You are on page 1of 49

®

EXTRANA
CABLE

CORE COLOUR STANDARD


FOR LOW VOLT AGE POWER AND CONTROL CABLE

NO SYSTEM CORE SNI/IEC COLOUR CABLE SPLN COLOUR CABLE


R Customer Requirement Customer Requirement
S Customer Requirement Customer Requirement
1 SINGLE CORE T Customer Requirement Customer Requirement
N Customer Requirement Customer Requirement
E Customer Requirement Customer Requirement
R BROW N RED
S - -
2 TWO CORE T - -
N BLUE BLUE
E - -
R BROW N RED
S - -
3 THREE CORE T - -
N BLUE BLUE
E YELLOW /GREEN STRIPE YELLOW /GREEN STRIPE
R BROW N RED
S BLACK YELLOW
4 FOUR CORE T GREY BLACK
N - BLUE
E YELLOW /GREEN STRIPE -
R BROW N RED
S BLACK YELLOW
5 FIVE CORE T GREY BLACK
N BLUE BLUE
E YELLOW /GREEN STRIPE YELLOW /GREEN STRIPE
R BLACK WITH NUMBERING BLACK WITH NUMBERING
6 MORE THAN FIVE CORE W ITHOUT W ITHOUT
E YELLOW /GREEN STRIPE YELLOW /GREEN STRIPE
R BLACK WITH NUMBERING BLACK WITH NUMBERING
7 MORE THAN FIVE CORE W ITH WITH
E YELLOW /GREEN STRIPE YELLOW /GREEN STRIPE

www.extranacable.com
®
EXTRANA
CABLE

NYA 450/750 V
SNI 04-6629.3; SNI 0225;
(Copper Conductor, PVC Insulated)

For building wire installed in conduit in dry location and interwiring in swich board and
control panel.

CONSTRUCTION DATA
Nominal Ov erall
Net Weight Bending Standard
Size Insulation Di a meter
Radius delivery length
Thi ckness Approximate

mm² mm mm kg/km mm mtr

1.5 0.7 3.0 21 18 100/coil


2.5 0.8 3.6 34 22 100/coil
4 0.8 4.1 51 25 100/coil
6 0.8 4.7 71 28 100/coil
10 1.0 6.0 119 36 100/coil
16 1.0 7.0 179 42 100/coil
25 1.2 8.7 281 52 1000/drum
35 1.2 9.8 379 59 1000/drum
50 1.4 1 1.2 507 67 1000/drum
70 1.4 13.2 713 79 1000/drum
95 1.6 15.5 985 93 1000/drum
120 1.6 17.1 1222 103 1000/drum
150 1.8 19.0 1532 114 1000/drum
185 2.0 21.2 1885 127 1000/drum
240 2.2 24.2 2465 145 1000/drum
300 2.4 26.9 3083 161 1000/drum
400 2.6 30.2 3926 181 1000/drum

ELECTRICAL DATA
Mi n. DC Ins ulation Ma x. Current Carr yi ng Ma x. Short
Max . Conductor Resistance
Size Resistance Capacity at 30ºC Inductance circuit current
DC at 20ºC AC at 70 ºC DC at 20ºC AC at 70 ºC in air in pi pe at 1 sec.

mm² Ω/km Ω/km M.Ω.km M.Ω.km A A mH/km kA

1.5 12.1 14.478 50 0.0100 24 15 0.320 0.17


2.5 7.41 8.866 50 0.0090 32 20 0.309 0.29
4 4.61 5.516 50 0.0077 42 25 0.290 0.46
6 3.08 3.685 40 0.0065 54 33 0.276 0.69
10 1.83 2.190 30 0.0065 73 45 0.274 1.15
16 1.15 1.376 30 0.0050 98 61 0.260 1.84
25 0.727 0.870 30 0.0050 129 83 0.257 2.88
35 0.524 0.627 20 0.0045 158 103 0.249 4.03
50 0.387 0.464 20 0.0040 198 132 0.248 5.75
70 0.268 0.321 20 0.0035 245 165 0.240 8.05
95 0.193 0.232 20 0.0035 292 197 0.239 10.93
120 0.153 0.184 20 0.0032 344 235 0.235 13.80
150 0.124 0.150 20 0.0032 391 - 0.235 17.25
185 0.0991 0.121 20 0.0032 448 - 0.235 21.28
240 0.0754 0.093 20 0.0032 525 - 0.233 27.60
300 0.0601 0.075 20 0.0030 608 - 0.232 34.50
400 0.0470 0.060 20 0.0028 726 - 0.231 41.20

www.extranacable.com
®
EXTRANA
CABLE

NYM 300/500 volt


SNI 04-6629.4; IEC 60277-4; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)

For building wire installed in conduit in dry location and interwiring in switch board and
control panel, inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA

Nominal Thi ckness Ov erall Net


Di a meter We ight Bending
Core Size
Radius
Ins ulation Sheath Approximate

- mm² mm mm mm kg/km mm

1. 5 0.7 1.2 9.1 121 73


2. 5 0.8 1.2 10.1 163 81
4 0.8 1.2 1 1.9 210 95
2
6 0.8 1.2 13.1 269 105
10 1.0 1.4 14.8 441 118
16 1.0 1.4 17.8 632 142
1. 5 0.7 1.2 9.2 141 74
2. 5 0.8 1.2 10.1 194 81
4 0.8 1.2 1 1.9 255 95
3
6 0.8 1.4 13.0 345 104
10 1.0 1.4 17.0 547 136
16 1.0 1.4 19.2 822 154
1. 5 0.7 1.2 9.9 167 79
2. 5 0.8 1.2 10.9 233 87
4 0.8 1.4 12.9 322 103
4
6 0.8 1.4 14.1 473 113
Core Identification:
2 cores : Black, Blue 10 1.0 1.4 18.5 730 148
3 cores : Green-yellow , Brown, Blue
4 cores : Green-yellow , Brown, Black, Grey
16 1.0 1.4 21.0 1014 168

ELECTRICAL DA TA
Min. DC Ma x. Current Carr yi ng
Max . Co nductor Resistance Ins ul ation Ma x. Short circuit
Core Size Capacity at 30ºC Inductance
Resis tance current at 1 sec.
DC at 20ºC AC at 70 ºC at 20ºC in air in ground

