Professional Documents
Culture Documents
Abstract: In distribution networks, the voltage unbalance occurrence is inevitable. The voltage unbalance can have negative
impacts on the customer equipment and the network performance if it exceeds the permissible limit. This study proposes a
novel control strategy to compensate for the voltage unbalance in stand-alone microgrids. The proposed control method applies
to the inverter-interfaced distributed generation units. The suggested control strategy is based on the decouple double
synchronous reference frame (DDSRF) that is modified to improve its effectiveness. The modified DDSRF can effectively
decouple the positive and negative sequence components. The simulation results depict that the proposed control strategy
provides faster dynamic response and more effective voltage unbalance compensation comparing to the DSRF-based control
method.
+
Nomenclature kdqI proportional–integral controller of the positive current
control loop
V sabc line-to-neutral voltages at the PCC −
kdqI proportional–integral controller of the negative current
Iabc line currents supplied by the VSC control loop
+∗
vsdq positive sequence d–q components of the reference τi time constant of the current controller
voltage
−∗
vsdq negative sequence d–q components of the reference
voltage 1 Introduction
+
vsdq positive sequence d–q components of the voltage at the Nowadays, the continuity of the electricity supply and the voltage
PCC quality with considering the environmental and economic aspects
−
vsdq negative sequence d–q components of the voltage at the are the important issues related to the power distribution operation.
PCC Adopting the distributed generations (DGs) in the distribution
+
vtdq positive sequence d–q components of the voltage at the networks is the main approach of the electrical engineers for
DG terminal guaranteeing the continuous supply of the local and sensitive loads,
−
vtdq negative sequence d–q components of the voltage at the improving the power quality, decreasing the emission of
DG terminal greenhouse gases, via utilising renewable energy resources, and
+
idq positive sequence d–q components of the DG current decreasing the power transmission losses.
−
idq negative sequence d–q components of the DG current The presence of DGs in the distribution systems has introduced
+ a new structure called microgrid (MG). MGs can either be
ildq positive sequence d–q components of the load current
−
connected to the main gird or be operated in the islanded (or stand-
ildq negative sequence d–q components of the load current alone) mode. The difference between the islanded and stand-alone
+
idq DC term of positive sequence d–q components of the mode is that: in the stand-alone mode, MG is isolated from the
current main grid (off-grid); while in the islanded mode, MG can be able to
−
idq DC term of negative sequence d–q components of the operate in the grid-connected mode [1]. Both grid-connected and
current stand-alone MGs require special control systems. When MGs are
+′ positive sequence d–q components of the current after
idq connected to the main grid, the DG control system is responsible
transformation for injecting a specified amount of the active and reactive power to
−′ negative sequence d–q components of the current after
idq the grid. In this case, the main grid controls the frequency. In the
transformation islanded and stand-alone mode of operation, the control system is
+∗
idq positive sequence d–q components of the reference responsible for keeping the voltage and frequency within a
current permitted limit and preserving the system stability [2, 3].
−∗
idq negative sequence d–q components of the reference frame In the distribution networks, unbalanced loads can cause the
+
idq estimated DC term of positive sequence d–q components voltage unbalance. The voltage unbalance has negative impacts on
of the current the equipment, such as induction motors, electronic converters, and
−
idq estimated DC term of negative sequence d–q components adjustable speed drives. Additionally, the voltage unbalance cause
of the current more losses in the power systems [4]. Due to these drawbacks, the
+
Δidq positive sequence d–q components of the current error IEC recommends that the voltage imbalance in electrical systems is
−
Δidq negative sequence d–q components of the current error limited to 2%.
The unbalanced voltage can be compensated via the injection of
K P, K Q droop controller coefficients
+
the negative sequence voltages by using series active power filters
kdqv proportional controller of the positive voltage control (APFs) or dynamic voltage restorers [5]. It is also possible to
loop balance the voltage of the point of common coupling (PCC) by
−
kdqv proportional controller of the negative voltage control injecting the negative sequence currents and compensating the
loop unbalanced loads using parallel APFs and static synchronous
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5093
© The Institution of Engineering and Technology 2020
compensators (STATCOMs) [6]. However, all these solutions • Introducing a modified DDSRF to increase the accuracy of the
impose additional costs. Therefore, researchers used the surplus oscillatory component estimation.
