the power flow. The After the proposed method is validated, it can be applied to
power-balance equations for the IC buses c ϵ BIC and the Jaco- various case studies to show its effectiveness and versatility.
bian matrix are given in the Appendix.
B. Multi-DC Subgrids
In the initial calculation of the power mismatches, the IC real
and reactive power is taken as zero. After forming the Jacobian This case study is used to demonstrate the power transfer
matrices and solving (28), the ac and dc bus voltage magni- from dc to ac using the ac-dc coupling presented above and the
tudes, ac system frequency, and bus voltage angles are updated. power sharing between two dc subgrids, controlled by the ICs.
With these updated variables, the injected power at each bus is In the multi-dc subgrids test system given in Fig. 3, two dc
calculated as well as the normalized frequency and dc bus subgrids with identical IC droop constants are connected to the
voltage magnitudes. Lastly, the power mismatch equations are 6-bus ac subgrid from Fig. 2. Identical IC droop constants were
updated. This process continues until the mismatch is smaller chosen to display how the power sharing among the subgrids is
than the predefined limit. determined by the difference between the ac frequency and the
dc bus voltages. DC subgrid 1 is connected to ac bus 2 whereas
V. CASE STUDIES dc subgrid 2 is connected to ac bus 4. The loads in dc subgrid 1
are chosen arbitrarily to be half of those in dc subgrid 2. Since
A. Single Subgrids the ac frequency and IC droop gains are identical for both dc
To validate the proposed unified approach, a simulation subgrids, the only difference between them is the bus voltage,
study was performed by comparing simulation results from the as shown in Table II.
implemented algorithm and steady-state values from a
time-domain simulation in PSCAD/EMTDC. The method was
applied on a hybrid microgrid consisting of a single ac and
single dc subgrid interlinked with one IC as given in Fig. 2. The
subgrids are a modification of the test systems used in [37] and
[38]. In both subgrids, there are droop-controlled DGs and
variable-controlled loads. The droop constant of the IC can be
calculated from
ωˆ − ωˆ
k IC , c = max max min (29)
PIC , c
where 𝜔�𝑚𝑎𝑥 and 𝜔 �𝑚𝑖𝑛 are the maximum and minimum nor-
malized frequency or 1 and -1, respectively. This results in kIC =
0.0015. In this test system, the IC maximum capacity equals to
the maximum capacity of the smallest DG, which is the ac DG. Fig. 3. Multi-bus ac subgrid with two dc subgrids test system.
The IC reactive power droop gain kqIC is chosen to be the in-
verse of the kqac of the ac DGs (9.1924 x 10-4 V/Var). The sys- The power transferred from dc subgrid 1 to the ac subgrid is
tem parameters are given in the Appendix A. Table I shows the larger than that from dc subgrid 2 despite the same frequency
voltage magnitude, angle, active and reactive power flow of and IC droop constant. This is because dc subgrid 1 has lower
each ac and dc bus. The base power is 1 kW. From Table I, it demands which result in higher bus voltages. Table II shows
can be seen that the simulation results of the unified approach that the bus voltages in dc subgrid 1 are higher than those in dc
agree with the results obtained from time-domain simulation subgrid 2. The power outputs from the ac DGs are no longer
using PSCAD/EMTDC. identical although the DGs are identical because ac bus 4 now
receives power from dc subgrid 2.
C. Multi-AC Subgrids
As a multi-terminal HVDC (MTDC) system can connect ac
grids with different frequencies, so can a multi-bus dc subgrid
connect several ac subgrids operating with different frequen-
cies [32]. Because each IC has its own droop curve, equilibrium
can then be achieved between each dc IC bus and its counter-
part ac subgrid. This is demonstrated by a test system consisting
of a 6-bus dc subgrid connecting two identical ac subgrids
based on Fig. 2 as shown in Fig. 4. Similar to the previous case
study, ac subgrids 1 and 2 are connected to dc bus 2 and 4,
respectively. The IC droop gain of ac subgrid 1 is chosen to be
three times that of ac subgrid 2. Although the ac subgrids are
identical, depending on the dc bus voltages and IC droop gains,
Fig. 2. Single-subgrid test system. the two ac subgrids will reach different steady-state frequen-
cies, as shown in Table III.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
7
From Table III, it can be seen that the dc bus 2 and dc bus 4 islanded systems prior to implementing the project. Thus, this
have very similar voltages although bus 4 voltage is slightly paper contributes towards this. Furthermore, as opposed to
higher. However, due to IC 1’s lower droop constant, the power PSCAD, such load flow algorithms, can be easily integrated in
transferred from ac subgrid 1 to dc subgrid is almost three times an optimal power flow framework for optimal planning and
higher than that from ac subgrid 2. This translates to higher operation of microgrids.
