Professional Documents
Culture Documents
Version 1.40
Contents
Contents ........................................................................................................................................................................ 2
1 Modbus RTU communication................................................................................................................................ 3
1.1 Serial port settings........................................................................................................................................ 3
1.2 Transmission mode ...................................................................................................................................... 3
1.3 Data Types ................................................................................................................................................... 3
1.4 Supported functions ..................................................................................................................................... 4
1.5 Exceptions .................................................................................................................................................... 4
1.6 Modbus/TCP ................................................................................................................................................ 5
1.7 Network setting............................................................................................................................................. 5
1.8 NTP synchronization .................................................................................................................................... 5
2 Logical organization of the protection’s data ........................................................................................................ 6
2.1 Basic Data Type ........................................................................................................................................... 6
2.1.1 BIT............................................................................................................................................................ 6
2.1.2 BYTE........................................................................................................................................................ 7
2.1.3 UBYTE ..................................................................................................................................................... 7
2.1.4 WORD...................................................................................................................................................... 8
2.1.5 UWORD ................................................................................................................................................... 8
2.1.6 LONG ....................................................................................................................................................... 9
2.1.7 ULONG .................................................................................................................................................... 9
2.1.8 ARR........................................................................................................................................................ 10
2.1.9 STR ........................................................................................................................................................ 11
2.1.10 CMD ....................................................................................................................................................... 11
3 How to read the Address Data Table.................................................................................................................. 12
3.1 Address Data Table.................................................................................................................................... 12
3.1.1 VAR........................................................................................................................................................ 12
3.1.2 REF ........................................................................................................................................................ 12
3.1.3 IDX ......................................................................................................................................................... 12
3.1.4 DIM......................................................................................................................................................... 13
3.1.5 TYPE...................................................................................................................................................... 13
3.1.6 UM.......................................................................................................................................................... 13
3.1.7 Kv 13
3.1.8 ENUM..................................................................................................................................................... 14
3.2 Common properties.................................................................................................................................... 14
3.2.1 Input state .............................................................................................................................................. 14
3.2.2 Output state............................................................................................................................................ 14
4 Examples ............................................................................................................................................................ 15
4.1 Example 1. How to read a variable ............................................................................................................ 15
4.2 Example 2. How to read a BIT data type ................................................................................................... 16
4.3 Example 3. How to execute a command.................................................................................................... 16
5 Glossary .............................................................................................................................................................. 17
6 Appendix A. Address Data Table........................................................................................................................ 18
Version 1.40
This Protocol Manual is for use with Thytronic Protective Relays, such as the DMC, NTG and PRO-N series that
support Modbus RTU and Modbus TCP communication protocol.
To communicate with a TPR, the serial port of the Master has to be configured with the following settings:
A TPR has 4 data table, each of which corresponds to one of the 4 basic Modbus data type. Each table contains up
to 1024 data that can be accessed with the proper function as described in the following table.
table/data type reference information Access Function Code for Function Code for
Reading Writing
Coils 0X 1 bit Read/Write 0x01 0x05
Discrete Inputs 1X 1 bit Read only 0x02 -
Input Registers 3X 16 bit Word Read only 0x04 -
Holding Registers 4X 16 bit Word Read/Write 0x03 0x06, 0x10
Table 2. Modbus Data Type
Version 1.40
Code Name
0x01 Read Coil Status
0x02 Read Input Status
0x03 Read Holding Registers
0x04 Read Input Registers
0x05 Force Single Coil
0x06 Preset Single Register
0x0F Force Multiple Coil
0x10 Preset Multiple Registers
Table 3 Supported Modbus functions
The smallest data that can be exchanged within a Modbus message is the Modbus Register.
A Modbus Register is a 16 bit data in the Big Endian representation, called WORD (W)
W = BH BL
1.5 Exceptions
When a TPR receives a request that can not handle (e.g. the data address doesn’t exists, the function is not
supported, etc.), a special response called Exception is returned to the Master. This message contains the
information needed to recognize the error occurred.
In an Exception message the most significant bit (msb) of the Function field is set to 1.