capacity of the inverter-interfaced DGs, recently, to improve the • Proposing a control system based on the modified DDSRF to
voltage quality in order to reduce the additional costs. For example, compensate for the unbalanced voltage in the dq reference
PV-STATCOM in which a photovoltaic (PV) inverter can be frame.
controlled as a STATCOM is proposed in literatures for voltage
control [7, 8]. PVs contain valuable inverters that hardly operate at The remaining of this paper is organised as follows: Section 2
their maximum rated power because of the variation of solar describes the structure of modified DDSRF. In Section 3, the
radiation over the day. Therefore, it is more efficient to use the proposed control strategy for unbalanced voltage compensation is
excess capacity of the inverters for compensating the voltage presented. The simulation results are provided in Section 4.
unbalance [9, 10]. Indeed, one can use an appropriate control Eventually, the conclusion and discussion are presented in Section
method in the control system of inverter-interfaced DGs to improve 5.
the voltage quality at the consumer's side [11].
The proposed method in [7] supposes that the current of 2 Structure of the proposed DDSRF
unbalanced loads is accessible. However, the unbalanced currents
of the local loads are generally inaccessible for the inverter- The injection of the positive and negative sequences of the current
interfaced DGs. is essential to compensate for the unbalanced networks. So the
A hierarchical control approach for voltage unbalance positive and negative sequence currents must be separated, which
compensation is suggested by sending appropriate control signals can perform using DSRF. In the DSRF, in order to extract the
from a central secondary controller to the primary level in [12]. In positive sequence, the currents in the αβ reference frame must be
[13], local distributed energy resource (DER) controllers are rotated, with the system angular frequency ω, in the
divided into primary and secondary levels to compensate for the counterclockwise direction. Also, to extract the negative sequence,
voltage unbalance. The secondary layer collects information from the currents must be rotated in the clockwise direction. After
all DERs and provides control rules for controlling the primary rotating, the positive and negative sequence currents in the dq
level using the averaging technique. In [14], a hierarchical control reference frame comprise two terms, a DC term, and an AC term as
structure is used to control the voltage unbalance factor (VUF) of follows [25]:
the PCC and shares the unbalanced currents among generators.
+ − −
Although the proposed approaches in [12–14] are highly effective, +
idq = +
idq + e− j θ idq −θ
follows: S + ωf S + ωf
5094 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103
© The Institution of Engineering and Technology 2020
Fig. 3 Positive sequence component of the current in the d-axis
+ +′ S2 + ωn2
idq = idq ×
S + 2ξωn + ωn2
2
(8)
− −′ S2 + ωn2
idq = idq ×
S + 2ξωn + ωn2
2
Fig. 1 DDSRF presented in [25] In (8), S2 + ωn2 /S2 + 2ξωn + ωn2 is the transfer function of the notch
filter, ωn and ξ are the natural frequency and the damping ratio,
respectively.
In order to compare the DDSRF presented in Fig. 1 (that is
named hereafter as the conventional DDSRF) and the proposed
DDSRF, a simulation is carried out in the condition that the
positive sequence component of the reference current in the d-axis
is changed at t = 1 s. In this simulation, the reference current is
id+ ∗ = 4 + 2sin(120πt) after t = 1 s. As shown in Fig. 3 when the
reference current is not DC and has an AC term, the conventional
DDSRF cannot appropriately extract the DC component. In
contrast, the proposed DDSRF can correctly eliminate the AC term
and extract the DC component.
+′ + − − + −
idq = +
idq + e− j θ −θ
idq − e− j θ −θ
.
