Product Guide: Relion® Protection and Control
Product Guide: Relion® Protection and Control
REX640
Product Guide
1MRS759144 B
REX640
Product version: 1
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2019 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
1MRS759144 B
REX640
Product version: 1 Issued: 2019-03-27
Revision: B
Feeder earth-fault
APP1
protection extension package
APP2
Feeder fault
locator package
APP3
Line distance
protection package
Line differential
APP4
protection package
Shunt capacitor
APP5
protection package
BASE Interconnection
FUNCTIONALITY APP6
protection package
Basic protection funtions Machine Synchronous
ADD1
Supervision functions APP7
protection package machine add-on
Measurement functions
Circuit breaker control fuction APP8
Power transformer ADD2 Three-winding
Disconnector control function protection package transformer add-on
Other functions
APP9
Busbar
protection package
APP10
Tap-changer control
package
Generator
APP11
autosynchronizer package
APP12
Network
autosynchronizer package
APP13
Petersen coil
control package
GUID-E397D6D3-D077-41CB-8ADB-58F4A91EB7E5 V1 EN
ABB 3
1MRS759144 B
REX640
Product version: 1
3. Relay hardware
The relay has mandatory and optional slots. A mandatory slot
always contains a module but an optional slot may be empty,
depending on the composition variant ordered.
ARC1001 o
COM1001 ●
COM1002 ●
COM1003 ●
COM1004 ●
COM1005 ●
BIO1001 ● o o
BIO1002 ● o o
BIO1003 o
BIO1004 o
RTD1001 o o
AIM1001 o ●
AIM1002 o ●
SIM1001 o ●
PSM1001 ●
PSM1002 ●
PSM1003 ●
● = Mandatory to have one of the allocated modules in the slot
o = Optional to have one of the allocated modules in the slot. The population (order) of the modules in the optional slots depends on the composition
variant ordered.
4 ABB
1MRS759144 B
REX640
Product version: 1
GUID-5D4C7B10-17CA-4F59-B9E0-8024CB82CDE8 V1 EN
ABB 5
1MRS759144 B
REX640
Product version: 1
Module Description
BIO1001/
14 × BI + 8 × SO
BIO1003
BIO1002/
6 × SPO + 2 × SPO (TCS) + 9 × BI
BIO1004
AIM1002 6 × CT + 4 × VT
The relay has a nonvolatile memory which does not need any events, recordings and logs to a memory which retains data if
periodical maintenance. The nonvolatile memory stores all the relay loses its auxiliary supply.
6 ABB
1MRS759144 B
REX640
Product version: 1
4. Local HMI
The LHMI uses rugged 7-inch high resolution color screen with
capacitive touch sensing technology. The user interface has
been carefully designed to offer the best situational awareness
to the user. Visualization of the primary process measurements,
events, alarms and switching objects’ statuses makes the local
interaction with the relay extremely easy and self-evident. The
LHMI provides a control point for the selected primary devices
via pop-up operator dialogs.
GUID-1A1D14B1-CE6F-4D39-8397-16EE6FDB015D V1 EN
ABB 7
1MRS759144 B
REX640
Product version: 1
Engineer pages
Operator pages
GUID-1B2FF5EE-2AC9-4EA3-A342-03857EDAB52C V1 EN
The LHMI is an accessory for the relay which is fully operational Additionally, the LHMI contains one Ethernet service port with
even without the LHMI. The relay communication card has a an RJ-45 connector and one USB port. The service port can be
dedicated port where the LHMI is connected using an RJ-45 used for the PCM600 connection or for Web HMI connection.
connector and a CAT6 S/FTP cable. The LHMI can be Data transfer to a USB memory is enabled via the USB port. By
connected to the relay also via station communication network default the USB port is disabled and has to be taken into use
if a longer distance is required between the relay and the LHMI. with a specific parameter.
8 ABB
1MRS759144 B
REX640
Product version: 1
1 2
GUID-D53AE6BA-8746-4796-B1C9-13352190FAEA V1 EN
1 USB port
2 RJ-45 ports
ABB 9
1MRS759144 B
REX640
Product version: 1
5. Application
3U
Uo
3× 3× AND
3I I2/I1> 3Ith>F 3I>/Io>BF Io>>> - 7-inch color touch screen OR
46PD 49F 50BF 50G/50N - Ready-made pages and
customizable pages
- Increased situational awareness
3× 3× 3× 3× 3× towards process
Io> Io>> 3I> 3I>>
3I>>> - Supports Relay testing and
51G/ 51G/ 51P-1 51P-2
50P commissioning
51N-1 51N-2
- Graphical editing of pages with
2× 4× 4× 4× 4× PCM600 tool
3I(U) 3U> Uo> U2> U1>
51V 59 59G/59N 59NS 59PS
U CONDITION MONITORING COMMUNICATION
3× 3× 4× 2× AND SUPERVISION
3I>→ 3I>>→ Io>→ Io>>→ Protocols:
I2>→
67P/ 67P/ 67G/N-1 67G/N-2 67Q IEC 61850-8-1/-9-2LE
51P-1 51P-2 51G/N-1 51G/N-2 Modbus®
IEC 60870-5-103
2× 12× 6× 2× 3× 5×
DNP3
3I2f> f>/f<,df/dt UFLS/R dIoHi> CBCM MCS 3I Interfaces:
Io 68HB 81 81LSH 87NHI 52CM CCM Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
2× 4× 24× 2× 6× 7× RS-485
dIoLo> ARC MAP CVPSOF OPTS TCS FUSEF Redundant protocols:
87NLI AFD MAP SOFT OPTM TCM VCM, 60 HSR
PRP
Time synchronization:1 0 1 0 0 0 1 1 0 0 1 1 0 0
A) SNTP 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
PCS 1 1 0 0 1 1 1 0 1 1 0 1 0
PTPv2 1 0 1 1 0 1 1 0 1 1 0 1 0 0
APPLICATION PACKAGE FOR FEEDER EF PROTECTION EXTENSION PCS
IRIG-B 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
APP3 / APP4 1 1 0 0 1 1 1 0 1 1 0 1 0
3× 3× 2×
1 0 1 1 0 1 1 0 1 1 0 1 0 0
Yo>→ Po>→ Io>HA I2→,Io→
21NY 32N 51NH 67N-TC CONTROL AND INDICATION MEASUREMENT
CL CLCRWN PQM3IH
85 21SCHLGC 85 67G/N CREV,WEI PQM ITHD, IDC
REMARKS
2× B)
CLN CLCRW BST PQM3VH
85 67G/N SCHLGC 85CRW 3× Total nr. of instances PQM VTHD, VDC
BST
A) One instance available, common for
APP3 Line Distance (APP3) and Line 2×
Differential (APP4) application PQMU
packages PQMV SWE,SAG,
APPLICATION PACKAGE FOR LINE DIFFERENTIAL PROTECTION
INT
2× B) B) Two instances available, common
3Id/I> BST for Line Distance (APP3) and Line 2×
87L BST Differential (APP4) application PQUUB
packages PQMV UB
APP4
GUID-71448271-EE0E-4E5B-BCB6-671CEB238139 V2 EN
Figure 7 presents REX640 in a feeder application. The base additional protection against earth faults along the feeder, an
functionality is enhanced with application packages providing additional application package has been selected.
both line distance and line differential protections. To provide Conventional measuring transformers are used in the example
10 ABB
1MRS759144 B
REX640
Product version: 1
case. The AIM1 analog input card provides the best match for
them with five voltage and five current inputs, one being a
sensitive input.
3U
3× 3× AND
3I (HV) I2/I1> 3Ith>F 3I>/Io>BF Io>>> - 7-inch color touch screen OR
46PD 49F 50BF 50G/50N - Ready-made pages and
customizable pages
mA/Ω - Increased situational awareness
3× 3× 3× 3× 3× towards process
Io> Io>> 3I> 3I>>
3I>>> - Supports Relay testing and
51G/ 51G/ 51P-1 51P-2 COMMUNICATION
50P commissioning
51N-1 51N-2
- Graphical editing of pages with
Protocols:
Io 2× 4× 4× 4× 4× PCM600 tool
IEC 61850-8-1/-9-2LE
3I(U) 3U> Uo> U2> U1> Modbus®
51V 59 59G/59N 59NS 59PS IEC 60870-5-103
RTD CONDITION MONITORING DNP3
3× 3× 4× 2× AND SUPERVISION Interfaces:
3I>→ 3I>>→ Io>→ Io>>→ I2>→ Ethernet: TX (RJ45), FX (LC)
67P/ 67P/ 67G/N-1 67G/N-2 67Q Serial: Serial glass fiber (ST),
51P-1 51P-2 51G/N-1 51G/N-2 RS-485
3I
3× 5× Redundant protocols:
2× 12× 6× 2×
CBCM MCS 3I HSR
3I2f> f>/f<,df/dt UFLS/R dIoHi>
68HB 52CM CCM PRP
81 81LSH 87NHI
Time synchronization: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I 2× 6× 7× SNTP 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
2× 4× 24× PTPv2 1 1 0 0 1 1 1 0 1 1 0 1 0
CVPSOF OPTS TCS FUSEF 1 0 1 1 0 1 1 0 1 1 0 1 0 0
dIoLo> ARC MAP IRIG-B 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0
SOFT OPTM TCM VCM, 60
87NLI AFD MAP 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3U 1 1 0 0 1 1 1 0 1 1 0 1 0
Uo 1 0 1 1 0 1 1 0 1 1 0 1 0 0
2× 2× 3× 3× 3× 2×
Z< GT U/f> P>/Q> P< SYNC 25AU- O→I PQM3IH
21GT 24 32R/32O 32U 25 TOSYNC 79 PQM ITHD, IDC
3× 3× 3×
3Ith>T/G/C dHi_A> dHi_B> dHi_C> PQM3VH
49T/G/C 87A 87B 87C APPLICATION PACKAGE FOR OLTC CONTROL PQM VTHD, VDC
5× 2×
3dI>T COLTC OLGAPC PQMU
87T 90V OLGAPC PQMV SWE,SAG,
INT
APP8 APP10
2×
PQUUB
3 WINDING ADD-ON PACKAGE FOR TRANSFORMER PROTECTION REMARKS PQMV UB
ADD2 APP10
GUID-CBE90DC2-08A4-425C-A34B-02FBA3D95004 V2 EN
Figure 8 presents REX640 in a three-winding power transformer add-on package. In the example case, REX640 also manages
application. The base functionality is enhanced with a power the on-load tap changer’s manual and automatic control. For
transformer application package and the related three-winding this purpose, the application package for OLTC control has
ABB 11
1MRS759144 B
REX640
Product version: 1
been selected as well. Best match for current and voltage changer’s actual position. To be able to provide this
measurement can be managed by selecting two AIM2 cards for information, the relay is equipped with an RTD card which can
the relay. This combination offers 12 current and 8 voltage measure the OLTC position either as a resistance value or as an
channels to be freely allocated for the relay functionalities. The mA signal.
