Product Brochure

V Series
Expulsion Dropout Fuses
V Series
Expulsion Dropout Fuses

V Series single pole, single insulator, single venting expulsion


drop-out (EDO) disconnector fuse unit is designed to be
used on overhead distribution systems in a totally exposed
environment. The V Series Drop-out disconnector fuse
unit can primarily be used for the protection of distribution
transformers and the protection of spur sections of overhead
lines from the main backbone line.

Key Features
—— complies with AS 1033.1-1990.
IEC Publication 60282-2:1995
ANSI/NEMA specifications

—— Rated voltage 24 kV and 36 kV

—— Rated current: 100 A

—— Breaking capacity : 6 and 8 kA (24 kV),


2 and 4 kA (36 kV).

—— Porcelain or polymer insulators up to 170 kV BIL

—— UV resistant, high strength fibreglass fuse holder

—— Silver plated copper contacts

—— Corrosion resistant Stainless steel 316 ferrous


components- durable in harsh environment

—— Choice of 10 kA and 16 kA Earth stirrup

—— Accessories such as Emission control device, bird


cap,stand-off insulator mounting bracket, etc.

2 | V Series brochure
Construction

Fuse Carrier Other Features


The fuse carrier is a high strength fibreglass filament wound A flipper spring mechanism is incorporated to assist ejection
tube with a UV resistant external coating. An inner liner of of the fuse link. This mechanism also incorporates a
bone fibre is used for arc quenching. mechanical stop to prevent strain on the fuse link when the
carrier is being closed. The fuse link tail is held clear of the
The fuse carrier is self aligning with a spring loaded top tube liner to minimize corona.
socket contact. This socket also prevents the closure of the
fuse without the top cap. The trunnion design uses a pressure Clamp supports are supplied for interfacing to a live line
die casting made from high tensile leaded brass. Die casting clamp or an earthing clamp. They can be fitted adjacent to
requires precision tooling and produces a casting of superior the top or bottom contacts of the fuse unit.
finish and dimensional tolerance. The design ensures the
hinge cannot distort even when closing or opening the carrier Type “V” expulsion dropout fuses are provided with hooks
with a hook stick operated at an angle to the fuse mount. allowing attachment of a portable load break device.

The fuse tube is clearly marked with the year of manufacture Emission Control
and reflective tape on the fuse tube easily identifies that the The “V” Series Expulsion Dropout Fuse when used with ABB
fuse has blown, even at night.. PROLINK type fuse links significantly reduces the risk of
emission of incandescent particles. However, incandescent
Contacts particles which have the capability of igniting combustible
The top contact assembly and the bottom hinge are materials, such as dry grass, may still be emitted.
assembled using a sizing jig to eliminate the risk of
misalignment. All the main current carrying parts are silver
plated with a minimum of 12 µm ensuring minimum electrical
resistance even after many closing and opening operations.
The hinged contacts have parallel spring loaded current
carrying parts. All contacts have a wiping action.

Terminal Palms
The assembly is fitted with bright tin plated copper terminal
palms, fitted stainless steel pressure pad, stud, nut and
washer. The terminal pads will accept copper or aluminium
terminal lugs or stranded conductors for 16 mm2 to 193 mm2
cross section areas.

Insulator
The insulator is designed to reduce the possibility of flashover
due to birds or animal life without the use of plastic or
rubber coverings which may cause radio interference or
require regular replacement. The insulator is available in
various creepage lengths and is suitable for use in adverse
environments. The insulator colour is Munsell Grey for
improved environmental appearance.