(idq − Δidq) − ∗
−
← − − − → ← − − − − − − − − − − → ← − − − − − − − − − →
DC term AC term DC term
← − − − − − − − − − − − − − − − − − − →
Cross − coupling term
− + + − +
(5)
−′
idq = −
idq + e− j θ −θ
idq − e− j θ −θ
. +
(i+dq∗ − Δidq)
← − − − → ← − − − − − − − − − − → ← − − − − − − − − − →
DC term AC term DC term
← − − − − − − − − − − − − − − − − − − →
Cross − coupling term
+′ + − − + − −
idq = +
idq + e− j θ − θ idq − e− j θ − θ idq
← − − − → ← − − − − − − − − − − → ← − − − − − − − − − − − →
DC term AC term Cross − coupling term
− + + − + +
(7)
−′
idq = −
idq + e− j θ −θ
idq − e− j θ −θ
idq
← − − − → ← − − − − − − − − − − → ← − − − − − − − − − − − →
DC term AC term Cross − coupling term
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5095
© The Institution of Engineering and Technology 2020
Fig. 4 Proposed control system
sequence components of the DG current. Finally, the switching problems, the virtual impedance is implemented in the control
signals are produced via a PWM block. In Fig. 4, the negative system. The most important advantage of the virtual impedance is
sequence components of the reference voltage in the dq reference the tuning of DG output impedance. This means that by employing
−∗ −∗
frame, V sd and V sq are equal to zero. In the following subsections, the virtual impedance, not only the output impedance of the
the design procedure of each control block is explained. parallel DGs will be equal; the inductive property will be enhanced
as well. So, by adding the virtual impedance loop the required
+∗ +∗
3.1 Droop controllers in the unbalanced conditions reference voltage V sd and V sq are generated.
Based on the theory of the instantaneous powers, the delivered 3.3 Voltage controller design
active and reactive powers to the PCC caused by positive sequence
components are as follows: The dynamic model of the LCL filter can be achieved by using
KCL at the point of the capacitor connection. After transforming to
3 + + the dq reference frame, the following equations are obtained:
Ps+ t = +
V t i t + V sq t iq+ t (9)
2 sd d
+
dV sd t
3 Cf = id+ t − iLd
+ +
t + C f ω t V sq t (13)
+ +
Qs t = −V sd t iq+ t + V sq
+
t id+ t (10) dt
2
+
dV sq t
After calculating the active and reactive powers, using the voltage Cf = iq+ t − iLq
+ +
t − C f ω t V sd t (14)
dt
and frequency droop controllers, the PCC voltage and the
frequency are regulated as follows [27]: −
dV sd t
Cf = id− t − iLd
− −
t − C f ω t V sq t (15)
f − f 0 = − KP Ps+ − P0 (11) dt
−
dV sq t
V − V 0 = − KQ Qs+ − Q0 (12) Cf = iq− t − iLq
− −
t + C f ω t V sd t (16)
dt
where f0 and V0 are the rated frequency and voltage, respectively.
where ω t = dρ/dt .
Also P0 and Q0 are the tuned active and reactive powers, Equations (13)–(16) show that there is a coupling between V sd
respectively. and V sq for both positive and negative sequence components. To
Actually, droop control is an imitation of the steady-state
eliminate this coupling, the feed-forward compensator is used. In
treatment of synchronous generator, where by increasing demand
order to design the voltage controllers, the simplified block
for the active power, the frequency is reduced and vice versa. The
diagram of the closed-loop voltage control system for both positive
main advantage of the droop method is that it does not require a
and negative sequence components is considered as shown in
communication link for load sharing, which increases the reliability
of the system. Therefore, the droop controllers produce a sinusoidal Fig. 5. In this figure, kd±, qv denotes the voltage controller, and τi is
waveform as the positive component of the reference voltage. the desired time constant of the closed-loop current control system
which is explained in the next part.