demand in ac subgrid 1 which results in lower frequency.
B. Computation Time
As shown in Table I, the proposed method can solve the
power flow in 0.16 s compared to 49.32 s in PSCAD/EMTDC.
The simulations were performed on a desktop running on In-
tel® Core i5-6600 3.30GHz processor with 8GB RAM. The
superiority of the proposed method’s computation time com-
pared to PSCAD is displayed for the other case studies too,
especially with multiple ac subgrids. It should be noted that the
case study with multiple ac subgrids doubled the computation
time in PSCAD but using the proposed algorithm, the compu-
tation time did not increase significantly.
The value of the IC droop constant kIC influences the amount
of power transfer between the ac and dc subgrids. It is worthy to
note that it can also impact the power flow algorithm conver-
Fig. 4. Multi-bus dc subgrid with two ac subgrids test system.
gence time. The more power transferred between the subgrids,
The two case studies discussed above demonstrate the ge- the longer it takes for the algorithm to converge.
nericity of the proposed algorithm. It can easily be expanded to C. Normalized Frequency and DC Voltage
larger systems consisting of several ac subgrids or several dc The IC power is determined by the difference between the
subgrids or even both. normalized frequency and dc voltage. A normalized value in
principle shows the location of a given value, relative to the
VI. DISCUSSION maximum and minimum values. In this case, to fairly compare
A. Simultaneous Power Flow Calculation the normalized frequency and dc voltage, the range of allowa-
ble frequency and dc voltage should be similar. Otherwise, it
The comparison with a time-domain simulation such as will create instability in the algorithm. This can be achieved by
PSCAD/EMTDC was performed to validate the accuracy of the using a per-unit value of the frequency and voltage. A variation
proposed method. However, commercial power flow packages of ±2% in the frequency and ±5% in the voltage is considered
do not solve ac and dc power flow simultaneously. MatACDC sensible and applied in the case studies presented here.
program, running in Matlab, does solve ac and dc power flow of A case study where the ac loading is large enough such that
HVDC transmission system [39]. However, as discussed in the the normalized frequency is below the minimum frequency has
introduction, it only considers unidirectional power flow from also been tested. With 𝜔 � < -1, the algorithm still reached con-
dc sources to the ac grid. The proposed method can solve power vergence with no instability or significant extra computation
flow bidirectionally between the ac and dc subgrids. In time. The power transferred from dc to ac increased accord-
PSCAD/EMTDC simulation, the ac and dc subgrids are mod- ingly but the increment is not straightforward. This is because
eled and calculated separately. To mimic what the proposed the more power demanded from dc subgrid, the lower the dc
method does, the IC is modeled as a frequency-dependent voltages, including at the IC bus, become (in this case, the IC
voltage source to the ac subgrid and as a voltage-dependent acts as a load to the dc subgrid). In this way, the difference
voltage source to the dc subgrid. The frequency and dc voltage between the normalized frequency and dc voltage will never be
governing the voltage sources are taken from the proposed significantly large because one subgrid will follow the change
method’s results. This is the main advantage of this method. in the other subgrid – which is precisely the goal of the power
Load flow algorithms are essential for planning conventional sharing between ac and dc subgrids.