04 07 A5 50 00 02 - -
TX
S F ADR DIM CRC
04 87 01 - -
RX
S F DATA CRC
S = Slave Address
F = Function Code
ADR = Modbus Data Address
DIM = Dimension (number of registers)
DATA = data value
CRC = Cyclical Redundancy Code
In this example the function code 07 is not supported by the TPR. The response is an exception message (the msb
of function code F=0x87 is set to 1). The Data field value is 1 and according with the Modbus standard corresponds
to the “Illegal function” exception.
Version 1.40
1.6 Modbus/TCP
Modbus/TCP, an extension of Modbus/RTU, defines how Modbus/RTU and Modbus/ASCII messages are encoded
within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible to
apply as the original Modbus/RTU. The specification can be found online at www.modicon.com
To synchronize the Real Time Clock of more than one protection at the same time the NTP service is available.
Network Time Protocol (NTP) is a protocol for synchronizing the clocks of computer systems over packet-switched,
variable-latency data networks. NTP uses UDP port 123 as its transport layer. It is designed particularly to resist
the effects of variable latency.
To synchronize all the TPR in a network is sufficient to send a broadcast NTP packet on the network.
The NTP service can be enabled/disabled changing the “NTP synchronization” parameter (Appendix A –
Address Data Table).
More information about the NTP protocol and service can be found online at www.ntp.org
Version 1.40
Example: let’s read the value of the variable ”I> Start”. This variable is the first one in the Discrete Input data table.
To read this kind of data the Modbus function 0x02 has to be used. As described in the standard the Modbus
address to access the data is given by IDX-1 = 5 in this case.
To read the data from the Slave address 1 the next request has to be sent:
01 02 00 05 00 01 - -
TX
S F ADR DIM CRC
In this chapter all the basic TPR data type and their relationship with the Modbus data type will be described.
2.1.1 BIT
Description:
Variable with 1 bit of information.
Version 1.40
2.1.2 BYTE
Description:
Signed variable with 1 byte (8 bit) of information. Range: -128 +127
B 00 B
Modbus
Byte
Register
Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:
0D 00 0D
Modbus
Byte
Register
2.1.3 UBYTE
Description:
Unsigned variable with 1 byte (8 bit) of information. Range: 0 +255
B 00 B
UByte Modbus
Register
Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:
0D 00 0D
Modbus
Byte
Register
Version 1.40
2.1.4 WORD
Description:
Signed variable with 2 byte (16 bit) of information. Range: -32.768 +32.767
BH BL BH BL
Modbus
Word
Register
Example:
relationship between the data WORD whose value is 3073 (0x0C01) and its Modbus representation:
0C 01 0C 01
Modbus
Word
Register
2.1.5 UWORD
Description:
Unsigned variable with 2 byte (16 bit) of information. Range: 0 +65.535
BH BL BH BL
Modbus
UWord
Register
Example:
relationship between the data UWORD whose value is 3073 (0x0C01) and its Modbus representation:
0C 01 0C 01
Modbus
UWord
Register
Version 1.40
2.1.6 LONG
Description:
Signed variable with 4 byte (32 bit) of information. Range: -2.147.483.648 +2.147.483.647
Example:
relationship between the data LONG 66536 (0x103E8) and its value in the Modbus protocol domain:
00 01 03 E8 03 E8 00 01
Long Modbus Registers
2.1.7 ULONG
Description:
Unsigned variable with 4 byte (32 bit) of information. Range: -0 +4.294.967.295
Example:
relationship between the ULONG data whose value is 66536 (0x103E8) and its Modbus representation:
00 01 03 E8 03 E8 00 01
ULong Modbus Registers
Version 1.40
2.1.8 ARR
Description:
Array of BYTE.
If even n:
B1 B2 Bn B1 B2 Bn-1 Bn
1 2 n 1 N
Array[n] Modbus Registers
N = ceil(n/2)
If odd n:
B1 B2 Bn B1 B2 Bn 0
1 2 n 1 N
Array[n] Modbus Registers
Example:
Let’s consider an array with 3 bytes whose values are: (0x01, 0x3A, 0x1F). This array can be placed in
N=ceil(3/2)=ceil(1.5)=2 Modbus registers.