3.2 Virtual impedance Since the transfer function of the open-looped voltage control
system has a pole in the coordinate origin, the steady-state error of
The voltage and frequency droop controllers can only perform the closed-loop system is zero. Therefore, one can consider the
correctly if the line reactance is much greater than the line kd±, qv as a proportional control with the value of k pv. Thus,
resistance. Also, the impedance between each DG and the PCC according to Fig. 5, the transfer function of the open-looped
(including transmission line impedance and the output impedance voltage control system can be attained as follows:
of DGs) is generally different. Therefore, resulting in unequal
power-sharing among DGs. In addition, the line impedance is not kpv 1
essentially inductive. Consequently, in this condition, the droop T olv s = (17)
C f s τis + 1
controllers are no longer effective. In order to overcome these
5096 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103
© The Institution of Engineering and Technology 2020
Fig. 5 Simplified block diagram of the voltage control loop
did+ t
L + R + ron id+ t
dt (18)
+ + +
= V td t − V sd t + Lω0iq t
diq+ t
L + R + ron iq+ t
dt (19)
+ + +
= V tq t − V sq t − Lω0id t
did− t
L + R + ron id− t
dt (20)
− − −
= V td t − V sd t − Lω0iq t
diq− t
L + R + ron iq− t
dt (21)
− −
= V tq t − V sq t + Lω0id− t
where
± V dc ±
V td t = m (22)
2 d
Fig. 7 PCC voltage and VUF when DSRF-based method is used
± V dc ±
V tq t = m (23) (a) PCC voltage, (b) VUF
2 q
Fig. 6. To control of the VSI currents a proportional–integral (PI)
Equations (18)–(21) show that there is a coupling between Id and Iq controller is considered where
for both positive and negative sequence components. To eliminate
this coupling, the feed-forward compensator is used. Considering ki
the control variable as follows: kd±, qI = kp + (26)
s
udq(t) = V tdq t − V sdq t ± Lω0idq t (24) Based on Fig. 6, the transfer function of the open-loop system can
be written as follows:
The dynamic model of VSI can be represented in Laplace domain
as kp s + ki /kp
T ol s = (27)
± Ls s + R + ron /L
± udq
idq = (25)
Ls + R + ron Considering (27), it is clear that, the transfer function of the open-
loop system has a stable pole at p = − (R + ron)/L. Typically, this
The block diagram of the closed-loop current control system for pole is fairly close to the origin and corresponds to a slow system
both positive and negative sequence components are illustrated in
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5097
© The Institution of Engineering and Technology 2020
Table 1 Parameters of the test system with one DG
Parameter Value
peak phase voltage, V 391
DC link voltage, V 1500
nominal frequency, Hz 60
switching frequency, kHz 3
inverter filter inductance, μH 100
inverter filter capacitance, μF 2500
line impedance, Ω 0.01 + j3.7
damping coefficient of notch filter (ξ) 0.707
kpv 1.6
kp 0.2
ki 4.14
KP 6 × 10−6
KQ 2 × 10−3
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5099
© The Institution of Engineering and Technology 2020
Fig. 11 Negative sequence components
Fig. 13 Voltage, current and VUF at the DG output when the proposed
method is used
(a) Voltage, (b) Current, (c) VUF
Fig. 15 VUF of the PCC voltage when sever unbalanced load is connected
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5101
© The Institution of Engineering and Technology 2020
Fig. 19 Frequency of the test stand-alone MG
In addition, the VUF in the steady-state conditions remains less According to the aforementioned, finding the solutions for a trade-
than 1%. Furthermore, the comparison between the DSRF-based off between unbalanced voltage compensation and power
method, the conventional DDSRF-based method, and the proposed oscillation reduction can be considered as a topic for future
control method is done for different loads in the first test system. researches.
The simulation results show that the proposed control method can
effectively compensate the unbalanced voltage even under severe 7 References
unbalanced load connection, while other methods can not satisfy
the permissible limit and VUF exceeds 2%. [1] Jiang, Q., Xue, M., Geng, G.: ‘Energy management of microgrid in grid-
connected and stand-alone modes’, IEEE Trans. Power Syst., 2013, 28, (3),
Since, in the proposed approach for compensating the pp. 3380–3389
unbalanced voltage at PCC, the current, which contains the [2] Guerrero, J.M., Chandorkar, M., Lee, T., et al.: ‘Advanced control
negative sequence component is injected by the inverter-interfaced architectures for intelligent micro-grids – part II: power quality, energy
DG, the DG's terminal voltage will be unbalanced. In addition, as storage, and AC/DC micro-grids’, IEEE Trans. Ind. Electron., 2013, 60, (4),
pp. 1263–1270
presented in Section 4, the negative sequence component causes [3] Sabzevari, K., Karimi, S., Khosravi, F., et al.: ‘Modified droop control for
also the oscillatory component in the instantaneous active and improving adaptive virtual impedance strategy for parallel distributed
reactive powers. The power oscillation causes the issues that generation units in islanded microgrids’, Int. Trans. Electr. Energy Syst., 2019,
should be taken into account. The oscillation in the DC-link 113, pp. 758–771
[4] Acharya, S., El-Moursi, M.S., Al-Hinai, A., et al.: ‘A control strategy for
voltage (if the DC-link capacitor is used), and the possibility of voltage unbalance mitigation in an islanded microgrid considering demand
overloading the inverter are the issues that should be considered in Side management capability’, IEEE Trans. Smart Grid, 2019, 10, (3), pp.
the control system. In order to prevent overloading of the inverter, 2558–2568
current limiter should be considered for the reference currents in [5] Li, Y.W., Loh, P.C., Blaabjerg, F., et al.: ‘Investigation and improvement of
transient response of DVR at Medium voltage level’, IEEE Trans. Indus.
the current control loop. Appl., 2007, 43, (5), pp. 1309–1319
As shown in Section 4, under unbalanced conditions, the [6] Kuang, L., Jinjun, L., Zhaoan, W., et al.: ‘Strategies and operating point
instantaneous active and reactive powers contain the oscillatory optimization of STATCOM control for voltage unbalance mitigation in three-
components with the frequency equal to 2ω. In this paper, the phase three-wire systems’, IEEE Trans. Power Deliv., 2007, 22, pp. 413–422
[7] Varma, R.K., Siavashi, E.M.: ‘PV-STATCOM: A new smart inverter for
inverter-interfaced DG is a grid-forming inverter, and thus the voltage control in distribution systems’, IEEE Trans. Sustain. Energy, 2018,
inverter is connected to a stiff DC source. However, in the grid- 9, (4), pp. 1681–1691
following inverters, the oscillation components flow through the [8] Lourenco, L.F.N., de Camargo Salles, M.B., Monaro, R.M., et al.: ‘Technical
DC-link capacitor and cause the oscillation with the same cost of operating a photovoltaic installation as a STATCOM at nighttime’,
IEEE Trans. Sustain. Energy, 2019, 10, (1), pp. 75–81
frequency on the DC-link voltage. This oscillation component [9] Naggar, A.E., Erlich, I.: ‘Control approach of three-phase grid connected PV
degrades the converter functionality and imposes more stress on inverters for voltage unbalance mitigation in low-voltage distribution grids’,
the capacitor, and converter switches. In this case, as the power IET Renew. Power Gener., 2016, 10, pp. 15–1586
increases or the DC-link capacitance decreases, the ripples on DC- [10] Hoseinnia, S., Akhbari, M., Hamzeh, M., et al.: ‘A control scheme for voltage
unbalance compensation in an islanded microgrid’, Electr. Power Syst. Res.,
link increases. Then, the capacitance should be selected high 2019, 177, p. 106016
enough to mitigate the ripples. For grid-following inverters under [11] Fei, W., Duarte, J.L., Hendrix, M.A.M.: ‘Grid-interfacing converter systems
unbalanced conditions, to reduce the capacitor size while keeping with enhanced voltage quality for microgrid application – concept and
the level of ripples low, a proportional–integral–resonant (PIR) implementation’, IEEE Trans. Power Electron., 2011, 26, (12), pp. 3501–
3513
DC-link controller can be used [29]. In this controller, the PI [12] Savaghebi, M., Jalilian, A., Vasquez, J.C., et al.: ‘Secondary control scheme
compensator is responsible for regulating the DC component of the for voltage unbalance compensation in an islanded droop-controlled
DC-link voltage, while the PR compensator controls the 2ω microgrid’, IEEE Trans. Smart Grid, 2012, 3, (2), pp. 797–807
component and forces it to zero. [13] Lizhen, W., Xiaohong, H., Zhengzhe, L., et al.: ‘Decentralized control
approach for voltage unbalance compensation in islanded microgrid’. IEEE
Regarding to the above descriptions, the limitations of the 8th Int. Power Electronics and Motion Control Conf. (IPEMC-ECCE Asia),
proposed control strategy as well as the issue that need to be Hefei, China, 2016
considered in order to extend the proposed approach are [14] Han, Y., Shen, P., Zhao, X., et al.: ‘An enhanced power sharing scheme for
summarised as follows: voltage unbalance and harmonics compensation in an islanded AC microgrid’,
IEEE Trans. Energy Convers., 2016, 31, (3), pp. 1037–1050
Limitations: [15] Najafi, F., Hamzeh, M., Fripp, M.: ‘Unbalanced current sharing control in