- mm² Ω/km Ω/km M.Ω.km A A mH/km kA

1.5 12.1 14.478 50 18 16 0.329 0.17


2.5 7.41 8.866 50 26 23 0.318 0.29
4 4.61 5.516 50 34 30 0.297 0.46
2
6 3.08 3.685 40 44 38 0.281 0.69
10 1.83 2.190 30 61 53 0.278 1.15
16 1.15 1.376 30 82 71 0.255 1.84
1.5 12.1 14.478 50 18 16 0.329 0.17
2.5 7.41 8.866 50 26 23 0.318 0.29
4 4.61 5.516 50 34 30 0.297 0.46
3
6 3.08 3.685 40 44 38 0.281 0.69
10 1.83 2.190 30 61 53 0.278 1.15
16 1.15 1.376 30 82 71 0.255 1.84
1.5 12.1 14.478 50 18 16 0.329 0.17
2.5 7.41 8.866 50 26 23 0.318 0.29
4 4.61 5.516 50 34 30 0.297 0.46
4
6 3.08 3.685 40 44 38 0.281 0.69
10 1.83 2.190 30 61 53 0.278 1.15
16 1.15 1.376 30 82 71 0.255 1.84

www.extranacable.com
®
EXTRANA
CABLE

NYY 0.6/1 kV
1 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Ov erall
Nominal Thi ckness Net Weight Bending
Size Di a meter
Radius
Insulation Sheath Approximate

mm² mm mm mm kg/km mm
1. 5 0.8 1.4 6.0 55 48
2. 5 0.8 1.4 6.5 70 52
4 1.0 1.4 7.4 97 59
6 1.0 1.4 8.0 121 64
10 1.0 1.4 9.4 168 75
16 1.0 1.4 9.9 234 79
25 1.2 1.4 1 1.6 344 93
35 1.2 1.4 12.7 445 102
50 1.4 1.4 14.3 578 114
70 1.4 1.4 16.0 793 128
95 1.6 1.5 18.5 1,079 148
120 1.6 1.6 20.0 1,319 160
150 1.8 1.7 22.2 1,622 178
185 2.0 1.7 24.6 2,009 197
240 2.2 1.8 27.7 2,612 222
300 2.4 1.9 30.7 3,236 246
400 2.6 2.1 34.2 4,077 274
500 2.8 2.2 38.1 5,139 305
630 2.8 2.3 42.4 6,712 339

ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA


1.5 12.1 14.478 26 26 40 30 0.505 0.17
2.5 7.41 8.866 35 34 41 30 0.470 0.29
4 4.61 5.516 46 45 42 31 0.450 0.46
6 3.08 3.685 58 57 43 32 0.426 0.69
10 1.83 2.190 79 77 44 33 0.396 1.15
16 1.15 1.376 105 103 160 119 0.374 1.84
25 0.727 0.870 140 137 206 153 0.358 2.88
35 0.524 0.627 174 169 249 183 0.345 4.03
50 0.387 0.464 212 206 296 216 0.336 5.75
70 0.268 0.321 269 261 365 265 0.326 8.05
95 0.193 0.232 331 321 438 316 0.321 10.93
120 0.153 0.184 386 374 499 359 0.316 13.80
150 0.124 0.150 442 428 561 402 0.313 17.25
185 0.0991 0.121 511 494 637 454 0.310 21.28
240 0.0754 0.093 612 590 743 527 0.307 27.60
300 0.0601 0.075 707 678 843 544 0.305 34.50
400 0.0470 0.061 859 817 986 686 0.302 46.02
500 0.0366 0.049 1000 940 1 125 774 0.299 57.53
630 0.0283 0.041 1 124 1060 1 198 846 0.293 72.52

www.extranacable.com
®
EXTRANA
CABLE

2 CORE NYY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheat hed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Ov erall
Nominal Thi ckness Net Weight
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate

mm² mm mm mm kg/km mm

1.5 0.8 1.8 12.2 213 98


2.5 0.8 1.8 13.5 259 108
4 1.0 1.8 14.9 351 119
6 1.0 1.8 16.2 422 130
10 1.0 1.8 17.9 557 143
16 1.0 1.8 20.0 744 160
25 1.2 1.8 23.4 1,066 187
35 1.2 1.8 25.6 1,342 205
50 1.4 1.8 29.1 1,735 233
70 1.4 1.9 33.3 2,331 266
95 1.6 2.1 38.1 3,159 305
120 1.6 2.2 42.4 3,829 339
150 1.8 2.4 46.2 4,667 370
185 2.0 2.5 50.8 5,805 406
240 2.2 2.7 57.9 7,482 463
300 2.4 2.9 64.3 9,253 514

ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

3 CORE NYY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 12.7 237 102


2. 5 0.8 1.8 13.7 295 110
4 1.0 1.8 15.7 406 126
6 1.0 1.8 16.9 495 135
10 1.0 1.8 18.9 669 151
16 1.0 1.8 21.1 912 169
25 1.2 1.8 24.8 1,325 198
35 1.2 1.8 27.2 1,688 218
50 1.4 1.8 26.0 1,829 208
70 1.4 1.8 28.9 2,527 231
95 1.6 1.9 33.5 3,404 268
120 1.6 2.0 36.3 4,155 290
150 1.8 2.2 39.8 5,119 318
185 2.0 2.3 44.7 6,324 358
240 2.2 2.5 49.8 8,224 398
300 2.4 2.6 55.3 1,0304 442

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 13.6 272 109


2. 5 0.8 1.8 14.7 343 118
4 1.0 1.8 16.9 477 135
6 1.0 1.8 18.2 589 146
10 1.0 1.8 20.4 807 163
16 1.0 1.8 22.9 1,113 183
25 1.2 1.8 27.0 1,630 216
35 1.2 1.8 29.8 2,092 238
50 1.4 1.8 29.7 2,491 238
70 1.4 2.0 34.1 3,381 273
95 1.6 2.1 38.1 4,534 305
120 1.6 2.2 42.6 5,596 341
150 1.8 2.4 46.8 6,877 374
185 2.0 2.5 51.8 8,462 414
240 2.2 2.8 59.5 1,0999 476
300 2.4 3.0 66.1 1,3616 529

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

5 CORE NYY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal Thi ckness Net Weight
Diam eter Bending
Size Radius
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

1.5 0.8 1.8 14.5 317 145

2.5 0.8 1.8 15.7 401 157

4 1.0 1.8 18.2 568 182

6 1.0 1.8 19.7 701 197

10 1.0 1.8 22.1 974 221

16 1.0 1.8 25.0 1,343 250

25 1.2 1.8 29.6 1,992 296

35 1.2 1.9 33.2 2,569 332

50 1.4 2.1 38.3 3,421 383

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17

2.5 7.41 8.866 25 34 0.304 0.29

4 4.61 5.516 34 44 0.303 0.46

6 3.08 3.685 43 56 0.288 0.69

10 1.83 2.190 60 75 0.269 1.15

16 1.15 1.376 80 98 0.255 1.84

25 0.727 0.870 106 128 0.255 2.88

35 0.524 0.627 131 157 0.246 4.03

50 0.387 0.464 159 185 0.247 5.75

www.extranacable.com
®
EXTRANA
CABLE

1 CORE N2XY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight Bending
Size Dia m eter
Radius
In s ulation Sheath Approximate
mm² mm mm mm kg/km mm
1. 5 0.7 1.4 6.0 48 48
2. 5 0.7 1.4 6.5 62 52
4 0.7 1.4 7.4 81 59
6 0.7 1.4 8.0 104 64
10 0.7 1.4 9.4 150 75
16 0.7 1.4 9.9 213 79
25 0.9 1.4 1 1.6 318 93
35 0.9 1.4 12.7 419 102
50 1.0 1.4 14.3 546 114
70 1.1 1.4 16.0 766 128
95 1.1 1.6 18.5 1,033 148
120 1.2 1.6 20.0 1,287 160
150 1.4 1.6 22.2 1,575 178
185 1.6 1.8 24.6 1,965 197
240 1.7 1.8 27.7 2,552 222
300 1.8 1.8 30.7 3,071 246
400 2.0 2.0 34.2 4,028 274
500 2.2 2.1 38.1 5,051 305
630 2.4 2.2 42.4 6,478 339

