Professional Documents
Culture Documents
Abstract—In an islanded microgrid, the wire impedance mis- CDSC Cascaded delayed signal cancellation.
matches among distributed generation (DG) units lead to inaccu- LPF Low-pass filter.
rate power sharing results, which influences the system’s normal DRP Droop.
operation. The output impedances of DG units can be reshaped to
deal with this issue. In this paper, an impedance reshaping strategy CI Constant impedance.
for the resistive microgrid is proposed based on the combination of PR Proportion-resonant.
droop control and adaptive virtual impedance regulation (AVIR). Sj∗ Power rating of the j-th DG unit.
Firstly, DG units operate in droop mode and the steady-state mj The proportion the j-th DG unit shares.
reactive power from Q − f droop is restored as the reference.
Pj Active power from j-th DG unit.
Then the droop loops are removed and an AVIR based on the
error between instantaneous reactive power and its reference is Qj Reactive powers from j-th DG unit.
implemented. Since reactive power sharing with Q − f is relatively Ps,j Uniform active powers from j-th DG unit.
accurate, the impedance mismatches could be eliminated by the Qs,j Uniform reactive powers from j-th DG unit.
virtual impedances introduced with the proposed strategy, all the VC,j Output voltage magnitude in j-th DG unit.
accurate active, reactive, unbalanced and harmonic power sharing
δC,j Power angle in j-th DG unit.
could be realized simultaneously. In this strategy, communication
among DG units or between DG unit and central control is not Rw,j Wire impedance in j-th DG unit.
required, neither the wire impedances nor bus voltage or load Rv,j Virtual impedance in j-th DG unit.
current is measured, which reveals the high system reliability. Eb Bus voltage magnitude.
Finally, the simulation and experimental results are presented to V∗ Rated voltage magnitude.
verify the effectiveness of the proposed control method.
Vj Reference voltage magnitude.
Index Terms—Islanded resistive microgrid, distributed ω∗ Rated angle frequency.
generation, power sharing, unbalanced and harmonic power, ωj Angle frequency reference.
droop control, adaptive virtual impedance. kp /kq Droop coefficients.
io,b,j Balanced output current component in j-th DG unit.
NOMENCLATURE ωc,p Cut-off frequency of LPF for power calculation.
DER Distributed energy resource. ωc,td Cut-off frequency of LPF for transient detection.
DG Distributed generation. Q∗s,0,j Uniform reactive power reference.
MGCC Microgrid central controller. Q∗s,j Corrected uniform eactive power reference.
∗
VIR Virtual impedances regulation. V0,j Voltage reference magnitude stored in droop mode.
AVIR Adaptive virtual impedances regulation. kc,j Correction factor in j-th DG unit.
Gr (s) Regulator for AVIR.
Manuscript received June 20, 2021; revised September 28, 2021; accepted ki,r Integral coefficient for AVIR.
November 8, 2021. Date of publication November 26, 2021; date of current eQ,s,j Relative uniform reactive power error in j-th DG unit.
version March 22, 2022. This work was supported in part by the National Natural
Science Foundation of China under Grant 52007154 and in part by the Central
University Basic Research Fund of China under Grant G2020KY05107. Paper I. INTRODUCTION
no. TSTE-00633-2021. (Corresponding author: Fei Deng.)
Fei Deng, Yang Li, Wenli Yao, and Xiaobin Zhang are with the ISTRIBUTED energy resources (DERs) have been more
School of Automation, Northwestern Polytechnical University, Xi’an 710072,
China (e-mail: dengfei@mail.nwpu.edu.cn; li_yang_nwpu@mail.nwpu.edu.cn;
yaowl@nwpu.edu.cn; dgl907@126.com).
