You are on page 1of 6

A Method to Reduce DC-link Overvoltage of PMSG

Based WECS during LVRT


Papan Dey, Manoj Datta, Nuwantha Fernando Tomonobu Senjyu
School of Electrical and Computer Engineering, Dept. of Electrical and Electronics of Engineering,
RMIT University, Melbourne, University of the Ryukyus, Nishihara
Victoria 3000, Australia Okinawa, Japan

Abstract—Low Voltage Ride-Through (LVRT) is one of the The organisation of this paper is as follows: PMSG based
most important grid connection requirements for the wind wind turbine with conventional control is described in Section
energy conversion systems (WECS). In this paper, flux II. The proposed control is discussed in Section III. Simulation
weakening control of permanent magnet synchronous generator results with analysis and discussions are presented in Section
(PMSG) based WECS is proposed to reduce the DC-link IV. Finally, conclusions are drawn in Section V.
capacitor overvoltage for the enhancement of LVRT during
symmetrical and asymmetrical grid voltage dips. The controller II. DESCRIPTION OF SYSTEM AND CONTROL
is developed based on the proportional resonant (PR) current A block diagram of the grid connected PMSG based
controller. The proposed method is compared with the braking WECS is shown in Fig.1. It comprises of a wind turbine,
chopper (BC) based conventional method. Time series simulation
PMSG, machine side converter (MSC), DC- link capacitor and
results illustrate the validity and effectiveness of the proposed
control.
a grid side converter (GSC). The system is connected to grid
via transformer and transmission lines. The PMSG is modelled
Keywords— Low voltage ride through (LVRT); Flux weakenin; with the d-q equivalent circuits [4],[5].The grid side voltage is
Permanent magnet synchronous generator (PMSG); Fault; Dc-link d-axis oriented; hence voltage of q-axis is zero.
voltage A. Control of MSC
I. INTRODUCTION MSC is controlled by applying zero α-axis component of
stator current. Two independent PR controllers are designed as
PMSG based wind turbine generator (WTG) with back to back shown in Fig. 1.They control the α-axis and ȕ- axis currents
converters has achieved a lot of interest due to its excellent such as current of α- axis to be zero and current of ȕ- axis can
performance in the aspect of LVRT during grid faults [1]. The
utilize the torque of the generator.
control methods to limit DC-link capacitor overvoltage during
fault ride through (FRT) mostly contain: unloading circuit
B. Control of GSC
installation at converter DC-link to absorb the excess power;
For the GSC, two PI controllers are designed as shown in
energy storage element connection at the DC-link, e.g., super
Fig. 1. The d-axis PI current control loop is for controlling the
capacitor for quick active power exchange; connecting a
voltage of DC-link and to inject the real power and the PI loop
secondary converter in parallel to the DC-link to deliver a
of q-axis current is used for controlling the reactive power or
bypass for excess power [2]. These types of arrangements
for the regulation of grid voltage [6].
require additional devices; increase the size of converter and
system cost as well as the controller becomes complicated [3]. C. Conventional control with the BC
Flux weakening control is an established technique for motor The BC [6] is used in the DC-link for the active power
drives. However; its use for LVRT of WTG is not reported in dissipation during the grid faults. It comprises of a high power
any literature so far. This method weakens the flux of PMSG resistor with a series switch which is shown in Fig.2 (a).
by supplying negative field regulating current to use the Control of BC is based on voltage limit. The real voltage
maximum voltage limit of the converter. For flux weakening frequently tracks the reference voltage via a hysteresis-band.
region, it is required to limit the current and voltage of the Pre-set higher and lower tolerance limits are matched to the
converter and the generator. The voltage limit is selected extracted signal as shown in Fig.2 (b). As long as the signal is
based on the generator rated voltage or the DC-link voltage. within the tolerance band, no switching action is taken.
Therefore, DC-link voltage is related with the flux weakening Switching occurs whenever the voltage signal crosses the
control. threshold voltage limit.
In this paper, a PR current controller based flux weakening
method is adopted to minimize the DC-link overvoltage and to III. PROPOSED CONTROL METHOD
enhance the LVRT performances during symmetrical and At the time of symmetrical and asymmetrical grid faults,
asymmetrical grid faults. From numerical simulation results, it high voltage is induced in the rotor of the PMSG due to the
is evident that the proposed method works satisfactorily to flux linkages [7]. This induced EMF is higher enough
limit DC-link over voltage during grid faults. compared to the usual EMF under normal operating condition
and it exceeds the maximum voltage of the MSC.

