You are on page 1of 147

BellTel Project Site Installation Guidelines

ZTE Quality & HSE Team


BellTel Project 2G/4G Nationwide

Author & Document Version Information

Version Date Author Reviewer Approver Description

V1.2 2016-Jan-10 Wu shuzhong

V1.3 2016-Jan-12 Wu shuzhong Revised of V1.2

V1.4 2016-Jan-12 Wu shuzhong Revised of V1.3 base


on the discussion with
BellTel
V1.5 2016-Jan-19 Wu shuzhong Revised of V1.4 base
on the discussion with
BellTel
V1.6 2016-Feb-05 Wu shuzhong ZTE Rollout and Update Extension Cabinet
Technical Team Cable connection and
Commscope on site
jumper cable connection

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel Confidential to ZTE and Belltel 2
Version No: V1.5
BellTel Project 2G/4G Nationwide

Referenced Document
SN Document Name Author Version

RD1 Installation Guide & Trouble Shooting Delta R04


RD2 7711303 Rev E SiteRise 4x6 Fiber Trunk Installation Instructions Commscope Rev E
RD3 Northstar NSB170FT Blue+ Installation Training Manila Northstar V1.0
RD4 BellTel_STD_HQ_QM_Site Labeling Guidelines ZTE V1.5
RD5 Equipment Connectivity Layer Diagram ZTE V1.4
RD6 BellTel ZTE SiteRise Trial Commscope V1.0
RD7 New Cable Gland Arrangement 2015-11-25 Delta V0.02
RD8 86061438RevB_V.00(BB111015) Commscope Rev B
RD9 Site Detail Design Drawing (DDD) ZTE
RD10 DC Truck Cable Grounding Kit Installation Instruction Commscope V1.0
RD11 Fiber Truck Cable Grounding Kit Installation Instruction Commscope V1.0

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel Confidential to ZTE and Belltel 3
Version No: V1.5
BellTel Project 2G/4G Nationwide

Referenced Document
SN Document Name Author Version

RD12 SSC-760220228-SD_G Commscope Rev G


RD13 SSC-760220236-SD_G Commscope Rev G
RD14 SSC-760220244-SD_G Commscope Rev G
RD15 SSC-760221325-SD_G Commscope Rev G
RD16 SSC-760221333-SD_G Commscope Rev G
RD17 SSC-760221408-SD_G Commscope Rev G
RD18 SSC-760221416-SD_G Commscope Rev G
RD19 SSC-760221432-SD_G Commscope Rev G
RD20 SSC-760221663-SD_G Commscope Rev G

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel Confidential to ZTE and Belltel 4
Version No: V1.5
BellTel Project 2G/4G Nationwide

CONTENTS
• Configuration Diagram and Layout
• Cabinet Installation
• Cabinet Cabling
• Battery Installation
• TTA Installation
• RTA Installation
• Antenna Installation
• TTA/RTA Cable Installation
• MW Installation
• Labeling
• Site Environment
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel Confidential to ZTE and Belltel 5
Version No: V1.5
BellTel Project 2G/4G Nationwide

Schematic Diagram

DC Power/OF/IF

Fiber

DC Power

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel Confidential to ZTE and Belltel 6
Version No: V1.5
BellTel Project 2G/4G Nationwide

Configuration of Cabinet
For the ODF, have 2 types:

1. For FOC sites:

2. For non-FOC sites:

Maximum-1 (IPRAN is 9000-2E4,3U) Maximum-2 (IPRAN is 6120S,1U)

This is the layout of Maximum configuration in cabinet, if there is


any module not available, the space of this module will be blank.

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel Confidential to ZTE and Belltel 7
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet System Layout

BTS Master Cabinet

(*)References Page 4 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 8
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet System Layout

Extension Cabinet
(if available)

(*)References Page 6 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 9
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Installation
Cabinet located in position as Site
Detail Design Drawing (DDD)

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 10
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Installation
Install C- Channel Adapter

Anchor Bolt M12, One


flat washer+ spring washer

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 11
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Installation
Install C- Channel Adapter

The installation pattern of C –channel as per the site DDD

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 12
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling

Cable gland
assignment for
scenario 1
(First Batch Sites)

For Metro configuration site the DC trunk


cable and fiber trunk cable use the hole of
“Sector A” only

References Page 19 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 13
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Cable bushing assignment for scenario 1 (First Batch Sites)
For the Sites that cable can not go through from the bottom of the cabinet can use cable bushing of Cabinet

MW Fiber Battery
Trunk Fiber Cable
Sector A&B&C Genset
Trunk Power Modbus/SNMP
MW IF Cable Cable Sector B For temp probe to Slave
MW DC Grounding Cable of
Trunk Power Cable
FOC Fiber Cabinet plinth GPS Feeder Cable
Cable Sector C Trunk Power
Cable Sector A
AC Power Cable
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 14
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling

Cable gland
assignment for
scenario 2

For Metro configuration site the DC trunk


cable and fiber trunk cable use the hole of
“Sector A” only

References Page 2 of RD 7
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 15
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Cable bushing assignment for scenario 2
For the Sites that cable can not go through from the bottom of the cabinet can use cable bushing of Cabinet

FOC Fiber Battery Cable


Trunk Fiber Bank 3&4
Sector A&B&C
Trunk Power MW DC Cable
MW IF Cable Battery Cable
Cable Sector B For temp probe to Slave
Bank 1&2
Grounding Cable of
MW Fiber Trunk Power Cabinet plinth GPS Feeder Cable
Trunk Power
Cable Sector A
Cable Sector C Genset Modbus/SNMP
AC Power Cable
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 16
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Cable Glands


Cables entries in plinth must sealed with glands and rubber clay

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 17
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling

Cables entries of the cabinet must be


sealed by cable bushing

References Page 21 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 18
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Signal cables and power cable routing
shall be separately at least 2cm.

DC Power Cable

Fiber ,IF and


Signal Cables

Power cable To
Battery Cabinet
AC Power Cable

Doc No: BTL P15-PM-QM-STD-SIG-003


Signal Cables to Battery Cabinet
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 19
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Conduit
Below cables need to put protective conduit between cabinet and cable tray

SN. Outdoor Cable Need to Put Conduit Conduit Type


(Diameter)
1 AC power cable and grounding cable for AC power put 1 inch with gland
together in one conduit
2 DC/Battery power cable between Master and Extension 1.5 inch
cabinet put together in one conduit
3 Signal/Alarm cable between Master and Extension cabinet 1 inch
put together in one conduit
4 MW Fiber and IF cable put together in one conduit 1 inch

5 MW DC power cable for outdoor unit put together in one 1 inch


conduit
End of the conduit need
to be sealed with clay

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 20
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Routing of cable should through from the bottom of the cabinet, if can not, then go through the cable bushing of
cabinet.

