Professional Documents
Culture Documents
Abstract—This paper presents implementations of a laboratory- STATCOM is an appropriate solution to mitigate voltage
scaled static synchronous compensator (STATCOM) for reactive unbalances in the grid caused by fluctuating loads such as arc
power compensation for unbalanced voltage sags. In order to furnaces [10,11]. In addition, fast and precise regulation of the
attenuate the effects of coupling terms between sequence
components, double decoupled synchronous reference frame voltage at critical loads and fulfillment of the reactive currents
(DDSRF) current controllers are implemented. Under this requirements of distributed generators connected to the grid
framework, adequate decoupling between positive and negative [12-14] stand out among the possibilities of the STATCOM.
sequence components can be achieved. PSCAD/EMTDC Mitigation of unbalanced voltage sags is addressed in [16-
simulator is used to verify implementation results. A 2kVA, 220 18] where voltage and current sequence components are
V AC, 60 Hz laboratory-scaled STATCOM platform is considered to produce an unbalanced set of compensating
constructed for evaluating the dynamic performance of the currents based on the double synchronous reference frame
DDSRF-based STATCOM when unbalanced voltage sags occur
(DSRF) scheme. Filtering techniques were used to attenuate
in a weak grid.
the effects of coupling 2 ω terms between the sequence
Keywords—Voltage Sag; Unbalanced Systems; Static components. The drawback of this approach is the inherent
Synchronous Compensator (STATCOM); Double Decoupled reduction of controller bandwidth caused by direct influences
Synchronous Reference Frame (DDSRF);Weak Grid; of filters in the control loop. To overcome this problem, recent
studies have confirmed that cancelation of the 2ω terms can be
achieved by the use of double decoupled synchronous
I. INTRODUCTION
reference frame (DDSRF) current controller [18,19]. In this
This work was supported in part by the National Science Council of Taiwan,
R.O.C., under Grant NSC 98-3114-E-007-004 and NSC 100-3113-E-007-006.
terminal voltages are denoted by Vta, Vtb, and Vtc. In Fig. 1, the sequence components of current controllers in the
resistance of the inductive filter (Rf) is combined with the synchronous reference frame (SRF), two new schemes will be
switching devices loss resistance (ron). In order to stabilize and examined: (i) double synchronous reference frame (DSRF)
filter the harmonic content at the PCC, a shunt capacitance scheme, and (ii) double decoupled synchronous reference
filter, Cf is added. The resistance Rf1 in series with Cf, provides frame (DDSRF) scheme.
damping at the resonance frequency. The point of common
A. Double Synchronous Reference Frame (DSRF) Control
coupling (PCC) voltages are labeled as Vsa, Vsb, and Vsc. In the
Fig. a load is also connected to the PCC. The grid voltages are
denoted by Vga, Vgb, and Vgc and the power line inductance is
represented by Lg.
CURRENT INJECTION
Under unbalanced grid faults, the currents injected by a ⎡ id − ⎤ ⎡ i d ⎤ ⎡ i d ⎤
− −
⎡ cos(δ − ) ⎤
STATCOM might include negative-sequence components;
+
idq = ⎢ − ⎥ = ⎢ − ⎥ + ⎢ − ⎥ = I− ⎢ ⎥
⎢⎣ iq ⎥⎦ ⎢ i q ⎥ ⎢⎣ i q ⎥⎦ sin(δ − ) ⎦⎥
⎣⎢ (3)
therefore inject a set of unbalanced currents. In order to ⎣ ⎦
D Cterms
attenuate the effects of coupling 2 ω terms between the ⎡ cos(2ω t ) ⎤ + ⎡
− sin(2 ω t ) ⎤
+ I + cos(δ + ) ⎢ ⎥ + I sin(δ ) ⎢
+
⎣ sin(2 ω t ) ⎦ ⎣ cos(2 ω t ) ⎥⎦
AC term s
In the above two equations (2)-(3), the appearance current errors ΔI+ and ΔI-, are free from oscillations, thus a
of 2 ω cross-coupling oscillations overlapping opposite low pass filter with cut-off frequency ω f = ω 2 can be used
sequence DC magnitudes is observed. PI controllers achieve to filter them, as proposed in [23] for PLL applications. Fig. 3
good tracking of the DC terms; however, the 2 ω oscillations shows the DDSRF current controller implementations.