978-1-5090-2597-8/16/$31.00 2016
c IEEE 1894
Fig. 1. Grid connected PMSG with back to back converter

V max = 1 / 3 V dc is considered for the sinusoidal vector


modulation. Imax is defined by the power ratings of the
generator and converter. To maximise the torque per ampere
ratio Iα is set to zero at low speeds for surface mounted PMSG
[8], [9]. It indicates that by injecting negative ъ-axis current,
the total flux in PMSG windings can be decreased.
Fig. 2(a). Wind turbine with DC-link BC protection Though PI controller is frequently considered in conventional
flux weakening control, it requires axis transformations and it
cannot track sinusoidal reference currents without static
tracking error. To realise good dynamic performance, the
decoupling current control system are usually used in the MSC
with cross-coupling terms and feed forward compensation
Fig. 2 (b). BC controller block diagram terms. These terms vary with the circuit parameters and
temperature and affect the system robustness.
Due to this voltage, high current flows in the rotor circuit that
can damage the converter and can increase the DC-link In the decoupling current control system, an integrator is used
voltage above the acceptable limit. As the excitation of the for steady-state error elimination. This integrator’s
magnetic field is constant, the induced voltage increases with performance can be improved, by transforming it in to a
the increase of the rotor speed [8]. Therefore, the field resonator to track the sinusoidal reference current via (3)
excitation has to be adjusted to achieve a constant DC-link
voltage. Gac ( S ) = Gdc ( S − jω 0 ) + G dc ( S + jω 0 ) (3)
In stationary frame, the three phase stator currents can be Now the equivalent transfer function Gac(s) is
represented as the flux current component, Iα and the torque 2S
current component, Iȕ; and at any time, the limits of voltage Gac ( S ) = K i ( S ) * (4)
S + ω0
2 2
and current must satisfy the following:

Vα + Vβ ≤ Vmax (1)
2 2 2
Therefore, the transfer function of PR controller is
I α + I β ≤ I max
2 2 2 2S
(2) G PR ( S ) = K P + K i ( S ) * (5)
S + ω0
2 2

where, the maximum magnitude of phase voltage and phase


current is Vmax and Imax respectively. Vmax is determined by the where, Ki and Kp are the proportional constant and the time
available DC-link voltage, Vdc and the converter modulation integral constant respectively. Ȧ0 is the resonant frequency
method. [10].

2016 IEEE Region 10 Conference (TENCON) — Proceedings of the International Conference 1895
limit with the proposed control and overall fluctuations and
transients are less than that of the conventional control.

However, at the fault clearance time of 1.5s, the proposed


method shows little higher DC-link voltage transients
compared to the conventional method. Coordination of the
MSC and GSC controllers along with better gain tuning will
minimize these transients.

B. Asymmetrical Fault
For the second simulation scenario, a double line to ground
fault is considered. It is the most common type of grid fault
Fig.3. PR based Flux weakening control for MSC and is applied on the 25 kV line of Fig. 1 at 1s. The fault
duration is 0.5s. Simulation results by using the conventional
The PR based flux weakening control diagram is shown in control with BC are shown in Fig. 6 and by using the proposed
Fig. 3.Using Clarke transformation three phase ac currents can method are shown in Fig. 7 for asymmetrical grid fault.
be converted into orthogonal Į-ȕ currents. The difference
between PR current controllers’ output voltages (V*α, V*β) and As shown in Fig. 6 (a) and Fig. 7(a), a medium dip in the grid
the converter DC-link voltage is passed through a PI controller voltage is occurred and the grid voltage is reduced from 100%
and a limiter to generate the Id reference current for flux of its nominal value to 60%. As a consequence, the DC-link
weakening control. Iq reference current is the difference voltage is increased to approximately 1.4 times its rated value
between maximum converter current and Id reference current. as shown in Fig. 6(e) and Fig. 7(e) respectively without any
Then the Id and Iq reference currents are transformed to LVRT control.
generate IĮ reference current. It can be noticed that, there is no
coupling terms (ȦeLdsIds, ȦeLdsIqs) and feed forward The LVRT control takes action and the fault is cleared at 1.5s.
compensation term (Ȧeijs ) eliminating the impact of the Grid current, generator voltage, generator current during this
circuit parameters on the control system, which improves condition are shown in Figs. 6(b) to(d) and Figs. 7(b) to(d) for
system robustness [11]. the conventional control and the proposed control
respectively. From Fig. 6(e) and Fig. 7(e), it is observed that
IV. SIMULATION RESULTS AND ANALYSIS the DC-link voltage is quite well regulated within the
Numerical simulation results are obtained in acceptable limit with the proposed control and overall
MATLAB/Simulink for a 1.5 MW WECS during grid faults. fluctuations and transients are quite less than that of the
Simulation time is 2 seconds. conventional control.

A. Symmetrical Fault For the asymmetrical fault, at the fault clearance time of 1.5s,
A three line to ground fault is considered as the most severe the proposed method shows very few DC-link voltage
type of grid fault and is applied on the 25 kV line of Fig. 1 at transients compared to the conventional method. With the
1s. This fault duration is 0.5s. Simulation results by using the coordination of the MSC and GSC controllers and better gain
conventional control with BC are shown in Fig. 4 and by using tuning these transients can ne minimized more.
the proposed method are shown in Fig. 5 for symmetrical grid
fault. V. CONLUSION
From Fig.4 (a) and Fig. 5(a), it is observed that a large dip in To limit the DC-link capacitor overvoltage during LVRT of
the grid voltage is occurred and the grid voltage is reduced direct driven PMSG based WECS, this paper proposed a
from 100% of its nominal value to 30%. As a consequence, control technique based on flux weakening. From the
the DC-link voltage is increased to approximately 1.5 times of numerical simulation results, it is observed that the proposed
its rated value as shown in Fig. 4(e) and Fig. 5(e) respectively method is capable of limiting the DC-link overvoltage under
without any LVRT control. symmetrical and asymmetrical grid faults. Due to the
simplicity and effectiveness of the proposed control, it can be
The LVRT control takes action and the fault is cleared at 1.5s. a superior choice compared to the conventional control during
Grid current, generator voltage, generator current during this LVRT. Future works will coordinate the proposed control with
condition are shown in Figs. 4(b) to(d) and Figs. 5(b) to(d) for the pitch angle and GSC controls to provide a better during
the conventional control and the proposed control and after fault transient performances validated through
respectively. From Fig. 4(e) and Fig. 5(e), it is observed that experimental results.
the DC-link voltage is well regulated within the acceptable

1896 2016 IEEE Region 10 Conference (TENCON) — Proceedings of the International Conference
(a) (a)

(b) (b)

(c) (c)

(d) (d)

(e) (e)
Fig. 4. Simulation results using the BC for the symmetrical grid fault. (a) Grid Fig. 5. Simulation results using the proposed controller for the asymmetrical
voltage; (b) Grid current; (c) Generator voltage; (d) Generator current; (e) DC- grid fault. (a) Grid voltage; (b) Grid current; ( c) Generator voltage; (d)
link voltage. Generator current; (e) DC-link voltage

2016 IEEE Region 10 Conference (TENCON) — Proceedings of the International Conference 1897
(a) (a)

(b) (b)

(c) (c)

(d) (d)

(e) (e)
Fig.6. Simulation results using the BC for the asymmetrical grid fault. (a) Grid Fig.7. Simulation results for flux weakening controller a) Grid voltage b) Grid
voltage; (b) Grid current; (c) Generator voltage; (d) Generator current; (e) DC- current c) Generator voltage d) Generator current e) DC voltage
link voltage.

1898 2016 IEEE Region 10 Conference (TENCON) — Proceedings of the International Conference
REFERENCES
[1] B. Jain, S. Jain, R.K. Nema, "Control strategies of grid interfaced
wind energy conversion system: An overview," Renewable and
Sustainable Energy Reviews, vol. 47, pp. 983-996, 2015.
[2] S. Zhang, K.-J. Tseng, D. M. Vilathgamuwa, T. D. Nguyen, and
X.-Y. Wang, "Design of a robust grid interface system for PMSG-
based wind turbine generators," IEEE Transactions on Industrial
Electronics, vol. 58, pp. 316-328, 2011.
[3] M. Singh, V. Khadkikar, and A. Chandra, "Grid synchronisation
with harmonics and reactive power compensation capability of a
permanent magnet synchronous generator-based variable speed
wind energy conversion system," IET Power Electronics, vol. 4,
pp. 122-130, 2011.
[4] V. Yaramasu, B. Wu, S. Alepuz, and S. Kouro, "Predictive Control
for Low Voltage Ride-Through Enhancement of Three-Level
Boost and NPC Converter based PMSG Wind Turbine," IEEE
Transactions on Industrial Electronics, vol.61, no. 12, 2014.
[5] K.-H. Kim, Y.-C. Jeung, D.-C. Lee, and H.-G. Kim, "LVRT
scheme of PMSG wind power systems based on feedback
linearization," IEEE Transactions on Power Electronics, vol. 27,
pp. 2376-2384, 2012.
[6] M. Nasiri, J. Milimonfared, and S. Fathi, "A review of low-voltage
ride-through enhancement methods for permanent magnet
synchronous generator based wind turbines," Renewable and
Sustainable Energy Reviews, vol. 47, pp. 399-415, 2015.
[7] M. Chowdhury, W. Shen, N. Hosseinzadeh, and H. Pota, "A
review on transient stability of DFIG integrated power system,"
International Journal of Sustainable Engineering, pp. 1-12, 2015.
[8] Z. Zhou, F. Scuiller, J. F. Charpentier, M. El Hachemi Benbouzid,
and T. Tang, "Power smoothing control in a grid-connected marine
current turbine system for compensating swell effect,", IEEE
Transactions on Sustainable Energy, vol. 4, pp. 816-826, 2013.
[9] P. Sandulescu, F. Meinguet, X. Kestelyn, E. Semail, and A.
Bruyere, "Control Strategies for Open-End Winding Drives
Operating in the Flux-Weakening Region," IEEE Transactions on
Power Electronics, vol. 29, pp. 4829-4842, 2014.
[10] D.Zmood and D. G. Holmes, “ Stationary frame current regulation
of PWM inverters with zero steady-state error,” IEEE Transactions
on Power Electronics. 2003,18( 3): 814–822.
[11] Y. Jiang, Q. Pu, S. Huang, Z. Xu, K. Huang, and L. Xiao,
"Improved method on flux-weakening control of permanent
magnet synchronous motor in electric vehicles," in International
Conference on Electrical Machines and Systems (ICEMS), 2011,
pp. 1-4.

2016 IEEE Region 10 Conference (TENCON) — Proceedings of the International Conference 1899

You might also like