You are on page 1of 50

PRON NA11-MBx

MODBUS PROTOCOL USER GUIDE 2.50


Modbus Communication Protocol User Guide
PRON NA11-MBx

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 1 of 50


PRON NA11-MBx

Contents
Contents ........................................................................................................................................................................ 2
1 Modbus RTU communication................................................................................................................................ 3
1.1 Serial port settings........................................................................................................................................ 3
1.2 Transmission mode ...................................................................................................................................... 3
1.3 Data Types ................................................................................................................................................... 3
1.4 Supported functions ..................................................................................................................................... 4
1.5 Exceptions .................................................................................................................................................... 4
1.6 Modbus/TCP ................................................................................................................................................ 5
1.7 Network setting............................................................................................................................................. 5
1.8 NTP synchronization .................................................................................................................................... 5
2 Logical organization of the protection’s data ........................................................................................................ 6
2.1 Basic Data Type ........................................................................................................................................... 6
2.1.1 BIT............................................................................................................................................................ 6
2.1.2 BYTE........................................................................................................................................................ 7
2.1.3 UBYTE ..................................................................................................................................................... 7
2.1.4 WORD...................................................................................................................................................... 8
2.1.5 UWORD ................................................................................................................................................... 8
2.1.6 LONG ....................................................................................................................................................... 9
2.1.7 ULONG .................................................................................................................................................... 9
2.1.8 ARR........................................................................................................................................................ 10
2.1.9 STR ........................................................................................................................................................ 11
2.1.10 CMD ....................................................................................................................................................... 11
3 How to read the Address Data Table.................................................................................................................. 12
3.1 Address Data Table.................................................................................................................................... 12
3.1.1 VAR........................................................................................................................................................ 12
3.1.2 REF ........................................................................................................................................................ 12
3.1.3 IDX ......................................................................................................................................................... 12
3.1.4 DIM......................................................................................................................................................... 13
3.1.5 TYPE...................................................................................................................................................... 13
3.1.6 UM.......................................................................................................................................................... 13
3.1.7 Kv 13
3.1.8 ENUM..................................................................................................................................................... 14
3.2 Common properties.................................................................................................................................... 14
3.2.1 Input state .............................................................................................................................................. 14
3.2.2 Output state............................................................................................................................................ 14
4 Examples ............................................................................................................................................................ 15
4.1 Example 1. How to read a variable ............................................................................................................ 15
4.2 Example 2. How to read a BIT data type ................................................................................................... 16
4.3 Example 3. How to execute a command.................................................................................................... 16
5 Glossary .............................................................................................................................................................. 17
6 Appendix A. Address Data Table........................................................................................................................ 18

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 2 of 50


PRON NA11-MBx
Introduction

This Protocol Manual is for use with Thytronic Protective Relays, such as the DMC, NTG and PRO-N series that
support Modbus RTU and Modbus TCP communication protocol.

1 Modbus RTU communication


The Thytronic Protective Relay (TPR) uses a communication protocol called Modbus. A company called Modicon,
for use with their programmable controllers, developed the Modbus protocol. Since that time Modbus has evolved
into common communication protocol in industry and it’s now a “de-facto” standard.
The communication method involves using a master-slave technique, in which there is one master and several
slaves. The TPR is a slave device. Only the master can initiate queries. These queries are directed to an individual
slave device and the appropriate slave responds with the requested data.
There are two transmission modes. These modes are known as RTU (Remote Terminal Unit) and ASCII (American
Standard Code for Information Interchange).
The TPR can be setup in a network of up to 247 slave devices. Each device must have a different address (1-247).
The TPR can be set for RTU mode only.

 The MODBUS protocol documentation can be found online at www.modicon.com or www.modbus.org


(document “PDI-MBUS-300 REV J”).

1.1 Serial port settings

To communicate with a TPR, the serial port of the Master has to be configured with the following settings:

Address Baud Rate Parity Stop bits Data bits


1 19200 No 1 8
Table 1 Serial port settings

Remark: Every TPR has a default MODBUS Slave Address set to 1.

1.2 Transmission mode

The transmission mode supported by TPR is RTU.


The ASCII transmission mode is not supported.

1.3 Data Types

A TPR has 4 data table, each of which corresponds to one of the 4 basic Modbus data type. Each table contains up
to 1024 data that can be accessed with the proper function as described in the following table.

table/data type reference information Access Function Code for Function Code for
Reading Writing
Coils 0X 1 bit Read/Write 0x01 0x05
Discrete Inputs 1X 1 bit Read only 0x02 -
Input Registers 3X 16 bit Word Read only 0x04 -
Holding Registers 4X 16 bit Word Read/Write 0x03 0x06, 0x10
Table 2. Modbus Data Type

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 3 of 50


PRON NA11-MBx
1.4 Supported functions

TPR supports the following Modbus functions:

Code Name
0x01 Read Coil Status
0x02 Read Input Status
0x03 Read Holding Registers
0x04 Read Input Registers
0x05 Force Single Coil
0x06 Preset Single Register
0x0F Force Multiple Coil
0x10 Preset Multiple Registers
Table 3 Supported Modbus functions

The smallest data that can be exchanged within a Modbus message is the Modbus Register.
A Modbus Register is a 16 bit data in the Big Endian representation, called WORD (W)

W = BH BL

1.5 Exceptions

When a TPR receives a request that can not handle (e.g. the data address doesn’t exists, the function is not
supported, etc.), a special response called Exception is returned to the Master. This message contains the
information needed to recognize the error occurred.

In an Exception message the most significant bit (msb) of the Function field is set to 1.

• Function Code field: in case of exception, the msb is set to 1.


• Data field: this field contains a value related to the kind of error generated by the request.

An example of request with exception response could be the following:

04 07 A5 50 00 02 - -
TX
S F ADR DIM CRC

04 87 01 - -
RX
S F DATA CRC

S = Slave Address
F = Function Code
ADR = Modbus Data Address
DIM = Dimension (number of registers)
DATA = data value
CRC = Cyclical Redundancy Code

In this example the function code 07 is not supported by the TPR. The response is an exception message (the msb
of function code F=0x87 is set to 1). The Data field value is 1 and according with the Modbus standard corresponds
to the “Illegal function” exception.

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 4 of 50


PRON NA11-MBx
The next table describes all the exceptions handled by the TPRs.

Code Name Description


The function code received in the query is not an allowable action for
01 ILLEGAL FUNCTION
the slave.
The data address received in the query is not an allowable address for
02 ILLEGAL DATA ADDRESS
the slave
A value contained in the query data field is not an allowable value for
03 ILLEGAL DATA VALUE
the slave
An unrecoverable error occurred while the slave was attempting to
04 SLAVE DEVICE FAILURE
perform the requested action.
The slave has accepted the request and is processing it, but a long
05 ACKNOWLEDGE duration of time will be required to do so. This response is returned to
prevent a timeout error from occurring in the master.
The slave is engaged in processing a long-duration program command.
06 SLAVE DEVICE BUSY
The master should retransmit the message later when the slave is free.

1.6 Modbus/TCP
Modbus/TCP, an extension of Modbus/RTU, defines how Modbus/RTU and Modbus/ASCII messages are encoded
within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible to
apply as the original Modbus/RTU. The specification can be found online at www.modicon.com

Transaction Protocol Length Field Modbus Frame CHECKSUM TCP FRAME


Identifier Identifier

MODBUS FRAME S F DATA

1.7 Network setting


Every device connected to the TCP/IP network including the TPRs must have a unique IP address. Every TPR has
the following default IP address:

Default IP Address = 200.1.1.135

1.8 NTP synchronization

To synchronize the Real Time Clock of more than one protection at the same time the NTP service is available.
Network Time Protocol (NTP) is a protocol for synchronizing the clocks of computer systems over packet-switched,
variable-latency data networks. NTP uses UDP port 123 as its transport layer. It is designed particularly to resist
the effects of variable latency.

To synchronize all the TPR in a network is sufficient to send a broadcast NTP packet on the network.

 The NTP service can be enabled/disabled changing the “NTP synchronization” parameter (Appendix A –
Address Data Table).

More information about the NTP protocol and service can be found online at www.ntp.org

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 5 of 50


PRON NA11-MBx

2 Logical organization of the protection’s data


Each TPR has some data that can be read and/or written. These data are grouped in 4 data table.
Data with 1 bit of information (e.g. the state of an output), can be placed in the Discrete Inputs table or in the Coils
table, while data with more than 1 bit of information (e.g. the value of a current), can be placed in the Register
table, sometimes fitting more than one register as described in the following example.

