Digital Power Meter

DPM680
Features
Measurement Parameters:
• Phase & Line Voltages (L-N)
• Phase Current & Neutral Current
• Bidirectional kW, kVAR & kVA
• Bidirectional kWh, kVARh & kVAh
• Frequency
• Total & Displacement Power Factor
• Voltage Total Harmonic Distortion
• Current Total Harmonic Distortion
• Thermal Current Demand
• Power Demand
• Current Sequence Components
• Voltage Sequence Components

TFT Colour LCD Display


Serial RS-485 Modbus RTU
Modbus TCP/IP
Built-in Webserver
Voltage & Current Waveform Display
Voltage & Current Harmonics Display

Technical Data
WIRING SYSTEMS POWER & THERMAL CURRENT DEMAND Protocol : Modbus TCP/IP
3-phase 4-wire system Interval : 1 ~ 30 mins Interface : Ethernet 10M/100M BaseT
3-phase 3-wire system
VOLTAGE AND CURRENT SEQUENCE Protocol : HTTP Server
CURRENT MEASUREMENT (TRMS) COMPONENTS Interface : Ethernet 10M/100M BaseT
Nominal current :5A Positive, negative and zero sequence
Min. measurement : 5 mA AUXILIARY POWER SUPPLY
Accuracy : 0.2% of full scale FREQUENCY MEASUREMENT AC voltage : 90 ~ 415 V AC
Burden : < 0.05 VA at 5 A Measurement range : 45 ~ 65 Hz Frequency : 50 / 60 Hz
Measurement range : 10 A Accuracy : 0.2% DC voltage : 100 ~ 300 V DC
Pulsed withstand : 100 A for 1 sec Power consumption : 3W typical
CT primary : 5 ~ 50,000 A ENERGY MEASUREMENT ACCURACY Sustained overload : 500 V AC
Active : IEC 62053-22 class 0.5
VOLTAGE MEASUREMENT (TRMS) Reactive : IEC 62053-23 class 2 ENVIRONMENTAL CONDITIONS
Nominal phase voltage : 0 ~ 300 V AC Overvoltage category : IV
Minimum measurement : 10 V HARMONICS DISPLAY Pollution degree :2
Accuracy : 0.2% at full scale Fundamental up to 32nd order Operating temperature : -10˚C ~ +55˚C
Phase voltage via VT : 60 ~ 50,000 V Storage temperature : -20˚C ~ +70˚C
VOLTAGE & CURRENT WAVEFORM Humidity : 0 – 95%,
DPM 680

POWER MEASUREMENT DISPLAY non condensing


Real power, apparent power, reactive power Simultaneous 3-phase voltage or
Accuracy : 0.5% current waveforms MECHANICAL
Mounting : according to DIN 43700 /
POWER FACTOR MEASUREMENT COMMUNICATION ANSI C39.1
Total and displacement power factor Protocol : Modbus RTU Dimension (mm) : 96(w) x 96(h) x 100(d)
Accuracy : 0.5% Interface : Isolated RS485 Enclosure protection : IP63 at the panel
IP20 at the body
Approximate weight : 0.5 kg
Digital Power Meter

Typical Application Diagrams Case Dimensions


96 mm
3-PHASE 4-WIRE SYSTEM : 4 CTs, Direct V Input 3-PHASE 4-WIRE SYSTEM : 3 CTs, Direct V Input

L1 L2 L3 Ln L1 L2 L3 Ln
90~415 V AC / 90~415 V AC /
AUX 100~300 V DC AUX 100~300 V DC

96 mm
S1
S2
l1
S1
S2
l1 Front
S1
S1
l2 Ethernet l2 Ethernet
S2 S2
S1 S1
l3 l3
S2 S2

S1 S1
ln ln
S2 S2

GND GND
L1 RS 485 L1 RS 485
Modbus-RTU Modbus-RTU
L2 L2

L3 L3
Ln Ln

90 mm
LOAD LOAD

Side

3-PHASE 3-WIRE SYSTEM : 3 CTs, 3 VTs 3-PHASE 3-WIRE SYSTEM : 3 CTs, Direct V Input 83 mm
L1 L2 L3 L1 L2 L3
17 mm

m
0m
90~415 V AC / 90~415 V AC /
AUX 100~300 V DC AUX 100~300 V DC

10
S1 S1
l1 l1
S2 S2
S1 S1
l2 Ethernet l2 Ethernet
S2 S2
S1 S1
l3

86 mm
l3
S2 S2

S1
ln
S1
ln Rear
ea
S2 S2
GND GND
L1 RS 485 L1 RS 485
Modbus-RTU Modbus-RTU
L2 L2

L3 L3
Ln Ln
LOAD GND
LOAD

Test Standards Cut-Out Recommendations

IEC 61010-1
Safety requirements.

91±0.5mm
IEC 61326-1
EMC requirements.

91±0.5mm

Ordering Information 101.6±0.5mm

MODEL DESCRIPTION
DPM 680

DPM 680-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC