You are on page 1of 7

Data sheet 3WL1116-2EB36-1AA2

withdrawable circuit breaker with guide frame 3-pole, size I, IEC


In=1600A to 690V, AC50/60Hz Icu=55kA at 500V rear connection
horizontal Overcurrent release ETU 45 LSIN protection adjustable
0.4-1 in with cubicle bus Opt.: Comm. /measuring func./ground fault/
ZSS With manual operating mechanism with storage with mechanical
request without 1st auxiliary release without 2nd auxiliary release
2NO+2NC

Model
Product brand name SENTRON
Product designation ACB
Design of the auxiliary switch 2 NO + 2 NC
Design of the product IEC 60947-2
Design of the operating mechanism Pushbutton
Type of the driving mechanism Manual operating mechanism with mechanical closing

3WL1116-2EB36-1AA2 Subject to change without notice


Page 1/7 12/06/2019 © Copyright Siemens
Type of the driving mechanism / motor drive No
Design of the overcurrent release ETU45B

General technical data


Number of poles 3
Size of the circuit-breaker 1
Usage category B
circuit-breaker / Design 3WL1

Voltage
Rated insulation voltage Ui 1 000 V

Protection class
Protection class IP IP20
Protection class IP / on the front IP20
Protective function of the overcurrent release LSIN

Dissipation
Power loss [W] / for rated value of the current / at AC 116.7 W
/ in hot operating state / per pole

Electricity
Operating current / at 45 °C / rated value 1 600 A
Continuous current / rated value 1 600 A
Adjustable pick-up value current
● of the current-dependent overload release / 1 600 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 2 400 A
value
● of instantaneous short-circuit trip unit / Full- 19 200 A
scale value

Main circuit
Operating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Operating current
● at 40 °C / rated value 1 600 A
● at 50 °C / rated value 1 600 A
● at 55 °C / rated value 1 600 A
● at 60 °C / rated value 1 600 A
● at 65 °C / rated value 1 600 A
● at 70 °C / rated value 1 490 A

Auxiliary circuit

3WL1116-2EB36-1AA2 Subject to change without notice


Page 2/7 12/06/2019 © Copyright Siemens
Number of NC contacts / for auxiliary contacts 2
Number of NO contacts / for auxiliary contacts 2

Suitability
Suitability for use Plant / motor protection

Adjustable parameters
Adjustable pick-up value current
● of the L-trip / with I4t characteristic / initial value 640 A
● of the L-trip / with I4t characteristic / Full-scale 1 600 A
value
Adjustable pick-up value current / of the current- 640 A
dependent overload release / initial value

Product details
Product component
● Trip indicator Yes
● Voltage trigger No
● undervoltage release No
Product extension / optional / motor drive Yes

Product function
Product function
● Ground fault protection No
● Phase failure detection Yes

Display and operation


Display version without display

Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 415 V / rated value 55 kA
● at 500 V / rated value 55 kA
● at 690 V / rated value 42 kA
Maximum short-circuit current breaking capacity (Icu)
● at 415 V / rated value 55 kA
● at 500 V / rated value 55 kA
● at 690 V / rated value 42 kA

Connections
Arrangement of electrical connectors / for main Main connection rear side horizontal
current circuit
Type of electrical connection / for main current circuit busbar connection

Mechanical Design
Height 460 mm
Width 320 mm

3WL1116-2EB36-1AA2 Subject to change without notice


Page 3/7 12/06/2019 © Copyright Siemens
Depth 456 mm
Mounting type drawer unit

Environmental conditions
Ambient temperature
-20 ... +70 °C
-40 ... +70 °C

Certificates
Reference code
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q

General Product Approval Declaration of Test Certificates


Conformity
Miscellaneous Special Test Certi-
ficate

Shipping Approval other


CCS / China Classi- Environmental Con-
fication Society firmations

other
Manufacturer De- Confirmation Miscellaneous
claration

Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WL1116-2EB36-1AA2
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3WL1116-2EB36-1AA2
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WL1116-2EB36-1AA2
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

3WL1116-2EB36-1AA2 Subject to change without notice


Page 4/7 12/06/2019 © Copyright Siemens
270 1.5

275

327.5
465

15
460

275

15
150
123.5

76
40

31

30 27 220 45 15 90 90

210 55 42 58

367.5

382.5

55
13
.5
38

139 68

320

3WL1116-2EB36-1AA2 Subject to change without notice


Page 5/7 12/06/2019 © Copyright Siemens
L / L+
L1

L2

L3

-Q
X8.1

X8.2

X6.2
X8.4

X6.4
X8.3

X6.12
X6.10

-A1 ETU45B

I> S

I >> I

N N

In = 1600A
Ir = 640A-1600A
Isd = 2000A-19200A
Ii = 2400A - 19200A; MAX=0.8*Ics
IN = 0.5* In / 1* In / OFF

-Q1

-S1 -S2

-T1

-T2

-T3

-F5
X8.10

X6.11
X8.9

X6.9

X6.1

X6.3
L1

L2

L3

N / L-

L (Long Time Delay / Überlastschutz); S (Short Time Delay / Kurzschlussschutz, kurzzeitverzögert);


I (Instantaneous / Kurzschlussschutz, unverzögert); N (Neutral Protection / Neutralleiterschutz); F5 (Maglatch for trip unit / Auslösemagnet);
S1 - S8 (Auxiliary switch / Hilfsschalter);

3WL1116-2EB36-1AA2 Subject to change without notice


Page 6/7 12/06/2019 © Copyright Siemens
last modified: 11/30/2019

3WL1116-2EB36-1AA2 Subject to change without notice


Page 7/7 12/06/2019 © Copyright Siemens

You might also like