Professional Documents
Culture Documents
Operation
The handle, fabricated from channel, lever and turned pipe gripper, are designed for smooth,
sturdy and trouble free operation. The handle is provided with locking arrangement in both ON and
OFF position.
Installation
It is designed to be mounted in horizontal upright position on 2 nos. channels based on structure.
Install three phases of isolator on structure parallel to each other, couple the pole with coupling
pipe, link it with operating lever, align all the elements in ON position, fix the operating pipe
vertically and clamp the handle in ON position. Make it ON and OFF several times.
3
2
8
1
14
16 4 4 7
6
13
11
15
TECHNICAL PARTICULARS 5
1 SYSTEM VOLTAGE 33 KV
12 2 RATED VOLTAGE 36 KV
12
3 RATED CURRENT 1250 AMP.
4 IMPULSE WITHSTAND VOLTAGE TO EATH 170 KV
ACROSS THE TERMINALS 195 KV
FOR EARTH SWITCH FOR ROTATING ISOLATOR
AUXILIARY SWITCH (2 NO + 2 NC)
10 5 POWER FREQ. WITH STAND VOLT TO EARTH 70 KV
AUXILIARY SWITCH (4 NO + 4 NC)
ACROSS THE TERMINALS 80 KV
6 RATED SHORT TIME CURRENT FOR 3 SEC. 25 KA
NO NC 10 NO NC
7 RATED PEAK WITHSTAND CURRENT 63 KA
8 WEIGHT OF ISOLATOR (APP) 210 KG.
9 GOVERNING SPECIFICATION IS 9921-1985 / IEC 129-1975
No. PART NAME QTY
G.L.