OLTC control function requires information on the tap-
3U
Uo
APPLICATION PACKAGE FOR MACHINE PROTECTION Analog interface types AIM1 + AIM2
CONTROL AND INDICATION
+ RTD1
3× 2× Current transformer 111)
3I< I2>M I2>> 3Ith>M Object Ctrl 1) Ind 2)
P>/Q>
32R/32O 37 46M 46R 49M CB 3 - Voltage transformer 9
8 8 mA input/output 2
Is2t n< Ist> n< DC
49,66,48,50TDLR 50TDJAM 66 ES 3 3
1)
One of available current transformer
inputs is sensitive (0.2/1 A)
1) Control and status indication function for
3× 3× 3× primary object
dHi_A> dHi_B> dHi_C> 3dl>M/G 3dIHi>M 2) Status indication function for primary LOADPROF
87A 87B 87C 87M/87G 87HIM object LOADPROF
APP7
3× 2×
SYNC 25AU- O→I PQM3IH
ADD-ON PACKAGE FOR SYNCHRONOUS MACHINE PROTECTION 25 TOSYNC 79 PQM ITHD, IDC
2× 2× 3× 2×
Z< G U/f> P< X< ESTART PQM3VH
21G 24 32U 40 EST,62 PQM VTHD, VDC
APP7
2× 2× 2×
3Ith>T/G/C PF< Io>R PQMU
49T/G/C 55U 64R PQMV SWE,SAG,
REMARKS INT
3× Total nr. of instances
2×
dUo>/Uo3H OOS PQUUB
64TN 78PS PQMV UB
ADD1
GUID-EF50EACA-C47D-4F0A-A1FA-935A94282DF6 V2 EN
Figure 9 presents REX640 in a synchronous motor application. add-on package. Best match for current and voltage
The base functionality is enhanced with a machine protection measurement can be managed by selecting both AIM1 and
application package and the related synchronous machine AIM2 cards for the relay. This combination offers 11 current and
12 ABB
1MRS759144 B
REX640
Product version: 1
9 voltage channels to be freely allocated for the relay via the temperature sensors in the motor. These sensors are
functionalities. The stator winding temperatures are monitored connected to the RTD card within the relay.
IEC 61850-8-1 GOOSE (signal interfacing between relays for synchronizing purposes)
LHMI LHMI LHMI
3U 3U 3U 3U
LHMI
U U
REX640 REX640
2 x AIM2 | CT: 12, VT: 8 2 x AIM2 | CT: 12, VT: 8
Protection Protection
APP11 APP11
Inst. ANSI IEC Inst. ANSI IEC
1x 25AUTOSYNC AUTOSYNC 1x 25AUTOSYNC AUTOSYNC
1x 25AUTOSYNCG AUTOSYNCG 1x 25AUTOSYNCG AUTOSYNCG
3U 3U
U f U f
LHMI
AVR AVR
Governor Governor
Generator 1 Generator 2
GUID-6D58C7F7-C41B-405E-B8F5-F6BDA25A6927 V1 EN
In addition to conventional protection, control, measurement requesting the generator’s AVR and prime mover’s governor to
and supervision duties, REX640 can perform both generator change the set-points accordingly. The generator circuit
(APP11) and non-generator (APP12) circuit breaker breaker synchronizing does not require information exchange
synchronizing. Successful synchronization of two alternating between other REX640 relays within the scheme.
power sources can be done by matching their voltage,
frequency, phase sequence and phase angle. The circuit When a non-generator CB is to be synchronized, all the REX640
breaker (CB) connects the two sources after a period of CB relays within the scheme exchange information between
closing time from the instant of a given close command. Hence, themselves in order to identify suitable generator(s) for the
all the conditions of synchronization need to be met at the voltage and frequency matching. Once the generators are
instant of CB close operation for successful synchronization. identified and selected, the REX640 related to the circuit
breaker to be synchronized sends a request to the selected
Each REX640, being part of the overall synchronizing scheme, generator(s) REX640 for the required voltage and frequency
contains its own synchronizer function. When a generator CB is corrections. When the voltage, frequency and the angle
to be synchronized, the related REX640 controls the difference across the CB under synchronization are within the
generator’s voltage, frequency and angle difference by set limits, REX640 closes the circuit breaker. The information
ABB 13
1MRS759144 B
REX640
Product version: 1
exchange between the REX640s takes place using IEC REX640-based synchronizing scheme supports manual, semi-
61850-8-1 binary and analog GOOSE signaling over Ethernet. manual and automatic synchronizing modes.
The LHMI panels of REX640 can be used as local user interface When the synchronizing scheme includes both generator and
for circuit breaker synchronization. The upper-level remote non-generator CBs, the maximum size of the supported system
control systems like SCADA, DCS or PMS can interact with the is eight generator and 17 non-generator CBs.
synchronizing scheme using MMS or Modbus protocols. The
REX640 / APP9
2 x AIM2 | CT: 12, VT: 8
Inst. ANSI IEC
3x 87_A dHi_A>
Rs Rs Rs Ru Ru Ru
3x 87_B dHi_B>
3x 87_C dHi_C>
3x CCM_A MCS I_A
3x CCM_B MCS I_B
3x CCM_C MCS I_C
Zone A
Zone B
Check Zone
Bus A
Bus B
3I 3I
3I 3I
3I 3I
GUID-E302427A-35A5-4CA0-AAED-75308A388E23 V1 EN
Figure 11 presents REX640 in a phase-dedicated high- called check zone, covers both busbars. The check zone works
impedance busbar protection application for a double busbar as the final trip release condition for the selective zones; it
switchgear. The relay’s base functionality is enhanced with the provides security against false trip commands initiated by the
busbar protection application package (APP9). The two AIM2 selective zones, for example, due to a fault within the
cards in the relay provide a total of 12 current channels. In the disconnector’s auxiliary switch circuitry. The current
example, 9 out of the 12 current channels are used to create transformers’ secondary buswires for the three protection
three busbar protection zones. Zones A and B provide selective zones are supervised by dedicated functions within the relay.
protection for Bus A and Bus B, respectively. The third zone,
14 ABB
1MRS759144 B
REX640
Product version: 1
compartment
Bus A
Loop sensor
compartment
Bus B
Loop sensor
Circuit breaker
compartment
3I 3I
compartment
3I 3I
compartment
3I
Cable end
Bus riser
Loop sensor
3I 3I
Inst. ANSI IEC Inst. ANSI IEC Inst. ANSI IEC Inst. ANSI IEC Inst. ANSI IEC
4x AFD ARC 4x AFD ARC 4x AFD ARC 4x AFD ARC 4x AFD ARC
Incoming Feader Outgoing Feader Bus coupler Outgoing Feader Incoming Feader
GUID-FCEB1FAB-ED80-4086-AABF-FA58F644F0A3 V1 EN
Figure 12 presents an installation-wide arc flash protection section of the switchgear. The arc flash protection operation is
scheme for a double busbar switchgear. REX640 protection not dependent on light detection only; it is also supervised by
relays are equipped with arc flash sensor card. The card arc fault current measurement. Since the arc flash protection
supports a maximum of four pieces of either loop or lens operation should be as fast as possible, the use of static power
sensors or a combination thereof. By using suitable sensor outputs for tripping circuits is highly recommended. The
combinations for different bays, we can build up a selective arc functional condition of the arc flash sensor is continuously
flash protection scheme for the complete switchgear. The supervised and if a problem is detected, an alarm is triggered;
selective operation of the arc flash protection scheme limits the this applies to both loop and lens sensors.
power outage caused by the arc fault to the smallest possible
ABB 15
1MRS759144 B
REX640
Product version: 1
3U
Uo
3× 3× AND
I2/I1> 3Ith>F 3I>/Io>BF Io>>> - 7-inch color touch screen
- Ready-made pages and OR
46PD 49F 50BF 50G/50N
customizable pages
- Increased situational awareness
Io 3× 3× 3× 3× 3× towards process
Io> Io>> 3I> 3I>>
3I>>> - Supports Relay testing and
51G/ 51G/ 51P-1 51P-2 COMMUNICATION
50P commissioning
51N-1 51N-2
- Graphical editing of pages with
PCM600 tool Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 4× 4× 4× 4× IEC 61850-8-1/-9-2LE1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I(U) 3U> Uo> U2> U1> Modbus® 1 1 0 0 1 1 1 0 1 1 0 1 0
51V 59 59G/59N 59NS 59PS 1 0 1 1 0 1
IEC 60870-5-103 1 0 1 0 0 0
1 0 1 1 0 1 0 0
1 1 0 0 1 1 0 0 1 0 1 0 0
CONDITION MONITORING DNP3 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3× 3× 4× 2× AND SUPERVISION Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
3I>→ 3I>>→ Io>→ Io>>→ 1 0 1 1 0 1 1 0 1 1 0 1 0 0
I2>→ Ethernet: TX (RJ45), FX (LC)
67P/ 67P/ 67G/N-1 67G/N-2 67Q Serial: Serial glass fiber (ST),
51P-1 51P-2 51G/N-1 51G/N-2 RS-485
6× 2× 3× 5× Redundant protocols:
2× 12×
3I2f> f>/f<,df/dt CBCM HSR
UFLS/R dIoHi> MCS 3I
68HB 81 81LSH 87NHI 52CM PRP
CCM
Time synchronization:
3U SNTP
2× 4× 24× 2× 6× 7× PTPv2
dIoLo> ARC MAP CVPSOF OPTS TCS FUSEF IRIG-B
87NLI AFD MAP SOFT OPTM TCM VCM, 60
2× 2× 3× 2× 3× 2×
Z< G U/f> P< X< SYNC 25AU- O→I LOADPROF
21G 24 32U 40 25 TOSYNC 79 LOADPROF
2× 2×
3Ith>T/G/C PF< Io>R ESTART PQM3IH
49T/G/C 55U 64R EST,62 PQM ITHD, IDC
APP7
dUo>/Uo3H OOS PQM3VH
64TN 78PS PQM VTHD, VDC
APPLICATION PACKAGE FOR GENERATOR
ADD1 AUTOSYNCHRONIZER
2×
PQMU
PQMV SWE,SAG,
APPLICATION PACKAGE FOR POWER TRANSFORMER PROTECTION AUTOSYNCG
INT
25AUTOSYNCG
2× 2× 3× 3× 2×
APP11
Z< GT U/f> P>/Q> P< 3dI>T PQUUB
21GT 24 32R/32O 32U 87T PQMV UB
REMARKS
3× 3× 3×
3Ith>T/G/C dHi_A> dHi_B> dHi_C> 3× Total nr. of instances
49T/G/C 87A 87B 87C
APP8
GUID-4DF9D45D-8F00-4294-AAD3-FDAE5CDC393B V2 EN
Figure 13 presents REX640 in a synchronous generator machine add-on package supports the related protection
application including a block transformer. The base functions for a synchronous generator. Generator
functionality is enhanced with the machine protection and autosynchronizer application packages support the
transformer protection application packages. The synchronous generator’s synchronized connection into the busbars, in both
16 ABB
1MRS759144 B
REX640
Product version: 1
manual and auto modes. The relay’s LHMI works as the local managed by selecting both AIM1 and AIM2 cards for the relay.
operator interface for controlling the autosynchronizing This combination offers 11 current and 9 voltage channels to be
sequence. An external injection device (REK 510) enables the freely allocated to the functionalities in the relay. The
generator’s excitation circuit supervision against earth faults. generator’s stator winding temperatures are monitored using
Best match for current and voltage measurement needs can be RTD sensors.
Bus A
3U
Bus B
LHMI
Io Io
2)
REX640
SIM1
1CT + 1VT + 3 combi
sensors
3)
Base Functionality
RTD RTD
GUID-4205F769-320E-42B1-8206-1F266F73D4FC V1 EN
REX640 is perfectly aligned with the needs of digital switchgear. measured values (SMV) according to IEC 61850-9-2 LE.
Sensors are used for the local phase current and voltage Depending on the type of the feeder, it receives either one or
measurements, apart from the high-voltage side current two SMV streams. The feeders receiving two SMV streams
measurement used for power transformer protection, which is automatically switch between the streams based on the
carried out by conventional current transformers. For the position of the busbar disconnectors. All interlocking signals
outgoing cable feeders, the earth-fault protection uses core between the panels use binary GOOSE messaging according to
balance current transformers. The Bus A voltage is measured IEC 61850-8-1. The incoming power transformer feeders
by the relay in panel +J2, whereas the Bus B voltage is measure also the cable side voltages to enable automatic
measured by the relay in panel +J3. Both relays send the voltage regulation (tap changer control) and synchronizing
measured bus voltages to the Ethernet bus as sampled check functionality for circuit breaker closing.
ABB 17
1MRS759144 B
REX640
Product version: 1
6. Supported ABB solutions COM600S features a Web browser-based HMI, which provides
The REX640 protection relay together with the Substation a customizable graphical display for visualizing single-line
Management Unit COM600S constitutes a genuine IEC 61850 mimic diagrams for switchgear bay solutions. The Web HMI of
solution for reliable power distribution in utility and industrial COM600S also provides an overview of the whole substation,
power systems. To facilitate the system engineering, ABB's including relay-specific single-line diagrams, which makes
relays are supplied with connectivity packages. The information easily accessible. Substation devices and
connectivity packages include a compilation of software and processes can also be remotely accessed through the Web
relay-specific information, including single-line diagram HMI, which improves personnel safety.
templates and a full relay data model. The data model includes
event and parameter lists. With the connectivity packages, the In addition, COM600S can be used as a local data warehouse
relays can be readily configured using PCM600 and integrated for the substation's technical documentation and for the
with COM600S or the network control and management network data collected by the devices. The collected network
system MicroSCADA Pro. data facilitates extensive reporting and analyzing of network
fault situations by using the data historian and event handling
REX640 offers native support for IEC 61850 Edition 2 including features of COM600S. The historical data can be used for
binary and analog horizontal GOOSE messaging. In addition, a accurate monitoring of process and equipment performance,
process bus enabling sending and receiving of sampled values using calculations based on both real-time and historical
of analog currents and voltages is supported. values. A better understanding of the process dynamics is
achieved by combining time-based process measurements
Unlike the traditional hardwired, inter-device signaling, peer-to- with production and maintenance events.
peer communication over a switched Ethernet LAN offers an
advanced and versatile platform for power system protection. COM600S can also function as a gateway and provide
Among the distinctive features of the protection system seamless connectivity between the substation devices and
approach, enabled by the full implementation of the IEC 61850 network-level control and management systems, such as
substation automation standard, are fast communication MicroSCADA Pro and System 800xA.
capability, continuous supervision of the protection and
communication system's integrity, and flexible reconfiguration The GOOSE Analyzer interface in COM600S enables the
and upgrades. This protection relay series is able to optimally monitoring and the analysis of the horizontal IEC 61850
use the interoperability provided by the IEC 61850 Edition 2 application during commissioning and operation at station
features. level. It logs all GOOSE events during substation operation to
enable improved system supervision.
At substation level, COM600S uses the data content of the bay
level devices to enhance the substation level functionality.
Product Version
18 ABB
1MRS759144 B
REX640
Product version: 1
ABB
MicroSCADA Pro/
System 800xA
COM600S COM600S
Web HMI Web HMI
GUID-16386136-ADEF-4835-9177-D8B6650E05CB V2 EN
Figure 15. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA
ABB 19
1MRS759144 B
REX640
Product version: 1
20 ABB
1MRS759144 B
REX640
Product version: 1
power transformer. If support for three-winding power throughout the system before they cause customer complaints,
transformer is needed, the corresponding protection add-on equipment malfunctions and even equipment damage or
package can be selected. Both low-impedance differential failure. Power quality problems are not limited to the utility side
functions feature three-phase multi-slope stabilized stages and of the system. In fact, the majority of power quality problems
an instantaneous stage to provide fast and selective protection are localized within customer facilities. Thus, power quality
against short circuits, winding interturn faults and bushing monitoring is not only an effective customer service strategy but
flash-overs. A second harmonic restraint with advanced also a way to protect a utility's reputation for quality power and
waveform-based blocking ensures stability at transformer service.
energization. The fifth harmonic based blocking and unblocking
limits stabilize the protection performance in moderate The protection relay has the following power quality monitoring
overexcitation situations. In case of three-winding differential functions.
protection, the connection group phase shift matching can be
• Voltage variation
done with 0.1 degree resolution supporting cycloconverter
• Voltage unbalance
applications. If the tap-changer position information is
• Current harmonics
available, it is possible to further increase the protection
• Voltage harmonics
sensitivity by compensating the tap-changer position error
within the measured differential current. The voltage unbalance and voltage variation functions are used
for measuring short-duration voltage variations and monitoring
The power transformer protection application package also
voltage unbalance conditions in power transmission and
includes high-impedance differential functions for a phase-
distribution networks.