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 3 0ºC
M ax. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 2 0ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA


1.5 12.1 14.478 39 35 54 43 0.498 0.21
2.5 7.41 8.866 48 43 73 58 0.463 0.36
4 4.61 5.516 63 57 95 76 0.433 0.57
6 3.08 3.685 80 72 119 95 0.410 0.86
10 1.83 2.190 108 98 161 128 0.382 1.43
16 1.15 1.376 146 132 212 169 0.361 2.29
25 0.727 0.870 207 187 276 220 0.348 3.58
35 0.524 0.627 240 217 333 265 0.335 5.01
50 0.387 0.464 291 263 397 316 0.325 7.15
70 0.268 0.321 366 331 483 385 0.316 10.01
95 0.193 0.232 451 408 584 465 0.310 13.59
120 0.153 0.184 524 474 667 531 0.305 17.16
150 0.124 0.150 608 550 750 597 0.305 21.45
185 0.0991 0.121 700 633 854 680 0.304 26.46
240 0.0754 0.093 830 750 992 790 0.300 34.32
300 0.0601 0.075 963 871 1 131 901 0.295 42.90
400 0.0470 0.061 1 127 1019 1296 1032 0.295 57.20
500 0.0366 0.049 1314 1 188 1482 1 180 0.292 71.50
630 0.0283 0.041 1492 1349 1595 1270 0.289 90.09

www.extranacable.com
®
EXTRANA
CABLE

N2XY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insulated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximat e

mm² mm mm mm kg/km mm

1. 5 0.7 1.8 1 1.5 187 92


2. 5 0.7 1.8 12.5 236 100
4 0.7 1.8 13.5 293 108
6 0.7 1.8 14.7 362 118
10 0.7 1.8 16.4 495 131
16 0.7 1.8 18.5 674 148
25 0.9 1.8 21.8 982 174
35 0.9 1.8 24.1 1,258 193
50 1.0 1.8 27.1 1,610 217
70 1.1 1.8 31.2 2,265 250
95 1.1 2.0 35.5 2,986 284
120 1.2 2.1 39.3 3,692 314
150 1.4 2.2 43.4 4,564 347
185 1.6 2.3 48.2 5,220 386
240 1.7 2.5 54.4 6,729 435
300 1.8 2.7 59.9 8,342 479

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 27 33 0.315 0.21
2.5 7.41 8.866 36 44 0.293 0.36
4 4.61 5.516 48 58 0.275 0.57
6 3.08 3.685 61 72 0.263 0.86
10 1.83 2.190 83 97 0.248 1.43
16 1.15 1.376 113 128 0.238 2.29
25 0.727 0.870 150 167 0.240 3.58
35 0.524 0.627 186 201 0.233 5.01
50 0.387 0.464 226 239 0.232 7.15
70 0.268 0.321 290 295 0.229 10.01
95 0.193 0.232 353 355 0.224 13.59
120 0.153 0.184 413 404 0.223 17.16
150 0.124 0.150 468 458 0.224 21.45
185 0.0991 0.121 540 516 0.225 26.46
240 0.0754 0.093 590 600 0.223 34.32
300 0.0601 0.075 745 695 0.221 42.90

www.extranacable.com
®
EXTRANA
CABLE

3 CORE N2XY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insul ated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.7 1.8 12.0 207 96


2. 5 0.7 1.8 13.0 266 104
4 0.7 1.8 14.1 339 113
6 0.7 1.8 15.4 426 123
10 0.7 1.8 17.3 597 138
16 0.7 1.8 19.5 829 156
25 0.9 1.8 23.1 1,224 185
35 0.9 1.8 25.5 1,586 204
50 1.0 1.8 24.4 1642 195
70 1.1 1.9 28.3 2,404 226
95 1.1 2.0 31.6 3,255 253
120 1.2 2.1 34.8 4,067 278
150 1.4 2.3 38.7 4,950 310
185 1.6 2.4 43.3 6,184 346
240 1.7 2.6 48.4 7,976 387
300 1.8 2.8 54.0 9,940 432

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21
2.5 7.41 8.866 32 38 0.293 0.36
4 4.61 5.516 41 49 0.275 0.57
6 3.08 3.685 52 60 0.263 0.86
10 1.83 2.190 71 97 0.248 1.43
16 1.15 1.376 96 108 0.238 2.29
25 0.727 0.870 130 141 0.240 3.58
35 0.524 0.627 159 170 0.233 5.01
50 0.387 0.464 193 201 0.232 7.15
70 0.268 0.321 245 249 0.229 10.01
95 0.193 0.232 302 299 0.224 13.59
120 0.153 0.184 349 340 0.223 17.16
150 0.124 0.150 400 381 0.224 21.45
185 0.0991 0.121 464 434 0.225 26.46
240 0.0754 0.093 552 506 0.223 34.32
300 0.0601 0.075 640 585 0.221 42.90

www.extranacable.com
®
EXTRANA
CABLE

4 CORE N2XY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insul ated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.7 1.8 12.7 235 102


2. 5 0.7 1.8 13.9 308 111
4 0.7 1.8 15.2 397 122
6 0.7 1.8 16.6 507 133
10 0.7 1.8 18.7 720 150
16 0.7 1.8 21.2 1,013 170
25 0.9 1.8 25.2 1,508 202
35 0.9 1.8 27.9 1,980 223
50 1.0 1.9 29.1 2,182 233
70 1.1 2.0 33.7 3,222 270
95 1.1 2.1 37.3 4,314 298
120 1.2 2.3 41.9 5,356 335
150 1.4 2.4 45.5 6,628 364
185 1.6 2.6 51.5 8,216 412
240 1.7 2.8 57.5 10,678 460
300 1.8 3.0 64.0 13,229 512