D and more popular for the environmental problem and the
concept microgrid is proposed to integrate various DERs [1],
Xiangke Li is with the Department of Electrical Engineering, [2]. In the normal case, the microgrid is connected with the
HongKong Polytechnic University, HongKong 999077, China (e-mail:
lixiangke@mail.nwpu.edu.cn). utility, when disconnecting from the utility it operates in islanded
Paolo Mattavelli is with the Department of Management, Engineering, mode. For the normal operation of the islanded microgrid shown
University of Padova, 36100 Vicenza, Italy (e-mail: paolo.mattavelli@unipd.it). in Fig. 1, power sharing is an essential issue [3]. Besides,
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TSTE.2021.3130983. when the unbalanced and nonlinear loads are supplied, not only
Digital Object Identifier 10.1109/TSTE.2021.3130983 the balanced powers (active and reactive powers) but also the
1949-3029 © 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
744 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
DENG et al.: DECENTRALIZED IMPEDANCE RESHAPING STRATEGY FOR BALANCED, UNBALANCED AND HARMONIC POWER SHARING 745
In resistive microgrids, the output active and reactive power idea, an decentralized impedance reshaping strategy is proposed
in DG #j are expressed as [28] in this paper.
VC,j (VC,j − Eb )
Pj = (2) III. PROPOSED CONTROL STRATEGY
Rw,j
In this section, the proposed impedance reshaping strategy is
VC,j Eb illustrated by an example of a resistive microgrid with two par-
Qj = − · δC,j (3)
Rw,j allel DG units. Firstly, transient detection is adopted to activate
the proposed strategy, with which the communication among DG
where VC,j , δC,j and Rw,j are output voltage magnitude, power
units is unnecessary. Then DG units operate in droop mode to
angle and wire resistance in DG #j respectively, Eb is bus
generate uniform reactive power reference. After that, the droop
voltage magnitude.
loops are removed and the AVIR is implemented. Herein, a flag
In (2) and (3), since the output voltage magnitude almost
F m is introduced to indicate the operation mode of DG units.
is constant, the active power mainly is influenced by wire
A DG unit with the proposed strategy is presented in Fig. 2.
impedance and its voltage drop, the reactive power is determined
with power angle and wire impedance. Therefore, to improve
power sharing accuracy, two strategies are available: 1) adjusting A. Power Calculation
active and reactive power with wire impedance voltage drop In this paper, the output voltage is replaced with voltage
compensation and power angle regulation respectively; 2) mod- reference, with which the active and reactive power in (2) and
ifying active and reactive power with wire impedance mismatch (3) are modified as
elimination.
Vj (Vj − Eb )
The first strategy can be achieved with P − V and Q − f Pj = (7)
droop control as Re,j
Vj = V ∗ − kp ·Ps,j (4) V j Eb
Qj = − · δj (8)
∗
Re,j
ωj = ω + kq ·Qs,j (5)
where Vj and δj are reference voltage magnitude before virtual
where V∗ and Vj are rated and reference voltage magnitudes impedance and corresponding power angle respectively, Re,j is
respectively, ω ∗ and ωj are rated and reference angular frequen- equivalent impedance, it is sum of Rv,j and Rw,j .
cies respectively, kp and kq are the droop coefficients, they are In (7) and (8), the virtual impedance is a part of the equivalent
same in each DG units. Ps,j and Qs,j are uniform active and impedance, with which after the impedance reshaping process
reactive powers respectively, they are defined as Ps,j = Pj /mj completes, all DG units can be regarded as same with each other.
and Qs,j = Qj /mj respectively. Afterwards, the power sharing performance during transient
In this strategy, communication is unnecessary, accurate re- could be improved.
active power sharing could be achieved but the active power To calculating the active and reactive powers, the balanced
sharing still is inaccurate. Besides, an unexpected voltage drop component in output current (io,b,j ) is extracted with the cas-
and frequency deviation are introduced. caded delayed signal cancellation (CDSC)-based decomposition
For the second strategy, adaptive virtual impedance regulation method in [29]. In the stationary reference frame, the uniform
(AVIR) is widely adopted. The virtual resistance is regulated average active and reactive powers are calculated as
according to the power error or current error as
ωc,p vj,α · io,b,j,α + vj,β · io,b,j,β
Rv,j = Gr (s) (Xj − Xref ) (6) Ps,j = · (9)
s + ωc,p mj
where X could be active power, reactive power, harmonic power ωc,p vj,β · io,b,j,α − vj,α · io,b,j,β
or current magnitude, Gr (s) is the regulator for AVIR, it can be Qs,j = · (10)
s + ωc,p mj
an integrator or a proportional-integral (PI) regulator.