1x, Discrete Input 3x, Input Registers


n° var n° var
6 I> Start 157 Power frequeny
7 I> Trip 158 Phase current IL1 value – Word L
8 I> Block1 159 Phase current IL1 value – Word H
160 Phase current IL2 value – Word L
161 Phase current IL2 value – Word H

Table 4. Example of data structures

Example: let’s read the value of the variable ”I> Start”. This variable is the first one in the Discrete Input data table.
To read this kind of data the Modbus function 0x02 has to be used. As described in the standard the Modbus
address to access the data is given by IDX-1 = 5 in this case.
To read the data from the Slave address 1 the next request has to be sent:

01 02 05 00 00 01 - -
TX
S F ADR DIM CRC

2.1 Basic Data Type

In this chapter all the basic TPR data type and their relationship with the Modbus data type will be described.

2.1.1 BIT
Description:
Variable with 1 bit of information.

Relationship with Modbus:


The information corresponds to the least significant bit (lsb) of the first data byte addressed in the query.

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 6 of 50


PRON NA11-MBx

2.1.2 BYTE

Description:
Signed variable with 1 byte (8 bit) of information. Range: -128  +127

Relationship with Modbus:


A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).

B 00 B
Modbus
Byte
Register

Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:

0D 00 0D
Modbus
Byte
Register

2.1.3 UBYTE

Description:
Unsigned variable with 1 byte (8 bit) of information. Range: 0  +255

Relationship with Modbus:


A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).

B 00 B
UByte Modbus
Register

Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:

0D 00 0D
Modbus
Byte
Register

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 7 of 50


PRON NA11-MBx

2.1.4 WORD

Description:
Signed variable with 2 byte (16 bit) of information. Range: -32.768  +32.767

Relationship with Modbus:


A WORD data type is always placed in a Modbus Register (DIM=1) keeping the representation (Big Endian).

BH BL BH BL
Modbus
Word
Register

Example:
relationship between the data WORD whose value is 3073 (0x0C01) and its Modbus representation:

0C 01 0C 01
Modbus
Word
Register

2.1.5 UWORD

Description:
Unsigned variable with 2 byte (16 bit) of information. Range: 0  +65.535

Relationship with Modbus:


A UWORD data type is always placed in a Modbus Register (DIM=1) keeping the representation (Big Endian).

BH BL BH BL
Modbus
UWord
Register

Example:
relationship between the data UWORD whose value is 3073 (0x0C01) and its Modbus representation:

0C 01 0C 01
Modbus
UWord
Register

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 8 of 50


PRON NA11-MBx

2.1.6 LONG

Description:
Signed variable with 4 byte (32 bit) of information. Range: -2.147.483.648  +2.147.483.647

Relationship with Modbus:


A LONG data type is placed in two Modbus Registers (DIM=2). The Least Significant Word of the LONG data type
is placed in the first Modbus register while the Most Significant Word of the LONG data type is placed in the second
Modbus register.

BHH BHL BLH BLL BLH BLL BHH BHL


WH WL WL WH
Long Modbus Registers

Example:
relationship between the data LONG 66536 (0x103E8) and its value in the Modbus protocol domain:

00 01 03 E8 03 E8 00 01
Long Modbus Registers

2.1.7 ULONG

Description:
Unsigned variable with 4 byte (32 bit) of information. Range: -0  +4.294.967.295

Relationship with Modbus:


A ULONG data type is placed in two Modbus Registers (DIM=2). The Least Significant Word of the ULONG data
type is placed in the first Modbus register while the Most Significant Word is placed in the second Modbus register.

LHH LHL LLH LLL LLH LLL LHH LHL


WH WL WL WH
ULong Modbus Registers

Example:
relationship between the ULONG data whose value is 66536 (0x103E8) and its Modbus representation:

00 01 03 E8 03 E8 00 01
ULong Modbus Registers

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 9 of 50


PRON NA11-MBx

2.1.8 ARR

Description:
Array of BYTE.

Relationship with Modbus:



An ARR data type of length n is placed in N Modbus Registers (N= ceil(n/2) ) keeping the byte ordering. If odd n,
the last byte of ARR is placed in the MSB of the last Modbus register, while the LSB is set to 0

If even n:

B1 B2 Bn B1 B2 Bn-1 Bn
1 2 n 1 N
Array[n] Modbus Registers
N = ceil(n/2)
If odd n:

B1 B2 Bn B1 B2 Bn 0
1 2 n 1 N
Array[n] Modbus Registers
Example:
Let’s consider an array with 3 bytes whose values are: (0x01, 0x3A, 0x1F). This array can be placed in
N=ceil(3/2)=ceil(1.5)=2 Modbus registers.

01 3A 1F 01 3A 1F 00
1 2 3 1 2
Array[3] Modbus Registers


The ceil function returns the smallest integer value that is greater than or equal to a number. For example,
ceil(2.3)=3 , ceil(1.5)=2.
Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 10 of 50


PRON NA11-MBx

2.1.9 STR

Description:
String data type. It’s represented by an array of BYTE. Every byte represents the hexadecimal ASCII code
associated with the character of the string

Relationship with Modbus:



An STR data type of length n is placed in N Modbus Registers (N= ceil(n/2) ) keeping the byte ordering. If odd n,
the last byte is placed in the MSB of the last Modbus register. A zero padding operation (with char ‘\0’) is necessary
for every writing operation where the length of the string is lower than the number of bytes contained in the Modbus
registers.

If even n:

C1 C2 Cn C1 C2 Cn-1 Cn
1 2 n 1 N
String[n] Modbus Registers
N = ceil(n/2)
If odd n:

C1 C2 Cn C1 C2 Cn ‘\0’
1 2 n 1 N
String[n] Modbus Registers

Example:
Let’s assume “Relay reference name” is a STRING variable whose length is 8 characters, its Modbus address is
0x0029 and its dimension is 4 Modbus registers. Let’s set its value to “NAxx”.

First of all the ASCII code in hexadecimal notation for each character of the string “NA10” is equal to 0x4E417878
An example of write request could be the following:

01 10 00 29 00 05 10 4E 41 78 78 00 00 00 00 - -
TX
S F ADR DIM B DATA1 DATA2 DATA3 DATA4 CRC
‘N’ ‘A’ ‘x’ ‘x’ ‘\0’ ‘\0’ ‘\0’ ‘\0’

Remark. A zero padding operation is necessary because the length of the string “DMC901” is lower than the length
of the RACK_TYPE variable.

2.1.10 CMD
Description:
This type of data represents a command.

Every Command corresponds to a Coil data type. To execute the command, the value of the associated Coil has to
be set to 1 with the Modbus function 0x05.


The ceil function returns the smallest integer value that is greater than or equal to a number. For example,
ceil(2.3)=3 , ceil(1.5)=2.
Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 11 of 50


PRON NA11-MBx

3 How to read the Address Data Table


All the information necessary to read/write data from/to a TPR is contained in the Address Data Table (see
Appendix A).

3.1 Address Data Table

Now a description of all the Address Data Table’s fields is given:

VAR REF IDX DIM TYPE UM KV ENUM

Table 5. Address Data Table’s field

3.1.1 VAR

The VAR field contains the description of the variable.


An example of VAR fields could be: “Relay phase nominal current - In ”, “Relay reference name” or “I> Trip”.

3.1.2 REF

The REF field tells which data table the variable is stored in.
The REF field can assume one of the following values:

• 0x: data stored in the COIL table


• 1x: data stored in the DISCRETE INPUT table
• 3x: data stored in the INPUT REGISTER table
• 4x: data stored in the HOLDING REGISTER table

3.1.3 IDX

The IDX field represents the position of the table (specified by REF) in which the variable VAR is stored.
The IDX value is related to the Modbus address of the variable. The relationship between IDX and Modbus address
is the following:
MB address = IDX - 1

Example: let’s consider the following Address Data Table

VAR REF IDX DIM


Relay phase nominal current - In 3x 50 1
Relay reference name 3x 42 8
I> Trip 1x 7 1

Let’s see that the variable “Relay phase nominal current - In” is the 50th variable stored in the Input Registers
table (reference 3x) and its dimension is 1 Modbus register (DIM=1).

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 12 of 50


PRON NA11-MBx

3.1.4 DIM

The DIM field is the number of Modbus registers necessary to contain the VAR data.

Example: let’s read the value of the variable “Relay phase nominal current - In ”.
From the previous table we see that the reference is 3x for which the function 0x04 has to be used for reading.
The Modbus address is IDX-1=50-1=49.
The request for reading is the following:

01 03 00 31 00 01 - -
TX
S F ADR DIM CRC

3.1.5 TYPE

The TYPE field specifies the basic data type associated with VAR, as described in chapter 2.1.

3.1.6 UM

The UM field specifies the Unit of Measure of the variable.


If UM is empty, it means that the Unit is just a number.