power systems and the same applies to islanded systems. IEEE
Std. 1547.4 states clearly that a load flow needs to be applied to
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
8
TABLE I
VALIDATION RESULTS FOR SINGLE SUBGRIDS TEST SYSTEM
Proposed method PSCAD/EMTDC
Bus
Vac (pu) δ (rad) Vdc (pu) Pac (pu) Q (pu) Pdc (pu) Vac (pu) δ (rad) Vdc (pu) Pac (pu) Q (pu) Pdc (pu)
1 0.9908 0 0.9937 -1.6140 -1.0680 -10.0000 0.9907 0 0.9937 -1.6147 -1.0541 -10.0000
2 0.9936 -0.0002 0.9950 0.0492 0.8876 -0.0492 0.9934 -0.0002 0.9950 0.0513 0.9182 -0.0490
3 0.9884 -0.0061 0.9976 -2.1450 -1.5160 9.4685 0.9881 -0.0060 0.9976 -2.1468 -1.5189 9.4684
4 0.9987 0.0116 0.9962 1.2427 0.1782 15.2327 0.9986 0.0116 0.9962 1.2430 0.1755 15.2326
5 0.9980 0.0053 0.9953 1.2427 0.2746 -7.3000 0.9979 0.0054 0.9953 1.2430 0.2709 -7.3000
6 0.9907 -0.0054 0.9953 1.2427 1.2805 -7.3000 0.9904 -0.0052 0.9953 1.2429 1.3046 -7.3000
PIC (pu) 0.0492 0.0490
Comp. time 0.16 s 49.32 s
TABLE II
VALIDATION RESULTS FOR MULTI-DC SUBGRIDS TEST SYSTEM
Proposed method PSCAD/EMTDC
Bus AC subgrid DC subgrid 1 DC subgrid 2 AC subgrid DC subgrid 1 DC subgrid 2
Vac (pu) δ (rad) Vdc (pu) Vdc (pu) Vac (pu) δ (rad) Vdc (pu) Vdc (pu)
1 0.9910 0 0.9937 0.9968 0.9909 0 0.9937 0.9968
2 0.9937 -0.0003 0.9950 0.9975 0.9936 -0.0002 0.9950 0.9975
3 0.9884 -0.0064 0.9976 0.9988 0.9881 -0.0061 0.9976 0.9988
4 0.9993 0.0119 0.9962 0.9981 0.9992 0.0115 0.9962 0.9981
5 0.9980 0.0052 0.9953 0.9976 0.9979 0.0053 0.9953 0.9976
6 0.9907 -0.0056 0.9953 0.9977 0.9904 -0.0054 0.9953 0.9977
PIC (pu) 0.0478 0.0644 0.0478 0.0644
Comp. time 0.15 s 74.10 s
TABLE III
VALIDATION RESULTS FOR MULTI-AC SUBGRIDS TEST SYSTEM
Proposed method PSCAD/EMTDC
Bus DC AC subgrid 1 AC subgrid 2 DC AC subgrid 1 AC subgrid 2
Vdc (pu) Vac (pu) δ (rad) Vac (pu) δ (rad) Vdc (pu) Vac (pu) δ (rad) Vac (pu) δ (rad)
1 0.9937 0.9908 0 0.9909 0 0.9937 0.9907 0 0.9908 0
2 0.9950 0.9936 -0.0002 0.9937 -0.0001 0.9950 0.9934 -0.0002 0.9936 -0.0001
3 0.9976 0.9884 -0.0061 0.9883 -0.0063 0.9976 0.9881 -0.0060 0.9880 -0.0061
4 0.9962 0.9987 0.0116 0.9987 0.0111 0.9962 0.9986 0.0116 0.9985 0.0112
5 0.9952 0.9980 0.0053 0.9980 0.0053 0.9953 0.9979 0.0054 0.9979 0.0053
6 0.9953 0.9907 -0.0054 0.9907 -0.0056 0.9953 0.9904 -0.0052 0.9903 -0.0054
PIC (pu) 0.0491 0.1634 0.0533 0.1672
f (Hz) 49.9814 49.9820 49.9804 49.981
Comp. time 0.19 s 82.43 s
This is, however, very unlikely to happen because the IC subgrids. This is achieved through the coupling of normalized
droop constant has been chosen to keep the frequency and the ac frequency and dc voltage. The power flow calculation of the
dc voltage within the allowable range, and the power trans- ac and dc subgrids is solved simultaneously by Newton
ferred by the IC is not to exceed its capacity, as shown by (29). Raphson method using a modified Jacobian matrix. The results
The algorithm checks for violation of DG and IC capacities and obtained from the proposed algorithm have been validated
when that happens, sets them as PQ buses with the output using PSCAD/EMTDC. Case studies have been presented to
power set equal to their minimum or maximum rating. demonstrate that the proposed algorithm is effective in solving
ac/dc power flow of hybrid microgrids with several dc subgrids
VII. CONCLUSION or several ac subgrids.
In this paper, a unified ac/dc power flow algorithm for hybrid
microgrids with several ac/dc subgrids is proposed. The method APPENDIX A
considers islanded operation of microgrids where a single slack The elements of the Jacobian matrix in (27) are tabulated
bus is absent and the control over the system frequency and below. Each of the power balance equation is partially derived
voltage level lies primarily on the DGs. The real and reactive with respect to the unknown variables, i.e. the ac and dc bus
power droop mechanism of the DGs as functions of frequency voltage and the frequency denoted by ω. Index c is used for IC
and voltage as well as the dependency of the load on the fre- buses, i for any ac buses (including IC buses, unless mentioned
quency and voltage are presented. A major contribution of this otherwise) and k for any dc buses (including IC buses, unless
paper is the incorporation of the IC droop control which also mentioned otherwise).
controls the power sharing of the system demand among the
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
9
(A.1)
(A.2)
(A.3)
(A.4)
(A.5)
(A.6)
(A.7)
(A.8)
∂Pmis , ac ,c ∂P ∂P ∀i ∈ B ac ≠ B IC
∂Pmis , ac ,i = 0=, mis , ac ,i 0= , mis , ac ,i 0 (A.14)
=−Vac ,iYij cos (δ i − δ j − θ ij ) , ∀j ∈ B ac ≠ i (A.9) ∂V dc , k ∂V dc , k ∂V dc , c
∀k ∈ B dc ≠ B IC
∂Vac , j
∂Qmis , ac ,i
=−Vac ,iYij sin (δ i − δ j − θ ij ) , ∀j ∈ B ac ≠ i (A.15)
∂Yij X ij 2 / ω ∂θ ij X ij / ω Rij ∂Vac , j
= − & = − (A.10)
∂ω ( ) ∂ω ( )
3/ 2 2
Rij 2 + X ij 2 1 + X ij / Rij ∂Qmis , ac ,i
∂δ i
= −Vac ,i ∑ j ≠ i Vac , j Yij cos δ i − δ j − θij , ∀i ∈ B ac ( ) (A.16)
∂Pmis , ac ,i
= Vac ,i ∑ j ≠ i Vac , j Yij sin δ i − δ j − θij
∂δ i
( )
(A.11)
∂Qmis , ac ,i
= Vac ,iVac , j Yij cos (δ i − δ j − θ ij ) , ∀j ∈ B ac ≠ i (A.17)
∂Pmis , ac ,i ∂δ j
= −Vac ,iVac , j Yij sin (δ i − δ j − θ ij ) (A.12)
∂δ j ∂Qmis , ac ,i ∀i ∈ B ac
=0 (A.18)
∂Pmis , ac ,c ∂Vdc , k ∀k ∈ B dc
2
=
( )
(A.13) ∂Pmis , dc , k ∀k ∈ B dc
∂Vdc ,c , c − Vdc , c
k IC ,c Vdcmax min
=0 (A.19)
∂Vac ,i ∀i ∈ B ac
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
10
∂Pmis , dc , c 2 and Simulation in Power Networks, Chichester, UK: John Wiley & Sons,
= , ∀c ∈ B IC (A.20) Ltd, 2004, pp. 93–151.
∂ω k IC , c (ωmax − ωmin ) [9] O. A. Afolabi, W. H. Ali, P. Cofie, J. Fuller, P. Obiomon, and E. S.
Kolawole, “Analysis of the Load Flow Problem in Power System
∂Pmis , dc , k Planning Studies,” no. September, pp. 509–523, 2015.
