Professional Documents
Culture Documents
Model
Product brand name SENTRON
Product designation ACB
Design of the auxiliary switch 4 NO + 4 NC
Design of the product IEC 60947-2
Design of the operating mechanism Pushbutton
Voltage
Rated insulation voltage Ui 1 000 V
Protection class
Protection class IP IP20
Protective function of the overcurrent release LSING
Dissipation
Power loss [W] / for rated value of the current / at AC 55 W
/ in hot operating state / per pole
Electricity
Operating current / at 45 °C / rated value 1 250 A
Continuous current / rated value 1 250 A
Adjustable pick-up value current
● of the current-dependent overload release / 1 250 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 25 000 A
value
● of instantaneous short-circuit trip unit / Full- 25 000 A
scale value
Main circuit
Operating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Operating current
● at 40 °C / rated value 1 250 A
● at 50 °C / rated value 1 250 A
● at 55 °C / rated value 1 250 A
● at 60 °C / rated value 1 250 A
● at 65 °C / rated value 1 250 A
● at 70 °C / rated value 1 210 A
Suitability
Suitability for use Plant / motor protection
Adjustable parameters
Adjustable pick-up value current / of the current- 500 A
dependent overload release / initial value
Product details
Product component
● Trip indicator Yes
● Voltage trigger Yes
● undervoltage release No
Product extension / optional / motor drive No
Product function
Product function
● Ground fault protection Yes
● Phase failure detection Yes
Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 66 kA
● at 500 V / rated value 66 kA
● at 690 V / rated value 50 kA
Connections
Arrangement of electrical connectors / for main Main connection rear side horizontal
current circuit
Type of electrical connection / for main current circuit busbar connection
Mechanical Design
Height 465.5 mm
Width 590 mm
Depth 456 mm
Mounting type drawer unit
Certificates
Reference code
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q
other
Miscellaneous
Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WL1212-2DG76-4GG4-Z R21+T40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3WL1212-2DG76-4GG4-Z R21+T40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WL1212-2DG76-4GG4-Z R21+T40
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
275
327.5
10
465
460
275
10
150
123.5
76
40
31
480 55 42 58
367.5
382.5
30
30 90
13
.5
38
139 138
590
L2
L3
-Q
X8.11
X5.2
X6.7
X6.2
X6.4
X5.8
X5.4
X5.6
X8.12
X6.14
X5.12
X6.10
X6.12
X5.10
-A1 ETU27B
I> S
-F2
-Y1
I >> I
N N
In = 1250A
Ir = 500A-1250A -S11
Isd = 1562.5A-15000A
Ii = 25000A
IN = In / OFF
Ig = 100A / 300A / 600A / 900A / 1200A / OFF
-Q1
-T1
-T2
-T3
-F1
-F5
X8.10
X6.13
X5.11
X6.11
X8.9
X5.1
X6.8
X6.9
X6.1
X6.3
X5.7
X5.9
X5.3
X5.5
L1
L2
L3
N
N / L-
L (Long Time Delay / Überlastschutz); S (Short Time Delay / Kurzschlussschutz, kurzzeitverzögert); I (Instantaneous / Kurzschlussschutz, unverzögert); N (Neutral Protection / Neutralleiterschutz);
G (Ground Fault Protection / Erdschlussschutz); S11 (Internal motor shutdown switch, if spring is tensioned / Interner Motorabstellschalter, wenn Feder gespannt); F1 (1st auxiliary release / Erster Hilfsauslöser);
F2 (2nd auxiliary release / Zweiter Hilfsauslöser); F5 (Maglatch for trip unit / Auslösemagnet); S1 - S8 (Auxiliary switch / Hilfsschalter); Y1 (Closing coil / Einschaltmagnet);