segregated protection scheme. If this scheme is applied, the
related current transformers have to be correctly selected and The voltage and current harmonics functions provide a method
the necessary secondary circuit components, external to the for monitoring the power quality by means of the current
relay, defined. waveform distortion and voltage waveform distortion. The
functions provide selectable short-term 3- or 60- or 300 –
10. Measurements second sliding average and a long-term demand for total
The base functionality of the REX640 relay contains a number of demand distortion (TDD) and total harmonic distortion (THD).
basic measurement functions for current, voltage, frequency, The phase-specific harmonic content is measured for voltages
symmetrical components of currents and voltages, power, and currents, as well as DC component and fundamental
power factor and energy. These measurement functions can be content. The dedicated harmonics measurement page in the
freely connected to the measured secondary quantities LHMI presents the measurements in a user-friendly manner.
available in the relay. The relay can also measure various analog
signals via RTD and mA inputs. All these measurements can be 12. Fault locator
used within the relay configuration for additional logics. The The relay features an optional impedance-measuring fault
measurements are available locally on the HMI and can be location function suitable for locating short circuits in radial
accessed remotely via communication. The information is also distribution systems. Earth faults can be located in effectively
accessible via Web HMI. and low-resistance earthed networks, as well as in
compensated networks. When the fault current magnitude is at
The relay is also provided with a load profile recorder. The load
least of the same order of magnitude or higher than the load
profile feature stores the selected load measurement data
current, earth faults can also be located in isolated neutral
captured periodically (demand interval). The records can be
distribution networks. The fault location function identifies the
viewed on the LHMI and are available in COMTRADE format.
type of the fault and then calculates the distance to the fault
point. The calculations provide information on the fault
11. Power quality resistance value and accuracy of the estimated distance to the
In the EN standards, power quality is defined through the fault point.
characteristics of the supply voltage. Transients, short-duration
and long-duration voltage variations and unbalance and
13. Disturbance recorder
waveform distortions are the key characteristics describing
The relay is provided with a disturbance recorder featuring up to
power quality. The distortion monitoring functions are used for
24 analog and 64 binary signal channels. The analog channels
monitoring the current total demand distortion and the voltage
can be set to record either the waveform or the trend of the
total harmonic distortion.
currents and voltages measured.
Power quality monitoring is an essential service that utilities can
The analog channels can be set to trigger the recording function
provide for their industrial and key customers. A monitoring
when the measured value falls below or exceeds the set values.
system can provide information about system disturbances and
The binary signal channels can be set to start a recording either
their possible causes. It can also detect problem conditions
on the rising or the falling edge of the binary signal or on both.
ABB 21
1MRS759144 B
REX640
Product version: 1
The binary channels can be set to record external or internal relay. The information can also be accessed locally or remotely
relay signals, for example, the start or trip signals of the relay using the Web HMI.
stages, or external blocking or control signals. The recorded
information is stored in a nonvolatile memory in COMTRADE
15. Recorded data
format and can be uploaded for subsequent fault analysis.
The relay can store the records of the latest 128 fault events.
The records can be used to analyze the power system events.
14. Event log Each record includes, for example, current, voltage and angle
To collect sequence-of-events information, the relay has a values and a time stamp. The fault recording can be triggered
nonvolatile memory capable of storing 1024 events with the by the start or the trip signal of a protection block, or by both.
associated time stamps. The event log facilitates detailed pre- The available measurement modes include DFT, RMS and
and post-fault analyses of feeder faults and disturbances. The peak-to-peak. Fault records store relay measurement values
considerable capacity to process and store data and events in when any protection function starts. In addition, the maximum
the relay supports the growing information demand of future demand current with time stamp is separately recorded. The
network configurations. records are stored in the nonvolatile memory.
events
WHMI
DNP3
LHMI
(FIFO) 1024
Fault ge
r
records trig
(FIFO) 128
BASIC FUNCTIONS
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
Audit
trail
events
(FIFO) 2048
n…100
Load profile
record
...7 yrs Historical load data captured at a periodical
time interval (Demand interval 1...180min)
GUID-B3049DBE-4136-4774-9E9D-CB1762AAE858 V1 EN
22 ABB
1MRS759144 B
REX640
Product version: 1
16. Load profile example, SDM600 or an Active Directory (AD) server such as
The load profile recorder stores the historical load data Windows AD.
captured periodically (demand interval). Up to 12 load
quantities can be selected for recording and storing in the The relay supports full Public Key Infrastructure as defined by
nonvolatile memory. The recordable quantities include IEC 62351-9. With this, the user can ensure that the certificates
currents, voltages, power and power factor values. The used in secured communication are from a user-approved
recording time depends on a settable demand interval provider instead of device self-signed certificates.
parameter and the amount of quantities selected. The
quantities' type and amount to be recorded are determined in 20. Station communication
the application configuration. The recorded quantities are Operational information and controls are available through a
stored in the COMTRADE format. wide range of communication protocols including IEC 61850
Edition 2, IEC 61850-9-2 LE, IEC 60870-5-103, Modbus® and
17. Trip circuit supervision DNP3. The Profibus DPV1 communication protocol is
The trip circuit supervision continuously monitors the availability supported via the protocol converter SPA-ZC 302. Full
and operability of the trip circuit. It provides open-circuit communication capabilities, for example, horizontal
monitoring both when the circuit breaker is in closed and in communication between the relays, are only enabled by IEC
open position. It also detects loss of circuit-breaker control 61850.
voltage.
The IEC 61850 protocol is a core part of the relay as the
protection and control application is fully based on standard
18. Self-supervision modelling. The relay supports Edition 2 and Edition 1 versions
The relay’s built-in self-supervision system continuously of the standard. With Edition 2 support, the relay has the latest
monitors the state of the relay hardware and the operation of functionality modelling for substation applications and the best
the relay software. Any fault or malfunction detected is used for interoperability for modern substations.
alerting the operator.
The IEC 61850 communication implementation supports
A permanent relay fault blocks the protection functions to monitoring and control functions. Additionally, parameter
prevent incorrect operation. settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
19. Access control and cybersecurity
the standard COMTRADE file format. The relay supports
Cybersecurity measures are implemented to secure safe
simultaneous event reporting to five different clients on the
operation of the protection and control functions. The relay
station bus.
supports these measures with configuration hardening
capabilities, encrypted communication, security event logging The relay can send binary and analog signals to other devices
and user access control. using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile. Binary GOOSE messaging can, for
The relay supports role-based user authentication and
example, be used for protection and interlocking-based
authorization with individual user accounts as defined in IEC
protection schemes. The relay meets the GOOSE performance
62351-8. All user activity is logged as security events to an
requirements for tripping applications in distribution
audit trail in a nonvolatile memory and sent as messages to the
substations, as defined by the IEC 61850 standard (class P1,
SysLog server. The nonvolatile memory does not need battery
<3 ms data exchange between the devices). The relay also
backup or regular component exchange to maintain the
supports the sending and receiving of analog values using
memory storage. File transfer and Web HMI use communication
GOOSE messaging. Analog GOOSE messaging enables easy
encryption protecting the data in transit. Also, the
transfer of analog measurement values over the station bus,
communication link between the relay configuration tool
thus facilitating, for example, the sending of measurement
PCM600 and the relay is encrypted. All rear communication
values between the relays when controlling transformers
ports and optional protocol services can be activated according
running in parallel.
to the required system setup.
The relay also supports IEC 61850 process bus concept by
User accounts can be managed by PCM600 or centrally. A
sending sampled values of currents and voltages and by
central account management is an authentication infrastructure
receiving sampled values of voltages. With this functionality the
that offers a secure solution for enforcing access control to
galvanic interpanel wiring can be replaced with Ethernet
relays and other systems within a substation. This incorporates
communication. The analog values are transferred as sampled
management of user accounts, roles and certificates and the
values using the IEC 61850-9-2 LE protocol. The intended
distribution of such, a procedure completely transparent to the
application for sampled values are current-based differential
user. The central server handling user accounts can be, for
protection functions or sharing the voltage values with the
ABB 23
1MRS759144 B
REX640
Product version: 1
relays that have voltage-based protection or supervision redundancy can be applied to the Ethernet-based IEC 61850,
functions. The relay can receive up to four sampled value Modbus and DNP3 protocols.
streams and totally 16 measurements can be connected into
the protection relay application. The IEC 61850 standard specifies network redundancy which
improves the system availability for the substation
Relays with process bus based applications use IEEE 1588 communication. The network redundancy is based on two
edition 2 for high-accuracy time synchronization. complementary protocols defined in the IEC 62439-3 standard:
PRP and HSR protocols. Both protocols are able to overcome a
For redundant Ethernet communication in station bus, the relay failure of a link or switch with a zero switchover time. In both
offers either two optical or two galvanic Ethernet network protocols, each network node has two identical Ethernet ports
interfaces. An optional third port with optical or galvanic dedicated for one network connection.