With this method, accurate power sharing could be achieved, where ωc,p is the cut-off frequency of the low-pass filters
but the reference generation is based on communication among (LPFs), vj,αβ and io,b,j,αβ are voltage reference before virtual
DG units or between DG unit and MGCC, which degrades impedance and balanced output current in stationary reference
system reliability. frame respectively.
Since the reactive power sharing is accurate in droop control
and it also can be achieved with AVIR, the two above-mentioned B. Transient Detection
strategies can be combined: implement droop control firstly to
After a load demand change or a network structure change,
generate the reactive power reference, then remove the droop
the active power varies rapidly in response to the change and
control and introduce regulate reactive power to follow the
its derivative could be used for transient detection [30]. This
obtained reference for AVIR. With this process, all the balanced,
variable is expressed as
unbalanced and harmonic powers can be distributed accurately,
the voltage drop will be reduced and the frequency deviation ωc,td dPs,j
GP,j = (11)
can be eliminated, communication is not required. Based on this s + ωc,td dt
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
746 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
where ωc,td is the cut-off frequency of the LPF. reactive power error. It should be noted that, the disablement of
If GP,j becomes larger than a predefined threshold ξth , the droop loops eliminates voltage magnitude drop and frequency
transient flag F tr will be set. When the droop mode is finished, deviation, which changes the operation point of DG units, the
F tr would be reset. reference Q∗s,0,j can not be used directly. Therefore, a correction
factor kc,j is introduced, the uniform reactive power reference
is corrected as
C. Proposed Decentralized Impedance Reshaping Strategy
Q∗s,j = kc,j · Q∗s,0,j . (12)
After transient detection, the proposed impedance reshaping
strategy is activated. Firstly, the reference of uniform reactive Therefore, the virtual resistance is regulated as
power is generated with droop control. Then the droop loops are
replaced with AVIR to eliminate wire impedance mismatches. Gr (s) Qs,j − Q∗s,j
Rv,j = (13)
When the desired power sharing accuracy is obtained, the mj
DG units operate with constant virtual impedance. Without
where Gr (s) = ki,r /s is regulator for AVIR, ki,r is integral
loss of Generality, it is assumed that m1 Rw,1 < m2 Rw,2 , the
coefficient.
impedance reshaping process in the proposed strategy is dis-
Without communication among DG units, the active or reac-
played in Fig. 3.
tive power errors can not calculated directly. In this paper, the
1) Droop (DRP) Mode: After a transient is detected, the
local relative uniform reactive power error is defined as
value of F m is changed from 0 to 1, which enables DG units
operate in DRP mode, the droop control in (4) and (5) are Q − Q∗
s,j s,j
implemented for a time duration Tdrp . Tdrp should long enough eQ,s,j = . (14)
Q∗s,j
to ensure DG units reach steady states. When DG units have
operated in this mode for Tdrp , F tr would be reset and its falling When eQ,s,j in (14) is smaller than a predefined threshold
edge detection disables droop control and changes F m from 1 εQ,s , F m will be changed to 0 and the AVIR algorithm would
to 2. The uniform reactive power value and voltage reference be disabled.
magnitude at the end of DRP mode are restored as the references 3) Constant Impedance (CI) Mode: Before the proposed
Q∗s,0,j and V0,j respectively. strategy is implemented or after the AVIR is finished, F m = 0,
2) AVIR Mode: When F m = 2, DG units are in this mode, DG units operate in this mode. In this mode, the voltage reference
the virtual impedance is regulated according to uniform magnitude and angle frequency are their rated value and virtual
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
DENG et al.: DECENTRALIZED IMPEDANCE RESHAPING STRATEGY FOR BALANCED, UNBALANCED AND HARMONIC POWER SHARING 747
B. Stability Analysis
impedance keeps constant. This mode is ended only if another
transient signal is detected. During impedance reshaping process, the stability both in
DRP mode and AVIR mode should be guaranteed. Since the
D. Voltage Reference Compensation With Virtual Impedance bandwidth of inner loops is much greater than that of outer loops,
the dynamic response of inner loops is neglected.
When DG units operate in AVIR mode or CI mode, the voltage 1) Stability Analysis in DRP Mode: In this mode, the droop
reference for inner loops is compensated with virtual impedance, loops in (4) and (5) work, the small-signal model of power stage
it is expressed as can be induced from (7) and (8) as
vref,j,αβ = vj,αβ − io,j,αβ · Rv,j . (15)
ΔYj = Bj ΔXj (16)
It should be pointed out that, under unbalanced-load and
nonlinear-load condition, when DG units operate in DRP mode, where ΔXj = [ΔVj , Δδj ]T , ΔYj = [ΔPj , ΔQj ]T , Δx rep-
only the balanced power sharing is considered, unbalanced or resents the small-signal perturbation of variable x, and
harmonic power sharing issue is not involved. When DG units ⎡ ⎤
∂Pj ∂Pj
operate in AVIR and CI mode, the virtual resistance is intro- ⎢ ∂Vj ∂δj ⎥
duced, which is not relative to frequency, the voltage reference Bj = ⎢ ⎣ ∂Qj ∂Qj ⎦.
⎥
components at all frequencies contained in output current are
compensated. Therefore, all the balanced, unbalanced and har- ∂Vj ∂δj
monic power sharing performance are improved simultaneously. The small-signal model of the controller in (4) and (5) is
expressed as
E. Inner Loops
In the inner loops, a proportional regulator is adopted for ΔẊj = Cj ΔXj + Dj ΔYj (17)
inductor current regulation to enhance the system damping and where
a Proportional-resonant (PR) controller is designed for capac- ⎡ ⎤
itor voltage regulation to achieve steady-state zero error in the −kp ωc,p 0
−ωc,p 0
stationary reference frame [31], [32], in this paper, the 5th and Cj = , Dj = ⎣ ωc,p ⎦.
0 0 0 kq
7th harmonics are considered. s + ωc,p
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
748 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
Fig. 5. Eigenvalue loci of Gcl,j (s) when DG units operate in AVIR mode
with increasing ki,r (3×10−4 ∼ 2×10−2 ).
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
DENG et al.: DECENTRALIZED IMPEDANCE RESHAPING STRATEGY FOR BALANCED, UNBALANCED AND HARMONIC POWER SHARING 749
TABLE I
SYSTEM PARAMETERS
Substitute (24) and (25) into (12), the correction factor can be
obtained as Fig. 8. Simulation results: (a) Active and reactive powers, (b) output current
2 magnitudes, (c) bus voltage RMS, (d) frequency deviations and (e) virtual
V∗ impedances under balanced-load condition DG units with same capacities.
kc,j = . (26)
V0,j
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
750 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
TABLE II
COMPARISON OF STEADY-STATE PERFORMANCES AMONG DIFFERENT POWER SHARING STRATEGIES UNDER BALANCED-LOAD CONDITION
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
DENG et al.: DECENTRALIZED IMPEDANCE RESHAPING STRATEGY FOR BALANCED, UNBALANCED AND HARMONIC POWER SHARING 751
Fig. 11. Simulation results under unbalanced-load condition. (a) Active and
reactive powers (b) balanced and unbalanced output current magnitudes.
Fig. 12. Simulation results under nonlinear-load condition. (a) Active and
reactive powers (b) balanced, -5th and +7th harmonic output current magnitudes.
TABLE III
COMPARISON UNDER UNBALANCED-LOAD CONDITION
TABLE IV
COMPARISON UNDER NONLINEAR-LOAD CONDITION
B. Unbalanced-Load Condition
A single-phase load (Load 2) is supplied in this condition and
C. Nonlinear-Load Condition
the simulation results with the strategy in [21] and in this paper
are shown in Fig. 11 and Table III. With the method in [21], In this condition, a nonlinear load (Load 3) is connected to
both the balanced and unbalanced power sharing performance the microgrid. As the simulation results in Fig. 12 and Table IV
is improved but still is not accurate. Besides, it should be noted showing, comparing with the AVIR strategy in [21], all the
that the unbalanced power sharing performance is inferior to active, reactive and harmonic powers sharing are distributed rel-
balanced power. In contrast, with the proposed strategy, both atively accurately with the proposed strategy. Besides, during the
the balanced and unbalanced powers are shared relatively accu- load change transient, the maximum reactive power errors with
rately. Also, the maximum reactive power error during transient the strategy in [21] and with the proposed strategy are 100.5 var
with the proposed strategy (3.5 var) much smaller than that with and 4.7 var respectively, which means that the power sharing
the method in [21] (75.8 var), which puts up admirable transient performance during transient also is improved significantly with
dynamic power sharing performance. the proposed strategy.