produce steady state errors different from zero, thus causing
oscillations in the power delivered by the STATCOM. III. PCC AND DC VOLTAGE REGULATORS
B. Double Decoupled Synchronous Reference Frame The outer loop control of the STATCOM provides regulation
(DDSRF) Control of PCC and DC bus voltages, thus dictates the power
exchange dynamics. If the STATCOM guarantees balanced
The oscillations in the measured dq-currents under voltages at PCC, it is assumed that only the d-positive
unbalanced conditions must be avoided in order to provide sequence component of the voltage has a nonzero value, i.e.:
suitable compensating currents to regulate both, the PCC and Vd+=Vdref+, Vq+=0, Vd-=0, and Vq-=0. In the other hand, the
DC bus voltages of the STATCOM. The DDSRF current DC bus voltage, VDC, should remain constant at reference
controller minimizes the undesired oscillations by providing a value, VDC*. The convenience of controlling VDC2 instead of
decoupling structure based in the estimation of the amplitude VDC was presented in [22], given its direct relation with real
and phase of the coupling terms, maintaining the integrity of power.
the control loop [18,19] .
From (2) and (3), it is observed that the amplitude of
oscillations in the negative sequence is equal to the amplitude
of the DC term of the positive sequence injected current, and
vice versa. Therefore, it is feasible to use the DC current
references of opposite sequence components in the decoupling
structure. In addition, to minimize errors caused by sudden
perturbations at steady state, a measure of the error signal
feeding opposite sequence PI controllers is subtracted from the
current references.
The final expression of the DDSRF currents can be stated as
⎡cos(δ + ) ⎤
idq+ ' = I + ⎢ ⎥ Fig. 3. DDSRF current controller.
sin(δ + ) ⎦⎥
⎣⎢
Based in the deviation from the reference voltages, PI
DCterms
⎡cos(2ωt ) ⎤ ⎡sin(2ωt ) ⎤
compensators can be designed to produce the active and
+ I + cos(δ − ) ⎢ + I − sin(δ − ) ⎢ reactive power references of the STATCOM, P * and Q * ,
− sin(2ωt ) ⎥
cos(2ωt ) ⎥
⎣ ⎦ ⎣ ⎦
DCterms
DCterms
respectively. Then this power references are properly
ACterms
processed to feed the reference of the current controllers. This
⎡cos(2ωt ) ⎤ − ⎡
− sin(2ωt ) ⎤
(
)
− I −* − ΔI − cos(δ − ) ⎢ −*
⎣ − sin(2ωt ) ⎦
−
(
⎥ − I − ΔI sin(δ ) ⎢
⎣cos(2ωt ) ⎦
)
⎥ process is illustrated in Fig. 4.
DCterms DCterms
Cross − Couplingterms
DCterms
⎡cos(2ωt ) ⎤ + ⎡ − sin(2ωt ) ⎤
+ I + cos(δ + ) ⎢ + I sin(δ + ) ⎢
sin(2ωt ) ⎥
cos(2ωt ) ⎥
⎣ ⎦ ⎣ ⎦ Fig. 4. Outer voltage loop controller of the STATCOM.
DCterms
DCterms
ACterms
⎡cos(2ωt ) ⎤ + ⎡
− sin(2ωt ) ⎤ IV. SIMULATION AND EXPERIMENTAL RESULTS
(
)
− I +* − ΔI + cos(δ + ) ⎢ +*
⎣sin(2ωt ) ⎦
+
(
⎥ − I − ΔI sin(δ ) ⎢
⎣cos(2ωt ) ⎦
⎥)
The STATCOM experimental platform schematic is
DCterms
DCterms
Cross − Couplingterms presented in Fig. 5. The proposed control strategy based in the
for the negative- sequence current component, where I+* and DDSRF current controller is performed using a TI F28335
ΔI+ are the reference and error signals in the positive sequence microcontroller. The parameters used in the experimental
component, respectively. Under steady state conditions, the platform and in the simulations are presented in Table 1. It is
worth mentioning that a large value for grid inductance, Lg, is pu and 0.035 pu, respectively. The voltage unbalance ratio
chosen in order to emulate a weak grid resembling the voltage (VUR) during the fault is 7.5%.
conditions at rural areas far away from main generators. The The compensating effect of the STATCOM is shown in Fig.
purpose of this configuration is to request reactive power 7, where three phase voltages are regulated at rated 220V
compensation from the STATCOM to reach the steady state RMS. The occurrence of the voltage sag at time 150 ms,
voltage. Moreover, the parameters Kp and Ki of current and observes a decrease to 0.95 pu in Vd+. Given the fast response
voltage controllers are determined to achieve desired closed- of the controller, the steady state is recovered within 50 ms,
loop unit-step response [21]. corresponding to 3 fundamental frequency periods.