3.1.7 Kv

The Kv field contains the scale factor that has to be applied to the variable to obtain the real value. If Kv is not
equal to 1, the value of the variable must be divided by Kv.

Example: let’s consider the following address data table

VAR REF IDX DIM TYPE UM KV ENUM


Phase current IL1 - Value 3x 159 2 LONG In 16000

Let’s read the “Phase current IL1 - Value “ from the Slave address 1.

01 04 00 9E 00 02 - -
TX
S F ADR DIM CRC

Let’s assume the following response:

01 04 04 A9 80 00 03 - -
RX
S F B DATA1 DATA2 CRC
LONG
VALL VALH

The TYPE field is necessary to decode the right value returned from the Modbus response, as described in chapter
2.1. The decoded value contained in the response is 0x0003A980 = 240000. Kv=16000 means that the value of the
variable has to be divided by 16000. UM specify the Unit. The “Phase current IL1 – Value” is equal to 15 In.

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 13 of 50


PRON NA11-MBx

3.1.8 ENUM

The ENUM field, whenever is defined, contains the meaning of all possible values assumed by the variable.

3.2 Common properties


Some common properties are now described for a better understanding.

3.2.1 Input state


• State
It’s the physical state of the Input: 0 or 1 (OFF or ON)

3.2.2 Output state


• State
It’s the logical state of the output: 0 or 1 (OFF or ON); could not correspond with its physical state
• Fail
It’s the Coil Failure Status: 0 or 1 (OFF=”OK” o ON=”Fault”).

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 14 of 50


PRON NA11-MBx

4 Examples
For all the examples, the following symbols are assumed:

S = Slave Modbus address (1-247)


F = Modbus Function code (1,2,3,4,5,6,15,16)
B = number of byte in the DATA field
ADR = Modbus DATA address
DIM = number of Modbus DATA address
CRC = Cyclical Redundancy Check
DATAx = register x of DATA field
VALx = value x of the variable

4.1 Example 1. How to read a variable

Let’s read from the Slave address 1 the value of the “Relay phase nominal current - In ”.

From the Address Data Table (Appendix A) we find out the following information;

VAR REF IDX DIM TYPE UM Kv ENUM


Relay phase nominal current - In 3x 50 1 UWORD A 1

The REF field value specify an Input Register (3x), so the function 0x04 is used for reading. From the IDX the
Modbus address is derived: Modbus address = IDX -1 = 50 - 1 = 49. DIM specify the number of register to be read.

01 04 00 3E 00 02 - -
TX
S F ADR DIM CRC

01 04 04 00 05 - -
RX
S F B DATA CRC

The TYPE field value is equal to UWORD. Applying the rules described in the chapter 2.1, the following value is
obtained
VAL = 0x0005= 5.

Il UM field specify the Unit of measure that is “Ampere”, while Kv = 1 means that the value doesn’t need to be
scaled. The “Relay phase nominal current – In” is equal to 5A.

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 15 of 50


PRON NA11-MBx

4.2 Example 2. How to read a BIT data type


Let’s read from the Slave address 1 the variable “I> Trip”.

From the Address Data Table (Appendix A) we find out the following information;

VAR REF IDX DIM TYPE UM Kv ENUM


I> Trip 1x 7 1 BIT 0=OFF, 1=ON

The REF field value specify a Discrete Input (1x), so the function 0x02 is used for reading. From the IDX the
Modbus address is derived: Modbus address = IDX -1 = 7 - 1 = 6. DIM specify the number of register to be read.

01 02 00 06 00 01 - -
TX
S F ADR DIM CRC

01 02 01 00 01 - -
RX
S F B VAL CRC

The TYPE field value is equal to BIT. Applying the rules described in the chapter 2.1, the following value is
obtained
VAL = 1.

The ENUM field specifies the meaning of the value. In this case, the value 1 corresponds to the “ON” state and it
means that a Trip has occurred on the first threshold of the 51 function.

4.3 Example 3. How to execute a command

Let’s execute the command “Reset events” on the Slave address 1.


From the Address Data Table (Appendix A) we find out the following information;

VAR REF IDX DIM TYPE UM Kv ENUM


Reset LEDs 0x 2 1 CMD 0=OFF, 1=ON

The TYPE field value specifies a Command (CMD). As described in chapter 2.1, to execute the command, it is
necessary to set its value to 1.
The REF field value specify a Coil (0x), so the function 0x05 is used for writing. From the IDX the Modbus address
is derived: Modbus address = IDX -1 = 2 - 1 = 1
The Response message is known as an “Acknowledge” because it’s an echo of the request, and it means that the
Coil has been set:

01 05 00 01 FF 00 - -
TX
S F ADR DATA CRC

01 05 00 01 FF 00 - -
RX
S F ADR DATA CRC

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 16 of 50


PRON NA11-MBx

5 Glossary
BH Most significative Byte of a Word data (Higher byte)
BL Least significative Byte of a Word data (Lower byte)
LSB Least Significative Byte
lsb least significative bit
MSB Most Significative Byte
msb Most significative bit
NTP Network Time Protocol
RTU Remote Terminal Unit
TPR Thytronic Protective Relay
WH Most significative Word of a Long data (Higher word)
WL Least significative Word of a Long data (Lower word)

Version 2.50

PRON NA11-MBx Remote Setting Manual Page: 17 of 50


PRON NA11-MBx

6 Appendix A. Address Data Table


VAR REF IDX DIM TYPE Range Um Kv ENUM
Commands
Set RTC 0x 1 1 CMD 0=OFF, 1=ON
Reset CB Open counter 0x 2 1 CMD 0=OFF, 1=ON
Reset LEDs 0x 3 1 CMD 0=OFF, 1=ON
Reset CB time action 0x 4 1 CMD 0=OFF, 1=ON
Reset Breaking currents SumI2t 0x 5 1 CMD 0=OFF, 1=ON
Reset Breaking currents SumI 0x 6 1 CMD 0=OFF, 1=ON
Reset partial counters 0x 7 1 CMD 0=OFF, 1=ON
Fault reading 0x 8 1 CMD 0=OFF, 1=ON
Reset faults 0x 9 1 CMD 0=OFF, 1=ON
Reset faults identifier 0x 10 1 CMD 0=OFF, 1=ON
Events reading 0x 11 1 CMD 0=OFF, 1=ON
Reset events 0x 12 1 CMD 0=OFF, 1=ON
Reset event identifier 0x 13 1 CMD 0=OFF, 1=ON
Open CB 0x 14 1 CMD 0=OFF, 1=ON
Close CB 0x 15 1 CMD 0=OFF, 1=ON
Test-off 0x 16 1 CMD 0=OFF, 1=ON
Test-on 0x 17 1 CMD 0=OFF, 1=ON
Reset on demand measures 0x 18 1 CMD 0=OFF, 1=ON
Enable reclose 0x 19 1 CMD 0=OFF, 1=ON
Disable reclose 0x 20 1 CMD 0=OFF, 1=ON
Day 4x 1 1 UWORD 1,31,1 1
Month 4x 2 1 UWORD 1,12,1 1
Year 4x 3 1 UWORD 2000,2099,1 1
Hour 4x 4 1 UWORD 0,23,1 1
Minute 4x 5 1 UWORD 0,59,1 1
Second 4x 6 1 UWORD 0,59,1 1
Testing rele 4x 7 1 WORD 0="K1",1="K2",2="K3",3="K4",4="
K5",5="K6",6="K7",7="K8",8="K9"
,9="K10"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 18 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Info
Code 3x 1 6 STR
Serial number - 3x 7 2 LONG 1
Application sw release 3x 9 6 STR
Base sw release 3x 15 6 STR
DSP fw identifier 3x 21 1 UWORD 1
DSP fw release 3x 22 6 STR
Communication
Address 3x 28 1 UBYTE 1
IP host address 3x 29 8 STR
IP net mask 3x 37 8 STR
Autonegotiation 1x 1 1 BIT 0=OFF, 1=ON
Enable 1x 2 1 BIT 0=OFF, 1=ON
Rated nominal values
Relay reference name 3x 45 8 STR
Relay phase nominal current - In 3x 53 2 ULONG A 1
Relay residual nominal current - IEn 3x 55 2 ULONG A 1
Phase CT primary nominal current - Inp 3x 57 2 ULONG A 1
Residual CT primary nominal current - IEnp 3x 59 2 ULONG A 1
Relay nominal frequency - fn 3x 61 2 ULONG Hz 1
Measurements reading mode 3x 63 1 WORD 0="RELATIVE",1="PRIMARY"
Profile selection
Profile 3x 64 1 WORD 0="A",1="B"
Clock
Day 3x 65 1 UWORD 1
Month 3x 66 1 UWORD 1
Year 3x 67 1 UWORD 1
Hour 3x 68 1 UWORD 1
Minute 3x 69 1 UWORD 1
Second 3x 70 1 UWORD 1