01 3A 1F 01 3A 1F 00
1 2 3 1 2
Array[3] Modbus Registers
†
The ceil function returns the smallest integer value that is greater than or equal to a number. For example,
ceil(2.3)=3 , ceil(1.5)=2.
Version 1.40
2.1.9 STR
Description:
String data type. It’s represented by an array of BYTE. Every byte represents the hexadecimal ASCII code
associated with the character of the string
If even n:
C1 C2 Cn C1 C2 Cn-1 Cn
1 2 n 1 N
String[n] Modbus Registers
N = ceil(n/2)
If odd n:
C1 C2 Cn C1 C2 Cn ‘\0’
1 2 n 1 N
String[n] Modbus Registers
Example:
Let’s assume “Relay reference name” is a STRING variable whose length is 8 characters, its Modbus address is
0x0029 and its dimension is 4 Modbus registers. Let’s set its value to “NAxx”.
First of all the ASCII code in hexadecimal notation for each character of the string “NA10” is equal to 0x4E417878
An example of write request could be the following:
01 10 00 29 00 05 10 4E 41 78 78 00 00 00 00 - -
TX
S F ADR DIM B DATA1 DATA2 DATA3 DATA4 CRC
‘N’ ‘A’ ‘x’ ‘x’ ‘\0’ ‘\0’ ‘\0’ ‘\0’
Remark. A zero padding operation is necessary because the length of the string “DMC901” is lower than the length
of the RACK_TYPE variable.
2.1.10 CMD
Description:
This type of data represents a command.
Every Command corresponds to a Coil data type. To execute the command, the value of the associated Coil has to
be set to 1 with the Modbus function 0x05.
†
The ceil function returns the smallest integer value that is greater than or equal to a number. For example,
ceil(2.3)=3 , ceil(1.5)=2.
Version 1.40
3.1.1 VAR
3.1.2 REF
The REF field tells which data table the variable is stored in.
The REF field can assume one of the following values:
3.1.3 IDX
The IDX field represents the position of the table (specified by REF) in which the variable VAR is stored.
The IDX value is related to the Modbus address of the variable. The relationship between IDX and Modbus address
is the following:
MB address = IDX - 1
Let’s see that the variable “Relay phase nominal current - In” is the 50th variable stored in the Input Registers
table (reference 3x) and its dimension is 1 Modbus register (DIM=1).
Version 1.40
3.1.4 DIM
The DIM field is the number of Modbus registers necessary to contain the VAR data.
Example: let’s read the value of the variable “Relay phase nominal current - In ”.
From the previous table we see that the reference is 4x for which the function 0x03 has to be used for reading.
The Modbus address is IDX-1=50-1=49.
The request for reading is the following:
01 03 00 31 00 01 - -
TX
S F ADR DIM CRC
3.1.5 TYPE
The TYPE field specifies the basic data type associated with VAR, as described in chapter 2.1.
3.1.6 UM
3.1.7 Kv
The Kv field contains the scale factor that has to be applied to the variable to obtain the real value. If Kv is not
equal to 1, the value of the variable must be divided by Kv.
Let’s read the “Phase current IL1 - Value “ from the Slave address 1.
01 04 00 9E 00 02 - -
TX
S F ADR DIM CRC
01 04 04 A9 80 00 03 - -
RX
S F B DATA1 DATA2 CRC
LONG
VALL VALH
The TYPE field is necessary to decode the right value returned from the Modbus response, as described in chapter
2.1. The decoded value contained in the response is 0x0003A980 = 240000. Kv=16000 means that the value of the
variable has to be divided by 16000. UM specify the Unit. The “Phase current IL1 – Value” is equal to 15 In.
Version 1.40
3.1.8 ENUM
The ENUM field, whenever is defined, contains the meaning of all possible values assumed by the variable.
Version 1.40
4 Examples
For all the examples, the following symbols are assumed:
Let’s read from the Slave address 1 the value of the “Relay phase nominal current - In ”.