The VUR during STATCOM compensation is depicted in
Fig. 7 (d). Since the outer loop control has a fast response, the
VUR reaches a maximum value of 2.1 % at the beginning and
end of the sag.
400
V Vbc V 1
ab ca
300
200 0.8
V+d
100
(p u )
(V )
0.6 0.85 pu
0
PC C
PCC
0.4
V
-100 0.75 pu
V
-200 0.2 +
Vq
-300
0
-400
Fig. 5. STATCOM experimental platform. 0 50 100 150 200 250
Time (ms)
300 350 400 450 500 0 50 100 150 200 250
Time (ms)
300 350 400 450 500
V U R (% )
V base 220 V AC Power factor 0.8 Lagging
I base 5.25 A Load Resistance (R L, R L1 ) 19.36 Ω, 24Ω 0.02 4
V PC C (p u )
+ 0.6
Vd Proportional gain (Kp Vd) 10 pu 0
+
Vd Integral gain (KiVd) 76 pu -100 0.4
Inner Loop Bandwidth 696 rad/sec Vd - , Vq- Proportional gain (Kp V2) 4 pu -200 0.2 Vq
+
Outer Loop PCC control Bandwi 162 rad/sec Vd - , Vq- Integral gain (KiV2) 24 pu -300
0
-400
0 50 100 150 200 250 300 350 400 450 500 0 50 100 150 200 250 300 350 400 450 500
VUR
2
(A)
0 Vabc (V)
abc
I
-2
-4
-6
-8
0 50 100 150 200 250 300 350 400 450 500
Time (ms)
Vd- (pu)
(b)
Fig. 10. Experimental PCC voltages without compensation. (a) Three
Fig. 9. Experimental platform of STATCOM. phase voltages and Vd+; (b) Three phase voltages and Vd-
Vabc (V)
The uncompensated voltages measured from the
experimental platform are shown in Fig. 10. In addition to the
three phase voltages, the d-positive sequence component is
also shown in Fig. 10(a) and the homologous d-negative
sequence component in Fig 10(b).
Vd+ (pu)
The PCC voltages obtained when the STATCOM is online
are shown in Fig. 11. The steady state Vd+ voltage is boosted
to 1.0 pu in accordance with the simulation results. The
unbalanced sag is generated at time 150 ms, and the
STATCOM injects a set of unbalanced currents to the PCC
during the sag in order to maintain the PCC voltage at rated
conditions. The settling time to recover steady state voltage is Fig. 11. Experimental three phase and Vd+ PCC voltages when the
65 ms. At the end of the sag, a set of balanced compensating STATCOM is online.
currents is delivered. REFERENCES
V. CONCLUSIONS [1] T. Davis, G. E. Beam, and C. J. Melhorn, “Voltage sags: their impact
on the utility and industrial customers,” in Industrial and Commercial
In this paper, the analysis and implementation of a Power Systems Technical Conference Record, pp. 65-73, 1996.
laboratory scaled STATCOM was performed and evaluated in [2] “IEEE Recommended Practice for Monitoring Electric Power Quality,”
a weak grid configuration. The DDSRF current control IEEE Std 1159-1995, p. i, 1995.
strategy was adopted, and proved to be a suitable solution to [3] [3] A. Sannino, M. G. Miller, and M. H. J. Bollen, “Overview of
voltage sag mitigation,” in IEEE Power Engineering Society Winter
provide reactive power compensation during unbalanced
Meeting, , vol.4, pp. 2872-2878, 2000.
voltage sags without compromising the bandwidth of the [4] P. Rao, M. L. Crow, and Z. Yang, “STATCOM control for power
controller. The average response of the implemented system voltage control applications,” IEEE Trans. Power Delivery, vol.
controller is 50 ms. Simulations in PSCAD/EMTDC and 15, pp. 1311-1317, 2000.
[5] P. S. Sensarma, K. R. Padiyar, and V. Ramanarayanan, “Analysis and
performance evaluation of a distribution STATCOM for compensating
voltage fluctuations,” IEEE Trans. Power Delivery, vol. 16, pp. 259-
264, 2001.