= 0 ∀k ∈ B dc ≠ B IC (A.21) [10] J. J. Grainger and W. D. Stevenson, Power system analysis, 1st editio.
∂ω New York: McGraw-Hill, 1994.
∂Pmis , dc , k ∀k ∈ B dc [11] M. A. Hassan and M. A. Abido, “Optimal Design of Microgrids in
=0 (A.22) Autonomous and Grid-Connected Modes Using Particle Swarm
∂δ i ∀i ∈ B ac Optimization,” IEEE Trans. Power Electron., vol. 26, no. 3, pp. 755–769,
Mar. 2011.
∂Pmis , dc , k
=−Vdc , k Gkl , ∀l ∈ B dc ≠ k (A.23) [12] M. M. A. Abdelaziz, H. E. Farag, E. F. El-Saadany, and Y. A.-R. I.
∂Vdc ,l Mohamed, “A Novel and Generalized Three-Phase Power Flow
Algorithm for Islanded Microgrids Using a Newton Trust Region
Method,” IEEE Trans. Power Syst., vol. 28, no. 1, pp. 190–201, Feb.
APPENDIX B 2013.
[13] L. Rese, A. S. Costa, and A. S. e Silva, “A modified load flow algorithm
Line and bus data for the 6-bus ac and dc test system is given in for microgrids operating in islanded mode,” in 2013 IEEE PES
Table IV and V. Conference on Innovative Smart Grid Technologies (ISGT Latin
America), 2013, pp. 1–7.
TABLE IV [14] A. Elrayyah, Y. Sozer, and M. E. Elbuluk, “A Novel Load-Flow Analysis
PARAMETERS FOR THE 6-BUS AC TEST SYSTEM for Stable and Optimized Microgrid Operation,” IEEE Trans. Power
Deliv., vol. 29, no. 4, pp. 1709–1717, Aug. 2014.
Three identical DGs (1.6kVA 1-φ, 127V, 50Hz)
[15] X. Lu, J. M. Guerrero, K. Sun, J. C. Vasquez, R. Teodorescu, and L.
kpac = 10638 W/rads-1, kqac = 1087.9 Var/V
Huang, “Hierarchical Control of Parallel AC-DC Converter Interfaces for
Line parameters Load connected to From bus Hybrid Microgrids,” IEEE Trans. Smart Grid, vol. 5, no. 2, pp. 683–692,
From To R (Ω) X (mH) P (kW) Q (kVar) Mar. 2014.
1 2 0.02 0.12732 1.614 1.068 [16] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla,
“Hierarchical Control of Droop-Controlled AC and DC Microgrids—A
2 3 0.06 0.38197 - - General Approach Toward Standardization,” IEEE Trans. Ind. Electron.,
3 6 0.01 0.06366 2.145 1.516 vol. 58, no. 1, pp. 158–172, Jan. 2011.
4 1 0.08 0.50930 - - [17] M. E. Nassar and M. M. A. Salama, “A novel branch-based power flow
5 2 0.04 0.25465 - - algorithm for islanded AC microgrids,” Electr. Power Syst. Res., vol. 146,
pp. 51–62, 2017.
[18] G. Diaz, J. Gomez-Aleixandre, and J. Coto, “Direct Backward/Forward
TABLE V Sweep Algorithm for Solving Load Power Flows in AC Droop-Regulated
PARAMETERS FOR THE 6-BUS DC TEST SYSTEM Microgrids,” IEEE Trans. Smart Grid, vol. 7, no. 5, pp. 2208–2217, Sep.
Two identical DGs (15kW, 400V, kpdc = 10000 W/V) 2016.
[19] C. Li, S. K. Chaudhary, M. Savaghebi, J. C. Vasquez, and J. M. Guerrero,
Line parameters Load connected to From bus “Power Flow Analysis for Low-voltage AC and DC Microgrids
From To
R (Ω) P (kW) Considering Droop Control and Virtual Impedance,” IEEE Trans. Smart
1 2 0.1 10 Grid, no. 99, 2016.