From the Address Data Table (Appendix A) we find out the following information;
The REF field value specify an Input Register (3x), so the function 0x04 is used for reading. From the IDX the
Modbus address is derived: Modbus address = IDX -1 = 50 - 1 = 49. DIM specify the number of register to be read.
01 04 00 3E 00 02 - -
TX
S F ADR DIM CRC
01 04 04 00 05 - -
RX
S F B DATA CRC
The TYPE field value is equal to UWORD. Applying the rules described in the chapter 2.1, the following value is
obtained
VAL = 0x0005= 5.
Il UM field specify the Unit of measure that is “Ampere”, while Kv = 1 means that the value doesn’t need to be
scaled. The “Relay phase nominal current – In” is equal to 5A.
Version 1.40
From the Address Data Table (Appendix A) we find out the following information;
The REF field value specify a Discrete Input (1x), so the function 0x02 is used for reading. From the IDX the
Modbus address is derived: Modbus address = IDX -1 = 7 - 1 = 6. DIM specify the number of register to be read.
01 02 00 06 00 01 - -
TX
S F ADR DIM CRC
01 02 01 00 01 - -
RX
S F B VAL CRC
The TYPE field value is equal to BIT. Applying the rules described in the chapter 2.1, the following value is
obtained
VAL = 1.
The ENUM field specifies the meaning of the value. In this case, the value 1 corresponds to the “ON” state and it
means that a Trip has occurred on the first threshold of the 51 function.
The TYPE field value specifies a Command (CMD). As described in chapter 2.1, to execute the command, it is
necessary to set its value to 1.
The REF field value specify a Coil (0x), so the function 0x05 is used for writing. From the IDX the Modbus address
is derived: Modbus address = IDX -1 = 2 - 1 = 1
The Response message is known as an “Acknowledge” because it’s an echo of the request, and it means that the
Coil has been set:
01 05 00 01 FF 00 - -
TX
S F ADR DATA CRC
01 05 00 01 FF 00 - -
RX
S F ADR DATA CRC
Version 1.40
5 Glossary
BH Most significative Byte of a Word data (Higher byte)
BL Least significative Byte of a Word data (Lower byte)
LSB Least Significative Byte
lsb least significative bit
MSB Most Significative Byte
msb Most significative bit
NTP Network Time Protocol
RTU Remote Terminal Unit
TPR Thytronic Protective Relay
WH Most significative Word of a Long data (Higher word)
WL Least significative Word of a Long data (Lower word)
Version 1.40
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 18 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 19 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 20 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 21 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 22 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 23 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 24 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 25 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 26 of 73
NVA100X-T-MB0
Commands relays module 2 - Boot 3x 170 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
Commands relays module 2 - Run-time 3x 171 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
PT100 module - Boot 3x 172 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
PT100 module - Run-time 3x 173 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MCI module (4...20mA) - Boot 3x 174 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
