Professional Documents
Culture Documents
Kaiqi Sun, Member, IEEE, Huangqing Xiao, Member, IEEE, Shengyuan Liu, Student Member, IEEE,
and Yilu Liu, Fellow, IEEE
With the rapid development of voltage source converter the North American interconnections.
(VSC) technology, the HVDC system applications have been
enlarged [8]-[10]. In addition to the long-distance bulk power The rest of the paper is organized as follows. The system
transmission, the HVDC system can also provide a quick model description is introduced in Section II. Section III
dynamic response to various system disturbances. The sharing introduces a fast frequency response control using the
of the frequency response reserves through the HVDC system VSC-HVDC system based on MRFR. The simulation
have been expected as a potential high-value product. In the verifications are presented based on a highly reduced power
past decade, some industries and academics have studied the system model of the North American interconnections in
inclusion of HVDC systems as part of the power system PSCAD/EMTDC in Section IV. The conclusions of this paper
frequency control [11]-[13]. The HVDC system can realize a are presented in Section V.
very fast frequency response to the disturbed system under
contingency since its active power control is decoupled from II. MODEL DESCRIPTION
the frequency deviation [14]. In practice, the power regulation In this paper, a large power system model is adopted which
of the HVDC system under different events can be up to combines the highly reduced models of EI and WECC. A
hundreds of MWs per second, which can significantly improve two-terminal VSC-HVDC system is used between the two
the frequency low point during the event [15]. However, most interconnections, as shown in Fig. 1.
of the existing HVDC frequency control strategies are coupled
with system primary frequency control and secondary A. Highly reduced models description
frequency control [16]-[19]. Because the traditional system
The highly reduced EI and WECC models are developed
frequency control is dominated by the thermal generators, the
according to a reduced equivalent system [24], whose
advantages of fast frequency response by the HVDC system are
parameters have been published in [26]. The EI reduced
not being demonstrated.
equivalent system has 528 buses and the WECC reduced
With the recent progress on machine learning, frequency equivalent system has 191 buses. The system performance,
response estimation has become more accurate and reliable for especially the frequency response perspective, has been
large power system disturbances. Reference [20] proposes a verified using the full EI and WECC models. The simulation is
measurement-driven approach for frequency response planned for use in the PSCAD/EMTDC software. In this paper,
estimation from synchrophasor data. References [21]-[23] have in order to improve the simulation speed, based on the highly
used machine learning to predict stability, and have usually reduced EI model, which is represented by 8 dynamic cluster
used specific power flow solution parameters as input to a generations, and the highly reduced WECC model, which is
machine learning tool, such as voltage and angle at particular represented by 6 dynamic cluster generations, the system is
buses, power flow of individual branches, along with individual developed with the generation aggregation of a reduced
machine and load data. However, the existing research focuses equivalent system. The capacity of the dynamic cluster
on the method improvement of the frequency response generations in the highly reduced models are shown in Table I.
estimation, while the coordination with the HVDC system for Fig. 1. Scheme of the study system, which is referred to the map of the North
the frequency response application has not received much American grid [25].
attention.
Fig. 2. Schematic diagram of a VSC in the VSC-HVDC system, where uabc Where kp and ki are the proportional and integral gains.
denotes the grid voltage, vabc and iabc represents the output voltage and current
of the VSC, R and L are the resistance and inductance of the interfacing reactor.
PLL ș
abc abc
dia ½ Outer loop
L Ria va ua ș
Pulses
dq0
dt ° ș dq0
°
di ° usd
L b Rib vb ub ¾ (1) usd
Selector
CDVC
dt ° PIu us-ref
id-ref
dic °
Voltage Modulation
PI
L Ric vc uc °
fremote
dt ¿ ȦLc id FRC fref
flocal
iq ɧ PdcCAPC
ȦLc
iq-ref PIp Pdc-ref
For the inner current control loop of VSC, the current PI Pdc
iq
controller is implemented in the synchronous dq-frame. usq CRPC
PI Qac-ref
Balanced static abc-axis voltages and currents can be
Inner loop Qac
transformed into the synchronous dq-axis voltage and current
components through the Park Transformation. In the
synchronous dq-frame, the dynamic equations of the VSC can Fig. 3. Basic control of the VSC-HVDC system (one terminal).