Ethernet network interface is also available. The relay also
provides an optional fiber-optic port for dedicated protection The protocols rely on the duplication of all transmitted
communication which can be used for up to 50 km distances information and provide a zero switchover time if the links or
depending on the selected fiber transceiver. The intended switches fail, thus fulfilling all the stringent real-time
teleprotection applications for this port are line differential and requirements of substation automation.
line distance protection communication or binary signal
transfer. The optional third Ethernet interface provides In PRP, each network node is attached to two independent
connectivity for any other Ethernet device to an IEC 61850 networks operated in parallel. The networks are completely
station bus inside a switchgear bay, for example connection of separated to ensure failure independence and can have
a remote I/O. Ethernet network redundancy can be achieved different topologies. As the networks operate in parallel, they
using the high-availability seamless redundancy (HSR) protocol provide zero-time recovery and continuous checking of
or the parallel redundancy protocol (PRP), or with a self-healing redundancy to avoid failures.
ring using RSTP in the managed switches. Ethernet
COM600
SCADA
GUID-AC53358A-5E83-4694-9BC2-29F5C4F4988C V2 EN
HSR applies the PRP principle of parallel operation to a single through each port. Both frames circulate in opposite directions
ring. For each message sent, the node sends two frames, one over the ring. Every node forwards the frames it receives from
24 ABB
1MRS759144 B
REX640
Product version: 1
one port to another to reach the next node. When the be connected, it is recommended to split the network into
originating sender node receives the frame it sent, the sender several rings to guarantee the performance for real-time
node discards the frame to avoid loops. The HSR ring supports applications.
the connection of up to 30 relays. If more than 30 relays are to
COM600
Devices not supporting HSR
SCADA
Ethernet switch
GUID-ED51EEB9-98EB-4D4D-B0F8-BB965927FAF4 V2 EN
The relay can be connected to Ethernet-based communication 60870-5-103 format. Further, IEC 60870-5-103 can be used at
systems in a station bus using the RJ-45 connector (100Base- the same time with the IEC 61850 protocol.
TX) or the multimode fiber optic LC connector (100Base-FX). A
dedicated protection communication port uses a pluggable DNP3 supports both serial and TCP modes for the connection
multimode or single-mode fiber optic LC connector (100Base- of up to five masters. Changing the active setting and reading
FX). If connection to a serial bus is required, the RS-485 or fault records are supported. DNP serial and DNP TCP can be
fiber-optic serial communication ports can be used. used in parallel. If required, both IEC 61850 and DNP can be run
simultaneously.
Modbus implementation supports RTU, ASCII and TCP modes.
Besides standard Modbus functionality, the relay supports The relay supports Profibus DPV1 with support of SPA-ZC 302
retrieval of time-stamped events, changing the active setting Profibus adapter. If Profibus is required, the relay must be
group and uploading of the latest fault records. If a Modbus ordered with Modbus serial options. Modbus implementation
TCP connection is used, five clients can be connected to the includes SPA protocol emulation functionality. This functionality
relay simultaneously. Further, Modbus serial and Modbus TCP enables connection to SPA-ZC 302.
can be used in parallel, and, if required, both IEC 61850 and
When the relay uses the RS-485 bus for the serial
Modbus can be run simultaneously.
communication, both two- and four-wire connections are
The IEC 60870-5-103 implementation supports two parallel supported. Termination and pull-up/down resistors can be
serial bus connections to two different masters. Besides basic configured with DIP switch on the communication card so that
standard functionality, the relay supports changing of the active external resistors are not needed.
setting group and uploading of disturbance recordings in IEC
ABB 25
1MRS759144 B
REX640
Product version: 1
PTPv2 (IEEE 1588) with Power Profile (IEEE Std C37.238-2011) 4 μs3)
1) Ethernet-based
2) With special time synchronization wiring
3) Required especially in process bus applications
The required accuracy of the grandmaster clock is +/-1 μs to
PTPv2 features: guarantee performance of protection applications. The relay
can work as a backup master clock per BMC algorithm if the
• Ordinary Clock with Best Master Clock algorithm
external primary grandmaster clock is not available for short
• One-step Transparent Clock for Ethernet ring topology
term.
• PTPv2 Power Profile
• Receive (slave): 1-step/2-step In addition, the relay supports time synchronization via
• Transmit (master): 1-step Modbus, DNP3 and IEC 60870-5-103 serial communication
• Layer 2 mapping protocols.
• Peer-to-peer delay calculation
• Multicast operation
IEC 61850-8-1 ● ● - -
IEC 61850-9-2 LE ● ● - -
MODBUS RTU/ASCII - - ● ●
MODBUS TCP/IP ● ● - -
DNP3 (serial) - - ● ●
DNP3 TCP/IP ● ● - -
IEC 60870-5-103 - - ● ●
● = Supported
21. Protection communication and supervision can be selected. The variants support optical communication
The protection communication between the relays is enabled for distances typically up to 2 km (multimode), 20 km (single-
by means of a dedicated fiber optic communication channel; mode) and 50 km (single-mode). The SFP plug-in unit can be
1310 nm multimode or single-mode fibers with LC connectors ordered together with the relay or later on when the need to
are used. The communication link transfers analog and binary establish the link arises. The line differential protection can be
information between line ends for line differential, line distance realized between two REX640 relays or between REX640 and
and transfer trip functions. No external devices, such as GPS RED615 relays. If the line differential protection is to be realized
clocks, are needed for the line differential protection between REX640 and RED615 relays, the SFP plug-in module
communication. Additionally, the link can be used to transfer has to match the RED615 communication card variant.
any freely selectable binary data between line ends. In total, 16 Additionally, the RED615 relay version must be 5.0 FP1 or later.
binary signals can be transferred between two REX640
protection relays. If a galvanic protection communication link is requested, it can
be realized with RPW600 modems. The RPW600 modem offers
Each REX640 communication card variant contains an SFP a 5 kV (RMS) level of isolation between the pilot wire terminals
rack for dedicated point-to-point protection communication via and ground. The RPW600 modems (master and follower) are
an SFP plug-in module. Three variants of SFP plug-in modules galvanically connected to either end of the pilot wire and
26 ABB
1MRS759144 B
REX640
Product version: 1
optically connected to the relays using short optical single- The protection communication supervision continuously
mode cables. Using 0.8 mm 2 twisted pair cables, pilot wire link monitors the protection communication link. The line differential
distances up to 8 km are typically supported. However, twisted protection function can be blocked if severe interference in the
pair pilot wire cables in good conditions may support even communication link, risking the correct operation of the
longer distances to be covered. The length of the supported function, is detected. If the interference persists, an alarm
pilot wire link also depends on the noise environment in the signal is triggered indicating permanent failure in the protection
installation. Should the need arise to replace the pilot wire communication.
cables with fiber optic cables, the single-mode fiber optic LC
connectors of the relays can be used for direct connection of
the fiber optic communication link.
GUID-5735D9CC-B1D2-4D73-85C2-1389ED25563B V1 EN
GUID-9A404E8B-1120-42B4-B72E-8EEFC15E4960 V1 EN
ABB 27
1MRS759144 B
REX640
Product version: 1
Description Value
Width 304.0 mm
Height 264.8 mm
Description Value
Width 212.5 mm
Height 177.5 mm
Depth 57.6 mm
Weight 1.6 kg
Nominal auxiliary voltage Un 24, 30, 48, 60 V DC 100, 110, 120, 220, 240 V AC, 50 110, 125 V DC
and 60 Hz
Auxiliary voltage variation 50...120% of Un (12...72 V DC) 38...110% of Un (38...264 V AC) 70...120% of Un (77...150 V DC)
Burden of auxiliary voltage supply DC <18.0 W (nominal)/<25.0 W DC <20.0 W (nominal)/<25.0 W DC <17.0 W (nominal)/<25.0 W
under quiescent (Pq)/operating (max.) (max.) (max.)
condition AC <20.0 W (nominal)/<25.0 W
(max.)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
28 ABB
1MRS759144 B
REX640
Product version: 1
Description Value
Nominal auxiliary voltage Un 100, 110, 120, 220, 240 V AC, 50 and 60 Hz
Burden of auxiliary voltage supply under quiescent (Pq)/operating DC <6.0 W (nominal)/<14.0 W (max.)
condition AC <7.0 W (nominal)/<12.0 W (max.)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
• Continuously 4A 20 A
Voltage withstand:
• Continuous 288 V AC
• For 10 s 360 V AC
Description Value
Current sensor input Rated current voltage (in secondary 75 mV...9000 mV1)
side)
ABB 29
1MRS759144 B
REX640
Product version: 1
Description Value
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
± 2.0% or ±1 Ω ±1°C
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 1 A/0.25 A/0.15 A
48/110/220 V DC
30 ABB
1MRS759144 B
REX640
Product version: 1
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at >0.25 A
110 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 5 A/3 A/1 A
48/110/220 V DC (two contacts connected in series)
ABB 31
1MRS759144 B
REX640
Product version: 1
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at 16 A/6 A/3 A
48/110/220 V DC two contacts connected in series
Type Description
1) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path
2) Maximum allowed attenuation caused by connectors and cable togethe
Permitted path
Connector Part number Fiber type Wave Length Max. length
attenuation
MM 62.5/125 or
SFP 2RCA045621 1310 nm 2 km <8 dB
50/125 μm
32 ABB
1MRS759144 B
REX640
Product version: 1
Description Value
Modulation Unmodulated
Table 24. Lens sensor and optical fiber for arc protection
Description Value
Description Value
Front/connector side IP 20
Rear IP 40
Description Value
Front IP 54
Other sides IP 20
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For relays with an LC communication interface the maximum operating temperature is +70 ºC
ABB 33
1MRS759144 B
REX640
Product version: 1
• Contact discharge 8 kV
• Air discharge 15 kV
• Communication 2 kV
• Other ports 4 kV
• 2s 100 A/m
34 ABB
1MRS759144 B
REX640
Product version: 1
• Conducted
• Radiated
Dielectric tests 500 V, 50 Hz, 1 min, RS-485 and IRIG-B IEC 60255-27
1 kV, 50 Hz, 1 min, across open contacts
1.5 kV, 50 Hz, 1 min, Ethernet RJ-45
2 kV, 50 Hz, 1 min, all other circuits
Impulse voltage test 1 kV, 1.2/50 μs, 0.5 J, RS-485 and IRIG-B IEC 60255-27
2.4 kV, 1.2/50 μs, 0.5 J, Ethernet RJ-45
5 kV, 1.2/50 μs, 0.5 J, all other circuits
ABB 35
1MRS759144 B
REX640
Product version: 1
1) For relays with an LC communication interface the maximum operating temperature is +70o C
Description Reference
LV directive 2006/95/EC
Description Reference
Description
36 ABB
1MRS759144 B
REX640
Product version: 1
Protection functions
Characteristic Value
Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Impedance:
±2.5% of the set value or ±0.05 Ω
Phase angle: ±2°
ABB 37
1MRS759144 B
REX640
Product version: 1
38 ABB
1MRS759144 B
REX640
Product version: 1
ABB 39
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Characteristic Value
40 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Table 42. Current reversal and weak-end infeed logic (CRWPSCH) main settings
Characteristic Value
Table 44. Communication logic for residual overcurrent (RESCPSCH) main settings
Table 45. Current reversal and weak-end infeed logic for residual overcurrent (RCRWPSCH)
Characteristic Value
ABB 41
1MRS759144 B
REX640
Product version: 1
Table 46. Current reversal and weak-end infeed logic for residual overcurrent (RCRWPSCH) main settings
Table 47. Line differential protection with in-zone power transformer (LNPLDF)
Characteristics Value
20 ms 23 ms 27 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms 4)
1) With the symmetrical communication channel (as when using dedicated fiber optic).
2) Without additional delay in the communication channel (as when using dedicated fiber optic).
3) Measured with static power output. When differential current = 2 × High operate value and fn = 50 Hz with galvanic pilot wire link + 5 ms.
4) Low operate value multiples in the range of 1.5...20
42 ABB
1MRS759144 B
REX640
Product version: 1
Table 48. Line differential protection with in-zone power transformer (LNPLDF) main settings
Characteristic Value
Characteristic Value
ABB 43
1MRS759144 B
REX640
Product version: 1
Characteristic Value
PHIPTOC2):
IFault = 2 × set Start value 8 ms 12 ms 15 ms
IFault = 10 × set Start value
7 ms 9 ms 12 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms
1) Set Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency
injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Measured with static signal output (SSO)
3) Includes the delay of the signal output contact (SO)
PHIPTOC 20...300000 ms 10
44 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 × In, voltage before fault = 1.0 × Un, fn = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
ABB 45
1MRS759144 B
REX640
Product version: 1
Characteristic Value
EFIPTOC2):
IFault = 2 × set Start value 8 ms 11 ms 14 ms
IFault = 10 × set Start value 8 ms 9 ms 11 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
1) Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Measured with static signal output (SSO)
3) Includes the delay of the signal output contact (SO)
4) Maximum Start value = 2.5 × In , Start value multiples in the range of 1.5...20
EFIPTOC 20...300000 ms 10
46 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DEFHPDEF
IFault = 2 × set Start value 42 ms 46 ms 49 ms
DEFLPDEF 58 ms 62 ms 66 ms
IFault = 2 × set Start value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In , fn = 50 Hz, earth-fault current with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
ABB 47
1MRS759144 B
REX640
Product version: 1
DEFHPDEF 40...300000 ms 10
48 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
56 ms 60 ms 64 ms
Reset time 40 ms
1) Uo = 1.0 × Un
2) Includes the delay of the signal output contact, results based on statistical distribution of 1000 measurements
ABB 49
1MRS759144 B
REX640
Product version: 1
Characteristic Value
1) Includes the delay of the signal output contact, results based on statistical distribution of 1000 measurements
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode ±5.0% of the set value or ±20 ms
1) Io varied during the test, Uo = 1.0 × Un = phase to earth voltage during earth fault in compensated or un-earthed network, the residual power value before fault = 0.0 pu, fn = 50 Hz, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
50 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: fn ±2 Hz
ABB 51
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms
-3 dB at f = 13 × fn
1) Fundamental frequency current = 1.0 × I n , harmonics current before fault = 0.0 × In , harmonics fault current 2.0 × Start value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 2...20
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
52 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 × Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
ABB 53
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
54 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 0.9 × Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × Un, Start value multiples in range of 1.10...2.00
ABB 55
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, positive-sequence overvoltage of nominal frequency injected from random phase angle
2) Measured with static signal output (SSO)
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 1.0 × Un, positive-sequence voltage before fault = 1.1 × Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
56 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
df/dt <120 ms
ABB 57
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
fn ±2 Hz
Current:
±1.5% of the set value or ± 0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms
1) Measurement mode = default, current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
58 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Voltage change:
Typically 40 ms
Operate time accuracy in definite-time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse-time mode ±5.0% of the theoretical value or ±50 ms
Table 96. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
Characteristic Value
ABB 59
1MRS759144 B
REX640
Product version: 1
Table 97. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR) main settings
Table 98. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic Value
Table 99. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Operation T2PTTR 1 = on -
5 = off
60 ABB
1MRS759144 B
REX640
Product version: 1
Table 100. Three-phase overload protection for shunt capacitor banks (COLPTOC)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz, and no
harmonics
Operate time accuracy in definite time mode 1% of the set value or ±20 ms
Operate time accuracy in inverse time mode 10% of the theoretical value or ±20 ms
Suppression of harmonics for under current stage DFT: -50 dB at f = n × fn, where n = 2,3,4,5,..
1) Harmonics current before fault = 0.5 × In, harmonics fault current 1.5 × Start value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Harmonics current before fault = 1.2 × In , harmonics fault current 0.8 × Start value, results based on statistical distribution of 1000 measurements
Table 101. Three-phase overload protection for shunt capacitor banks (COLPTOC) main settings
Table 102. Current unbalance protection for shunt capacitor banks (CUBPTOC)
Characteristic Value
Operate time accuracy in definite time mode 1% of the theoretical value or ±20 ms
Operate time accuracy in inverse definite minimum time mode 5% of the theoretical value or ±20 ms
1) Fundamental frequency current = 1.0 × In, current before fault = 0.0 × In, fault current = 2.0 × Start value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 61
1MRS759144 B
REX640
Product version: 1
Table 103. Current unbalance protection for shunt capacitor banks (CUBPTOC) main settings
Table 104. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC)
Characteristic Value
Operate time accuracy in definite time mode 1% of the theoretical value or ±20 ms
1) Fundamental frequency current = 1.0 × In, current before fault = 0.0 × In, fault current = 2.0 × Start value, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 105. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC) main settings
62 ABB
1MRS759144 B
REX640
Product version: 1
Table 106. Shunt capacitor bank switching resonance protection, current based (SRCPTOC)
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Table 107. Shunt capacitor bank switching resonance protection, current based (SRCPTOC) main settings
Characteristic Value
1) Start value = 0.1 × Un, Voltage before fault = 0.9 × Un, fn = 50 Hz, overvoltage in one phase-to-earth with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Measured with static signal output (SSO)
Table 109. Compensated neutral unbalance voltage protection (CNUPTOV) main settings
ABB 63
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Measurement mode NPS, NPS current before fault = 0.0 × In, fn = 50 Hz, fault NPS current with nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2) Measured with static signal output (SSO)
Characteristic Value
1) Tested for Number of Start phases = 1 out of 3, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
64 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
±1°
ABB 65
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
fn ±2 Hz
Reactive power range |PF| <0.71
Power:
±3.0% or ±0.002 × Qn
Voltage:
±1.5% of the set value or ±0.002 × Un
1) Start value = 0.05 × Sn, reactive power before fault = 0.8 × Start value, reactive power overshoot 2 times, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 117. Directional reactive power undervoltage protection (DQPTUV) main settings
66 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation accuracy 1) Depending on the frequency of the measured current and voltage:
f = fn ±2 Hz
Characteristic Value
Operation accuracy 1) Depending on the frequency of the measured current and voltage:
fn ±2 Hz
ABB 67
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage: fn ±2
Hz
Characteristic Value
Operation accuracy Depending on the frequency of the measured current and voltage:
f = fn ± 2 Hz
Retardation time Total retardation time when the impedance returns from the operating
circle <40 ms
68 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Table 127. Third harmonic-based stator earth-fault protection (H3EFPSEF) main settings
ABB 69
1MRS759144 B
REX640
Product version: 1
Characteristic Value
1) Current before fault = 0.0 × In , fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 129. Rotor earth-fault protection, injection method (MREFPTOC) main settings
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
1) Measurement mode = “Peak-to-Peak”, current before fault = 0.0 × In, fn = 50 Hz, fault current with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 131. High-impedance or flux-balance based differential protection (MHZPDIF) main settings
70 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Impedance reach Depending on the frequency of the measured current and voltage: fn ±2
Hz
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10...5.00
ABB 71
1MRS759144 B
REX640
Product version: 1
Table 135. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings
Operation MNSPTOC 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode mode ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
72 ABB
1MRS759144 B
REX640
Product version: 1
Operation LOFLPTUC 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operation JAMPTOC 1 = on -
5 = off
Characteristic Value
1) Current before = 0.0 × In , fn = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 73
1MRS759144 B
REX640
Product version: 1
Operation STTPMSU 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Operation PREVPTOC 1 = on -
5 = off
74 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Table 148. Thermal overload protection for motors (MPTTR) main settings
Operation MPTTR 1 = on -
5 = off
Table 149. Stabilized and instantaneous differential protection for machines (MPDIF)
Characteristic Value
Low stage 32 ms 35 ms 37 ms
High stage 9 ms 13 ms 19 ms
ABB 75
1MRS759144 B
REX640
Product version: 1
Table 150. Stabilized and instantaneous differential protection for machines (MPDIF) main settings
Characteristic Value
Table 153. Stabilized and instantaneous differential protection for two- or three-winding transformers (TR3PTDF)
Characteristic Value
1) Current before fault = 0.0 × In , fn = 50 Hz. Injected differential current = 2.0 × set operation value.