Site ACPDB Cable


cable tray Cable bushing of Cabinet Entries sealed with IP
cable gland

Conduit

Need to
install C- For AC Power cable from site
Channel ACDB to cabinet ACPDU use
Adapter protective conduit that with
IP cable gland

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 21
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---AC Power Cable

Before connect the AC power must make sure:


(Delta rectifier working voltage range is 180 Vac – 250Vac)
1. Verify that Site ACPDB’s grounding bus bar is integrated to site MGB ;
2. Verify that the Neutral cable is firmly terminated to the PLN supply and is not “floating” ;
3. AC Input voltage measurements:
 L1 – L2 (180Vac – 250Vac)
L1 – Ground (90Vac – 125Vac)
L2 – Ground (90Vac – 125Vac)
OR:
 L1 – Neutral (180Vac – 250Vac)
L1 – Ground (180Vac – 250Vac)
Neutral – Ground (<5Vac)
4. Grounding cable from site ACPDB to Cabinet ACPDU had connected.

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 22
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---AC Power Cable


AC power and grounding cable connection
Attention: These AC cables are electriferous, if need to
operate must switch off the AC power in Site ACPDB First.

OR

Shorting pin Shorting pin

Black Brown Blue Brown


32mm2 32mm2 Must connect the Grounding cable
ACPDU in Cabinet
32mm2 32mm2 first then connect AC cable

16mm2 16mm2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 23
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---AC Power Cable


AC power connection (Temporary installation to be changed once proper cables are received)
This 4×10mm AC power cable had delivered and using on site now is temporary, it can connect as below, and it will
be replaced by 2×35mm later as required by BellTel when the new AC cable is available.

L1 L
OR

L2 N

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 24
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling--- DC Power cable


DC breaker Assignment for Modules Inside Cabinet

Battery FAN PRIORITY BREAKERS

BKR LVBD
1 2 1 2 3 4 5 6 7 8 9 10

125A 125A 10A 16A 25A 25A 16A 16A 16A 16A 16A 16A

IDU01 & IDU02 Redundancy


DC SPD

IDU01 Redundancy & IDU02

IPRAN Redundancy
Extension Cabinet

BBU02 or AOU03

MW AOU01

MW AOU02
DC Fan

BBU01
BAT02
BAT01

IPRAN
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 25
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling--- DCPDU in Master Cabinet


Some sites need to install one DCPDU in Master Cabinet

Newly Increased 63A Breaker

References Page 38 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 26
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling --- Extension Cabinet


Extension Cabinet PDU

CB for Battery CB Load1 to Load 6 for TDD RRU


CB for Extension Cabinet Fan

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 27
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Cable Connection Schematic Diagram between Master Cabinet and Extension Cabinet
Battery Extension
breakers power breaker
SSM1 Positive
Negative module Bus bar
Bus bar (+0V)
(-48V) FAN breaker
Positive Bus
bar (+0V) 2AWG x 2

RFID
Signal
Cable

Ethernet
cable x 1
16AWG x1

/1
16AWG x1
/1
/1
/1
/1 2AWG x 4
References Page 39 of RD 1 /2 2AWG x 4
Doc No: BTL P15-PM-QM-STD-SIG-003 /2
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 28
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling --- Extension Cabinet Cable Gland Assignment

For Battery String 3 (+/-)

For Battery String 4 (+/-)

DC Power From Master Ethernet Cable from


Cabinet (+/-) Master cabinet

RFID Signal Cable


DC Power From Master
from Master cabinet
Cabinet for Extension Fan

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 29
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Battery Power Cable 0V for Batt 4
Connection From 0V for Batt 3 Positive Bus bar (+0V) of PDU
Master Cabinet to
Extension Cabinet 0V for Batt 2
PDU 0V for Batt 1

Power system in Master Cabinet

-48V for Batt 3

-48V for Batt 4 Extension Cabinet PDU

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 30
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling Extension Cabinet PDU


DC Power Cable Connection From Master 0V
Cabinet to Extension Cabinet PDU
Power system in Master Cabinet

-48V

Insulation panel

NPL2 –Bus bar

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 31
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Extension Cabinet Fan Power Cable Connection From Master Cabinet to Extension Cabinet PDU

Extension Cabinet PDU


0V

Power system in
Master Cabinet -48V

Power Cable provide for


Extension Cabinet Fan

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 32
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
Ethernet Cable Connection From Master Cabinet to Extension Cabinet
Master Cabinet

Extension Cabinet

The Ethernet cable is available in


the Extension Cabinet already

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 33
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling
RFID Signal RS485 Cable Connection From Master Cabinet to Extension Cabinet

Master Cabinet

Extension Cabinet

The Signal cable is available in the Extension


Cabinet already, if not long enough, can ask
for a through connection cable
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 34
Version No: V1.5
BellTel Project 2G/4G Nationwide

Master Cabinet Extension Cabinet


Cabinet Cabling
--- Temperature Sensor

TE1
(Temp. Equipment)
There is 2 strings
battery in Extension
Cabinet only

TE2
(For fan control)
String 03
String 01

TB1

TB2
String 02 String 04
TA
References Page 44 of RD 1
(Temp. Ambient)
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 35
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Cabinet Internal Grounding


For Verification only, no connection required on site

All modules must grounding properly connect to the grounding bar of the cabinet ,
connector should be lugged, with heat shrink tube or boots.
For the cable inside the cabinet use white cable tie (except fiber),
black cable tie be used outdoor.

The bolt of grounding terminal must tighten up.

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 36
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber
For Verification only, no connection required on site

Indoor fiber must be protected


by specified coiled pipe
Strap the fiber with specified
cable tie
Fiber routing in the right side of the cabinet
Redundant indoor fiber must be spiral wrapped properly
in the cabinet side with bend radius no less than 3cm
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 37
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber From RTA/TTA to MPO Metro RTA/TTA

Red is connect Fiber From Split RTA/TTA


to the ports 13
to 24 in MPO

Blue is
connect to Sector B Sector C
the ports 1 Sector A Connect Sector A/B/C in one MPO Cassette
to 12 in MPO

MPO Fiber from junction box

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 38
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Routing from BBU to MPO Cassette

Spool the excess length of the fibre Terminate the fiber according to the design and use specified BELCRO ties.
cables inside the fibre cable tray.