[20] A. C. Z. de Souza, M. Santos, M. Castilla, J. Miret, L. G. de Vicuña, and
2 3 0.2 -
D. Marujo, “Voltage security in AC microgrids: a power flow-based
1 4 0.05 - approach considering droop-controlled inverters,” IET Renew. Power
4 5 0.02 - Gener., vol. 9, no. 8, pp. 954–960, Nov. 2015.
5 6 0.2 7.3 [21] F. Mumtaz, M. H. Syed, M. Al Hosani, and H. H. Zeineldin, “A Novel
6 3 0.05 7.3 Approach to Solve Power Flow for Islanded Microgrids Using Modified
Newton Raphson With Droop Control of DG,” IEEE Trans. Sustain.
Energy, vol. 7, no. 2, pp. 493–503, Apr. 2016.
REFERENCES [22] A. A. Hamad, M. A. Azzouz, and E. F. El Saadany, “A Sequential Power
Flow Algorithm for Islanded Hybrid AC/DC Microgrids,” IEEE Trans.
[1] A. T. Ghareeb, A. A. Mohamed, and O. A. Mohammed, “DC microgrids Power Syst., vol. 31, no. 5, pp. 3961–3970, Sep. 2016.
and distribution systems: An overview,” in 2013 IEEE Power and Energy [23] A. A. Eajal, M. A. Abdelwahed, E. F. El-Saadany, and K. Ponnambalam,
Society General Meeting, 2013, pp. 1–5. “A Unified Approach to the Power Flow Analysis of AC/DC Hybrid
[2] X. Liu, P. Wang, and P. C. Loh, “A hybrid AC/DC microgrid and its Microgrids,” IEEE Trans. Sustain. Energy, vol. 7, no. 3, pp. 1145–1158,
coordination control,” IEEE Trans. Smart Grid, vol. 2, no. 2, pp. 278– Jul. 2016.
286, Jun. 2011. [24] J. Beerten, S. Cole, and R. Belmans, “A sequential AC/DC power flow
[3] N. Eghtedarpour and E. Farjah, “Power Control and Management in a algorithm for networks containing Multi-terminal VSC HVDC systems,”
Hybrid AC/DC Microgrid,” IEEE Trans. Smart Grid, vol. 5, no. 3, pp. in IEEE PES General Meeting, 2010, pp. 1–7.
1494–1505, May 2014. [25] J. Beerten, S. Cole, and R. Belmans, “Generalized Steady-State VSC
[4] E. Unamuno and J. A. Barrena, “Hybrid ac/dc microgrids-Part I: Review MTDC Model for Sequential AC/DC Power Flow Algorithms,” IEEE
and classification of topologies,” Renew. Sustain. Energy Rev., vol. 52, Trans. Power Syst., vol. 27, no. 2, pp. 821–829, May 2012.
pp. 1251–1259, Dec. 2015. [26] W. Wang and M. Barnes, “Power Flow Algorithms for Multi-Terminal
[5] E. Unamuno and J. A. Barrena, “Hybrid ac/dc microgrids-Part II: Review VSC-HVDC With Droop Control,” IEEE Trans. Power Syst., vol. 29, no.
and classification of control strategies,” Renew. Sustain. Energy Rev., vol. 4, pp. 1721–1730, Jul. 2014.
52, pp. 1123–1134, Dec. 2015. [27] M. Baradar and M. Ghandhari, “A Multi-Option Unified Power Flow
[6] “IEEE Guide for Design, Operation, and Integration of Distributed Approach for Hybrid AC/DC Grids Incorporating Multi-Terminal
Resource Island Systems with Electric Power Systems,” IEEE Std VSC-HVDC,” IEEE Trans. Power Syst., vol. 28, no. 3, pp. 2376–2383,
1547.4-2011, pp. 1–54, 2011. Aug. 2013.
[7] J.-H. Teng and C.-Y. Chang, “A novel and fast three-phase load flow for [28] W. Price, “Load representation for dynamic performance analysis (of
unbalanced radial distribution systems,” IEEE Trans. Power Syst., vol. power systems),” IEEE Trans. Power Syst., vol. 8, no. 2, pp. 472–482,
17, no. 4, pp. 1238–1244, Nov. 2002. May 1993.