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 19 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


READINGS
Diagnostic
MINOR Fail alarm 1x 3 1 BIT 0=NO, 1=YES
Protection and controls 1x 4 1 BIT 0=OUT OF SERVICE, 1=ON
SERVICE
System diagnostic 3x 71 1 WORD 0="OK",1="FATAL",2="MAJOR",3
="MINOR"
Device diagnostic 1x 5 1 BIT 0=OK, 1=NOT OK
Program diagnostic 3x 72 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data-base boot 3x 73 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data-base run-time 3x 74 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
DSP boot 3x 75 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
DSP run-time 3x 76 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Memory boot 3x 77 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Memory run-time 3x 78 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Serial flash startup 3x 79 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Serial flash run-time 3x 80 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data Bus heavy 3x 81 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data Bus minor 3x 82 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify startup 3x 83 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify run-time major 3x 84 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify run-time minor 3x 85 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
PLC I/O assigned verify startup 3x 86 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
PLC I/O assigned verify run-time major 3x 87 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
PLC I/O assigned verify run-time minor 3x 88 1 WORD 0="OK",1="NOT
OK",2="Disappeared"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 20 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Diagnostic
MMI module - Boot 3x 89 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MMI module - Run-time 3x 90 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MRI module - Boot 3x 91 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MRI module - Run-time 3x 92 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MID16-1 module - Boot 3x 93 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 21 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Diagnostic
MID16-1 module - Run-time 3x 94 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MID16-2 module - Boot 3x 95 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MID16-2 module - Run-time 3x 96 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
PT100 module - Boot 3x 97 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
PT100 module - Run-time 3x 98 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 22 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Diagnostic
MCI module (4...20mA) - Boot 3x 99 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MCI module (4...20mA) - Run-time 3x 100 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 23 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


PROTECTIONS
Auto-reclose - 79
ActiveMode 79 3x 101 1 WORD 0="OFF",1="Rapid",2="Rapid+Slo
w"
Run 79 1x 6 1 BIT 0=OFF, 1=ON
LastEvent 79 3x 102 1 WORD 0="No events",1="Rapid
reclosure OK",2="Slow reclosure
OK",3="Delayed reclosure
OK",4="Fail reclosure
phase",5="Fail reclosure
earth",6="Manual close",7="Cycle
interrupted",8="Cycle in progress"
CycleState 79 3x 103 1 WORD 0="Rest",1="Rapid reclosure
time",2="Slow reclosure
time",3="Fault discrimination
time",4="Reclaim
time",5="Delayed reclosure
time",6="Reclaim final time"
Residual-time 79 3x 104 2 ULONG s 1000
EnableState 79 1x 7 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 24 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Thermal protection with RTD thermometric probes - 26
Alarm ThAL1 1x 8 1 BIT 0=OFF, 1=ON
Trip Th>1 1x 9 1 BIT 0=OFF, 1=ON
Alarm ThAL2 1x 10 1 BIT 0=OFF, 1=ON
Trip Th>2 1x 11 1 BIT 0=OFF, 1=ON
Alarm ThAL3 1x 12 1 BIT 0=OFF, 1=ON
Trip Th>3 1x 13 1 BIT 0=OFF, 1=ON
Alarm ThAL4 1x 14 1 BIT 0=OFF, 1=ON
Trip Th>4 1x 15 1 BIT 0=OFF, 1=ON
Alarm ThAL5 1x 16 1 BIT 0=OFF, 1=ON
Trip Th>5 1x 17 1 BIT 0=OFF, 1=ON
Alarm ThAL6 1x 18 1 BIT 0=OFF, 1=ON
Trip Th>6 1x 19 1 BIT 0=OFF, 1=ON
Alarm ThAL7 1x 20 1 BIT 0=OFF, 1=ON
Trip Th>7 1x 21 1 BIT 0=OFF, 1=ON
Alarm ThAL8 1x 22 1 BIT 0=OFF, 1=ON
Trip Th>8 1x 23 1 BIT 0=OFF, 1=ON
Diag PT100 1x 24 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 25 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Phase overcurrent - 50/51
Start I> 1x 25 1 BIT 0=OFF, 1=ON
Trip I> 1x 26 1 BIT 0=OFF, 1=ON
BLK1 I> 1x 27 1 BIT 0=OFF, 1=ON
BLK2IN I> 1x 28 1 BIT 0=OFF, 1=ON
CLP I> 1x 29 1 BIT 0=OFF, 1=ON
Start I>> 1x 30 1 BIT 0=OFF, 1=ON
Trip I>> 1x 31 1 BIT 0=OFF, 1=ON
BLK1 I>> 1x 32 1 BIT 0=OFF, 1=ON
BLK2IN I>> 1x 33 1 BIT 0=OFF, 1=ON
CLP I>> 1x 34 1 BIT 0=OFF, 1=ON
Start I>>> 1x 35 1 BIT 0=OFF, 1=ON
Trip I>>> 1x 36 1 BIT 0=OFF, 1=ON
BLK1 I>>> 1x 37 1 BIT 0=OFF, 1=ON
BLK2IN I>>> 1x 38 1 BIT 0=OFF, 1=ON
CLP I>>> 1x 39 1 BIT 0=OFF, 1=ON
Residual overcurrent - 50N/51N
Start IE> 1x 40 1 BIT 0=OFF, 1=ON
Trip IE> 1x 41 1 BIT 0=OFF, 1=ON
BLK1 IE> 1x 42 1 BIT 0=OFF, 1=ON
BLK2IN IE> 1x 43 1 BIT 0=OFF, 1=ON
CLP IE> 1x 44 1 BIT 0=OFF, 1=ON
Start IE>> 1x 45 1 BIT 0=OFF, 1=ON
Trip IE>> 1x 46 1 BIT 0=OFF, 1=ON
BLK1 IE>> 1x 47 1 BIT 0=OFF, 1=ON
BLK2IN IE>> 1x 48 1 BIT 0=OFF, 1=ON
CLP IE>> 1x 49 1 BIT 0=OFF, 1=ON
Start IE>>> 1x 50 1 BIT 0=OFF, 1=ON
Trip IE>>> 1x 51 1 BIT 0=OFF, 1=ON
BLK1 IE>>> 1x 52 1 BIT 0=OFF, 1=ON
BLK2IN IE>>> 1x 53 1 BIT 0=OFF, 1=ON
CLP IE>>> 1x 54 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 26 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Second Harmonic Restraint
Start I2ndh> 1x 55 1 BIT 0=OFF, 1=ON
Trip circuit supervision - 74TCS
Start 74TCS 1x 56 1 BIT 0=OFF, 1=ON
Trip 74TCS 1x 57 1 BIT 0=OFF, 1=ON
BLK1 74TCS 1x 58 1 BIT 0=OFF, 1=ON
Breaker Failure - BF
Trip Int/Ext 1x 59 1 BIT 0=OFF, 1=ON
Start IBF> 1x 60 1 BIT 0=OFF, 1=ON
Start IEBF> 1x 61 1 BIT 0=OFF, 1=ON
Start BF 1x 62 1 BIT 0=OFF, 1=ON
Trip BF 1x 63 1 BIT 0=OFF, 1=ON
BLK1 BF 1x 64 1 BIT 0=OFF, 1=ON
CT supervision - 74CT
Start I* 1x 65 1 BIT 0=OFF, 1=ON
Trip S< 1x 66 1 BIT 0=OFF, 1=ON
BLK1 S< 1x 67 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 27 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


PLC
State 1 3x 106 1 WORD 0="0",1="1"
State 2 3x 107 1 WORD 0="0",1="1"
State 3 3x 108 1 WORD 0="0",1="1"
State 4 3x 109 1 WORD 0="0",1="1"
State 5 3x 110 1 WORD 0="0",1="1"
State 6 3x 111 1 WORD 0="0",1="1"
State 7 3x 112 1 WORD 0="0",1="1"
State 8 3x 113 1 WORD 0="0",1="1"
State 9 3x 114 1 WORD 0="0",1="1"
State 10 3x 115 1 WORD 0="0",1="1"
State 11 3x 116 1 WORD 0="0",1="1"
State 12 3x 117 1 WORD 0="0",1="1"
State 13 3x 118 1 WORD 0="0",1="1"
State 14 3x 119 1 WORD 0="0",1="1"
State 15 3x 120 1 WORD 0="0",1="1"
State 16 3x 121 1 WORD 0="0",1="1"
State 17 3x 122 1 WORD 0="0",1="1"
State 18 3x 123 1 WORD 0="0",1="1"
State 19 3x 124 1 WORD 0="0",1="1"
State 20 3x 125 1 WORD 0="0",1="1"
State 21 3x 126 1 WORD 0="0",1="1"
State 22 3x 127 1 WORD 0="0",1="1"
State 23 3x 128 1 WORD 0="0",1="1"
State 24 3x 129 1 WORD 0="0",1="1"
State 25 3x 130 1 WORD 0="0",1="1"
State 26 3x 131 1 WORD 0="0",1="1"
State 27 3x 132 1 WORD 0="0",1="1"
State 28 3x 133 1 WORD 0="0",1="1"
State 29 3x 134 1 WORD 0="0",1="1"
State 30 3x 135 1 WORD 0="0",1="1"
State 31 3x 136 1 WORD 0="0",1="1"
State 32 3x 137 1 WORD 0="0",1="1"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 28 of 50
PRON NA11-MBx
VAR REF IDX DIM TYPE Range Um Kv ENUM
Circuit Breaker supervision
CB-State 3x 138 1 WORD 0="Open",1="Closed",2="?"
52a 1x 68 1 BIT 0=OFF, 1=ON
52b 1x 69 1 BIT 0=OFF, 1=ON
CB fail 1x 70 1 BIT 0=OFF, 1=ON
Break time assigned relays state 1x 71 1 BIT 0=OFF, 1=ON
State N.Open 1x 72 1 BIT 0=OFF, 1=ON
State SumI 1x 73 1 BIT 0=OFF, 1=ON
SumIL1 3x 139 2 ULONG In 16000
SumIL2 3x 141 2 ULONG In 16000
SumIL3 3x 143 2 ULONG In 16000
State SumI^2t 1x 74 1 BIT 0=OFF, 1=ON
SumIL1^2t 3x 145 2 ULONG In^2s 250000
SumIL2^2t 3x 147 2 ULONG In^2s 250000
SumIL3^2t 3x 149 2 ULONG In^2s 250000
State tbreak 1x 75 1 BIT 0=OFF, 1=ON
PARTIAL COUNTERS
Auto-reclose - 79
ParRR79cnt - Value 3x 151 1 WORD
ParSR79cnt - Value 3x 152 1 WORD
ParDR79cnt - Value 3x 153 1 WORD
ParFR79Pcnt - Value 3x 154 1 WORD
ParFR79Ecnt - Value 3x 155 1 WORD

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 29 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Thermal protection with RTD thermometric probes - 26
ParThAL1cnt - Value 3x 156 1 WORD
ParTh>1cnt - Value 3x 157 1 WORD
ParThAL2cnt - Value 3x 158 1 WORD
ParTh>2cnt - Value 3x 159 1 WORD
ParThAL3cnt - Value 3x 160 1 WORD
ParTh>3cnt - Value 3x 161 1 WORD
ParThAL4cnt - Value 3x 162 1 WORD
ParTh>4cnt - Value 3x 163 1 WORD
ParThAL5cnt - Value 3x 164 1 WORD
ParTh>5cnt - Value 3x 165 1 WORD
ParThAL6cnt - Value 3x 166 1 WORD
ParTh>6cnt - Value 3x 167 1 WORD
ParThAL7cnt - Value 3x 168 1 WORD
ParTh>7cnt - Value 3x 169 1 WORD
ParThAL8cnt - Value 3x 170 1 WORD
ParTh>8cnt - Value 3x 171 1 WORD
Phase overcurrent - 50/51
ParStI>cnt - Value 3x 172 1 WORD
ParTrI>cnt - Value 3x 173 1 WORD
ParBk1I>cnt - Value 3x 174 1 WORD
ParBk2I>cnt - Value 3x 175 1 WORD
ParStI>>cnt - Value 3x 176 1 WORD
ParTrI>>cnt - Value 3x 177 1 WORD
ParBk1I>>cnt - Value 3x 178 1 WORD
ParBk2I>>cnt - Value 3x 179 1 WORD
ParStI>>>cnt - Value 3x 180 1 WORD
ParTrI>>>cnt - Value 3x 181 1 WORD
ParBk1I>>>cnt - Value 3x 182 1 WORD
ParBk2I>>>cnt - Value 3x 183 1 WORD

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 30 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Residual overcurrent - 50N/51N
ParStIE>cnt - Value 3x 184 1 WORD
ParTrIE>cnt - Value 3x 185 1 WORD
ParBk1IE>cnt - Value 3x 186 1 WORD
ParBk2IE>cnt - Value 3x 187 1 WORD
ParStIE>>cnt - Value 3x 188 1 WORD
ParTrIE>>cnt - Value 3x 189 1 WORD
ParBk1IE>>cnt - Value 3x 190 1 WORD
ParBk2IE>>cnt - Value 3x 191 1 WORD
ParStIE>>>cnt - Value 3x 192 1 WORD
ParTrIE>>>cnt - Value 3x 193 1 WORD
ParBk1IE>>>cnt - Value 3x 194 1 WORD
ParBk2IE>>>cnt - Value 3x 195 1 WORD
Second Harmonic Restraint
ParStI2ndh>cnt - Value 3x 196 1 WORD
Trip circuit supervision - 74TCS
ParTr74TCScnt - Value 3x 197 1 WORD
ParBk1-74TCScnt - Value 3x 198 1 WORD
Circuit Breaker supervision
N.OpenCBcnt 3x 199 1 UWORD 1
CT supervision - 74CT
ParTr74CTcnt - Value 3x 200 1 WORD
ParBk1-74CTcnt - Value 3x 201 1 WORD
Accessory counters
ParStBFcnt - Value 3x 202 1 WORD
ParTrBFcnt - Value 3x 203 1 WORD
ParBk1BFcnt - Value 3x 204 1 WORD

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 31 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Delayed inputs
IN1 1x 76 1 BIT 0=OFF, 1=ON
IN2 1x 77 1 BIT 0=OFF, 1=ON
IN3 1x 78 1 BIT 0=OFF, 1=ON
IN4 1x 79 1 BIT 0=OFF, 1=ON
IN5 1x 80 1 BIT 0=OFF, 1=ON
IN6 1x 81 1 BIT 0=OFF, 1=ON
IN7 1x 82 1 BIT 0=OFF, 1=ON
IN8 1x 83 1 BIT 0=OFF, 1=ON
IN9 1x 84 1 BIT 0=OFF, 1=ON
IN10 1x 85 1 BIT 0=OFF, 1=ON
IN11 1x 86 1 BIT 0=OFF, 1=ON
IN12 1x 87 1 BIT 0=OFF, 1=ON
IN13 1x 88 1 BIT 0=OFF, 1=ON
IN14 1x 89 1 BIT 0=OFF, 1=ON
IN15 1x 90 1 BIT 0=OFF, 1=ON
IN16 1x 91 1 BIT 0=OFF, 1=ON
IN17 1x 92 1 BIT 0=OFF, 1=ON
IN18 1x 93 1 BIT 0=OFF, 1=ON
IN19 1x 94 1 BIT 0=OFF, 1=ON
IN20 1x 95 1 BIT 0=OFF, 1=ON
IN21 1x 96 1 BIT 0=OFF, 1=ON
IN22 1x 97 1 BIT 0=OFF, 1=ON
IN23 1x 98 1 BIT 0=OFF, 1=ON
IN24 1x 99 1 BIT 0=OFF, 1=ON
IN25 1x 100 1 BIT 0=OFF, 1=ON
IN26 1x 101 1 BIT 0=OFF, 1=ON
IN27 1x 102 1 BIT 0=OFF, 1=ON
IN28 1x 103 1 BIT 0=OFF, 1=ON
IN29 1x 104 1 BIT 0=OFF, 1=ON
IN30 1x 105 1 BIT 0=OFF, 1=ON
IN31 1x 106 1 BIT 0=OFF, 1=ON
IN32 1x 107 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 32 of 50
PRON NA11-MBx
VAR REF IDX DIM TYPE Range Um Kv ENUM
Delayed inputs
IN33 1x 108 1 BIT 0=OFF, 1=ON
IN34 1x 109 1 BIT 0=OFF, 1=ON
IN35 1x 110 1 BIT 0=OFF, 1=ON
IN36 1x 111 1 BIT 0=OFF, 1=ON
IN37 1x 112 1 BIT 0=OFF, 1=ON
IN38 1x 113 1 BIT 0=OFF, 1=ON
IN39 1x 114 1 BIT 0=OFF, 1=ON
IN40 1x 115 1 BIT 0=OFF, 1=ON
IN41 1x 116 1 BIT 0=OFF, 1=ON
IN42 1x 117 1 BIT 0=OFF, 1=ON
IN43 1x 118 1 BIT 0=OFF, 1=ON
IN44 1x 119 1 BIT 0=OFF, 1=ON
IN45 1x 120 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 33 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Internal states
Reset LEDs 1x 121 1 BIT 0=OFF, 1=ON
Profile selection 1x 122 1 BIT 0=OFF, 1=ON
Fault trigger 1x 123 1 BIT 0=OFF, 1=ON
IE/IPh Block2 1x 124 1 BIT 0=OFF, 1=ON
IPh Block2 1x 125 1 BIT 0=OFF, 1=ON
IE Block2 1x 126 1 BIT 0=OFF, 1=ON
Block1 1x 127 1 BIT 0=OFF, 1=ON
Tcs1 1x 128 1 BIT 0=OFF, 1=ON
Tcs2 1x 129 1 BIT 0=OFF, 1=ON
Trip External protections 1x 130 1 BIT 0=OFF, 1=ON
Reset partial counters 1x 131 1 BIT 0=OFF, 1=ON
Reset CB monitoring data 1x 132 1 BIT 0=OFF, 1=ON
52a 1x 133 1 BIT 0=OFF, 1=ON
52b 1x 134 1 BIT 0=OFF, 1=ON
Open CB 1x 135 1 BIT 0=OFF, 1=ON
Close CB 1x 136 1 BIT 0=OFF, 1=ON
Remote trip 1x 137 1 BIT 0=OFF, 1=ON
Reset on demand measures 1x 138 1 BIT 0=OFF, 1=ON
Auto-reclose enable 1x 139 1 BIT 0=OFF, 1=ON
Block auto-reclose 1x 140 1 BIT 0=OFF, 1=ON
Auto-reclose from external 1x 141 1 BIT 0=OFF, 1=ON
Block2
BLK2IN-Iph 1x 142 1 BIT 0=OFF, 1=ON
BLK2IN-IE 1x 143 1 BIT 0=OFF, 1=ON
tB timeout 1x 144 1 BIT 0=OFF, 1=ON
ST-Iph-BLK2 1x 145 1 BIT 0=OFF, 1=ON
ST-IE-BLK2 1x 146 1 BIT 0=OFF, 1=ON
BLK2OUT-Iph 1x 147 1 BIT 0=OFF, 1=ON
BLK2OUT-IE 1x 148 1 BIT 0=OFF, 1=ON
BLK2OUT-Iph/IE 1x 149 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 34 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Relays
K1 - State 1x 150 1 BIT 0=OFF, 1=ON
K1 - Diagnostic 1x 151 1 BIT 0=OFF, 1=ON
K2 - State 1x 152 1 BIT 0=OFF, 1=ON
K2 - Diagnostic 1x 153 1 BIT 0=OFF, 1=ON
K3 - State 1x 154 1 BIT 0=OFF, 1=ON
K3 - Diagnostic 1x 155 1 BIT 0=OFF, 1=ON
K4 - State 1x 156 1 BIT 0=OFF, 1=ON
K4 - Diagnostic 1x 157 1 BIT 0=OFF, 1=ON
K5 - State 1x 158 1 BIT 0=OFF, 1=ON
K5 - Diagnostic 1x 159 1 BIT 0=OFF, 1=ON
K6 - State 1x 160 1 BIT 0=OFF, 1=ON
K6 - Diagnostic 1x 161 1 BIT 0=OFF, 1=ON
K7 - State 1x 162 1 BIT 0=OFF, 1=ON
K7 - Diagnostic 1x 163 1 BIT 0=OFF, 1=ON
K8 - State 1x 164 1 BIT 0=OFF, 1=ON
K8 - Diagnostic 1x 165 1 BIT 0=OFF, 1=ON
K9 - State 1x 166 1 BIT 0=OFF, 1=ON
K9 - Diagnostic 1x 167 1 BIT 0=OFF, 1=ON
K10 - State 1x 168 1 BIT 0=OFF, 1=ON
K10 - Diagnostic 1x 169 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 35 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


MEASURES
Physical
f - Value 3x 205 2 LONG Hz 1000
IL1 - Value 3x 207 2 LONG In 16000
IL2 - Value 3x 209 2 LONG In 16000
IL3 - Value 3x 211 2 LONG In 16000
IE - Value 3x 213 2 LONG IEn 80000
Calculated
ILmax - Value 3x 215 2 LONG In 16000
ILmin - Value 3x 217 2 LONG In 16000
IL - Value 3x 219 2 LONG In 16000
2nd harmonic
IL1-2nd - Value 3x 221 2 LONG In 16000
IL2-2nd - Value 3x 223 2 LONG In 16000
IL3-2nd - Value 3x 225 2 LONG In 16000
I-2nd/IL - Value 3x 227 2 LONG % 20
3rd harmonic
IL1-3rd - Value 3x 229 2 LONG In 16000
IL2-3rd - Value 3x 231 2 LONG In 16000
IL3-3rd - Value 3x 233 2 LONG In 16000
IE-3rd - Value 3x 235 2 LONG IEn 80000
4th harmonic
IL1-4th - Value 3x 237 2 LONG In 16000
IL2-4th - Value 3x 239 2 LONG In 16000
IL3-4th - Value 3x 241 2 LONG In 16000
5th harmonic
IL1-5th - Value 3x 243 2 LONG In 16000
IL2-5th - Value 3x 245 2 LONG In 16000
IL3-5th - Value 3x 247 2 LONG In 16000

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 36 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Phase demands
IL1FIX - Value 3x 249 2 LONG In 16000
IL2FIX - Value 3x 251 2 LONG In 16000
IL3FIX - Value 3x 253 2 LONG In 16000
IL1ROL - Value 3x 255 2 LONG In 16000
IL2ROL - Value 3x 257 2 LONG In 16000
IL3ROL - Value 3x 259 2 LONG In 16000
IL1MAX - Value 3x 261 2 LONG In 16000
IL2MAX - Value 3x 263 2 LONG In 16000
IL3MAX - Value 3x 265 2 LONG In 16000
IL1MIN - Value 3x 267 2 LONG In 16000
IL2MIN - Value 3x 269 2 LONG In 16000
IL3MIN - Value 3x 271 2 LONG In 16000

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 37 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


PT100 Probes
PT1 3x 273 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T1 3x 274 2 LONG ^C 10
PT2 3x 276 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T2 3x 277 2 LONG ^C 10
PT3 3x 279 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T3 3x 280 2 LONG ^C 10
PT4 3x 282 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T4 3x 283 2 LONG ^C 10
PT5 3x 285 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T5 3x 286 2 LONG ^C 10
PT6 3x 288 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T6 3x 289 2 LONG ^C 10
PT7 3x 291 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T7 3x 292 2 LONG ^C 10
PT8 3x 294 1 WORD 0="ON",1="WAIT",2="LOW",3="H
IGH",4="FAIL"
T8 3x 295 2 LONG ^C 10

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 38 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 0
Fault n. 0 - Fault counter 3x 297 2 LONG 1
Fault n. 0 - Date 3x 299 6 STR
Fault n. 0 - Time 3x 305 6 STR
Fault n. 0 - Fault cause 3x 311 1 WORD 0="No faults",1="I> Start",2="I>
Trip",3="I>> Start",4="I>>
Trip",5="I>>> Start",6="I>>>
Trip",7="IE> Start",8="IE>
Trip",9="IE>> Start",10="IE>>
Trip",11="IE>>> Start",12="IE>>>
Trip",13="PT1 Alarm",14="PT1
Trip",15="PT2 Alarm",16="PT2
Trip",17="PT3 Alarm",18="PT3
Trip",19="PT4 Alarm",20="PT4
Trip",21="PT5 Alarm",22="PT5
Trip",23="PT6 Alarm",24="PT6
Trip",25="PT7 Alarm",26="PT7
Trip",27="PT8 Alarm",28="PT8
Trip",29="74TCS Trip",30="74CT
Trip",31="BF Start",32="BF
Trip",33="Logic input"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 39 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 0
Fault n. 0 - IL1r 3x 312 2 ULONG In 16000
Fault n. 0 - IL2r 3x 314 2 ULONG In 16000
Fault n. 0 - IL3r 3x 316 2 ULONG In 16000
Fault n. 0 - IEr 3x 318 2 ULONG IEn 80000
Fault n. 0 - T1r 3x 320 2 LONG ^C 10
Fault n. 0 - T2r 3x 322 2 LONG ^C 10
Fault n. 0 - T3r 3x 324 2 LONG ^C 10
Fault n. 0 - T4r 3x 326 2 LONG ^C 10
Fault n. 0 - T5r 3x 328 2 LONG ^C 10
Fault n. 0 - T6r 3x 330 2 LONG ^C 10
Fault n. 0 - T7r 3x 332 2 LONG ^C 10
Fault n. 0 - T8r 3x 334 2 LONG ^C 10
Fault n. 0 - Inputs IN1-IN5 3x 336 1 UWORD 1
Fault n. 0 - Inputs IN6-IN13 3x 337 1 UWORD 1
Fault n. 0 - Inputs IN14-IN29 3x 338 1 UWORD 1
Fault n. 0 - Inputs IN30-IN45 3x 339 1 UWORD 1
Fault n. 0 - Outputs K1-K6 3x 340 1 UWORD 1
Fault n. 0 - Outputs K7-K10 3x 341 1 UWORD 1
Fault n. 0 - Fault cause info 3x 342 8 STR