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
752 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
TABLE V
SYSTEM PARAMETERS OF EXPERIMENTAL SETUP
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
DENG et al.: DECENTRALIZED IMPEDANCE RESHAPING STRATEGY FOR BALANCED, UNBALANCED AND HARMONIC POWER SHARING 753
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.
754 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, VOL. 13, NO. 2, APRIL 2022
[24] P. Sreekumar and V. Khadkikar, “A new virtual harmonic impedance Wenli Yao (Member, IEEE) received the B.S., M.S.,
scheme for harmonic power sharing in an islanded microgrid,” IEEE Trans. and Ph.D. degrees in electrical engineering from
Power Del., vol. 31, no. 3, pp. 936–945, Jun. 2016. Northwestern Polytechnical University, Xi’an, China,
[25] L. Hongpeng, L. Xiaoxi, Z. Wei, and W. Wei, “An improved harmonic in 2009, 2012, and 2017, respectively. From 2013
power sharing scheme of paralleled inverter system,” in Proc. Int. Power to 2015, he was a Visiting Scholar with Aalborg
Electron. Conf. (IPEC-Niigata 2018 -ECCE Asia), 2018, pp. 2969–2972. University, Aalborg, Denmark. From 2017 to 2019, he
[26] H. Qian, Q. Xu, P. Du, Y. Xia, and J. Zhao, “A distributed control scheme was a Research Fellow with the Rolls-Royce@NTU
for accurate power sharing and fixed frequency operation in islanded Corporate Lab, School of Electrical and Electronics
microgrids,” IEEE Trans. Ind. Electron., vol. 68, no. 12, pp. 12229-12238, Engineering, Nanyang Technological University, Sin-
Dec. 2021. gapore. Since May 2019, he has been with Northwest-
[27] X. Yu, A. M. Khambadkone, H. Wang, and S. T. S. Terence, “Control of ern Polytechnical University, Xi’an, China, as an As-
parallel-connected power converters for low-voltage microgrid-part I: A sociate Professor. His research interests include current control, grid-connected
hybrid control architecture,” IEEE Trans. Power Electron., vol. 25, no. 12, inverter, multipulse converter, and power decoupling.
pp. 2962–2970, Dec. 2010.
[28] J. M. Guerrero, J. Matas, L. Garcia de Vicuna, M. Castilla, and J. Miret,
“Decentralized control for parallel operation of distributed generation
inverters using resistive output impedance,” IEEE Trans. Ind. Electron.,
vol. 54, no. 2, pp. 994–1004, Apr. 2007.
[29] Y. F. Wang and Y. W. Li, “Three-phase cascaded delayed signal cancella-
tion PLL for fast selective harmonic detection,” IEEE Trans. Ind. Electron.,
vol. 60, no. 4, pp. 1452–1463, Apr. 2013.
[30] Y. Gupta, K. Chatterjee, and S. Doolla, “A simple control scheme for
improving reactive power sharing in islanded microgrid,” IEEE Trans.
Power Syst., vol. 35, no. 4, pp. 3158–3169, Jul. 2020. Xiaobin Zhang received the B.S. and M.S. degrees
[31] J. He and Y. W. Li, “Analysis, design, and implementation of virtual in electrical engineering from the School of Automa-
impedance for power electronics interfaced distributed generation,” IEEE tion, Northwestern Polytechnical University, Xi’an,
Trans. Ind. Appl., vol. 47, no. 6, pp. 2525–2538, Nov./Dec. 2011. China, in 1983 and 1986, respectively. Since 1986, he
[32] J. C. Vasquez, J. M. Guerrero, M. Savaghebi, J. Eloy-Garcia, and R. has been with the School of Automation, Northwest-
Teodorescu, “Modeling, analysis, and design of stationary-reference- ern Polytechnical University, where he is currently a
frame droop-controlled parallel three-phase voltage source inverters,” Professor.
IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1271–1280, Apr. 2013. His research interests include power electronic
control, aircraft power system, multi-pulse converter,
and power decoupling.
Authorized licensed use limited to: Tsinghua University. Downloaded on March 21,2023 at 04:22:36 UTC from IEEE Xplore. Restrictions apply.