[6] W. Sung-Min, K. Dae-Wook, L. Woo-Chol, and H. Dong-Seok, “The
distribution STATCOM for reducing the effect of voltage sag and
swell,” in The 27th Annual Conference of the IEEE Industrial
Electronics Society, 2001. IECON '01, vol.2, pp. 1132-1137, 2001.
[7] L. Kuang, L. Jinjun, W. Zhaoan, and W. Biao, “Strategies and
Operating Point Optimization of STATCOM Control for Voltage
Unbalance Mitigation in Three-Phase Three-Wire Systems,” IEEE
Trans. Power Delivery, vol. 22, pp. 413-422, 2007.
[8] A. Edris, “FACTS technology development: an update,” IEEE Power
Engineering Review, vol. 20, pp. 4-9, 2000.
[9] N. Mithulananthan, C. A. Canizares, J. Reeve, and G. J. Rogers,
“Comparison of PSS, SVC, and STATCOM controllers for damping
power system oscillations,” IEEE Trans. Power Systems, vol. 18, pp.
786-792, 2003.
[10] H. Chong, Y. Zhanoning, C. Bin, A. Q. Huang, Z. Bin, M. R. Ingram,
and A. A. Edris, “Evaluation of Cascade-Multilevel-Converter-Based
STATCOM for Arc Furnace Flicker Mitigation,” IEEE Trans. Industry
Applications, vol. 43, pp. 378-385, 2007.
[11] C. Schauder, “STATCOM for compensation of large electric arc
furnace installations,” in IEEE Power Engineering Society Summer
Meeting, 1999., vol.2, pp. 1109-1112, 1999.
[12] H. Chong, A. Q. Huang, W. Litzenberger, L. Anderson, A. A. Edris, M.
Baran, S. Bhattacharya, and A. Johnson, “STATCOM Impact Study on
the Integration of a Large Wind Farm into a Weak Loop Power
System,” in 2006 IEEE PES Power Systems Conference and Exposition,
pp. 1266-1272, 2006.
[13] C. Wessels, F. W. Fuchs, and M. Molinas, “Voltage control of a
StatCom at a fixed speed wind farm under unbalanced grid faults,” in
IECON 2011 - 37th Annual Conference on IEEE Industrial Electronics
Society, pp. 979-984, 2011.
[14] M. Molinas, S. Jon Are, and T. Undeland, “Low Voltage Ride Through
of Wind Farms With Cage Generators: STATCOM Versus SVC,”
IEEE Trans. Power Electronics, vol. 23, pp. 1104-1117, 2008.
[15] C. Hochgraf and R. H. Lasseter, “STATCOM controls for operation
with unbalanced voltages,” IEEE Trans. Power Delivery, vol. 13, pp.
538-544, 1998.
[16] E. Twining, M. J. Newman, P. C. Loh, and D. G. Holmes, “Voltage
compensation in weak distribution networks using a D-STATCOM,” in
The Fifth International Conference Power Electronics and Drive
Systems, vol.1, pp. 178-183, 2003.
[17] B. Blazic and I. Papic, “Improved D-StatCom control for operation
with unbalanced currents and voltages,” IEEE Trans. Power Delivery,
vol. 21, pp. 225-233, 2006.
[18] M. Reyes, P. Rodriguez, S. Vazquez, A. Luna, R. Teodorescu, and J.
M. Carrasco, “Enhanced Decoupled Double Synchronous Reference
Frame Current Controller for Unbalanced Grid-Voltage Conditions,”
IEEE Trans. Power Electronics, vol. 27, pp. 3934-3943, 2012.
[19] R. Teodorescu, M. Liserre, and P. Rodríguez, Grid Converters for
Photovoltaic and Wind Power Systems: Wiley, 2011.
[20] C. D. Schauder and R. Caddy, “Current Control of Voltage-Source
Inverters for Fast Four-Quadrant Drive Performance,” IEEE Trans.
Industry Applications, vol. IA-18, pp. 163-171, 1982.
[21] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power
Systems: Wiley, 2010.
[22] S. Hong-Seok and N. Kwanghee, “Dual current control scheme for
PWM converter under unbalanced input voltage conditions,” IEEE
Trans. Industrial Electronics, vol. 46, pp. 953-959, 1999.
[23] P. Rodriguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D.
Boroyevich, “Decoupled Double Synchronous Reference Frame PLL
for Power Converters Control,” IEEE Trans. Power Electronics, vol. 22,
pp. 584-592, 2007.