Professional Documents
Culture Documents
Abstract of Over Current Protection of Transformer (NEC 450.3)
Abstract of Over Current Protection of Transformer (NEC 450.3)
Transformer (NEC 450.3)
September 18, 2012 8 Comments
Introduction:
The over current protection required for transformers is consider for Protection of
Transformer only.Such over current protection will not necessarily protect the primary or
secondary conductors or equipment connected on the secondary side of the transformer.
When voltage is switched on to energize a transformer, the transformer core normally
saturates. This results in a large inrush current which is greatest during the first half cycle
(approximately0.01 second) and becomes progressively less severe over the next several
cycles (approximately 1 second) until the transformer reaches its normal magnetizing
current.
To accommodate this inrush current, fuses are often selected which have time-current
withstand values of at least 12 times transformer primary rated current for 0.1 second and
25 times for 0.01 second. Some small dry-type transformers may have substantially
greater inrush currents.
To avoid using over sized conductors, over current devices should be selected at about
110 to 125 percent of the transformer full-load current rating. And when using such
smaller over current protection, devices should be of the time-delay type (on the primary
side) to compensate for inrush currents which reach 8 to 10 times the full-load primary
current of the transformer for about 0.1 s when energized initially.
Protection of secondary conductors has to be provided completely separately from any
primary-side protection.
A supervised location is a location where conditions of maintenance and supervision
ensure that only qualified persons will monitor and service the transformer installation.
Over current protection for a transformer on the primary side is typically a circuit
breaker. In some instances where there is not a high voltage panel, there is a fused
disconnect instead.
It is important to note that the over current device on the primary side must be sized
based on the transformer KVA rating and not sized based on the secondary load to the
transformer
Maximum Rating of Over current Protection for Transformers more than 600 Volts
LocationLimitation TransformerRate Primary Protection Secondary Protection
s d Impedance (More than 600 More than 600 Volts Less than
Volts) 600 Volts
Circuit Fuse Circuit Fuse C.B or
Breaker Rating Breaker Rating Fuse
Any location Less than 6% 600% 300% 300 % 250% 125%
(NH) (NH) ( NH) (NH) (NH)
6% To 10% 400% 300% 250% 225% 125%
(NH) (NH) (NH) (NH) (NH)
Supervisedlocations Any 300% 250% Not Not Not
(NH) (NH) required required required
only Less than 6% 600% 300% 300% 250% 250%
6% To 10% 400% 300% 250% 225% 250%
NH: Next Higher Standard Size.
Over current Protection of Transformers< 600 V (NEC
450.3-B)
1) Only Primary side Protection of Transformer:
Maximum Rating of Over current Protection for Transformers Less than 600
Volts
ProtectionMetho Primary Protection Secondary Protection
d More than 2A to 9A Less than More than Less than
9A 2A 9A 9A
Primary only 125%(NH) 167% 300% Not required Not required
protection
Primary and 250% 250% 250% 125%(NH) 167%
secondary
protection
NH: Next Higher Standard Size.