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21
2.5 7.41 8.866 32 38 0.293 0.36
4 4.61 5.516 41 49 0.275 0.57
6 3.08 3.685 52 60 0.263 0.86
10 1.83 2.190 71 97 0.248 1.43
16 1.15 1.376 96 108 0.238 2.29
25 0.727 0.870 130 141 0.240 3.58
35 0.524 0.627 159 170 0.233 5.01
50 0.387 0.464 193 201 0.232 7.15
70 0.268 0.321 245 249 0.229 10.01
95 0.193 0.232 302 299 0.224 13.59
120 0.153 0.184 349 340 0.223 17.16
150 0.124 0.150 400 381 0.224 21.45
185 0.0991 0.121 464 434 0.225 26.46
240 0.0754 0.093 552 506 0.223 34.32
300 0.0601 0.075 640 585 0.221 42.90

www.extranacable.com
®
EXTRANA
CABLE

5 CORE N2XY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insul ated, PVC Sheathed)

Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.7 1. 8 14.0 274 112

2. 5 0.7 1. 8 15.2 355 122

4 0.7 1. 8 16.6 467 133

6 0.7 1. 8 18.1 598 145

10 0.7 1. 8 20.5 863 164

16 0.7 1. 8 23.4 1,226 187

25 0.9 1. 8 27.9 1,843 223

35 0.9 1. 8 30.9 2,475 247

50 1.0 2. 0 35.9 3,224 287

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21

2.5 7.41 8.866 32 38 0.293 0.36

4 4.61 5.516 41 49 0.275 0.57

6 3.08 3.685 52 60 0.263 0.86

10 1.83 2.190 71 97 0.248 1.43

16 1.15 1.376 96 108 0.238 2.29

25 0.727 0.870 130 141 0.240 3.58

35 0.524 0.627 159 170 0.233 5.01

50 0.387 0.464 193 201 0.232 7.15

www.extranacable.com
®
EXTRANA
CABLE

2 CORE N2XCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Coppe r Conducto r, XLPE Insulated, Copper Wire Screen,
PVC Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size
Radius
Insulation Sheath Approxim ate

mm² mm mm mm kg/km mm

1.5/1 . 5 0.7 1,8 13,4 263 107


2.5/2 . 5 0.7 1,8 14,3 309 114
4/4 0.7 1,8 15,3 360 122
6/6 0.7 1,8 16,4 423 131
10/ 10 0.7 1,8 18,5 545 148
16/16 0.7 1,8 20,4 690 163
25/16 0.9 1,8 23,9 959 191
35/16 0.9 1,8 25,6 1.30 3 205
50/25 1.0 1,9 29,2 1.68 7 234
70/35 1.1 2,0 33,7 2.311 270
95/50 1.1 2,2 37,9 3.06 0 303
120/70 1.2 2,3 41,7 3.75 0 334
150/70 1.4 2,4 46,2 4.59 6 370
185/95 1.6 2,6 51,0 5.59 9 408
240/12 0 1.7 2,8 57,5 7.25 4 460
300/15 0 1.8 3,0 63,3 8.95 3 506

ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 27 33 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 36 44 0.29 3 0.36
4/4 4.61 5.51 6 48 58 0.27 5 0.57
6/6 3.08 3.685 61 72 0.26 3 0.86
10/ 10 1.83 2.19 0 83 97 0.24 8 1.43
16/16 1.15 1.376 113 128 0.23 8 2.29
25/16 0.72 7 0.87 0 150 167 0.24 0 3.58
35/16 0.52 4 0.62 7 186 201 0.23 3 5.01
50/25 0.38 7 0.464 226 239 0.23 2 7.15
70/35 0.26 8 0.321 290 295 0.22 9 10.0 1
95/50 0.19 3 0.232 353 355 0.22 4 13.5 9
120/70 0.15 3 0.18 4 413 404 0.22 3 17.1 6
150/70 0.12 4 0.15 0 468 458 0.22 4 21.4 5
185/95 0.09 91 0.121 540 516 0.22 5 26.4 6
240/12 0 0.07 54 0.093 590 600 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 745 695 0.22 1 42.9 0

www.extranacable.com
®
EXTRANA
CABLE

N2XCY 0.6/1 kV
3 CORE SNI IEC 60502-1; SNI 0255
(Copper Conducto r, XLPE Insulated, Copper Wire Screen,
PVC Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate

mm² mm mm mm kg/km mm

1.5/1 . 5 0.7 1,8 13,5 285 108


2.5/2 . 5 0.7 1,8 14,4 343 115
4/4 0.7 1,8 15,6 425 125
6/6 0.7 1,8 17,2 539 138
10/ 10 0.7 1,8 19,3 735 154
16/16 0.7 1,8 21,7 994 174
25/16 0.9 1,8 25,9 1.45 9 207
35/16 0.9 1,9 28,8 1.88 7 230
50/25 1.0 2,0 32,3 2.44 4 258
70/35 1.1 2,2 38,0 3.40 6 304
95/50 1.1 2,3 42,3 4.48 1 338
120/70 1.2 2,5 47,0 5.63 3 376
150/70 1.4 2,6 52,1 6.86 3 417
185/95 1.6 2,8 57,1 8.37 1 457
240/12 0 1.7 3,1 65,2 10.9 35 522
300/15 0 1.8 3,1 67,7 1 1.970 542

ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Carryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 23 29 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 32 38 0.29 3 0.36
4/4 4.61 5.51 6 41 49 0.27 5 0.57
6/6 3.08 3.685 52 60 0.26 3 0.86
10/ 10 1.83 2.19 0 71 97 0.24 8 1.43
16/16 1.15 1.376 96 108 0.23 8 2.29
25/16 0.72 7 0.87 0 130 141 0.24 0 3.58
35/16 0.52 4 0.62 7 159 170 0.23 3 5.01
50/25 0.38 7 0.464 193 201 0.23 2 7.15
70/35 0.26 8 0.321 245 249 0.22 9 10.0 1
95/50 0.19 3 0.232 302 299 0.22 4 13.5 9
120/70 0.15 3 0.18 4 349 340 0.22 3 17.1 6
150/70 0.12 4 0.15 0 400 381 0.22 4 21.4 5
185/95 0.09 91 0.121 464 434 0.22 5 26.4 6
240/12 0 0.07 54 0.093 552 506 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 640 585 0.22 1 42.9 0

www.extranacable.com
®
EXTRANA
CABLE

4 CORE N2XCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Coppe r Conducto r, XLPE Insulated, Co pper Wire Screen,
PVC Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate

mm² mm mm mm kg/km mm

1.5/1 . 5 0.7 1,8 14,3 320 114


2.5/2 . 5 0.7 1,8 15,3 390 122
4/4 0.7 1,8 16,6 489 133
6/6 0.7 1,8 17,9 612 143
10/ 10 0.7 1,8 20,7 790 166
16/16 0.7 1,8 23,1 1.04 8 185
25/16 0.9 1,8 27,3 1.52 1 218
35/16 0.9 1,9 30,0 2.09 1 240
50/25 1.0 2,1 34,5 2.74 9 276
70/35 1.1 2,2 39,4 3.75 2 315
95/50 1.1 2,4 44,7 5.03 3 358
120/70 1.2 2,6 49,6 6.29 0 397
150/70 1.4 2,7 54,5 7.65 0 436
185/95 1.6 2,9 60,5 9.42 8 484
240/12 0 1.7 3,2 68,0 12.2 23 544
300/15 0 1.8 3,4 75,4 15.2 60 603

ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Carryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 23 29 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 32 38 0.29 3 0.36
4/4 4.61 5.51 6 41 49 0.27 5 0.57
6/6 3.08 3.685 52 60 0.26 3 0.86
10/ 10 1.83 2.19 0 71 97 0.24 8 1.43
16/16 1.15 1.376 96 108 0.23 8 2.29
25/16 0.72 7 0.87 0 130 141 0.24 0 3.58
35/16 0.52 4 0.62 7 159 170 0.23 3 5.01
50/25 0.38 7 0.464 193 201 0.23 2 7.15
70/35 0.26 8 0.321 245 249 0.22 9 10.0 1
95/50 0.19 3 0.232 302 299 0.22 4 13.5 9
120/70 0.15 3 0.18 4 349 340 0.22 3 17.1 6
150/70 0.12 4 0.15 0 400 381 0.22 4 21.4 5
185/95 0.09 91 0.121 464 434 0.22 5 26.4 6
240/12 0 0.0754 0.093 552 506 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 640 585 0.22 1 42.9 0

www.extranacable.com
®
EXTRANA
CABLE

5 CORE N2XCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conducto r, XLPE Insulated, Co pper Wire Screen,
PV C Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DA TA
O ver all
Nominal Thickness Net W eig ht
Diameter Bending
Size Radius
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

1.5/1 . 5 0.7 1,8 15,2 358 122

2.5/2 . 5 0.7 1,8 16,3 440 130

4/4 0.7 1,8 17,7 556 142

6/6 0.7 1,8 19,2 703 154

10/ 10 0.7 1,8 22,3 926 178

16/16 0.7 1,8 24,9 1.23 9 199

25/16 0.9 1,9 29,3 1.92 0 234

35/16 0.9 2,0 33,3 2.54 7 266

50/25 1.0 2,2 37,8 3.29 4 302

ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.478 23 29 0.31 5 0.21

2.5/2. 5 7.41 8.86 6 32 38 0.29 3 0.36

4/4 4.61 5.51 6 41 49 0.27 5 0.57

6/6 3.08 3.685 52 60 0.26 3 0.86

10/ 10 1.83 2.190 71 97 0.24 8 1.43

16/16 1.15 1.37 6 96 108 0.23 8 2.29

25/16 0.72 7 0.87 0 130 141 0.24 0 3.58

35/16 0.52 4 0.627 159 170 0.23 3 5.01

50/25 0.38 7 0.46 4 193 201 0.23 2 7.15

www.extranacable.com
®
EXTRANA
CABLE

1 CORE NYSY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper Tape Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Over all
Nominal Thi ckness Net Weight Bending
Size Dia m eter
Radius
Insulation Sheath Approximat e
mm² mm mm mm kg/km mm
1. 5 0.8 1.8 9.45 168 76
2. 5 0.8 1.8 9.85 188 79
4 1.0 1.8 10.75 230 86
6 1.0 1.8 1 1.35 265 91
10 1.0 1.8 12.25 328 98
16 1.0 1.8 13.35 416 107
25 1.2 1.8 14.95 549 120
35 1.2 1.8 16.05 673 128
50 1.4 1.8 17.95 847 144
70 1.4 1.8 19.65 1,078 157
95 1.6 1.8 21.85 1,383 175
120 1.6 1.8 23.45 1,655 188
150 1.8 1.8 25.45 1,992 204
185 2.0 1.8 27.45 2,360 220
240 2.2 1.9 30.85 3,025 247
300 2.4 2.1 34.35 3,785 275
400 2.6 2.2 37.65 4,639 301
500 2.6 2.3 41.65 5,893 333
630 2.6 2.4 46.15 7,439 369

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 3 0ºC
M ax. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 2 0ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA


1.5 12.1 14.478 26 26 40 30 0.505 0.17
2.5 7.41 8.866 35 34 41 30 0.470 0.29
4 4.61 5.516 46 45 42 31 0.450 0.46
6 3.08 3.685 58 57 43 32 0.426 0.69
10 1.83 2.190 79 77 44 33 0.396 1.15
16 1.15 1.376 105 103 160 119 0.374 1.84
25 0.727 0.870 140 137 206 153 0.358 2.88
35 0.524 0.627 174 169 249 183 0.345 4.03
50 0.387 0.464 212 206 296 216 0.336 5.75
70 0.268 0.321 269 261 365 265 0.326 8.05
95 0.193 0.232 331 321 438 316 0.321 10.93
120 0.153 0.184 386 374 499 359 0.316 13.80
150 0.124 0.150 442 428 561 402 0.313 17.25
185 0.0991 0.121 511 494 637 454 0.310 21.28
240 0.0754 0.093 612 590 743 527 0.307 27.60
300 0.0601 0.075 707 678 843 544 0.305 34.50
400 0.0470 0.061 859 817 986 686 0.302 46.02
500 0.0366 0.049 1000 940 1 125 774 0.299 57.53
630 0.0283 0.041 1 124 1060 1 198 846 0.293 72.52

www.extranacable.com
®
EXTRANA
CABLE

NYSY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper Tape Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter. Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 12.75 284 102


2. 5 0.8 1.8 13.65 327 109
4 1.0 1.8 15.45 414 124
6 1.0 1.8 16.65 487 133
10 1.0 1.8 18.45 615 148
16 1.0 1.8 20.55 792 164
25 1.2 1.8 23.85 1,068 191
35 1.2 1.8 26.15 1,321 209
50 1.4 1.9 30.05 1,691 240
70 1.4 2.0 34.05 2,224 272
95 1.6 2.2 38.85 2,896 311
120 1.6 2.3 42.25 3,483 338
150 1.8 2.5 47.05 4,291 376
185 2.0 2.6 51.25 5,090 410
240 2.2 2.8 58.05 6,540 464
300 2.4 3.0 64.25 8,068 514

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

3 CORE NYSY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper Tape Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 13.25 321 106


2. 5 0.8 1.8 14.15 375 113
4 1.0 1.8 16.25 490 130
6 1.0 1.8 17.45 585 140
10 1.0 1.8 19.45 760 156
16 1.0 1.8 21.75 1,005 174
25 1.2 1.8 25.25 1,382 202
35 1.2 1.8 27.75 1,739 222
50 1.4 2.0 32.55 2,308 260
70 1.4 2.1 36.45 3,007 292
95 1.6 2.3 41.55 3,949 332
120 1.6 2.4 45.65 4,840 365
150 1.8 2.6 50.35 5,903 403
185 2.0 2.7 55.35 7,109 443
240 2.2 3.0 62.35 9,1 18 499
300 2.4 3.2 69.05 11,306 552

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYSY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper Tape Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 14.15 368 113