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 39
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection in BBU

BBU
MPO
FS5
BPN2

TX5/RX5 TX4/RX4 TX3/RX3 TX2/RX2 TX1/RX1 TX0/RX0


OF5_TX5/RX5
OF4_TX4/RX4 OF2_TX2/RX2 OF0_TX0/RX0
OF3_TX3/RX3 OF1_TX1/RX1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 40
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(1) Split (GSM/FDD): 6*R8863(900M/1800M)+ 6*R8882(700M)
Number of MPO
Scene Number of RRU Fiber No. Board Port MPO Cassette Port
Cassette
FS5 TX0 Sector_A-MPO 1 LC-LC
Fiber 1
FS5 RX0 Sector_A-MPO 2 LC-LC
FS5 TX1 Sector_B-MPO 1 LC-LC
Fiber 2
FS5 RX1 Sector_B-MPO 2 LC-LC
FS5 TX2 Sector_C-MPO 1 LC-LC
Fiber 3
FS5 RX2 Sector_C-MPO 2 LC-LC
6*R8863
FS5 TX3 Sector_A-MPO 9 LC-LC
Fiber 4
FS5 RX3 Sector_A-MPO 10 LC-LC
FS5 TX4 Sector_B-MPO 9 LC-LC
Fiber 5
FS5 RX4 Sector_B-MPO 10 LC-LC
FS5 TX5 Sector_C-MPO 9 LC-LC
Fiber 6
Split FS5 RX5 Sector_C-MPO 10 LC-LC
3
RTA/TTA BPN2 OF0_Tx0 Sector_A-MPO 18 LC-LC
Fiber 1
BPN2 OF0_Rx0 Sector_A-MPO 17 LC-LC
BPN2 OF1_Tx1 Sector_B-MPO 18 LC-LC
Fiber 2
BPN2 OF1_Rx1 Sector_B-MPO 17 LC-LC
BPN2 OF2_Tx2 Sector_C-MPO 18 LC-LC
Fiber 3
BPN2 OF2_Rx2 Sector_C-MPO 17 LC-LC
6*R8882
BPN2 OF3_Tx3 Sector_A-MPO 20 LC-LC
Fiber 4
BPN2 OF3_Rx3 Sector_A-MPO 19 LC-LC
BPN2 OF4_Tx4 Sector_B-MPO 20 LC-LC
Fiber 5
BPN2 OF4_Rx4 Sector_B-MPO 19 LC-LC
BPN2 OF5_Tx5 Sector_C-MPO 20 LC-LC
Fiber 6
Doc No: BTL P15-PM-QM-STD-SIG-003 BPN2 OF5_Rx5 Sector_C-MPO 19 LC-LC
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 41
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(2) Split (GSM/FDD): 6*R8863(900M/1800M)+ 3*R8862A(700M)
Quantity of MPO
Scene Quantity of RRU Fiber No. Board Port MPO Cassette Port
Cassette
FS5 TX0 Sector_A-MPO 1 LC-LC
Fiber 1
FS5 RX0 Sector_A-MPO 2 LC-LC
FS5 TX1 Sector_B-MPO 1 LC-LC
Fiber 2
FS5 RX1 Sector_B-MPO 2 LC-LC
FS5 TX2 Sector_C-MPO 1 LC-LC
Fiber 3
FS5 RX2 Sector_C-MPO 2 LC-LC
6*R8863
FS5 TX3 Sector_A-MPO 9 LC-LC
Fiber 4
FS5 RX3 Sector_A-MPO 10 LC-LC
FS5 TX4 Sector_B-MPO 9 LC-LC
Split Fiber 5
3 FS5 RX4 Sector_B-MPO 10 LC-LC
TTA/RTA
FS5 TX5 Sector_C-MPO 9 LC-LC
Fiber 6
FS5 RX5 Sector_C-MPO 10 LC-LC
BPN2 OF0_Tx0 Sector_A-MPO 18 LC-LC
Fiber 1
BPN2 OF0_Rx0 Sector_A-MPO 17 LC-LC
BPN2 OF1_Tx1 Sector_B-MPO 18 LC-LC
3*R8862A Fiber 2
BPN2 OF1_Rx1 Sector_B-MPO 17 LC-LC
BPN2 OF2_Tx2 Sector_C-MPO 18 LC-LC
Fiber 3
BPN2 OF2_Rx2 Sector_C-MPO 17 LC-LC

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 42
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(3) Metro (GSM/FDD): 4*R8863(900M/1800M)+ 3*R8862A(700M)

Quantity of MPO
Scene Quantity of RRU Fiber No. Board Port MPO Cassette Port
Cassette
FS5 TX0 MPO_1 LC-LC
Fiber 1
FS5 RX0 MPO_2 LC-LC
FS5 TX1 MPO_5 LC-LC
Fiber 2
FS5 RX1 MPO_6 LC-LC
4*R8863
FS5 TX3 MPO_9 LC-LC
Fiber 3
FS5 RX3 MPO_10 LC-LC

Metro FS5 TX4 MPO_13 LC-LC


1 Fiber 4
TTA/RTA FS5 RX4 MPO_14 LC-LC
BPN2 OF0_Tx0 MPO_18 LC-LC
Fiber 1
BPN2 OF0_Rx0 MPO_17 LC-LC
BPN2 OF1_Tx1 MPO_20 LC-LC
3*R8862A Fiber 2
BPN2 OF1_Rx1 MPO_19 LC-LC
BPN2 OF2_Tx2 MPO_22 LC-LC
Fiber 3
BPN2 OF2_Rx2 MPO_21 LC-LC

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 43
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(4) Split (GSM/FDD): 6*R8863(900M/1800M)+ 6*R8882(700M)
Scene Quantity of RRU Quantity of MPO Cassette Fiber No. Board Port MPO Cassette Port

FS5 TX0 Sector_A-MPO 9 LC-LC


Fiber 1
FS5 RX0 Sector_A-MPO 10 LC-LC
FS5 TX1 Sector_B-MPO 9 LC-LC
Fiber 2
FS5 RX1 Sector_B-MPO 10 LC-LC
FS5 TX2 Sector_C-MPO 9 LC-LC
Fiber 3
FS5 RX2 Sector_C-MPO 10 LC-LC
6*R8863
FS5 TX3 Sector_A-MPO 13 LC-LC
Fiber 4
FS5 RX3 Sector_A-MPO 14 LC-LC
FS5 TX4 Sector_B-MPO 13 LC-LC
Fiber 5
FS5 RX4 Sector_B-MPO 14 LC-LC
FS5 TX5 Sector_C-MPO 13 LC-LC
Fiber 6
Split FS5 RX5 Sector_C-MPO 14 LC-LC
3
RTA/TTA BPN2 OF0_Tx0 Sector_A-MPO 2 LC-LC
Fiber 1
BPN2 OF0_Rx0 Sector_A-MPO 1 LC-LC
BPN2 OF1_Tx1 Sector_B-MPO 2 LC-LC
Fiber 2
BPN2 OF1_Rx1 Sector_B-MPO 1 LC-LC
BPN2 OF2_Tx2 Sector_C-MPO 2 LC-LC
Fiber 3
BPN2 OF2_Rx2 Sector_C-MPO 1 LC-LC
6*R8882
BPN2 OF3_Tx3 Sector_A-MPO 6 LC-LC
Fiber 4
BPN2 OF3_Rx3 Sector_A-MPO 5 LC-LC
BPN2 OF4_Tx4 Sector_B-MPO 6 LC-LC
Fiber 5
BPN2 OF4_Rx4 Sector_B-MPO 5 LC-LC
BPN2 OF5_Tx5 Sector_C-MPO 6 LC-LC
Fiber 6
Doc No: BTL P15-PM-QM-STD-SIG-003 BPN2 OF5_Rx5 Sector_C-MPO 5 LC-LC
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 44
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(5) Split (GSM/FDD/TDD): 6*R8863(900M/1800M)+ 6*R8882(700M)+ 6*R8964(2300M/2600M) (totally in 2 pages, 1/2)
Scene Quantity of RRU Quantity of MPO Cassette Fiber No. Board Port MPO Cassette Port