be expressed as:
and the other terminal aims at controlling the DC power flow on flocal
the VSC-HVDC system. The frequency response control is ࡳ
configured in one terminal, which controls the power flow, in
order to respond to the frequency deviation of both sides of the + fdeadband
+
AC grids. The basic control of the VSC-HVDC system is fref Kf ǻPdc
shown in Fig.3, where CAPC is the constant active power
+ +
control, CDVC is the constant DC voltage control, CRPC is the
constant reactive power control and FRC is a frequency
ࡳ
response control. fremote
III. FAST FREQUENCY RESPONSE CONTROL USING THE HVDC Fig. 4. Frequency-active power droop control.
SYSTEM BASED ON MRFR
A. Motivation
The HVDC system can provide bulk power support to the Fig.5 shows a two-terminal VSC-HVDC system
disturbed system in a very short time, which can significantly interconnecting two asynchronous grids. It is assumed that a
suppress the influence of the disturbance and rescue the generator in the asynchronous grid I (the red indication in Fig.5)
disturbed system from a very bad condition. However, the is tripped. The original power flow on the VSC-HVDC system
traditional frequency response control approach is to track the is 900MW from grid I to grid II. With the conventional FPDC,
deviation of the system frequency and adjust the power flow of the frequency and power flow change on the VSC-HVDC
the HVDC system accordingly; this control strategy may not system are shown in Fig.6.
make the best use of the fast response capability of the HVDC
system. The development of the frequency response estimation
based on the machine learning algorithm provides another
approach to improve the frequency response capability of the VSC-HVDC system
HVDC system. Different from the frequency deviation tracking
control strategies, using the frequency response estimation Ă Ă
based on the machine learning algorithm within the HVDC Original Power
flow
frequency response control can directly increase the power Asynchronous grid I Asynchronous grid II
flow of the HVDC system by using the estimation system
generator or load lost to improve the system transient stability. Fig. 5. Configuration of the two-terminal VSC-HVDC system interconnecting
two asynchronous grids.
B. Comparison analysis between the traditional frequency
response control and machine learning based frequency
response control
The frequency-active power droop control (FPDC) is usually
adopted as the frequency response control configured for the
VSC-HVDC system. The control diagram of the FPDC is
shown in Fig.4, where flocal is the operating frequency
monitored at the PCC bus of the power control terminal, fremote
is the operating frequency monitored at the PCC bus of the DC
voltage control terminal, the fref is the nominal frequency,
fdeadband is the dead-band of the FPDC, Kf is the droop Prate
Fig. 6. One generator trips in grid I. (a) System frequency change. (b) Power
flow on the VSC-HVDC system.
> This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 5
Random Feature
Selection
Ă
MLFC pre-calculating
Instance in
^ ^ ^
Prediction
^ ^
MLFC working
testing database, Tree 2 Y2=f2(X) Y=f(Y1,Y2,ĂYm)
Prediction 2
Porder-MLFC X
Random Feature
Selection
Fig. 7. The diagram of the frequency response difference between the FPDC Tree 1
^
Y1=f1(X)
and MLFC. Prediction 1
According to the principle of the MRFR, the detailed D. Multivariate random forest regression based frequency
MRFR training flowchart for the tripped generation estimation response control (MRFR based FRC)
application is shown in Fig.9.
The control strategy of the MRFR based FRC is shown in
Fig.10.
Fig. 9. The training flowchart of MRFR for the tripped generator estimation
> This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 7
f nominal f nadir
K MRFR u K initial
0.1 (5)
OD: operating data
K f d K MRFR d K Max
AC system
A generator trip
ǻPnormal Signal fnadir PGT At the same time, the MRFR also sends PGT, which is the
estimated total power of the tripped generation to equation (6),
Equation (6) can be expressed as:
Selector Equ.(5) Equ.(6)
ǻPorder
KMRFR
'PMRFR PGT u K proportion (6)
ǻPnormal Response controller
59.7
59.90
59.6
59.875
59.5
59.4 59.85
(a) (b)
Table II The main circuit parameters of the VSC-HVDC system
Fig. 13. The comparison between the simulated frequency low point and
Converter Rated VSC Nominal DC Nominal AC
estimated frequency low point. (a) WECC. (b) EI.