MCI module (4...20mA) - Run-time 3x 175 1 WORD 0="NOT OK: Undefined
module",1="OK",2="NOT OK:
missing module",3="NOT OK:
incompatible
module",4="OK",5="NOT
OK",6="OFF",7="OFF: Remove
module"
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 27 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 28 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 29 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 30 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 31 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 32 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 33 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 34 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 35 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 36 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 37 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 38 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 39 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 40 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 41 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 42 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 43 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 44 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Trip circuit supervision side T - 74TCS side T
Start 74TCS(T) 1x 345 1 BIT 0=OFF, 1=ON
Trip 74TCS(T) 1x 346 1 BIT 0=OFF, 1=ON
BLK1 74TCS(T) 1x 347 1 BIT 0=OFF, 1=ON
Mancata apertura lato H - BF side H
Trip Int/Ext(H) 1x 348 1 BIT 0=OFF, 1=ON
Start IBF(H)> 1x 349 1 BIT 0=OFF, 1=ON
Start IEBF(H)> 1x 350 1 BIT 0=OFF, 1=ON
Start BF(H) 1x 351 1 BIT 0=OFF, 1=ON
Trip BF(H) 1x 352 1 BIT 0=OFF, 1=ON
BLK1 BF(H) 1x 353 1 BIT 0=OFF, 1=ON
Mancata apertura lato L - BF side L
Trip Int/Ext(L) 1x 354 1 BIT 0=OFF, 1=ON
Start IBF(L)> 1x 355 1 BIT 0=OFF, 1=ON
Start IEBF(L)> 1x 356 1 BIT 0=OFF, 1=ON
Start BF(L) 1x 357 1 BIT 0=OFF, 1=ON
Trip BF(L) 1x 358 1 BIT 0=OFF, 1=ON
BLK1 BF(L) 1x 359 1 BIT 0=OFF, 1=ON
Mancata apertura lato T - BF side T
Trip Int/Ext(T) 1x 360 1 BIT 0=OFF, 1=ON
Start IBF(T)> 1x 361 1 BIT 0=OFF, 1=ON
Start IEBF(T)> 1x 362 1 BIT 0=OFF, 1=ON
Start BF(T) 1x 363 1 BIT 0=OFF, 1=ON
Trip BF(T) 1x 364 1 BIT 0=OFF, 1=ON
BLK1 BF(T) 1x 365 1 BIT 0=OFF, 1=ON
CT supervision side H - 74CT side H
Start I(H)* 1x 366 1 BIT 0=OFF, 1=ON
Trip S(H)< 1x 367 1 BIT 0=OFF, 1=ON
BLK1 S(H)< 1x 368 1 BIT 0=OFF, 1=ON
CT supervision side L - 74CT side L
Start I(L)* 1x 369 1 BIT 0=OFF, 1=ON
Trip S(L)< 1x 370 1 BIT 0=OFF, 1=ON
BLK1 S(L)< 1x 371 1 BIT 0=OFF, 1=ON
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 45 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 46 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 47 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 48 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Minima corrente - 37 side L
ParStI(L)<cnt - Value 3x 245 1 WORD
ParTrI(L)<cnt - Value 3x 246 1 WORD
Minima corrente - 37 side T
ParStI(T)<cnt - Value 3x 247 1 WORD
ParTrI(T)<cnt - Value 3x 248 1 WORD
Negative sequence overcurrent side H - 46 side H
ParStI2(H)>cnt - Value 3x 249 1 WORD
ParTrI2(H)>cnt - Value 3x 250 1 WORD
ParStI2(H)>>cnt - Value 3x 251 1 WORD
ParTrI2(H)>>cnt - Value 3x 252 1 WORD
Negative sequence overcurrent side L - 46 side L
ParStI2(L)>cnt - Value 3x 253 1 WORD
ParTrI2(L)>cnt - Value 3x 254 1 WORD
ParStI2(L)>>cnt - Value 3x 255 1 WORD
ParTrI2(L)>>cnt - Value 3x 256 1 WORD
