Professional Documents
Culture Documents
Get involved!
https://www.ashrae.org/technical-resources/technical-committees
Let’s Start Here
CKV Design
Flowchart
Construction:
• Test and Balance
• Commissioning
Kitchen Hoods
Let’s Start with the Hood
Why? Because everything else in a
CKV system is based on the hood!!!
• Important Details:
• UL vs Design Airflows
• UL tests with the appliance
(usually a griddle) at the
furthest location from the
exhaust collar, using 73% lean
ground beef patties.
• Typically, hoods in a CKV system
see different applications
Different Types of Exhaust Hoods
Let’s Start with the Hood
What is involved in the specification of a hood
• Type of Hood
• Cooking Duty (Temperatures – list tables of temps and appliances)
• Overhangs of 6 inches minimum front and sides unless side panels are utilized.
• Demand Control Kitchen Ventilation (DCKV)
• THE HOOD SHOULD "CAPTURE AND CONTAIN" ALL THE COOKING EFFLUENT.
•Hooded vs Unhooded
• For Unhooded, heat gain must be accounted for, and grease emissions must be
below 5mg/m3
Appliance Type By Duty and Typical Exhaust
As an example - Canopy Hoods:
Light Duty - 200°F: Ovens, Steamers
• 150 – 200 cfm/lf of hood length
Medium Duty - 400°F: Electric Ranges, Griddles, Fryers, Conveyor
(Pizza) Ovens
• 200 – 300 cfm/lf of hood
Heavy Duty - 600°F: Gas Ranges, Charbroilers, Wok Ranges
• 200 – 400 cfm/lf of hood
Extra Heavy Duty - 700°F: Solid Fuel Cooking
• +350 cfm/lf of hood
(See Chapter 34 of Applications, Tables 4 & 5)
Different Duty Appliances Under Different Hoods
Exhaust Hood Submittal Information
Side panels reduce
exhaust air requirement
Examples of Appliance Hood Overhangs
Optimizing Hood Design
• Talk to the owner
• Get involved in hood selection
• Do not settle for canopy hoods
• Reduction in CFM = Energy Saved
• Simple changes can have substantial impact
Front Supply with too Internal Supply with too much Front Supply operating as
much air being supplied air being supplied (more than intended – no spillage.
causing spillage. 10%) causing spillage. Also note
the air begin supplied provides
no benefit to the room.
Poll Question #5
Replacement Air at the Hood
Front Face Supply
100% heat gain to space
Heated in winter or not
tempered in summer
• About 50% of the make-up
air goes back into the kitchen
• Needs to be included in heat
gain calculations
• What about thermal
comfort?
Replacement Air at the Hood
Cooled in summer or not heated
enough in winter
• The cool air sinks to the floor
• The cold air can cause grease
and water to condense out
of the airstream
• Grease can accumulate on
the floor
Replacement Air at the Hood
Space neutral temperature
• Ensures proper capture and
containment
• Does not add heat to the
kitchen
• Keeps the workers
comfortable
Replacement Air in the Room
What’s wrong with this picture?
Replacement Air in the Room
Simple Rule
Do not place 4-way diffusers within 10 feet of any hood.
Recommended Rule
Do not use directional diffusers of any type in a commercial kitchen.
Replacement Air in the Room
63.66%
2.63%
2.65%
7.89%
Sources:
• Manufacturer data
• ASHRAE Handbook Ch. 18
Appliance Heat Gain
* Project had north and west exposures. Previous project was completely interior.
Test & Balance
Commissioning
CKC Testing and Balancing Hoods
• ALWAYS ensure that the balancer is following
the hood supplier's stated procedures for
measuring their hood's exhaust airflow
• Velocity Grid
• 4-inch rotating vane anemometer
• Factory installed Pitot tubes
• Duct traverse is not typically employed since it
involves penetrating the fire rated exhaust duct
CKV Testing with Smoke
• Using smoke to test for hood capture is
not recommend as an acceptable test.
• Smoke candles are good for visualizing air
currents and drafts, but they do not simulate
real cooking
• Smoke bombs cause too much smoke – they
do not simulate real cooking conditions.
• The best method to test a hood for
capture and containment is with actual
cooking.
CKV Test and Balance
• Confirm differential pressures between zones and outside, at
minimum and at maximum flow rates
• Don’t do it on a windy day!
• Assure all doors are closed while doing the tests.
• All building HVAC is running, all sources of transfer air are operational
• Replacement airflow rate should compensate synchronously with
each increment of exhaust
• Check pressure balance at each increment of speed change
• Adjustments in controls or in damper linkage settings may be needed
• Use data loggers to assure correct control sequences
CKV Commissioning
Commissioning goals:
• Verify hood proper capture and
containment
• During full load cooking
• At all minimum and maximum flow
rates
• Verify control sequences work
properly.
• Replacement air interlocks
• DCKV system (if applicable)
• HVAC/Fire Suppression system
interlocks
• Appliance/Hood Fan interlocks
• Verify proper space pressurization is
maintained during all operating
conditions
References
• ASHRAE Handbook – Fundamentals
• Chapter 18 – Non-Residential Heating and Cooling Load Calculations
• ASHRAE Handbook – HVAC Applications
• Chapter 34 – Kitchen Ventilation
• ASHRAE Std. 154 – Ventilation for Commercial Cooking Operations
• NFPA 96 – Standard for Ventilation Control