Station power (MVA) voltage(kV) voltage(kV)
In addition, it should be mentioned that one of the advantages point has been advanced to 3.8 s and the frequency low point of
of MRFR is that it is suffers from overfitting problems. To the WECC has been significantly improved to 59.82 Hz. As
illustrate this point, the MSEs of the proposed algorithm shown in Fig.16 (b), during the frequency response of the
training set and test set are shown in Table III. It can be seen VSC-HVDC system, EI also has some frequency drop, which is
that the mean-square errors (MSEs) in the test set are only acceptable and will not influence the operating stability.
slightly higher than the ones in the training set, while both of
them are quite small and close enough for practical application.
Table III The MSE comparison of the training set and test set
Table IV The performance comparison of the traditional FPDC and the Zoomed in
n
proposed MRFR based FRC
The WECC case and EI case indicate that the MRFR based Table V The performance comparison of the traditional FPDC and the
proposed MRFR based FRC
FPC has outstanding performance for the frequency response
control, which can significantly improve the frequency low Frequency low Stabilized frequency
point for the event, while stabilizing the frequency in advance, point(Hz) (Hz)
compared to the system frequency control and traditional
FPDC. Traditional FPDC 59.91 59.945
V. CONCLUSION
Providing ancillary services through the HVDC system has
been expected as a high-value product for system operations.
The HVDC system can provide bulk power support to the
disturbed system in a very short time, which can significantly
suppress the influence of the disturbance and rescue the
disturbed system from a very bad condition. However,
traditional frequency response control is needed to track the
> This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.11
deviation of the system frequency and adjust the power flow of Commutated HVDC Link Connection," 2006 IEEE International
Symposium on Industrial Electronics, Montreal, Que., 2006, pp.
the HVDC system accordingly. This traditional control strategy
1595-1600.
may not make the best use of the fast response capability of the
HVDC system. With the development of machine learning, the [7] S. Liu, Y. Zhao, Z. Lin, Y. Liu, Y. Ding, L. Yang, and S. Yi, "Data-driven
frequency response estimation based on the machine learning event detection of power systems based on unequal-interval reduction of
PMU data and local outlier factor," IEEE Transactions on Smart Grid, vol.
algorithm provides another approach to improve the frequency
10, no. 11, pp. 1630-1643, Mar. 2020.
response capability of the HVDC system. In this paper, a fast
frequency response control using the VSC-HVDC system for a [8] K. Sun, H. Xiao, J. Pan and Y. Liu, "A Station-hybrid HVDC System
large power system disturbance based on the multivariate Structure and Control Strategies for Cross-seam Power Transmission," in
IEEE Transactions on Power Systems, doi:
random forest regression (MRFR) algorithm is proposed. 10.1109/TPWRS.2020.3002430.
Different from the frequency deviation tracking control
strategies, the MRFR based fast frequency response control can [9] J. Sun et al., "Renewable energy transmission by HVDC across the
make the most use of the fast response capability of the HVDC continent: system challenges and opportunities," CSEE Journal of Power
and Energy Systems, vol. 3, no. 4, pp. 353-364, Dec. 2017.
system to provide fast power support to the disturbed AC
system. The simulation results show that the proposed MRFR [10] K. Sun et al., "VSC-MTDC System Integrating Offshore Wind Farms
based frequency response control can significantly improve the Based Optimal Distribution Method for Financial Improvement on Wind
Producers," IEEE Transactions on Industry Applications, vol. 55, no. 3, pp.
frequency low point for the event while stabilizing the
2232-2240, May-June 2019.
frequency as soon as possible, which proves the effectiveness
of the proposed MRFR based frequency response control under [11] MISO, “MISO transmission expansion planning (MTEP),” MISO, 2014.
different contingencies.