Negative sequence overcurrent side T - 46 side T
ParStI2(T)>cnt - Value 3x 257 1 WORD
ParTrI2(T)>cnt - Value 3x 258 1 WORD
ParStI2(T)>>cnt - Value 3x 259 1 WORD
ParTrI2(T)>>cnt - Value 3x 260 1 WORD
Negative / Positive sequence current ratio side H - I2/I1 side
H
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 49 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 50 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Residual overcurrent - 50N.1/51N.1-87NHIZ.1
ParStIE1>cnt - Value 3x 294 1 WORD
ParTrIE1>cnt - Value 3x 295 1 WORD
ParStIE1>>cnt - Value 3x 296 1 WORD
ParTrIE1>>cnt - Value 3x 297 1 WORD
ParStIE1>>>cnt - Value 3x 298 1 WORD
ParTrIE1>>>cnt - Value 3x 299 1 WORD
Residual overcurrent - 50N.2/51N.2-87NHIZ.2
ParStIE2>cnt - Value 3x 300 1 WORD
ParTrIE2>cnt - Value 3x 301 1 WORD
ParStIE2>>cnt - Value 3x 302 1 WORD
ParTrIE2>>cnt - Value 3x 303 1 WORD
ParStIE2>>>cnt - Value 3x 304 1 WORD
ParTrIE2>>>cnt - Value 3x 305 1 WORD
Calculated residual overcurrent side H - 50N/51N side H
ParStIEC(H)>cnt - Value 3x 306 1 WORD
ParTrIEC(H)>cnt - Value 3x 307 1 WORD
ParStIEC(H)>>cnt - Value 3x 308 1 WORD
ParTrIEC(H)>>cnt - Value 3x 309 1 WORD
ParStIEC(H)>>>cnt - Value 3x 310 1 WORD
ParTrIEC(H)>>>cnt - Value 3x 311 1 WORD
Calculated residual overcurrent side L - 50N/51N side L
ParStIEC(L)>cnt - Value 3x 312 1 WORD
ParTrIEC(L)>cnt - Value 3x 313 1 WORD
ParStIEC(L)>>cnt - Value 3x 314 1 WORD
ParTrIEC(L)>>cnt - Value 3x 315 1 WORD
ParStIEC(L)>>>cnt - Value 3x 316 1 WORD
ParTrIEC(L)>>>cnt - Value 3x 317 1 WORD
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 51 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 52 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 53 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 54 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 55 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Internal states
Reset LEDs 1x 431 1 BIT 0=OFF, 1=ON
Profile selection 1x 432 1 BIT 0=OFF, 1=ON
Fault trigger 1x 433 1 BIT 0=OFF, 1=ON
IE/IPh Block2 1x 434 1 BIT 0=OFF, 1=ON
IPh Block2 1x 435 1 BIT 0=OFF, 1=ON
IE Block2 1x 436 1 BIT 0=OFF, 1=ON
Block1 87GMT and sides H-L-T 1x 437 1 BIT 0=OFF, 1=ON
Block1 side H 1x 438 1 BIT 0=OFF, 1=ON
Block1 side L 1x 439 1 BIT 0=OFF, 1=ON
Block1 side T 1x 440 1 BIT 0=OFF, 1=ON
Block1 87GMT 1x 441 1 BIT 0=OFF, 1=ON
Tcs1 side H 1x 442 1 BIT 0=OFF, 1=ON
Tcs2 side H 1x 443 1 BIT 0=OFF, 1=ON
Tcs1 side L 1x 444 1 BIT 0=OFF, 1=ON
Tcs2 side L 1x 445 1 BIT 0=OFF, 1=ON
Tcs1 side T 1x 446 1 BIT 0=OFF, 1=ON
Tcs2 side T 1x 447 1 BIT 0=OFF, 1=ON
External trips sides H-L-T 1x 448 1 BIT 0=OFF, 1=ON
External trips side H 1x 449 1 BIT 0=OFF, 1=ON
External trips side L 1x 450 1 BIT 0=OFF, 1=ON
External trips side T 1x 451 1 BIT 0=OFF, 1=ON
Reset partial counters 1x 452 1 BIT 0=OFF, 1=ON
Reset CB monitoring data side H 1x 453 1 BIT 0=OFF, 1=ON
52a side H 1x 454 1 BIT 0=OFF, 1=ON
52b side H 1x 455 1 BIT 0=OFF, 1=ON
Open CB side H 1x 456 1 BIT 0=OFF, 1=ON
Close CB side H 1x 457 1 BIT 0=OFF, 1=ON
Reset CB monitoring data side L 1x 458 1 BIT 0=OFF, 1=ON
52a side L 1x 459 1 BIT 0=OFF, 1=ON
52b side L 1x 460 1 BIT 0=OFF, 1=ON
Open CB side L 1x 461 1 BIT 0=OFF, 1=ON
Close CB side L 1x 462 1 BIT 0=OFF, 1=ON
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 56 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 57 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 58 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 59 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Measure differential phase L3