FS5 TX0 Sector_A-MPO 1 LC-LC


Fiber 1
FS5 RX0 Sector_A-MPO 2 LC-LC
FS5 TX1 Sector_B-MPO 1 LC-LC
Fiber 2
FS5 RX1 Sector_B-MPO 2 LC-LC
FS5 TX2 Sector_C-MPO 1 LC-LC
Fiber 3
FS5 RX2 Sector_C-MPO 2 LC-LC
6*R8863
FS5 TX3 Sector_A-MPO 9 LC-LC
Fiber 4
FS5 RX3 Sector_A-MPO 10 LC-LC
FS5 TX4 Sector_B-MPO 9 LC-LC
Fiber 5
FS5 RX4 Sector_B-MPO 10 LC-LC
FS5 TX5 Sector_C-MPO 9 LC-LC
Fiber 6
Split FS5 RX5 Sector_C-MPO 10 LC-LC
3
RTA/TTA BPN2 OF0_Tx0 Sector_A-MPO 18 LC-LC
Fiber 1
BPN2 OF0_Rx0 Sector_A-MPO 17 LC-LC
BPN2 OF1_Tx1 Sector_B-MPO 18 LC-LC
Fiber 2
BPN2 OF1_Rx1 Sector_B-MPO 17 LC-LC
BPN2 OF2_Tx2 Sector_C-MPO 18 LC-LC
Fiber 3
BPN2 OF2_Rx2 Sector_C-MPO 17 LC-LC
6*R8882
BPN2 OF3_Tx3 Sector_A-MPO 20 LC-LC
Fiber 4
BPN2 OF3_Rx3 Sector_A-MPO 19 LC-LC
BPN2 OF4_Tx4 Sector_B-MPO 20 LC-LC
Fiber 5
BPN2 OF4_Rx4 Sector_B-MPO 19 LC-LC
BPN2 OF5_Tx5 Sector_C-MPO 20 LC-LC
Fiber 6
BPN2 OF5_Rx5 Sector_C-MPO 19 LC-LC
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel (Next Page Continue) 45
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(5) Split (GSM/FDD/TDD): 6*R8863(900M/1800M)+ 6*R8882(700M)+ 6*R8964(2300M/2600M) (totally in 2 pages, 2/2)
(Continue for previous page)

Scene Quantity of RRU Quantity of MPO Cassette Fiber No. Board Port MPO Cassette Port

BPNT(SLOT 8) OF0_Tx0 Sector_A-MPO 14 LC-LC


Fiber 1
BPNT(SLOT 8) OF0_Rx0 Sector_A-MPO 13 LC-LC
BPNT(SLOT 8) OF1_Tx1 Sector_B-MPO 14 LC-LC
Fiber 2
BPNT(SLOT 8) OF1_Rx1 Sector_B-MPO 13 LC-LC

BPNT(SLOT 8) OF2_Tx2 Sector_C-MPO 14 LC-LC


Fiber 3
Split BPNT(SLOT 8) OF2_Rx2 Sector_C-MPO 13 LC-LC
6*R8964 3
RTA/TTA
BPNT(SLOT 7) OF0_Tx0 Sector_A-MPO 22 LC-LC
Fiber 1
BPNT(SLOT 7) OF0_Rx0 Sector_A-MPO 21 LC-LC

BPNT(SLOT 7) OF1_Tx1 Sector_B-MPO 22 LC-LC


Fiber 2
BPNT(SLOT 7) OF1_Rx1 Sector_B-MPO 21 LC-LC

BPNT(SLOT 7) OF2_Tx2 Sector_C-MPO 22 LC-LC


Fiber 3
BPNT(SLOT 7) OF2_Rx2 Sector_C-MPO 21 LC-LC

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 46
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(6) Metro (GSM/FDD): 4*R8863(900M/1800M)+ 3*R8862A(700M) + Metro (TDD): 6*R8964(2300M/2600M)
(totally in 2 pages, 1/2)
Quantity of MPO #1 MPO Cassette
Scene Quantity of RRU Fiber No. Board Port
Cassette Port

FS5 TX0 MPO_1 LC-LC


Fiber 1
FS5 RX0 MPO_2 LC-LC
FS5 TX1 MPO_5 LC-LC
Fiber 2
FS5 RX1 MPO_6 LC-LC
4*R8863
FS5 TX3 MPO_9 LC-LC
Fiber 3
FS5 RX3 MPO_10 LC-LC
2 FS5 TX4 MPO_13 LC-LC
Metro
(#1 for GSM and FDD Fiber 4
TTA/RTA FS5 RX4 MPO_14 LC-LC
#2 for TDD)
BPN2 OF0_Tx0 MPO_18 LC-LC
Fiber 1
BPN2 OF0_Rx0 MPO_17 LC-LC
BPN2 OF1_Tx1 MPO_20 LC-LC
3*R8862A Fiber 2
BPN2 OF1_Rx1 MPO_19 LC-LC
BPN2 OF2_Tx2 MPO_22 LC-LC
Fiber 3
BPN2 OF2_Rx2 MPO_21 LC-LC
Doc No: BTL P15-PM-QM-STD-SIG-003
Version No: V1.5
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel (Next Page Continue) 47
BellTel Project 2G/4G Nationwide

Cabinet Cabling---Fiber Connection Between BBU& MPO Cassette


(6) Metro (GSM/FDD): 4*R8863(900M/1800M)+ 3*R8862A(700M) + Metro (TDD): 6*R8964(2300M/2600M)
(totally in 2 pages, 2/2) (Continue for previous page)
Scene Quantity of RRU Quantity of MPO Cassette Fiber No. Board Port #2 MPO Cassette Port

BPNT(SLOT 8) OF0_Tx0 MPO_2 LC-LC


Fiber 1
BPNT(SLOT 8) OF0_Rx0 MPO_1 LC-LC
BPNT(SLOT 8) OF1_Tx1 MPO_6 LC-LC
Fiber 2
BPNT(SLOT 8) OF1_Rx1 MPO_5 LC-LC

BPNT(SLOT 8) OF2_Tx2 MPO_10 LC-LC


2 Fiber 3
Split BPNT(SLOT 8) OF2_Rx2 MPO_9 LC-LC
6*R8964 (#1 for GSM and FDD
RTA/TTA
#2 for TDD) BPNT(SLOT 7) OF0_Tx0 MPO_14 LC-LC
Fiber 1
BPNT(SLOT 7) OF0_Rx0 MPO_13 LC-LC

BPNT(SLOT 7) OF1_Tx1 MPO_18 LC-LC


Fiber 2
BPNT(SLOT 7) OF1_Rx1 MPO_17 LC-LC

BPNT(SLOT 7) OF2_Tx2 MPO_22 LC-LC


Fiber 3
BPNT(SLOT 7) OF2_Rx2 MPO_21 LC-LC

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 48
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---GPS Feeder Cable


One grounding Kit for one GPS Feed Cable

GPS Port Grounding Kit for GPS Feed Cable Cable will be
inside Cabinet installed 1m before entry the power Cabinet.(depend
on the position of the grounding bar)

1 (tape) +3 (putty) +3 (tape)


waterproof treatment

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 49
Version No: V1.5
BellTel Project 2G/4G Nationwide

Cabinet Cabling---External Grounding Layout

Where cables are bolted to


an earth bar or similar, one
cable per bolt
Grounding cable connector
should be lugged, with heat
35mm2 shrink tube or boots.
References Page 23 of RD 1 35mm2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 50
Version No: V1.5
BellTel Project 2G/4G Nationwide

Battery Installation
Do not drag a battery along the floor, if the battery has been dropped or has any damage
or electrolyte leakage, do not install this battery, need to change a new one!