[12] NREL, "Interconnections seam study." Available: https://www.nrel.gov/
REFERENCES [14] K. Sun, H. Xiao, S. You, H. Li, J. Pan, K. J. Li, & Y. Liu, . "Frequency
secure control strategy for power grid with large-scale wind farms through
[1] Y. Shu, X. Zhou, and W. Li, "Analysis of low frequency oscillation and
HVDC links", International Journal of Electrical Power & Energy
source location in power systems," CSEE Journal of Power and Energy
Systems, vol. 117, pp.105706, 2020.
Systems, vol. 4, no. 1, pp. 58-66, March 2018.
[15] P. Belkin, "HVDC and power electronic systems for overhead line and
[2] F. Bai, X. Wang, Y. Liu, X. Liu, Y. Xiang and Y. Liu,
insulated cable applications." 2012 CIGRE San Francisco Colloquium,
"Measurement-based frequency dynamic response estimation using
2012.
geometric template matching and recurrent artificial neural network,"
CSEE Journal of Power and Energy Systems, vol. 2, no. 3, pp. 10-18, Sept.
[16] Z. W. Zhang, K. Rouzbehi, A. Luna, G. B. Gharehpetian and P. Rodriguez,
2016.
"Multi-terminal HVDC grids with inertia mimicry capability," IET
Renewable Power Generation, vol. 10, no. 6, pp. 752-760, July 2016.
[3] S. Liu, Z. Lin, Y. Zhao, Y. Liu, Y. Ding, B. Zhang, L. Yang, Q. Wang, and
S. E. White, "Robust system separation strategy considering online
[17] Y. Cao et al., "A Virtual Synchronous Generator Control Strategy for
wide-area coherency identification and uncertainties of renewable energy
VSC-MTDC Systems," IEEE Transactions on Energy Conversion, vol. 33,
sources," IEEE Transactions on Power Systems, 2020. DOI:
no. 2, pp. 750-761, June 2018.
10.1109/TPWRS.2020.2971966.
[18] P. McNamara and F. Milano, "Model Predictive Control-Based AGC for
[4] J. Pan, M. Callavik, P. Lundberg, and L. Zhang, "A Subtransmission
Multi-Terminal HVDC-Connected AC grids," IEEE Transactions on
Metropolitan Power Grid: Using High-Voltage dc for Enhancement and
Power Systems, vol. 33, no. 1, pp. 1036-1048, Jan. 2018.
Modernization," IEEE Power and Energy Magazine, vol. 17, no. 3, pp.
94-102, May-June 2019. [19] E. Rakhshani, D. Remon, A. M. Cantarellas, J. M. Garcia and P. Rodriguez,
"Virtual Synchronous Power Strategy for Multiple HVDC
[5] K. Sun, K. J. Li, J. Pan, Y. Liu, and Y. Liu, "An optimal combined
Interconnections of Multi-Area AGC Power Systems," IEEE Transactions
operation scheme for pumped storage and hybrid wind-photovoltaic
on Power Systems, vol. 32, no. 3, pp. 1665-1677, May 2017.
complementary power generation system," Applied energy, vol. 242, pp.
1155-1163, May, 2019. [20] W. Wang, W. Yao, C. Chen, X. Deng and Y. Liu, "Fast and Accurate
Frequency Response Estimation for Large Power System Disturbances
[6] R. Li, S. Bozhko, G. M. Asher, J. C. Clare, L. Yao and C. Sasse, "Grid
using Second Derivative of Frequency Data," IEEE Transactions on
Frequency Control Design for Offshore Wind Farms with Naturally
Power Systems (early access).
> This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication.12
[24] K. Sun, H. Xiao, J. Pan and Y. Liu, "A Station-hybrid HVDC System
Structure and Control Strategies for Cross-seam Power Transmission,"
press in IEEE Transactions on Power Systems, doi:
10.1109/TPWRS.2020.3002430.
27152