IL3cH - Value 3x 425 2 LONG Inref 16000
IL3cL - Value 3x 427 2 LONG Inref 16000
IL3cT - Value 3x 429 2 LONG Inref 16000
ISL3 - Value 3x 431 2 LONG Inref 16000
IDL3 - Value 3x 433 2 LONG Inref 16000
IDL3-2nd - Value 3x 435 2 LONG Inref 16000
IDL3-5th - Value 3x 437 2 LONG Inref 16000
Calculated
DThetaH - Value 3x 439 2 LONG DThB(H) 1000
DThetaL - Value 3x 441 2 LONG DThB(L) 1000
DThetaT - Value 3x 443 2 LONG DThB(T) 1000
U/f - Value 3x 445 2 LONG Un/fn 5600
IECH - Value 3x 447 2 LONG InH 16000
IECL - Value 3x 449 2 LONG InL 16000
IECT - Value 3x 451 2 LONG InT 16000
IE1S - Value 3x 453 2 LONG IEn1 80000
IE2S - Value 3x 455 2 LONG IEn2 80000
ILmaxH - Value 3x 457 2 LONG InH 16000
ILminH - Value 3x 459 2 LONG InH 16000
ILH - Value 3x 461 2 LONG InH 16000
ILmaxL - Value 3x 463 2 LONG InL 16000
ILminL - Value 3x 465 2 LONG InL 16000
ILL - Value 3x 467 2 LONG InL 16000
ILmaxT - Value 3x 469 2 LONG InT 16000
ILminT - Value 3x 471 2 LONG InT 16000
ILT - Value 3x 473 2 LONG InT 16000
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 60 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 61 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 62 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 63 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 65 of 73
NVA100X-T-MB0
Start",123="Id>>-L2
Start",124="Id>>-L3
Start",125="Id>>-L1
Trip",126="Id>>-L2
Trip",127="Id>>-L3
Trip",128="PT1 Alarm",129="PT1
Trip",130="PT2 Alarm",131="PT2
Trip",132="PT3 Alarm",133="PT3
Trip",134="PT4 Alarm",135="PT4
Trip",136="PT5 Alarm",137="PT5
Trip",138="PT6 Alarm",139="PT6
Trip",140="PT7 Alarm",141="PT7
Trip",142="PT8 Alarm",143="PT8
Trip",144="74TCS(H)
Trip",145="74TCS(L)
Trip",146="74TCS(T)
Trip",147="74CT(H)
Trip",148="74CT(L)
Trip",149="74CT(T)
Trip",150="BF(H)
Start",151="BF(H)
Trip",152="BF(L)
Start",153="BF(L)
Trip",154="BF(T)
Start",155="BF(T)
Trip",156="Logic input"
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 66 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 67 of 73
NVA100X-T-MB0
VAR REF IDX DIM TYPE Range Um Kv ENUM
Fault 0
Fault n. 0 - U/fr 3x 668 2 ULONG Un/fn 5600
Fault n. 0 - IDL1r 3x 670 2 ULONG Inref 16000
Fault n. 0 - ISL1r 3x 672 2 ULONG Inref 16000
Fault n. 0 - IDL2r 3x 674 2 ULONG Inref 16000
Fault n. 0 - ISL2r 3x 676 2 ULONG Inref 16000
Fault n. 0 - IDL3r 3x 678 2 ULONG Inref 16000
Fault n. 0 - ISL3r 3x 680 2 ULONG Inref 16000
Fault n. 0 - T1r 3x 682 1 WORD ^C 10
Fault n. 0 - T2r 3x 683 1 WORD ^C 10
Fault n. 0 - T3r 3x 684 1 WORD ^C 10
Fault n. 0 - T4r 3x 685 1 WORD ^C 10
Fault n. 0 - T5r 3x 686 1 WORD ^C 10
Fault n. 0 - T6r 3x 687 1 WORD ^C 10
Fault n. 0 - T7r 3x 688 1 WORD ^C 10
Fault n. 0 - T8r 3x 689 1 WORD ^C 10
Fault n. 0 - Inputs IN1-1 IN1-16 3x 690 1 UWORD 1
Fault n. 0 - Inputs IN2-1 IN2-16 3x 691 1 UWORD 1
Fault n. 0 - Outputs KC1-1 KC1-8 3x 692 1 UWORD 1
Fault n. 0 - Outputs KC2-1 KC2-8 3x 693 1 UWORD 1
Fault n. 0 - Fault info 3x 694 2 ULONG 1
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 68 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 69 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 70 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 71 of 73
NVA100X-T-MB0
Version 1.40
NVA100X-T-MB0 Remote Setting Manual Page: 73 of 73