There are anti-rust oil on the battery terminal,


make sure keep the terminal clean
Each battery has one connecting
link tied on the handle, Don’t
break the insulating bush on the
connecting link

Make sure the degassing port of each battery


is not blocked after installation completed, or
References Page 29&30 of RD 3 else it may cause battery bulging
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 51
Version No: V1.5
BellTel Project 2G/4G Nationwide

Battery Installation

The covers shall be put back after all


connections have completed

Breaker of Battery Breaker of Battery


String 1&2 String 3,4,5,6

Before connect the Battery DC power


cable and connecting link, Must make sure 10mm evenly spaced between Temp sensor needs to be
the Battery Breaker had switched off. each battery, and batteries are installed
all aligned on a flat surface
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 52
Version No: V1.5
BellTel Project 2G/4G Nationwide

Battery Installation--- Battery Power Cable and Connecting Link Connection

Battery Cable (-) Battery Cable (+)


Must use insulated tools

References Page 35 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 53
Version No: V1.5
BellTel Project 2G/4G Nationwide

Battery Installation--- Battery Stolen Detect Cables


One battery connect one cable at negative
terminal (B1-B8) . If the cable didn’t connect
the battery(-), system will sent battery stolen
alarm.
Battery
Battery Stolen connecting link
Detect Cable

Battery Power
Cable(-)

References Page 36 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 54
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation
Bracket

One bolt with one flat washer+ spring washer


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 55
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation This bracket must be installed


between the upper and
Bracket middle mounting bracket and
close to the middle mounting
bracket

the upper mounting bracket

the middle mounting bracket

Installation this bracket


before Hoisting

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 56
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation

Bracket

Adjust the bracket base on the installation pole before Hoisting


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 57
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation
Hoisting

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 58
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation
Tower Top Assembly

References Page 35 of RD 6
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 59
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation Tower Top Assembly

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 60
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA Installation
Stiff Arms need to be installed for all tower or pole installation

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 61
Version No: V1.5
BellTel Project 2G/4G Nationwide

RTA Installation
RTA Overall view

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 62
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Installation --- Grounding

Connect the grounding cable from TTA/RTA to the Tower/Rooftop Grounding Bar

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 63
Version No: V1.5
BellTel Project 2G/4G Nationwide

Antenna Installation ---For Split TTA/RTA

Azimuth of antenna
reference to Site DDD

One bolt with one flat washer+ spring washer


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 64
Version No: V1.5
BellTel Project 2G/4G Nationwide

Antenna Installation

Must make sure the pole of antenna or the RTA/TTA is vertical


Vertical Line

The pole & antenna


not vertical

The pole & antenna is


not vertical
Verification by inclinometer
after antenna installation

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 65
Version No: V1.5
BellTel Project 2G/4G Nationwide

Antenna /TTA/RTA Installation


Antenna / TTA /RTA must make sure installed
in the coverage of lightning rod 45 degree

45 Degree

The lightning rod of the


pole is not high enough

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 66
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- DC and Fiber Trunk cable Hoisting for Tower sites

Key Points:

1. Apply force to hoist trunk cable slowly. Maintain even tension.


2. Untie trunk cable leader and make appropriate bends. Install the hoisting grip.
3. Need to use reel support stands.
4. Pay close attention to the cable radius bend.
5. Check the cable jacket.
6. Do not remove the fiber protect cap until the cable is confirmed to be in the final and correct position.

References Page 48 of RD 6
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 67
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- DC Trunk cable


DC Trunk cable for Tower Sites Hoisting Considerations

Reminder: Plan grip location


by measuring distance (D)
from Fiber Enclosure Box to
tower support member.

References Page 3&4 of RD 2 References Page 50 of RD 6


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 68
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- DC Trunk cable


DC Trunk cable for Tower Sites Hoisting
Considerations

Grip must be
used for cable
hoisting

References Page 5 of RD 2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 69
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation ---Junction Box

Junction Box Fiber Roll

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 70
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation ---DC Trunk Cable Preparation

For Junction Box Side For Cabinet Side

Prepare power conductor end by removing 50c m of


jacketing and outer shielding exposing power
conductors. Remove 5cm of jacketing from the end for
grounding inside of the enclosure.

After the trunk entry the cabinet,


removing the jacketing from here
References Page 6 of RD 2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 71
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- DC Trunk cable Connection in Junction Box


DC Power Trunk Preparation
1 2 3 4 5

Mark cutback length Notch Armor using flush cutter Place Rip Cord in Notches Pull Rip Cord Parallel to Cable
in-line with Kevlar strings
Stop at Length Marker
(while supporting breakout)
6 7 8 9 10

Remove Excess Rip Cord


Cut Armor Using Side Cutter
Remove Water Blocking Tape Remove 0.5 m of jacketing
Separate Armor
from the end of the cable
References Page 6&7 of RD 2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 72
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- DC Trunk cable Connection in Junction Box

Connect the DC
Power Cable as
the instruction
in the inside of
the Cover
RRU DC
TERMINAL

Fiber Optic
Cable
Terminal

Do not forget to connect the grounding cable


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 73
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Routing

Cable must enter straight in the enclosure box


for proper weather sealing of the gland.
Supportive clamp need to be fixed with the Fiber
References Page 7 of RD 2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 74
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB


Loosen Captive Screws Slide out power shelf

1 2

Must slide out the power


shelf before connect the
cable, otherwise the cable
Take out front top cover and top cover Ready for cable connection is not long enough and
power shelf can not slide
3 4 out when maintaining.

