You are on page 1of 2

APPENDIX 9.

A1

INSULATOR TYPES & USES

Insulator Set Type Suspension/ Tension Low Duty Jumper


Heavy Suspension
suspension
Nominal System Voltage {……………………..33 kV……………………….}
String Configuration Single Single Single Single
Reference Drawing
Insulator Unit type {…………………….Cap & Pin……………………..}
Coupling Type {……………………Ball & Socket………………….}
Security Clip type {………………………….R ……………………..}
Zinc Sleeve {…………………….Required……………………..}
Glaze Colour Brown Gray
Unit Puncture Voltage (KV) 110 125
Dry Lighting Impulse 70 75
Withstand Voltage (KV)
Wet power frequency 40 45
Withstand Voltage (KV)
Electro-mechanical failing 70 210
load (KN)

287
DNE(E)-RT-28
APPENDIX 9.A2/1

ELECTRICAL & MECHANICAL CHARACTERISTICS (33KV)

INSULATOR SETS – TYPES & USES

Insulator Set Type Suspension/Jumper Tension


Pollution Category {…………….Medium II………………}

Number of Insulator Units per 4 3


string
Dielectric material (Porcelain)

Nominal Insulator String mm 950 1500


Length
Dry Lighting Impulse KV (---------170---------)
Withstand voltage
Wet power frequency KV (-----------70--------)
Withstand voltage
Power Arc for insulator set KA (-----------31.5-----------)
-Current s (------------0.5-----------)
-Duration
Power arc for string insulator
units :
-Current for duration kA for (-------------12 for 0.1 or 6 for 0.2 -----------)
sec
Electromechanical failing load Kn 70 210

APPENDIX 9.A3

TYPE TEST - POLLUTION IEC 507

Salt Solution Salinity Not Required

288
DNE(E)-RT-28