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 40 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 1
Fault n. 1 - Fault counter 3x 350 2 LONG 1
Fault n. 1 - Date 3x 352 6 STR
Fault n. 1 - Time 3x 358 6 STR
Fault n. 1 - Fault cause 3x 364 1 WORD 0="No faults",1="I> Start",2="I>
Trip",3="I>> Start",4="I>>
Trip",5="I>>> Start",6="I>>>
Trip",7="IE> Start",8="IE>
Trip",9="IE>> Start",10="IE>>
Trip",11="IE>>> Start",12="IE>>>
Trip",13="PT1 Alarm",14="PT1
Trip",15="PT2 Alarm",16="PT2
Trip",17="PT3 Alarm",18="PT3
Trip",19="PT4 Alarm",20="PT4
Trip",21="PT5 Alarm",22="PT5
Trip",23="PT6 Alarm",24="PT6
Trip",25="PT7 Alarm",26="PT7
Trip",27="PT8 Alarm",28="PT8
Trip",29="74TCS Trip",30="74CT
Trip",31="BF Start",32="BF
Trip",33="Logic input"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 41 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 1
Fault n. 1 - IL1r 3x 365 2 ULONG In 16000
Fault n. 1 - IL2r 3x 367 2 ULONG In 16000
Fault n. 1 - IL3r 3x 369 2 ULONG In 16000
Fault n. 1 - IEr 3x 371 2 ULONG IEn 80000
Fault n. 1 - T1r 3x 373 2 LONG ^C 10
Fault n. 1 - T2r 3x 375 2 LONG ^C 10
Fault n. 1 - T3r 3x 377 2 LONG ^C 10
Fault n. 1 - T4r 3x 379 2 LONG ^C 10
Fault n. 1 - T5r 3x 381 2 LONG ^C 10
Fault n. 1 - T6r 3x 383 2 LONG ^C 10
Fault n. 1 - T7r 3x 385 2 LONG ^C 10
Fault n. 1 - T8r 3x 387 2 LONG ^C 10
Fault n. 1 - Inputs IN1-IN5 3x 389 1 UWORD 1
Fault n. 1 - Inputs IN6-IN13 3x 390 1 UWORD 1
Fault n. 1 - Inputs IN14-IN29 3x 391 1 UWORD 1
Fault n. 1 - Inputs IN30-IN45 3x 392 1 UWORD 1
Fault n. 1 - Outputs K1-K6 3x 393 1 UWORD 1
Fault n. 1 - Outputs K7-K10 3x 394 1 UWORD 1
Fault n. 1 - Fault cause info 3x 395 8 STR

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 42 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 2
Fault n. 2 - Fault counter 3x 403 2 LONG 1
Fault n. 2 - Date 3x 405 6 STR
Fault n. 2 - Time 3x 411 6 STR
Fault n. 2 - Fault cause 3x 417 1 WORD 0="No faults",1="I> Start",2="I>
Trip",3="I>> Start",4="I>>
Trip",5="I>>> Start",6="I>>>
Trip",7="IE> Start",8="IE>
Trip",9="IE>> Start",10="IE>>
Trip",11="IE>>> Start",12="IE>>>
Trip",13="PT1 Alarm",14="PT1
Trip",15="PT2 Alarm",16="PT2
Trip",17="PT3 Alarm",18="PT3
Trip",19="PT4 Alarm",20="PT4
Trip",21="PT5 Alarm",22="PT5
Trip",23="PT6 Alarm",24="PT6
Trip",25="PT7 Alarm",26="PT7
Trip",27="PT8 Alarm",28="PT8
Trip",29="74TCS Trip",30="74CT
Trip",31="BF Start",32="BF
Trip",33="Logic input"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 43 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 2
Fault n. 2 - IL1r 3x 418 2 ULONG In 16000
Fault n. 2 - IL2r 3x 420 2 ULONG In 16000
Fault n. 2 - IL3r 3x 422 2 ULONG In 16000
Fault n. 2 - IEr 3x 424 2 ULONG IEn 80000
Fault n. 2 - T1r 3x 426 2 LONG ^C 10
Fault n. 2 - T2r 3x 428 2 LONG ^C 10
Fault n. 2 - T3r 3x 430 2 LONG ^C 10
Fault n. 2 - T4r 3x 432 2 LONG ^C 10
Fault n. 2 - T5r 3x 434 2 LONG ^C 10
Fault n. 2 - T6r 3x 436 2 LONG ^C 10
Fault n. 2 - T7r 3x 438 2 LONG ^C 10
Fault n. 2 - T8r 3x 440 2 LONG ^C 10
Fault n. 2 - Inputs IN1-IN5 3x 442 1 UWORD 1
Fault n. 2 - Inputs IN6-IN13 3x 443 1 UWORD 1
Fault n. 2 - Inputs IN14-IN29 3x 444 1 UWORD 1
Fault n. 2 - Inputs IN30-IN45 3x 445 1 UWORD 1
Fault n. 2 - Outputs K1-K6 3x 446 1 UWORD 1
Fault n. 2 - Outputs K7-K10 3x 447 1 UWORD 1
Fault n. 2 - Fault cause info 3x 448 8 STR

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 44 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 3
Fault n. 3 - Fault counter 3x 456 2 LONG 1
Fault n. 3 - Date 3x 458 6 STR
Fault n. 3 - Time 3x 464 6 STR
Fault n. 3 - Fault cause 3x 470 1 WORD 0="No faults",1="I> Start",2="I>
Trip",3="I>> Start",4="I>>
Trip",5="I>>> Start",6="I>>>
Trip",7="IE> Start",8="IE>
Trip",9="IE>> Start",10="IE>>
Trip",11="IE>>> Start",12="IE>>>
Trip",13="PT1 Alarm",14="PT1
Trip",15="PT2 Alarm",16="PT2
Trip",17="PT3 Alarm",18="PT3
Trip",19="PT4 Alarm",20="PT4
Trip",21="PT5 Alarm",22="PT5
Trip",23="PT6 Alarm",24="PT6
Trip",25="PT7 Alarm",26="PT7
Trip",27="PT8 Alarm",28="PT8
Trip",29="74TCS Trip",30="74CT
Trip",31="BF Start",32="BF
Trip",33="Logic input"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 45 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Fault 3
Fault n. 3 - IL1r 3x 471 2 ULONG In 16000
Fault n. 3 - IL2r 3x 473 2 ULONG In 16000
Fault n. 3 - IL3r 3x 475 2 ULONG In 16000
Fault n. 3 - IEr 3x 477 2 ULONG IEn 80000
Fault n. 3 - T1r 3x 479 2 LONG ^C 10
Fault n. 3 - T2r 3x 481 2 LONG ^C 10
Fault n. 3 - T3r 3x 483 2 LONG ^C 10
Fault n. 3 - T4r 3x 485 2 LONG ^C 10
Fault n. 3 - T5r 3x 487 2 LONG ^C 10
Fault n. 3 - T6r 3x 489 2 LONG ^C 10
Fault n. 3 - T7r 3x 491 2 LONG ^C 10
Fault n. 3 - T8r 3x 493 2 LONG ^C 10
Fault n. 3 - Inputs IN1-IN5 3x 495 1 UWORD 1
Fault n. 3 - Inputs IN6-IN13 3x 496 1 UWORD 1
Fault n. 3 - Inputs IN14-IN29 3x 497 1 UWORD 1
Fault n. 3 - Inputs IN30-IN45 3x 498 1 UWORD 1
Fault n. 3 - Outputs K1-K6 3x 499 1 UWORD 1
Fault n. 3 - Outputs K7-K10 3x 500 1 UWORD 1
Fault n. 3 - Fault cause info 3x 501 8 STR

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 46 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Events
Event n. 0 - Event counter 3x 509 2 LONG 1
Event n. 0 - Date 3x 511 6 STR
Event n. 0 - Hour 3x 517 6 STR
Event n. 0 - Cause 3x 523 1 WORD SEE MANUAL END PAGE

Event n. 1 - Event counter 3x 524 2 LONG 1


Event n. 1 - Date 3x 526 6 STR
Event n. 1 - Hour 3x 532 6 STR
Event n. 1 - Cause 3x 538 1 WORD SEE MANUAL END PAGE