References Page 32 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 75
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB

DC Power cable terminal of


Terminal of Battery Modules in Power System
Cable in Power System -48VRTN
-48V
DC power cable connector should be lugged, with insulation jacket

DC Power cable
connection for RRU

DC Power Cable Connection


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 76
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB

DC Breaker in Master Cabinet Power System DC Breaker in Extension Cabinet PDU

SN of DC Breaker for 1 2 3 4 5 6
RTA/TTA from 12 to 23
SN of DC Breaker for TDD from 1 to 6

References Page 5 of RD 1
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 77
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB


Metro RTA/TTA (4-Port 700 RRU) SSC-760220228/SSC-760220236 (12 DC wires)
CB SN (*) DC Power Cable Color Terminal in Junction Box

12 BLUE 1
RED 2
13
ORANGE 3
14
YELLOW 4
15
BROWN 5
16
WHITE 6
17 BRIDGED
7

Note: In the Fiber Box, since terminal 5&6 and 6&7 were bridged; for troubleshooting and maintenance purposes - breakers 16 and 17 needs to be SWITCHED OFF

References Page 14&15 of RD 2 and Equipment Connectivity Layer Diagram RD 5


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 78
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB


Split Metro RTA/TTA (4-Port 700 RRU) SSC-760221432/SSC-760220244
CB SN (*) DC Power Cable Color Terminal in Junction Box Sector
12 BLUE 1 A

13 RED 2 A

14 ORANGE 3 A

15 Future 4

16 BLUE 1 B

17 RED 2 B

18 ORANGE 3 B

19 Future 4

20 BLUE 1 C

21 RED 2 C

22 ORANGE 3 C

23 Future 4

References Page 24&16 of RD 2 and Equipment Connectivity Layer Diagram RD 5


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 79
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB


Split Metro RTA/TTA (2-Port 700 RRU) SSC-760221325/SSC-760221333

CB SN (*) DC Power Cable Color Terminal in Junction Box Sector


12 BLUE 1 A

13 RED 2 A

14 ORANGE 3 A

15 YELLOW 4 A

16 BLUE 1 B

17 RED 2 B

18 ORANGE 3 B

19 YELLOW 4 B

20 BLUE 1 C

21 RED 2 C

22 ORANGE 3 C

23 YELLOW 4 C

References Page 19&17 of RD 2 and Equipment Connectivity Layer Diagram RD 5


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 80
Version No: V1.5
BellTel Project 2G/4G Nationwide
TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB
Split Metro RTA/TTA, TDD (2-Port 700 RRU) SSC-760221408/SSC-760221663
CB SN (*) DC Power Cable Color Terminal in Junction Box Sector

BLUE 1 A
12
RED 2 A
13
ORANGE 3 A
14
YELLOW 4 A
15
BROWN 5 A
16

17
WHITE 6 BRIDGED A

7 Note: In the Fiber Box, since terminal


BLUE 1 B
5&6 and 6&7 were bridged; for
18 troubleshooting and maintenance
RED 2 B purposes - breakers 16 and 17,22 and
19
ORANGE 3 B 23, 5 and 6 (in Slave Cabinet PDU)
20
needs to be SWITCHED OFF
YELLOW 4 B
21
BROWN 5 B
22

23
WHITE 6 BRIDGED B

BLUE 1 C
1 (Extension Cabinet PDU)
RED 2 C
2 (Extension Cabinet PDU)
ORANGE 3 C
3 (Extension Cabinet PDU)
YELLOW 4 C References Page 21&25 of RD 2 and
4 (Extension Cabinet PDU)
BROWN 5 C
Equipment Connectivity Layer Diagram
5 (Extension Cabinet PDU) RD 5
6 (Extension Cabinet PDU)
WHITE 6 BRIDGED C

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel
7
© ZTE All rights reserved Confidential to ZTE and Belltel 81
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation--- DC Trunk Cable Connection in MCB


Metro RTA/TTA, TDD (4-Port 700 RRU) SSC-760221416
CB SN (*) DC Power Cable Color Terminal in Junction Box Sector

BLUE 1 A
12
RED 2 A
13
ORANGE 3 A
14
YELLOW 4 A
15
BROWN 5 A
16
WHITE 6 BRIDGED A
17
7 A

BLUE 1 B
1 (Slave Cabinet PDU)
RED 2 B
2 (Slave Cabinet PDU)
ORANGE 3 B
3 (Slave Cabinet PDU)
YELLOW 4 B
4 (Slave Cabinet PDU)
BROWN 5 B
5 (Slave Cabinet PDU)
WHITE 6 BRIDGED B
6 (Slave Cabinet PDU)
7

References Page 22&23 of RD 2 and Equipment Connectivity Layer Diagram RD 5 Note: In the Fiber Box, since terminal 5&6 and 6&7 were bridged; for troubleshooting and maintenance
Doc No: BTL P15-PM-QM-STD-SIG-003 purposes - breakers 16 and 17 , 5 and 6 (in Slave Cabinet PDU) needs to be SWITCHED OFF
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 82
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber Trunk cable


Fiber Trunk cable For Tower Sites Hoisting Considerations

DC Trunk cable

References Page 11 of RD 2
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 83
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber Trunk cable


Fiber Trunk cable For Tower Sites Hoisting Considerations

Push a pipe with a hole at


each end through the Fiber
trunk reel.
Attached hoisting line
Install bridal and tag line ropes and slowly lower reel
to pipe. Install and attach inside of the tower
hoisting grip to tower before using the tag lines to
lowering fiber. control the reel.

References Page 11&12 of RD 2


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 84
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber and DC Trunk cable

Cable Clamp Installation Tighten to


3.5 – 4.5
N*m
Angle
Adapter

Tighten
to 6 - 8
N*m

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 85
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber and DC Trunk cable

Cable Clamp Installation

References Page 53 of RD 6
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 86
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber and DC Trunk cable

Cable Routing

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 87
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber and DC Trunk cable


one meter put one clam on the Tower cable tray or
Rooftop cable tray

Redundant DC and Fiber cable should spiral in the cabinet side, fix
to the cable tray, Power and Optical Cable bending radius does not
exceed minimum 6“ (152mm).

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 88
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Fiber and DC Trunk cable

Cable Routing

The DC and Fiber cable of RRU is on the ground Need to use hoisting rod to hold the DC and Fiber cable off the ground

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 89
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation ---DC /Fiber Trunk Cable Grounding

Grounding Kit for TTA/RTA DC /Fiber Trunk


Cable will be installed 1m before enter the
power Cabinet.(depend on the position of
the grounding bar)

Grounding Bar
Cabinet

Grounding Kit

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 90
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation ---DC Trunk Cable Grounding Kit


1 2 3
4

Break at closest diameter to cables


OD after installing onto cable
Use supplied emery cloth to remove any remaining
adhesive off the top of the corrugations
7
6
5

References Page 1 to 4 of RD 10
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 91
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation ---DC Trunk Cable Grounding Kit


One grounding Kit for one DC Trunk cable

Must remove the


plating paint before
grounding

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 92
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Fiber Trunk Grounding Kit


One grounding Kit for one
Fiber Trunk cable

References Page 1 to 2 of RD 11
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 93
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---AISG Cable Connection

RPX310B-B1
Low Band Antenna

AISG Port

IN
OUT
IN

From Low Band antenna AISG “OUT” Port connect to For each sector, from 700MHz RRU connect to Low Band antenna AISG
the ”IN” Port of the other antenna in the same sector “IN” Port. (connect on site, see next page for connection guideline)
(Connected in the Factory )
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 94
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---AISG Cable From RRU To Antenna


Sector 700MHz RRU Antenna
Antenna Labeling
Labeling Labeling
A 7R01 A01

B 7R01 A01
Split
C 7R01 A01

7R01 A01

7R02 A03
Metro
7R03 A05

700MHz RRU labeling can see in the


Hybrid cable (Fiber&Power) of each RRU
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 95
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation --- Jumper Routing

Jumper bending radius does not exceed minimum 6 inch (152mm).