[8] E. Acha, C. R. Fuerte-Esquivel, H. Ambriz-Pérez, and C. [29] B.-H. Kim, H. Kim, and B. Lee, “Parameter Estimation for the Composite
Angeles-Camacho, “Conventional Power Flow,” in FACTS: Modelling Load Model,” J. Int. Counc. Electr. Eng., vol. 2, no. 2, pp. 215–218, 2012.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2749435, IEEE
Transactions on Smart Grid
11
[30] “Standard load models for power flow and dynamic performance currently an Editor of the IEEE Transactions on Energy Conversion and the
simulation,” IEEE Trans. Power Syst., vol. 10, no. 3, pp. 1302–1313, IEEE Transactions on Smart Grid.
Aug. 1995.
[31] A. M. Rahimi and A. Emadi, “An Analytical Investigation of DC/DC Zhao Yang Dong (M’99-SM’06-F’17) obtained his Ph.D. degree from the
Power Electronic Converters With Constant Power Loads in Vehicular University of Sydney, Australia in 1999. He is now Professor of Energy Sys-
Power Systems,” IEEE Trans. Veh. Technol., vol. 58, no. 6, pp. 2689– tems with the School of Electrical Engineering and Telecommunications,
2702, Jul. 2009. University of New South Wales, Sydney, Australia. He was previously Ausgrid
[32] P. C. Loh, D. Li, Y. K. Chai, and F. Blaabjerg, “Autonomous Operation of Chair and Director of the Center for Intelligent Electricity Networks (CIEN),
Hybrid Microgrid With AC and DC Subgrids,” IEEE Trans. Power The University of Newcastle, Australia, and is now a conjoint professor there.
Electron., vol. 28, no. 5, pp. 2214–2223, May 2013. He also held academic and industrial positions with the The University of
[33] P. C. Loh, D. Li, Y. K. Chai, and F. Blaabjerg, “Autonomous operation of Sydney, Australia and Transend Networks (now TASNetworks), Tasmania,
ac–dc microgrids with minimised interlinking energy flow,” IET Power Australia. His research interest includes Smart Grid, power system planning,
Electron., vol. 6, no. 8, pp. 1650–1657, Sep. 2013. power system security, load modeling, electricity market, and computational
[34] G. Daelemans, “VSC HVDC in meshed networks,” Katholieke intelligence and its application in power engineering. Prof. Dong is Fellow of
Universiteit Leuven, 2008. IEEE and an editor of IEEE Transactions on Smart Grid, IEEE Power Engi-
[35] G. Daelemans, K. Srivastava, M. Reza, S. Cole, and R. Belmans, neering Letters, and IET Renewable Power Generation.
“Minimization of steady-state losses in meshed networks using VSC
HVDC,” in 2009 IEEE Power and Energy Society General Meeting,
2009, pp. 1–5.
[36] C. Wang, X. Li, L. Guo, and Y. W. Li, “A
Nonlinear-Disturbance-Observer-Based DC-Bus Voltage Control for a
Hybrid AC/DC Microgrid,” IEEE Trans. Power Electron., vol. 29, no. 11,
pp. 6162–6177, Nov. 2014.
[37] F. Mumtaz, M. H. Syedy, M. Al Hosani, and H. H. Zeineldin, “A simple
and accurate approach to solve the power flow for balanced islanded
microgrids,” in 2015 IEEE 15th International Conference on
Environment and Electrical Engineering (EEEIC), 2015, pp. 1852–1856.
[38] A. A. Hamad, M. A. Azzouz, and E. F. El-Saadany, “Multiagent
Supervisory Control for Power Management in DC Microgrids,” IEEE
Trans. Smart Grid, vol. 7, no. 2, pp. 1057–1068, Mar. 2016.
[39] J. Beerten and R. Belmans, “Development of an open source power flow
software for high voltage direct current grids and hybrid AC/DC systems:
MATACDC,” IET Gener. Transm. Distrib., vol. 9, no. 10, pp. 966–974,
Jul. 2015.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.