2) Measured with static power output (SPO)
76 ABB
1MRS759144 B
REX640
Product version: 1
Table 154. Stabilized and instantaneous differential protection for two- or three-winding transformers (TR3PTDF) main settings
Table 155. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF)
Characteristic Value
Low stage 31 ms 35 ms 40 ms
High stage 15 ms 17 ms 20 ms
1) Current before fault = 0.0 × In , fn = 50 Hz. Injected differential current = 2.0 × set operation value
2) Measured with static power output. fn = 50 Hz
ABB 77
1MRS759144 B
REX640
Product version: 1
Table 156. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF) main settings
Operation TR2PTDF 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
78 ABB
1MRS759144 B
REX640
Product version: 1
Table 158. Numerical stabilized low-impedance restricted earth-fault protection (LREFPNDF) main settings
Operation LREFPNDF 1 = on -
5 = off
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 160. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Operation HREFPDIF 1 = on -
5 = off
ABB 79
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Measured with static signal output (SSO)
Characteristic Value
80 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value
Characteristic Value
1) Phase start value = 1.0 × In, current before fault = 2.0 × set Phase start value, fn = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the power output (PO) contact
3) Measured with static power output (SPO)
ABB 81
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Impedance:
±2.5% or ±0.05 Ω
Distance:
±2.0% or ±0.04 km/0.025 mile
XC0F_CALC:
±3% or ±0.01 Zn/1.15 Ω
IFLT_PER_ILD:
±5% or ±0.05
Characteristic Value
df/dt <120 ms
82 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
ABB 83
1MRS759144 B
REX640
Product version: 1
84 ABB
1MRS759144 B
REX640
Product version: 1
Control functions
Characteristic Value
Operation ESMGAPC 1 = on -
5 = off
Characteristic Value
Characteristic Value
Voltage difference:
±1.0% or ±0.004 × Un
Frequency difference:
±10 mHz
Phase angle difference:
±1°
ABB 85
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Voltage difference:
±1.0% or ±0.004 × Un
Frequency difference:
±10 mHz
Phase angle difference:
±1°
86 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Voltage:
±3.0% of the set value or ±0.01 × Un
Frequency:
±10 mHz
Phase angle:
±3°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 87
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operate time accuracy in definite time mode2) +4.0%/-0% of the set value
Operate time accuracy in inverse time mode2) +8.5%/-0% of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time (IDMT) 1 s
88 ABB
1MRS759144 B
REX640
Product version: 1
Table 187. Tap changer control with voltage regulator (OL5ATCC) main settings
Characteristic Value
I_DAMPING:
Typically ±2 A
1) Network resonance point voltage must be at least 0.01 × Un, where Un = nominal phase-to-earth voltage
ABB 89
1MRS759144 B
REX640
Product version: 1
90 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Table 191. Hot-spot and insulation ageing rate monitoring for transformers (HSARSPTR)
Characteristic Value
Table 192. Hot-spot and insulation ageing rate monitoring for transformers (HSARSPTR) main settings
Characteristic Value
Characteristic Value
ABB 91
1MRS759144 B
REX640
Product version: 1
Table 196. Current circuit supervision for transformers (CTSRCTF) main settings
Table 197. Current transformer supervision for high-impedance protection scheme (HZCCxSPVC)
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Table 198. Current transformer supervision for high-impedance protection scheme (HZCCxSPVC) main settings
Characteristic Value
Operate time1) NPS function UFault = 1.1 × set Neg Seq voltage <33 ms
Lev
UFault = 5.0 × set Neg Seq voltage <18 ms
Lev
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Description Value
92 ABB
1MRS759144 B
REX640
Product version: 1
Table 201. Runtime counter for machines and devices (MDSOPT) main settings
Characteristic Value
20 Hz < f ≤ 70 Hz:
±1.5% of the set value or ±0.002 × Un
10 Hz < f ≤ 20 Hz:
±4.0% of the set value or ±0.002 × Un
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 93
1MRS759144 B
REX640
Product version: 1
Measurement functions
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
Characteristic Value
±0.5% or ±0.002 × Un
94 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
±0.5% or ±0.002 × Un
Characteristic Value
±1.0% or ±0.002 × Un
Characteristic Value
Characteristic Value
Descrpition Value
ABB 95
1MRS759144 B
REX640
Product version: 1
Table 214. Current total demand, harmonic distortion, DC component (TDD, THD, DC) and individual harmonics (CHMHAI)
Characteristic Value
Table 215. Current total demand, harmonic distortion, DC component (TDD, THD, DC) and individual harmonics (CHMHAI) main settings
Table 216. Voltage total harmonic distortion, DC component (THD, DC) and individual harmonics (VHMHAI)
Characteristic Value
Table 217. Voltage total harmonic distortion, DC component (THD, DC) and individual harmonics (VHMHAI) main settings
Characteristic Value
96 ABB
1MRS759144 B
REX640
Product version: 1
Characteristic Value
Operation VSQVUB 1 = on -
5 = off
ABB 97
1MRS759144 B
REX640
Product version: 1
Logging functions
98 ABB
1MRS759144 B
REX640
Product version: 1
Other functionality
Characteristic Value
Characteristic Value
Characteristic Value
ABB 99
1MRS759144 B
REX640
Product version: 1
23. Mounting methods Automation IEC products with emphasis on, but not exclusively
With appropriate mounting accessories, the protection relay for, the Relion product family. PST is an easy-to-use, online tool
can be rack mounted, wall mounted, roof mounted or door always containing the latest product information. The complete
mounted. The LHMI can be mounted either on a door or a order code can be created with detailed specification and the
surface, or in a tilted position (25°) using special accessories. It result can be printed and mailed. Registration is required.
is also possible to rack mount or door mount the protection
relay together with the LHMI.
25. Modification Sales
Mounting options for the relay: Modification Sales is a concept that provides modification
support for already delivered relays. Under Modification Sales it
• Rack mounting is possible to modify both the hardware and software
• Rack mounting with the LHMI capabilities of the existing relay. The same options are available
• Wall mounting as when a new relay variant is configured and ordered from the
• Roof mounting factory: it is possible to add new hardware modules into empty
• Door mounting slots, change the type of the existing modules within the slots or
• Door mounting with the LHMI add software functions by adding application and, if necessary,
add-on packages. If it is needed to use the possibilities
Mounting options for the LHMI: provided by the Modification Sales concept, please contact
your local ABB unit. The information that is requested by ABB is
• Rack mounting
a) Relay serial number, b) Relay order code and c) The
• Door mounting
requested modification, separately stated for each relay.
• Mounting in a 25° tilt
Modification Sales is based on license handling within the relay.
Modifying the relay without proper new license from ABB puts
24. Selection and ordering data the relay in internal relay failure mode.
Use ABB Library to access the selection and ordering
information and to generate the order number.
100 ABB
1MRS759144 B
REX640
Product version: 1
LHMI 2RCA033008A0001
ABB 101
1MRS759144 B
REX640
Product version: 1
access can be customized for every user to enable simple tools to connect and interact with the protection relay. The
operational usage for all user levels. connectivity packages reduce the risk of errors in system
integration, minimizing device configuration and setup times.
When the Web HMI is used, the protection relay can be
accessed from any of the relay’s access points, including the Further, the connectivity package for REX640 includes a flexible
Ethernet connection on the LHMI. For security reasons, the update tool for adding one additional LHMI language and new
Web HMI is disabled by default, but it can be enabled via the functionalities to the protection relay. The flexible modification
LHMI. The Web HMI functionality can be limited to read-only support of the relay enables adding new protection
access. functionalities whenever the protection and control needs are
changing.
The relay connectivity package is a collection of software and
specific relay information which enables system products and
Description Version
Web browser IE 11, Microsoft Edge, Google Chrome and Mozilla Firefox
Signal monitoring ● ●
Application configuration - ●
Event viewing ● ●
Online monitoring - ●
● = Supported
ABB 103
1MRS759144 B
REX640
Product version: 1
L1 L2 L3
L1
L2
L3
A n
n
a
da dn AIM1001
X1
57-240V
Positive 1
VT1
Load flow 2
N
Direction 3
57-240V
N
VT2
4
57-240V
5
N
VT3
6
57-240V
7
N
VT4
8
57-240V
P1 9
N
VT5
10
S1
S2 X2
1/5A
1
N
CT1
2
P2 3
1/5A
N
CT2
4
1/5A
5
N
CT3
6
1/5A
7
P1
S1 N
CT4
8
0.2/1A
9
S2 CT5 (for residual
N
P2 10
current only)
GUID-A274F38C-5302-4EA9-83F9-5BB17C7672BF V1 EN
104 ABB
1MRS759144 B
REX640
Product version: 1
L1 L2 L3
L1
L2
L3
A n
n
a
da dn AIM1002
X1
57-240V
Positive 1
VT1
Load flow 2
N
Direction 3
57-240V
N
VT2
4
57-240V
5
N
VT3
6
57-240V
7
N
VT4
8
1/5A
P1 9
N
CT6
10
S1
S2 X2
1/5A
1
N
CT1
2
P2 3
1/5A
N
CT2
4
1/5A
5
N
CT3
6
1/5A
7
P1
S1 N
CT4
8
1/5A
9
S2 CT5
N
P2 10
GUID-E49A0352-50CA-4FE5-9D3D-AD4F09A10F06 V1 EN
ABB 105
1MRS759144 B
REX640
Product version: 1
L1 L2 L3
Positive
Current
Direction
SIM1001
X1
s1
4
Sensor I
s2 5 DFF
7
Sensor U
8 DFF
X2
s1
4
Sensor I
s2 5 DFF
7
Sensor U
8 DFF
X3
s1
4
Sensor I
s2 5 DFF
7
Sensor U
8 DFF
X4
57-240
1
VT
2 N
3 0.2/1A
CT (for residual
N
4 current only)
P1
S1
S2
P2
GUID-549B3B87-483B-4411-9790-D4FA8525936B V1 EN
106 ABB
1MRS759144 B
REX640
Product version: 1
L1 L2 L3
Positive
Current
Direction
SIM1001
X1
s1
4
5 Sensor I
s2 DFF
7
Sensor U
8 DFF
X2
s1
4
5 Sensor I
s2 DFF
7
Sensor U
8 DFF
X3
s1
4
5 Sensor I
s2 DFF
7
Sensor U
8 DFF
X4
57-240
1
N
VT
2
0.2/1A
3
N
CT (for residual
4 current only)
P1
S1
S2
P2
GUID-D37ABF6A-CE39-4293-8D4B-1DA95A077D27 V1 EN
ABB 107
1MRS759144 B
REX640
Product version: 1
BIO1001/ BIO1003
X1 X2
1 BI1 3
SO1
4
2 5
BI2 SO2
6
3 7
BI3 SO3
4
8
5 9
BI4 SO4
10
6 11
BI5 SO5
12
7 13
BI6 SO6
8
14
9 15
BI7 SO7
16
10 17
BI8 SO8
18
11
BI9
12
13
BI10
14
BI11
15
BI12
16
17
BI13
18
X2
1
BI14
2
GUID-2F20AF34-230C-4E35-86AE-A6F930250E3C V1 EN
108 ABB
1MRS759144 B
REX640
Product version: 1
BIO1002/ BIO1004
X1 X2
1 BI1
3
SPO1
4
2 5
BI2
SPO2
6
3 7
BI3
4 SPO3
8
5 9
BI4
SPO4
10
6 11
BI5
I SPO5
12
7 13
BI6 SPO6
8 SPO6_TCS
14
9 15
BI7
I SPO7
16
10 17
BI8 SPO8
SPO8_TCS
18
11
BI9
12
GUID-46FF3F6E-0E8C-4FA7-8964-0480330AC56A V1 EN
ABB 109
1MRS759144 B
REX640
Product version: 1
PSM100x
X1
+/~ 1
Uaux Uaux
-/~
2
3
RF
4
5
6
SO1
7
8
9
SO2
10
11
SSO1
12
13
SSO2
14
POSP1
15
16
POSP2
17
18
X2
1
SO3
2
3
I 4
PODP1 6
5
PO1_TCS 7
8
I 9
PODP2 11
10
PO2_TCS 12
13
I 14
PODP3 16
15
PO3_TCS 17
18
GUID-6B2AB7B2-D285-4F90-A73D-40603FA7050B V1 EN
110 ABB
1MRS759144 B
REX640
Product version: 1
RTD1001
X1
1
mA
mA1
2
3
4
mA
mA2
5
6
7
8 RTD1
Ref
9
10
11 RTD2
Ref
12
13
14 RTD3
Ref
15
16
17 RTD4
Ref
18
X2
1
2 RTD5
Ref
3
4
5 RTD6
Ref
6
7
8 RTD7
Ref
9
10
11 RTD8
Ref
12
13
14 RTD9
Ref
15
16
17 RTD10
Ref
18
GUID-3EC6FABE-BF3C-4789-AC2F-428C7D177126 V1 EN
ABB 111
1MRS759144 B
REX640
Product version: 1
ARC1001
Slot A1
X11
Light sensor input 1
Slot A1
X12
Light sensor input 2
Slot A1
X13
Light sensor input 3
Slot A1
X14
Light sensor input 4
GUID-8CEA3233-FF96-49B8-B7BD-530C489CB9DD V1 EN
112 ABB
1MRS759144 B
REX640
Product version: 1
Additional certificates can be found on the product page. The latest relevant information on the REX640 protection and
control relay is found on the product page. Scroll down the
page to find and download the related documentation.
ABB 113
1MRS759144 B
REX640
Product version: 1
Protection
Current reversal and weak-end infeed logic for residual RCRWPSCH CLCRWN 85 67G/N CREV,WEI
overcurrent
Directional earth-fault protection, low stage DEFLPDEF Io> -> 67G/N-1 51G/N-1
Directional earth-fault protection, high stage DEFHPDEF Io>> -> 67G/N-1 51G/N-2
114 ABB
1MRS759144 B
REX640
Product version: 1
Three-phase thermal protection for feeders, cables and T1PTTR 3Ith>F 49F
distribution transformers
Three-phase overload protection for shunt capacitor COLPTOC 3I> 3I< 51,37,86C
banks
Current unbalance protection for shunt capacitor banks CUBPTOC dI>C 60N
Directional reactive power undervoltage protection DQPTUV Q> -> ,3U< 32Q,27
ABB 115
1MRS759144 B
REX640
Product version: 1
Control
116 ABB
1MRS759144 B
REX640
Product version: 1
Hot-spot and insulation ageing rate monitoring for HSARSPTR 3Ihp>T 26/49HS
transformers
Current circuit supervision for transformers CTSRCTF MCS 3I,I2 CCM 3I,I2
Measurement
Power quality
Voltage total harmonic distortion, DC component (THD, VHMHAI PQM3VH PQM VTHD,VDC
DC) and individual harmonics
ABB 117
1MRS759144 B
REX640
Product version: 1
Logging functions
Other functionality
SR flip-flop, volatile SR SR SR
RS flip-flop, volatile RS RS RS
Minimum pulse timer second resolution, two channels TPSGAPC TPS 62TPS
Minimum pulse timer minutes resolution, two channels TPMGAPC TPM 62TPM
118 ABB
1MRS759144 B
REX640
Product version: 1
ABB 119
1MRS759144 B
REX640
Product version: 1
120 ABB
1MRS759144 B
REX640
Product version: 1
Description ID
ABB 121
1MRS759144 B
REX640
Product version: 1
IEC 61850 Pcs Base APP APP APP APP APP APP APP APP APP APP APP APP APP ADD ADD
1 2 3 4 5 6 7 8 9 10 11 12 13 1 2
Protection
DSTPDIS 1 ●
DSTPLAL 1 ●
DSOCPSCH 1 ●
CRWPSCH 1 ●
RESCPSCH 1 ●
RCRWPSCH 1 ●
LNPLDF 1 ●
BSTGAPC 2 ● ●
CVPSOF 1 ●
PHLPTOC 3 ●
PHHPTOC 3 ●
PHIPTOC 3 ●
DPHLPDOC 3 ●
DPHHPDOC 3 ●
EFLPTOC 3 ●
EFHPTOC 3 ●
EFIPTOC 3 ●
DEFLPDEF 4 ●
DEFHPDEF 4 ●
DPSRDIR 2 ●
DNZSRDIR 2 ●
EFPADM 3 ●
MFADPSDE 3 ●
WPWDE 3 ●
INTRPTEF 1 ●
HAEFPTOC 1 ●
NSPTOC 3 ●
PDNSPTOC 1 ●
ROVPTOV 4 ●
PHPTUV 4 ●
PHVPTOV 2 ●
PHPTOV 4 ●
PSPTOV 4 ●
PSPTUV 4 ●
NSPTOV 4 ●
FRPFRQ 12 ●
PHPVOC 2 ●
OEPVPH 2 ● ●
T1PTTR 1 ●
T2PTTR 1 ● ●
COLPTOC 1 ●
CUBPTOC 3 ●
HCUBPTOC 2 ●
SRCPTOC 1 ●
CNUPTOV 2 ●
DNSPDOC 2 ●
LVRTPTUV 3 ●
VVSPPAM 1 ●
DQPTUV 2 ●
DOPPDPR 3 ● ● ●
DUPPDPR 3 ● ●
UZPDIS 2 ● ●
UEXPDIS 2 ●
122 ABB
1MRS759144 B
REX640
Product version: 1
ABB 123
1MRS759144 B
REX640
Product version: 1
124 ABB
1MRS759144 B
REX640
Product version: 1
ABB 125
1MRS759144 B
REX640
Product version: 1
126 ABB
1MRS759144 B
REX640
Product version: 1
ABB 127
128
—
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
www.abb.com/mediumvoltage
www.abb.com/relion
1MRS759144 B