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 96
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220228 , Metro RTA (4-Port 700 RRU)
Antenna sectors A,
B & C attached to a

R8863

R8863
1800
Bipod frame

1800
2X Comb
2X Filter
Sector A

R8862A

R8862A
700

700
2X Comb
2X Filter
Sector B

R8862A
R8863
900

700
Sector C

2X Comb
2X Filter
R8863

Fibre
900
References of RD 12 RTA Sector Assembly RTA Sector Assembly
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 97
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220228 , Metro RTA (4-Port 700 RRU) RVVPX310B-B1
P2 P1
Sector A
RPX310B-B1 700/900MHz
P2 P1

Coupler 3

Coupler 1
Coupler 4
Coupler 2

References of RD 12
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 98
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220228 , Metro RTA (4-Port 700 RRU) RVVPX310B-B1
P2 P1
Sector B
RPX310B-B1 700/900MHz
P2 P1

Coupler 7

Coupler 5
Coupler 8
Coupler 6

References of RD 12
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 99
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220228 , Metro RTA (4-Port 700 RRU) RVVPX310B-B1
P2 P1
Sector C
RPX310B-B1 700/900MHz
P2 P1

Coupler 11

Coupler 9
Coupler 12
Coupler 10

References of RD 12
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 100
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220228 , Metro RTA (4-Port 700 RRU)
Sector A RVVPX310B-B1
1800MHz P6 P5 P4 P3

1800MHz RRU 02 1800MHz RRU 01

Blue 4 Blue 1

Blue 3 Blue 2
To Sector B P6 To Sector B P3

To Sector B P5 To Sector B P4
To Sector C P6 To Sector C P3
To Sector C P5 To Sector C P4

References of RD 12
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 101
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221325, Split Metro RTA, 1.5M Compact (2-Port 700 RRU)

2 X Combiner/Filter

1800 RRU

900 RRU

1.5 m Structural Steel Frame Rear

Front Split Metro design has 3 identical


700 2-Port RRU Fiber Box sectors like the one shown here
References of RD 15
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 102
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221325, Split Metro RTA, 1.5M Compact (2-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector A
RPX310B-B1 700/900MHz
P2 P1

Coupler 3

Coupler 1
Coupler 4
Coupler 2

References of RD 15
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 103
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221325, Split Metro RTA, 1.5M Compact (2-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector B
RPX310B-B1 700/900MHz
P2 P1

Coupler 7

Coupler 5
Coupler 8
Coupler 6

References of RD 15
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 104
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221325, Split Metro RTA, 1.5M Compact (2-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector C
RPX310B-B1 700/900MHz
P2 P1

Coupler 11

Coupler 9
Coupler 12
Coupler 10

References of RD 15
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 105
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221325, Split Metro RTA, 1.5M Compact (2-Port 700 RRU)

RVVPX310B-B1
1800MHz 1800MHz RRU
P6 P5 P4 P3
Sector A
Blue 1

For Sector B and Sector C


Blue 2
the connection is the same
Blue 4
Blue 3

References of RD 15
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 106
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221432, Split Metro RTA, 1.5 M (4-Port 700 RRU)
2 X Combiner/Filter

1800 RRU

900 RRU

Front Rear Split Metro design has 3 identical


sectors like the one shown here
700 4-Port RRU 7-Port Fiber Box Structural Steel Frame
References of RD 19
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 107
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221432, Split Metro RTA, 1.5 M (4-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector A
RPX310B-B1 700/900MHz
P2 P1

Coupler 3

Coupler 1
Coupler 4
Coupler 2

References of RD 19
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 108
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221432, Split Metro RTA, 1.5 M (4-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector B
RPX310B-B1 700/900MHz
P2 P1

Coupler 7

Coupler 5
Coupler 8
Coupler 6

References of RD 19
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 109
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221432, Split Metro RTA, 1.5 M (4-Port 700 RRU)
RVVPX310B-B1
P2 P1
Sector C
RPX310B-B1 700/900MHz
P2 P1

Coupler 11

Coupler 9
Coupler 12
Coupler 10

References of RD 19
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 110
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221432, Split Metro RTA, 1.5 M (4-Port 700 RRU)

RVVPX310B-B1
1800MHz 1800MHz RRU
P6 P5 P4 P3
Sector A
Blue 1

For Sector B and Sector C


Blue 2
the connection is the same
Blue 4
Blue 3

References of RD 19
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 111
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220236, Metro TTA (4-Port 700 RRU)
RPX RVV

R8863

R8863
1800

1800
R8862A

R8862A
700

700
• Sector A is primary and has all
2X Comb RRU’s

R8862A
Sectors B & C include filters and
R8863
900

700 combiner
• 7m RF jumpers to sectors B & C
will be coiled and stored with
2X Filter
R8863

Fibre
900

sector A
Sector A
Sectors B and C
References of RD 13
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 112
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220236, Metro TTA (4-Port 700 RRU)
Coupler 8
RVVPX310B-B1 Sector B
Coupler 5 700MHz
Coupler 6 Coupler 7

700MHz RRU 02

Orange 1

Orange 2
Orange 4

Orange 3
References of RD 13
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 113
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220236, Metro TTA (4-Port 700 RRU)
Coupler 12
RVVPX310B-B1 Sector C
Coupler 9 700MHz
Coupler 10 Coupler 11

700MHz RRU 03

Orange 1

Orange 2
Orange 4

Orange 3
References of RD 13
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 114
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220236, Metro TTA (4-Port 700 RRU)

P1 P2
Sector B
Filter 3 900MHz Filter 4

P2 P1
900MHz RRU 01 900MHz RRU 02
To Sector A Filter 1 P1 To Sector A Filter 2 P1

To Sector A Filter 1 P2 To Sector A Filter 2 P2

To Sector C Filter 5 P1 To Sector C Filter 6 P1

To Sector C Filter 5 P2 To Sector C Filter 6 P2

References of RD 13
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 115
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760220236, Metro TTA (4-Port 700 RRU)
RVVPX310B-B1
Sector A P6 P5 P4 P3
1800MHz
1800MHz RRU 02 1800MHz RRU 01

Blue 4 Blue 1

Blue 3 Blue 2
To Sector B P6 To Sector B P3
To Sector B P5 To Sector B P4
To Sector C P6 To Sector C P3
To Sector C P5 To Sector C P4
References of RD 13
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 116
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)
2600 RRU