2. 5 0.8 1.8 15.15 435 121
4 1.0 1.8 17.45 577 140
6 1.0 1.8 18.75 696 150
10 1.0 1.8 20.95 918 168
16 1.0 1.8 23.55 1,233 188
25 1.2 1.8 27.45 1,718 220
35 1.2 1.9 30.45 2,198 244
50 1.4 2.1 35.75 2,920 286
70 1.4 2.2 40.05 3,829 320
95 1.6 2.4 46.15 5,107 369
120 1.6 2.6 50.45 6,230 404
150 1.8 2.8 56.05 7,680 448
185 2.0 2.9 61.15 9,174 489
240 2.2 3.2 68.95 11,794 552
300 2.4 3.4 76.75 14,746 614

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

1 CORE NYCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper W ire Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net Weight Bending
Size Diamete r
Radius
In s ulation Sheath App roximate
mm² mm mm mm kg/km mm
1. 5/1.5 0.8 1.8 9.55 167 76
2. 5/2.5 0.8 1.8 9.95 195 80
4/4 1.0 1.8 10.85 248 87
6/6 1.0 1.8 1 1.45 300 92
10 /10 1.0 1.8 12.35 396 99
16/16 1.0 1.8 13.45 535 108
25/16 1.2 1.8 15.05 664 120
35/16 1.2 1.8 16.15 784 129
50/25 1.4 1.8 18.05 953 144
70/35 1.4 1.8 19.75 1,262 158
95/50 1.6 1.8 21.95 1,651 176
120/7 0 1.6 1.8 23.55 2,056 188
150/7 0 1.8 1.8 25.55 2,567 204
185/9 5 2.0 1.8 27.55 2,929 220
240/1 20 2.2 1.9 30.95 4,055 248
300/1 50 2.4 2.1 34.45 5,063 276
400/1 20 2.6 2.2 37.75 6,226 302
500/2 40 2.6 2.3 41.75 7,968 334
630/3 00 2.6 2.4 46.25 10,045 370

ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA


1.5/1.5 12.1 14.478 26 26 40 30 0.505 0.17
2.5/2.5 7.41 8.866 35 34 41 30 0.470 0.29
4/4 4.61 5.516 46 45 42 31 0.450 0.46
6/6 3.08 3.685 58 57 43 32 0.426 0.69
10/10 1.83 2.190 79 77 44 33 0.396 1.15
16/16 1.15 1.376 105 103 160 119 0.374 1.84
25/16 0.727 0.870 140 137 206 153 0.358 2.88
35/16 0.524 0.627 174 169 249 183 0.345 4.03
50/25 0.387 0.464 212 206 296 216 0.336 5.75
70/35 0.268 0.321 269 261 365 265 0.326 8.05
95/50 0.193 0.232 331 321 438 316 0.321 10.93
120/70 0.153 0.184 386 374 499 359 0.316 13.80
150/70 0.124 0.150 442 428 561 402 0.313 17.25
185/95 0.0991 0.121 511 494 637 454 0.310 21.28
240/120 0.0754 0.093 612 590 743 527 0.307 27.60
300/150 0.0601 0.075 707 678 843 544 0.305 34.50
400/120 0.0470 0.061 859 817 986 686 0.302 46.02
500/240 0.0366 0.049 1000 940 1 125 774 0.299 57.53
630/300 0.0283 0.041 1 124 1060 1 198 846 0.293 72.52

www.extranacable.com
®
EXTRANA
CABLE

2 CORE NYCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper W ire Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net W eight
Diamete r Bending
Size Radius
Ins ulation Sheath App roximate

mm² mm mm mm kg/km mm

1. 5/1.5 0.8 1.8 12.9 262 103


2. 5/2.5 0.8 1.8 13.8 312 110
4/4 1.0 1.8 15.6 403 125
6/6 1.0 1.8 16.7 486 134
10 /10 1.0 1.8 18.6 646 149
16/16 1.0 1.8 20.6 861 165
25/16 1.2 1.8 24.0 1,132 192
35/16 1.2 1.8 26.3 1,372 210
50/25 1.4 1.9 29.9 1,773 239
70/35 1.4 2.0 34.0 2,392 272
95/50 1.6 2.2 39.0 3,204 312
120/7 0 1.6 2.3 42.4 3,972 339
150/7 0 1.8 2.5 47.1 4,738 377
185/9 5 2.0 2.6 51.7 5,816 414
240/120 2.2 2.9 58.8 7,550 470
300/150 2.4 3.1 65.0 9,333 520

ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 20 31 0.328 0.17
2.5/2.5 7.41 8.866 27 41 0.304 0.29
4/4 4.61 5.516 37 54 0.303 0.46
6/6 3.08 3.685 48 68 0.288 0.69
10/10 1.83 2.190 66 92 0.269 1.15
16/16 1.15 1.376 89 121 0.255 1.84
25/16 0.727 0.870 118 153 0.255 2.88
35/16 0.524 0.627 145 187 0.246 4.03
50/25 0.387 0.464 176 222 0.247 5.75
70/35 0.268 0.321 224 272 0.238 8.05
95/50 0.193 0.232 271 328 0.233 10.93
120/70 0.153 0.184 314 375 0.233 13.80
150/70 0.124 0.150 361 419 0.233 17.25
185/95 0.0991 0.121 412 475 0.233 21.28
240/120 0.0754 0.093 484 550 0.232 27.60
300/150 0.0601 0.075 590 525 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

3 CORE NYCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper W ire Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Ov erall
Nominal Thicknes s Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximat e

mm² mm mm mm kg/km mm

1.5/1.5 0.8 1.8 13.4 337 107


2.5/2.5 0.8 1.8 14.4 410 115
4/4 1.0 1.8 16.4 555 131
6/6 1.0 1.8 17.6 682 141
10 /10 1.0 1.8 19.5 922 156
16/16 1.0 1.8 21.8 1,254 174
25/16 1.2 1.8 25.4 1,730 203
35/16 1.2 1.8 27.8 2,147 222
50/25 1.4 2.0 32.4 2,871 259
70/35 1.4 2.1 36.4 3,825 291
95/50 1.6 2.3 41.7 5,159 334
120/70 1.6 2.4 45.8 6,438 366
150/70 1.8 2.6 50.4 7,715 403
185/95 2.0 2.8 55.9 9,583 447
240/1 20 2.2 3.0 62.9 12,359 503
300/1 50 2.4 3.2 69.6 15,359 557

ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 19 26 0.328 0.17
2.5/2.5 7.41 8.866 25 34 0.304 0.29
4/4 4.61 5.516 34 44 0.303 0.46
6/6 3.08 3.685 43 56 0.288 0.69
10/10 1.83 2.190 60 75 0.269 1.15
16/16 1.15 1.376 80 98 0.255 1.84
25/16 0.727 0.870 106 128 0.255 2.88
35/16 0.524 0.627 131 157 0.246 4.03
50/25 0.387 0.464 159 185 0.247 5.75
70/35 0.268 0.321 202 228 0.238 8.05
95/50 0.193 0.232 244 275 0.233 10.93
120/70 0.153 0.184 282 313 0.233 13.80
150/70 0.124 0.150 324 353 0.233 17.25
185/95 0.0991 0.121 371 399 0.233 21.28
240/120 0.0754 0.093 436 464 0.232 27.60
300/150 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper W ire Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net Weight
Diamete r Bending
Size Radius
Ins ulation Sheath App roximate

mm² mm mm mm kg/km mm

1. 5/1.5 0.8 1.8 14.3 433 114


2. 5/2.5 0.8 1.8 15.3 533 122
4/4 1.0 1.8 17.5 741 140
6/6 1.0 1.8 18.9 921 151
10 /10 1.0 1.8 21.1 1,261 169
16/16 1.0 1.8 23.6 1,725 189
25/16 1.2 1.8 27.7 2,448 222
35/16 1.2 1.9 30.6 3,091 245
50/25 1.4 2.1 35.5 4,134 284
70/35 1.4 2.2 40 5,524 320
95/50 1.6 2.4 46.3 7,530 370
120/7 0 1.6 2.6 50.6 9,320 405
150/7 0 1.8 2.8 56.1 11,328 449
185/9 5 2.0 2.9 61.5 13,920 492
240/1 20 2.2 3.2 69.5 18,067 556
300/1 50 2.4 3.5 77.6 22,634 621

ELECTRICAL DATA
M ax . Conductor Resistance Ma x. Current Carr yi n g Capacit y at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 7 0 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 19 26 0.328 0.17
2.5/2.5 7.41 8.866 25 34 0.304 0.29
4/4 4.61 5.516 34 44 0.303 0.46
6/6 3.08 3.685 43 56 0.288 0.69
10/10 1.83 2.190 60 75 0.269 1.15
16/16 1.15 1.376 80 98 0.255 1.84
25/16 0.727 0.870 106 128 0.255 2.88
35/16 0.524 0.627 131 157 0.246 4.03
50/25 0.387 0.464 159 185 0.247 5.75
70/35 0.268 0.321 202 228 0.238 8.05
95/50 0.193 0.232 244 275 0.233 10.93
120/70 0.153 0.184 282 313 0.233 13.80
150/70 0.124 0.150 324 353 0.233 17.25
185/95 0.0991 0.121 371 399 0.233 21.28
240/120 0.0754 0.093 436 464 0.232 27.60
300/150 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

5 CORE NYCY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper W ire Screen, PVC Sheathed)

For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.

CONSTRUCTION DATA
Ov erall
Nominal Thicknes s Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximat e

mm² mm mm mm kg/km mm

1.5/1.5 0.8 1.8 15.2 546 122

2.5/2.5 0.8 1.8 16.4 679 131

4/4 1.0 1.8 18.9 965 151

6/6 1.0 1.8 20.4 1,203 163

10 /1 0 1.0 1.8 22.8 1,656 182

16/16 1.0 1.8 25.6 2,275 205

25/16 1.2 1.9 30.4 3,302 243

35/16 1.2 2.0 34.0 4,227 272

50/25 1.4 2.2 39.1 5,611 313

ELECTRICAL DATA
M ax . Conductor Resistance Max. Current Carr yi n g Capacit y at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC A C at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1. 5/1.5 12.1 14.478 19 26 0.328 0.17

2. 5/2.5 7.41 8.866 25 34 0.304 0.29

4/4 4.61 5.516 34 44 0.303 0.46

6/6 3.08 3.685 43 56 0.288 0.69

10 /10 1.83 2.190 60 75 0.269 1.15

16/16 1.15 1.376 80 98 0.255 1.84

25/16 0.727 0.870 106 128 0.255 2.88

35/16 0.524 0.627 131 157 0.246 4.03

50/25 0.387 0.464 159 185 0.247 5.75

www.extranacable.com
®
EXTRANA
CABLE

2 CORE NYFGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Galvanized
Steel Flat Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 15.2 490 273


2. 5 0.8 1.8 16.1 558 289
4 1.0 1.8 17.9 667 322
6 1.0 1.8 19.0 761 341
10 1.0 1.8 20.9 915 376
16 1.0 1.8 22.9 1,132 412
25 1.2 1.8 26.3 1,464 473
35 1.2 1.9 28.8 1,777 518
50 1.4 2 32.4 2,159 583
70 1.4 2.1 36.5 2,774 656
95 1.6 2.3 41.5 3,539 746
120 1.6 2.4 44.9 4,186 808
150 1.8 2.5 49.4 5,010 889
185 2.0 2.7 54.2 5,974 975
240 2.2 2.9 61.1 7,584 1,099
300 2.4 3.1 67.3 9,204 1,21 1

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0º C AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

3 CORE
NYFGbY 0.6/1 kV
SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Galvanized
Steel Flat Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical
protection is required or where high-pulling stresses ma y occur during installation or operation.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm Mm mm kg/km mm

1. 5 0.8 1.8 15.7 526 282


2. 5 0.8 1.8 16.7 607 300
4 1.0 1.8 18.7 768 336
6 1.0 1.8 19.9 859 358
10 1.0 1.8 21.8 1,081 392
16 1.0 1.8 24.1 1,340 433
25 1.2 1.8 27.7 1,803 498
35 1.2 1.9 30.3 2,216 545
50 1.4 2.1 34.9 2,807 628
70 1.4 2.2 38.9 3,569 700
95 1.6 2.4 44.2 4,636 795
120 1.6 2.5 48.3 5,615 869
150 1.8 2.7 52.9 6,713 952
185 2.0 2.8 58.2 8,078 1,047
240 2.2 3.1 65.4 1,0274 1,177
300 2.4 3.3 72.1 1,2554 1,297

ELECTRICAL DATA
Max . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYFGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Galvanized
Steel Flat Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximate

mm² mm Mm mm kg/km mm

1.5 0.8 1.8 16.6 598 298


2.5 0.8 1.8 17.6 690 316
4 1.0 1.8 19.8 850 356
6 1.0 1.8 21.2 993 381
10 1.0 1.8 23.4 1,265 421
16 1.0 1.8 25.9 1,614 466
25 1.2 1.9 30.2 2,206 543
35 1.2 2 33.1 2,725 595
50 1.4 2 34.1 3,507 613
70 1.4 2.2 38.7 4,576 696
95 1.6 2.3 42.5 5,826 764
120 1.6 2.5 47.6 7,241 856
150 1.8 2.6 51.0 8,473 917
185 2.0 2.8 57.4 10,637 1,033
240 2.2 3 63.4 13,273 1,141
300 2.4 3.2 70.0 15,935 1,259

ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

5 CORE NYFGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Galvanized
Steel Flat Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 16.9 620 304