Event n. 2 - Event counter 3x 539 2 LONG 1


Event n. 2 - Date 3x 541 6 STR
Event n. 2 - Hour 3x 547 6 STR
Event n. 2 - Cause 3x 553 1 WORD SEE MANUAL END PAGE

Event n. 3 - Event counter 3x 554 2 LONG 1


Event n. 3 - Date 3x 556 6 STR
Event n. 3 - Hour 3x 562 6 STR
Event n. 3 - Cause 3x 568 1 WORD SEE MANUAL END PAGE

Event n. 4 - Event counter 3x 569 2 LONG 1


Event n. 4 - Date 3x 571 6 STR
Event n. 4 - Hour 3x 577 6 STR
Event n. 4 - Cause 3x 583 1 WORD SEE MANUAL END PAGE

Event n. 5 - Event counter 3x 584 2 LONG 1


Event n. 5 - Date 3x 586 6 STR
Event n. 5 - Hour 3x 592 6 STR
Event n. 5 - Cause 3x 598 1 WORD SEE MANUAL END PAGE

Event n. 6 - Event counter 3x 599 2 LONG 1


Event n. 6 - Date 3x 601 6 STR
Event n. 6 - Hour 3x 607 6 STR
Event n. 6 - Cause 3x 613 1 WORD SEE MANUAL END PAGE

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 47 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Events
Event n. 7 - Event counter 3x 614 2 LONG 1
Event n. 7 - Date 3x 616 6 STR
Event n. 7 - Hour 3x 622 6 STR
Event n. 7 - Cause 3x 628 1 WORD SEE MANUAL END PAGE

Event n. 8 - Event counter 3x 629 2 LONG 1


Event n. 8 - Date 3x 631 6 STR
Event n. 8 - Hour 3x 637 6 STR
Event n. 8 - Cause 3x 643 1 WORD SEE MANUAL END PAGE

Event n. 9 - Event counter 3x 644 2 LONG 1


Event n. 9 - Date 3x 646 6 STR
Event n. 9 - Hour 3x 652 6 STR
Event n. 9 - Cause 3x 658 1 WORD SEE MANUAL END PAGE

Event n. 10 - Event counter 3x 659 2 LONG 1


Event n. 10 - Date 3x 661 6 STR
Event n. 10 - Hour 3x 667 6 STR
Event n. 10 - Cause 3x 673 1 WORD SEE MANUAL END PAGE

Event n. 11 - Event counter 3x 674 2 LONG 1


Event n. 11 - Date 3x 676 6 STR
Event n. 11 - Hour 3x 682 6 STR
Event n. 11 - Cause 3x 688 1 WORD SEE MANUAL END PAGE

Event n. 12 - Event counter 3x 689 2 LONG 1


Event n. 12 - Date 3x 691 6 STR
Event n. 12 - Hour 3x 697 6 STR
Event n. 12 - Cause 3x 703 1 WORD SEE MANUAL END PAGE

Event n. 13 - Event counter 3x 704 2 LONG 1


Event n. 13 - Date 3x 706 6 STR
Event n. 13 - Hour 3x 712 6 STR
Event n. 13 - Cause 3x 718 1 WORD SEE MANUAL END PAGE

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 48 of 50
PRON NA11-MBx

VAR REF IDX DIM TYPE Range Um Kv ENUM


Events
Event n. 14 - Event counter 3x 719 2 LONG 1
Event n. 14 - Date 3x 721 6 STR
Event n. 14 - Hour 3x 727 6 STR
Event n. 14 - Cause 3x 733 1 WORD SEE MANUAL END PAGE

Event n. 15 - Event counter 3x 734 2 LONG 1


Event n. 15 - Date 3x 736 6 STR
Event n. 15 - Hour 3x 742 6 STR
Event n. 15 - Cause 3x 748 1 WORD SEE MANUAL END PAGE

Event n. 16 - Event counter 3x 749 2 LONG 1


Event n. 16 - Date 3x 751 6 STR
Event n. 16 - Hour 3x 757 6 STR
Event n. 16 - Cause 3x 763 1 WORD SEE MANUAL END PAGE

Event n. 17 - Event counter 3x 764 2 LONG 1


Event n. 17 - Date 3x 766 6 STR
Event n. 17 - Hour 3x 772 6 STR
Event n. 17 - Cause 3x 778 1 WORD SEE MANUAL END PAGE

Event n. 18 - Event counter 3x 779 2 LONG 1


Event n. 18 - Date 3x 781 6 STR
Event n. 18 - Hour 3x 787 6 STR
Event n. 18 - Cause 3x 793 1 WORD SEE MANUAL END PAGE

Event n. 19 - Event counter 3x 794 2 LONG 1


Event n. 19 - Date 3x 796 6 STR
Event n. 19 - Hour 3x 802 6 STR
Event n. 19 - Cause 3x 808 1 WORD SEE MANUAL END PAGE

VAR REF IDX DIM TYPE Range Um Kv ENUM


Test
TEST state 1x 170 1 BIT 0=OFF, 1=ON

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 49 of 50
PRON NA11-MBx

Event n. x - Cause 0="No events",1="IN1 on",2="IN1 off",3="IN2 on",4="IN2 off",5="IN3 on",


6="IN3 off",7="IN4 on",8="IN4 off",9="IN5 on",10="IN5 off",11="IN6 on",
12="IN6 off",13="IN7 on",14="IN7 off",15="IN8 on",16="IN8 off",17="IN9 on",
18="IN9 off",19="IN10 on",20="IN10 off",21="IN11 on",22="IN11 off",
23="IN12 on",24="IN12 off",25="IN13 on",26="IN13 off",27="IN14 on",
28="IN14 off",29="IN15 on",30="IN15 off",31="IN16 on",32="IN16 off",
33="IN17 on",34="IN17 off",35="IN18 on",36="IN18 off",37="IN19 on",
38="IN19 off",39="IN20 on",40="IN20 off",41="IN21 on",42="IN21 off",
43="IN22 on",44="IN22 off",45="IN23 on",46="IN23 off",47="IN24 on",
48="IN24 off",49="IN25 on",50="IN25 off",51="IN26 on",52="IN26 off",
53="IN27 on",54="IN27 off",55="IN28 on",56="IN28 off",57="IN29 on",
58="IN29 off",59="IN30 on",60="IN30 off",61="IN31 on",62="IN31 off",
63="IN32 on",64="IN32 off",65="IN33 on",66="IN33 off",67="IN34 on",
68="IN34 off",69="IN35 on",70="IN35 off",71="IN36 on",72="IN36 off",
73="IN37 on",74="IN37 off",75="IN38 on",76="IN38 off",77="IN39 on",
78="IN39 off",79="IN40 on",80="IN40 off",81="IN41 on",82="IN41 off",
83="IN42 on",84="IN42 off",85="IN43 on",86="IN43 off",87="IN44 on",
88="IN44 off",89="IN45 on",90="IN45 off",91="I> Start",92="I> Trip",
93="I>> Start",94="I>> Trip",95="I>>> Start",96="I>>> Trip",97="IE>
Start",98="IE> Trip",99="IE>> Start",100="IE>> Trip",101="IE>>> Start",
102="IE>>> Trip",103="PT1 Alarm",104="PT1 Trip",105="PT2 Alarm",
106="PT2 Trip",107="PT3 Alarm",108="PT3 Trip",109="PT4 Alarm",
110="PT4 Trip",111="PT5 Alarm",112="PT5 Trip",113="PT6 Alarm",
114="PT6 Trip",115="PT7 Alarm",116="PT7 Trip",117="PT8 Alarm",
118="PT8 Trip",119="74TCS Trip",120="BF Start",121="BF Trip",
122="CB State diag",123="Remote trip",124="79-X Reclosure",
125="79-FR Phase",126="79-FR Earth",127="Settings",128="Logic input",
129="Power down",130="Power up",200="TX Trip on",201="TX Trip off",
202="RX Trip on",203="RX Trip off",204="RX blkin on",205="RX blkin off",
206="TX blk2out on",207="TX blk2out off",208="61850 RX blin on",
209="61850 RX blin off",210="61850 RX open CB on",
211="61850 RX open CB off",212="61850 RX close CB on",
213="61850 RX close CB off",214="61850 Start simulator on",
215="61850 Start simulator off",216="61850 Trip simulator on",
217="61850 Trip simulator off",218="61850 Block simulator on",
219="61850 Block simulator off",
220="61850 Quality simulator on (quality=invalid)",
221="61850 Quality simulator off (quality=ok)"

Version 2.50
PRON NA11-MBx Remote Setting Manual Page: 50 of 50

You might also like