2 X Combine/Filter

1800 RRU

900 RRU

2300 RRU
Front Rear Split Metro design has 3
700 2-Port RRU Structural Steel Frame identical sectors like the
Fiber Box
one shown here
References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 117
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)
P2 P1 P2 P1
Sector A
700/900MHz
RV4PX310B1
RVVPX310B-B1

Coupler 1 Coupler 3

Coupler 2 Coupler 4

References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 118
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)
P2 P1 P2 P1
Sector B
700/900MHz
RV4PX310B1
RVVPX310B-B1

Coupler 5 Coupler 7

Coupler 6 Coupler 8

References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 119
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)
P2 P1 P2 P1
Sector C
700/900MHz
RV4PX310B1
RVVPX310B-B1

Coupler 9 Coupler 11

Coupler 10 Coupler 12

References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 120
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)

RVVPX310B-B1

Sector A
P6 P5 P4 P3
1800MHz
1800MHz RRU

For Sector B and Sector C Blue 1


the connection is the same
Blue 2
Blue 4
Blue 3

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 121
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)

RV4PX310B1
P6 P5 P4 P3
Sector A
2300MHz
2300MHz RRU

For Sector B and Sector C


Brown 1
the connection is the same
Brown 2
Brown 3
Brown 4
References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 122
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221408, Split Metro RTA, 1.5 M Compact, TDD (2-Port 700 RRU)
RV4PX310B1

Sector A P10 P9 P8 P7
2600MHz
2600MHz RRU

For Sector B and Sector C Yellow 1


the connection is the same
Yellow 2
Yellow 3

Yellow 4
References of RD 17
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 123
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)

2600 RRU
2300 RRU ZTE R8964
ZTE R8964

Fiber Boxes
Sector Frame A Sector Frame B (new TDD module)
(existing RTA 3.0)
References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 124
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)

RPX310B-B1 Sector A RVVPX310B-B1


P2 P1 P2 P1
700/900MHz

Coupler 1 Coupler 3

Coupler 2 Coupler 4

References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 125
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)

RPX310B-B1 Sector B RVVPX310B-B1


P2 P1 P2 P1
700/900MHz

Coupler 5 Coupler 7

Coupler 6 Coupler 8

References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 126
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)

RPX310B-B1 Sector C RVVPX310B-B1


P2 P1 P2 P1
700/900MHz

Coupler 9 Coupler 11

Coupler 10 Coupler 12

References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 127
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)
RVVPX310B-B1
Sector A
1800MHz
P6 P5 P4 P3
1800MHz RRU 02 1800MHz RRU 01

Blue 4 Blue 1

Blue 3 Blue 2
To Sector B P6 To Sector B P3
To Sector B P5 To Sector B P4
To Sector C P6 To Sector C P3
To Sector C P5 To Sector C P4
References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 128
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)

RV4PX310B1
Sector A P6 P5 P4 P3

2300MHz RRU

For Sector B and Sector C


the connection is the same Brown 1

Brown 2

Brown 3

Brown 4
References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 129
Version No: V1.5
BellTel Project 2G/4G Nationwide

TTA/RTA Cable Installation---Jumper Need to be Connected on Site


SSC-760221416, Metro RTA, 3.0 M, TDD (4-Port 700 RRU)
RV4PX310B1

Sector A
P10 P9 P8 P7

2600MHz RRU
For Sector B and Sector C
the connection is the same Yellow 1

Yellow 2

Yellow 3

Yellow 4
References of RD 18
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 130
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8250 ODU and Antenna

Grounding

IF Cable Connector 1+3+3 waterproof

1 layer of insulation tape


3 layers of waterproof tape
3 layers of insulation tape
Use cable tie fasten two ends

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 131
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8250 IF Cable Connector

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 132
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8250 IF Cable


Use cable tie to fix
with the cabinet rack

Cabinet
Grounding Bar

NR8250 ODU
NR8250 IDU

Connector inside Cabinet

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 133
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8950 AOU and Antenna

NR8950

Stainless steel
cable tie

MW antenna

Lightning arrester PIMDC


Grounding Point
of NR8950

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 134
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8950 AOU and Antenna

45 Degree

Lightning Rod

The MW Antenna must be installed


in the coverage of lightning rod 45
degree

Lightning arrester PIMDC

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 135
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8950 AOU DC Power Connection


Lightning arrester PIMDC

NR8950

Can also find cable


connect instruction in
the inside of the Cover

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 136
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---NR8950 AOU Fiber Connection

NR8950

Connect to IPRAN

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 137
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---MW Antenna (NR8250&NR8950) Support Rod

If MW antenna size is greater than or equal to 1.2 meter,


need to install support rod

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 138
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---Fiber/DC/IF Cabling


one meter put one clam on the Tower
cable tray or Rooftop cable tray
Small hole For Fiber
After remove the gasket ,this small
hole can be used for DC or IF cable

Big hole For DC/IF Cable


Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 139
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation ---DC/IF Cable Grounding Kit

DC/IF Cable Grounding

The redundant DC/IF/Fiber cable should


spiral in near by the cabinet, fix to the
cable tray, The bending radius does not
exceed minimum 6“ (152mm).
Grounding point (depend on the
existing tower grounding bar)

DC/IF cable length <=60m, 1point grounding connection


DC/IF cable length > 60m, 2points grounding connection
(the other point is 1m from the connector on top of tower)
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 140
Version No: V1.5
BellTel Project 2G/4G Nationwide

MW Installation --- DC/IF Cable Grounding Kit

DC/IF Cable Grounding

Grounding kit 1 (tape) +3 (putty) +3 (tape)


waterproof treatment

Doc No: BTL P15-PM-QM-STD-SIG-003


Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 141
Version No: V1.5
BellTel Project 2G/4G Nationwide

Labeling --- Cabinet Cable

All cables in cabinet are clearly labeled within 2-5 cm from end.

References of RD 4
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 142
Version No: V1.5
BellTel Project 2G/4G Nationwide

Labeling --- Component and Outdoor Cable

Site ID and Configuration The Sector label should be put in


Labeling the Junction Box of Split RTA/TTA

References of RD 4
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 143
Version No: V1.5
BellTel Project 2G/4G Nationwide

Labeling --- Power and Battery

DC breaker labeling

AC Power Cable AC Power Cable and Battery Labeling


Color Code Label
References of RD 4
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 144
Version No: V1.5
BellTel Project 2G/4G Nationwide

Labeling --- MW

MW Antenna Labeling

3cm 3cm
Waterproof
NR8250 ODU IF
NR8950 DC Cable Labeling Cable Labeling
3cm
NR8950 Fiber Labeling

References of RD 4
Doc No: BTL P15-PM-QM-STD-SIG-003
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 145
Version No: V1.5
BellTel Project 2G/4G Nationwide Internal use only▲

Site Environment

Clean and tidy


No waste or redundant material on site
Signs of burnt trash on site

Doc No:
Distribution – ZTE, Belltel © ZTE All rights reserved Confidential to ZTE and Belltel 146
Version No:
Thank you

You might also like