islanded low voltage microgrids’, Energies, 2018, 11, (10), p.2776
• It is assumed that there is no load connected to DG's terminal. [16] Savaghebi, M., Jalilian, A., Vasquez, J.C., et al.: ‘Autonomous voltage
So, the unbalanced voltage at the DG's terminal does not unbalance compensation in an islanded droop-controlled microgrid’, IEEE
Trans. Indus. Electron., 2013, 60, (4), pp. 1390–1402
negative impact on the loads. [17] Meng, L., Tang, F., Savaghebi, M., et al.: ‘Tertiary control of voltage
• It is assumed that the inverter has sufficient capacity for unbalance compensation for optimal power quality in islanded microgrids’,
unbalanced voltage compensation. IEEE Trans. Energy Convers., 2014, 29, (4), pp. 802–815
[18] Tang, F., Zhou, X., Meng, L., et al.: ‘Secondary voltage unbalance
compensation for three-phase four-wire islanded micro-grids’. Int. Multi-
Requirement to extend the proposed method: Conf. on Systems, Signals & Devices (SSD), Barcelona, 2014, pp. 1–5
[19] Yazdani, A., Iravani, R.: ‘Voltage-sourced converters in power system/
• In order to extend the proposed control strategy for grid- molding, control, and applications’ (Wiley, USA, 2010)
[20] Merritt, N.R., Chakraborty, C., Bajpai, P.: ‘New voltage control strategies for
following inverters, instead of the conventional DC-link VSC based DG units in an unbalanced microgrid’, IEEE Trans. Sustain.
controller, a PIR controller should be used, or the DC-link Energy, 2017, 8, (3), pp. 1127–1139
capacitance should be selected high enough to mitigate the [21] Delghavi, M.B., Yazdani, A.: ‘Islanded-mode control of electronically
ripples with the frequency of 2ω. coupled distributed-resource units under unbalanced and nonlinear load
conditions’, IEEE Trans. Power Deliv., 2011, 26, (2), pp. 661–673
5102 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103
© The Institution of Engineering and Technology 2020
[22] Nejabatkhah, F., Li, Y.W., Wu, B.: ‘Control strategies of three-phase [27] Guerrero, J.M., Matas, J., de Vicuña, L.G., et al.: ‘Decentralized control for
distributed generation inverters for grid unbalanced voltage compensation’, parallel operation of distributed generation inverters using resistive output
IEEE Trans. Power Electron., 2016, 31, (7), pp. 5228–5241 impedance’, IEEE Trans. Ind. Electron., 2007, 54, (2), pp. 994–1004
[23] Priyanka, M., Kumar, P.A., Prabodh, B.: ‘Voltage control of PV inverter [28] Vasquez, J.C., Guerrero, J.M., Savaghebi, M., et al.: ‘Modeling, analysis, and
connected to unbalanced distribution system’, IET Renew. Power Gener., design of stationary-reference-frame droop-controlled parallel three-phase
2019, 13, (9), pp. 1587–1594 voltage source inverters’, IEEE Trans. Indus. Electron., 2013, 60, (4), pp.
[24] Rodriguez, P., Pou, J., Bergas, J., et al.: ‘Decoupled double synchronous 1271–1280
reference frame PLL for power converter control’, IEEE Trans. Power [29] Zarei, S.F., Mokhtari, H., Ghasemi, M.A., et al.: ‘Control of grid-following
Electron., 2007, 22, (2), pp. 584–592 inverters under unbalanced grid conditions’, IEEE Trans. Energy Convers.,
[25] Reyes, M., Rodriguez, P., Vazquez, S., et al.: ‘Enhanced decoupled double 2020, 35, (1), pp. 184–192
synchronous reference frame current controller for unbalanced grid-voltage
conditions’, IEEE Trans. Power Electron., 2012, 27, (9), pp. 3934–3943
[26] Boscaino, V., Cipriani, G., Di Dio, V., et al.: ‘Effects of post-filtering in grid-
synchronization algorithms under grid faults’, Electr. Power Syst. Res., 2018,
161, pp. 167–176
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 22, pp. 5093-5103 5103
© The Institution of Engineering and Technology 2020