V Series brochure | 3
Selection Table

“V” Series Style Code: V150 PL 6 S 00 0 0

Rated Voltage:
12/24 kV, Insulator BIL: 150 V150
33/36 kV, Insulator BIL: 170 V170

Type of Insulator:
Polymer PL
Porcelain PC

Rated Breaking Capacity:


2 kA (For 33/36 kV) 2
4 kA (For 33/36 kV, with arc shortening rod) 4
6 kA (For 12/24 kV) 6
8 kA (For 12/24 kV, with arc shortening rod) 8

Mounting Bracket:
Standard Bracket S
NEMA Bracket N
Cycloaliphatic “Stand-off” insulator and bracket C
Direct to pole Bracket D

Earth Stirrup:
None 00
10 kA 10
16 kA 16

Emission Control Device (ECD):


None 0
Standard ABB ECD 1

Bird Cap:
None 0
Standard ABB Bird Cap 1

EDO C/W Stand-off insulator Standard EDO EDO C/W Earth stirrup

4 | V Series brochure
V Series brochure | 5
12.8

12.8

15.8
11.3

11.3

11.3
6.8

6.8

7.7

7.7

6.8

7.7
Total Weight in (kg) Total Weight in (kg)
-To earth and between -To earth and between
145

145
phases phases
Rating Lightening Rating Lightening
Impulse in (kV) Impulse in (kV)
150

165

150

165
-Across isolating distance -Across isolating distance
-To earth and between -To earth and between
50

70

50

70
Rated Power phases Rated Power phases
Frequency
Frequency Withstand
Withstand Voltage
Voltage (Wet) in (kV) (Wet) in (kV)
-Across isolating distance -Across isolating distance
60

80

60

80
Porcelain

Porcelain

Porcelain

Porcelain

Porcelain
Polymer

Polymer

Polymer

Polymer

Polymer
Insulator Material Insulator Material
620
460
620
460
730
660
730
660

620

730
660
Insulator Creepage in (mm) Insulator Creepage in (mm)

50-60

50-60
Rated Frequency in (Hz) Rated Frequency in (Hz)

Customized Units (C/W earth stirrup, bird cap or ECD)


12-24

33-36

12-24

33-36
Rated Voltage in (kV) Rated Voltage in (kV)
Rated Breaking Capacity in (kA) Rated Breaking Capacity in (kA)

2
4
100

100
Rated Current (Continuous) in (A) Rated Current (Continuous) in (A)
Technical Data

Standard Units

V170PC4C0001
V150PC6S0000

V150PC8S0000

V170PC2S0000

V170PC4S0000
V150PL6S0000

V150PL8S0000

V170PL2S0000

V170PL4S0000

V150PL8S1600
V150PL8S1000
V170PL2S1000
Style Code

Style Code
480

558
564
558
564
Overall height
M

314

393
399
393
399
Fuse holder length at engagement
L

Width of mounting bracket

50
K

125
129
125
129
115
120
115
120
J Outer diameter of insulator

550
520
550
520
564
534
564
534
Overall length

I
Diameter of mounting bracket hole

22
H
Distance of mounting bracket hole to the

40
G
edge
Inner diameter of hook ring

33
F

315

400
Fuse holder clearance

E
Insulator angle with upright plane

18
D

170
Mounting bracket length

C
General Configuration

110
Mounting bracket overlap on X-Arm

B
Mounting bracket thickness

10
A

All Dimensions are in mm

6 | V Series brochure
V150PC6S0000

V150PC8S0000

V170PC2S0000

V150PC4S0000
V150PL6S0000

V150PL8S0000

V170PL2S0000

V170PL4S0000
Style Code
Accessories

Earth Stirrup Bracket 16 kA Earth Stirrup

10 kA Earth Stirrup Bird Cap

Emission Control Device ‘Stand-off’ Insulator + Bracket

V Series brochure | 7
Contact

For more information please contact: Note

While care has been taken to ensure that the

V series brochure
Medium Voltage Products information contained in this document is
1 Baupaume Road correct, no responsibility can be accepted for any
inaccuracy. We reserve the right to alter or modify
Moorebank, NSW 2170 Australia
the information contained herein at any time in the
Phone: +61 2 9753 7111 light of technical or other developments. Technical
Fax: +61 2 9602 2454 specifications are valid under normal operating
conditions only. We do not accept any responsibility
for any misuse of the product and cannot be
www.abbaustralia.com.au
held liable for indirect or consequential damages.
Technical data and design is subject to change and
should be confirmed prior to ordering.

We reserve all rights in this document and in the


subject matter and illustrations contained therein.
Any reproduction–in whole or in parts–is forbidden
without ABB’s prior written consent.

Copyright 2013 ABB.

All rights reserved.