2. 5 0.8 1.8 18.0 725 323

4 1.0 1.8 20.3 923 365

6 1.0 1.8 21.6 1077 388

10 1.0 1.8 23.7 1348 426

16 1.0 1.8 17.5 670 314

25 1.2 1.8 18.7 777 336

35 1.2 1.8 21.2 965 381

50 1.4 1.8 22.7 1,132 408

ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17

2.5 7.41 8.866 25 34 0.304 0.29

4 4.61 5.516 34 44 0.303 0.46

6 3.08 3.685 43 56 0.288 0.69

10 1.83 2.190 60 75 0.269 1.15

16 1.15 1.376 80 98 0.255 1.84

25 0.727 0.870 106 128 0.255 2.88

35 0.524 0.627 131 157 0.246 4.03

50 0.387 0.464 159 185 0.247 5.75

www.extranacable.com
®
EXTRANA
CABLE

1 CORE NYR(Al)Y 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Coppe r Conductor, PVC Insulated, Aluminium
Round W ire Armoured, PVC Sh ea thed)

For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders and
street lighting.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht Bending
Size Di ameter
Radius
Ins ulation Sheath App roxim ate
mm² mm mm mm kg/km mm

25 1.2 1.8 17.6 601 316

35 1.2 1.8 18.7 726 336

50 1.4 1.8 20.5 885 368

70 1.4 1.8 22.7 1,15 9 408

95 1.6 1.8 25.0 1,48 4 449

12 0 1.6 1.8 26.6 1,76 8 478

15 0 1.8 1.9 28.8 2,1 15 518

18 5 2.0 1.9 30.9 2,52 0 555

24 0 2.2 2.1 35.4 3,33 3 636

30 0 2.4 2.2 38.9 4,12 0 699

40 0 2.6 2.3 42.4 5,05 5 762

50 0 2.8 2.5 47.9 6,56 7 861

63 0 2.8 2.6 52.0 7,96 6 935

ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C
Ma x . Sh ort circuit
Size in air in ground Induct anc e
curr en t at 1 sec.
DC at 20ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA

25 0.72 7 0.87 0 140 137 206 153 0.35 8 2.88

35 0.52 4 0.62 7 174 169 249 183 0.34 5 4.03

50 0.38 7 0.46 4 212 206 296 216 0.33 6 5.75

70 0.26 8 0.32 1 269 261 365 265 0.32 6 8.05

95 0.19 3 0.23 2 331 321 438 316 0.32 1 10.9 3

120 0.15 3 0.18 4 386 374 499 359 0.31 6 13.8 0

150 0.12 4 0.15 0 442 428 561 402 0.31 3 17.2 5

185 0.09 91 0.12 1 511 494 637 454 0.31 0 21.2 8

240 0.07 54 0.09 3 612 590 743 527 0.30 7 27.6 0

300 0.06 01 0.07 5 707 678 843 544 0.30 5 34.5 0

400 0.04 70 0.06 1 859 817 986 686 0.30 2 46.0 2


0.03 66
500 0.04 9 1000 940 1 125 774 0.29 9 57.5 3

630 0.0283 0.04 1 1 124 1060 1 198 846 0.29 3 72.5 2

www.extranacable.com
®
EXTRANA
CABLE

NYRY/NYRGbY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conducto r, PVC Insulated, Galvanized
Stee l Round Wire Armoured with or without Steel Tape
,
PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 14.4 367 258


2. 5 0.8 1.8 15.3 417 275
4 1.0 1.8 17.8 610 320
6 1.0 1.8 18.9 689 339
10 1.0 1.8 20.8 851 374
16 1.0 1.8 23.5 1,170 422
25 1.2 1.8 26.9 1,520 483
35 1.2 1.9 29.4 1,828 528
50 1.4 2.0 34.0 2,468 611
70 1.4 2.2 38.3 3,147 689
95 1.6 2.3 43.1 3,932 775
12 0 1.6 2.5 47.7 5,030 858
15 0 1.8 2.6 52.2 5,943 939
18 5 2.0 2.8 57.0 6,997 1,025
24 0 2.2 3.0 63.9 8,708 1,149
30 0 2.4 3.2 70.1 10,461 1,261

ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Size Induct anc e
c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.32 8 0.17
2.5 7.41 8.86 6 27 41 0.30 4 0.29
4 4.61 5.51 6 37 54 0.30 3 0.46
6 3.08 3.68 5 48 68 0.28 8 0.69
10 1.83 2.19 0 66 92 0.26 9 1.15
16 1.15 1.37 6 89 121 0.25 5 1.84
25 0.72 7 0.87 0 118 153 0.25 5 2.88
35 0.52 4 0.62 7 145 187 0.24 6 4.03
50 0.38 7 0.46 4 176 222 0.24 7 5.75
70 0.26 8 0.32 1 224 272 0.23 8 8.05
95 0.19 3 0.23 2 271 328 0.23 3 10.9 3
120 0.15 3 0.18 4 314 375 0.23 3 13.8 0
150 0.12 4 0.15 0 361 419 0.23 3 17.2 5
185 0.09 91 0.12 1 412 475 0.23 3 21.2 8
240 0.07 54 0.09 3 484 550 0.23 2 27.6 0
300 0.06 01 0.07 5 590 525 0.23 1 34.5 0

www.extranacable.com
®
EXTRANA
CABLE

3 CORE NYRY/NYRGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conducto r, PVC Insulated, Galvanized
Stee l Round Wire Armoured with or without Steel Tape
,
PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate

mm² mm Mm mm kg/km mm

1. 5 0.8 1.8 14.9 409 267


2. 5 0.8 1.8 16.6 557 298
4 1.0 1.8 18.6 699 334
6 1.0 1.8 19.8 800 356
10 1.0 1.8 22.4 1,122 402
16 1.0 1.8 24.7 1,401 444
25 1.2 1.9 28.5 1,886 512
35 1.2 1.9 30.9 2,277 555
50 1.4 2.1 36.5 3,122 656
70 1.4 2.3 40.7 3,977 732
95 1.6 2.5 47.0 5,446 845
12 0 1.6 2.6 51.1 6,517 919
15 0 1.8 2.7 55.5 7,677 998
18 5 2.0 2.9 61.0 9,154 1,097
24 0 2.2 3.2 68.2 1 1,491 1,227
30 0 2.4 3.4 76.2 14,701 1,371

ELECTRICAL DATA
M a x. C on ductor Resistance Max. Current Carrying Cap acity at 30º C M a x . Sh ort circuit
Size Induct anc e
c urrent at 1 sec..
D C at 20ºC A C at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1. 5 12.1 14.478 19 26 0.32 8 0.17
2. 5 7.41 8.86 6 25 34 0.30 4 0.29
4 4.61 5.51 6 34 44 0.30 3 0.46
6 3.08 3.68 5 43 56 0.28 8 0.69
10 1.83 2.19 0 60 75 0.26 9 1.15
16 1.15 1.37 6 80 98 0.25 5 1.84
25 0.72 7 0.87 0 106 128 0.25 5 2.88
35 0.52 4 0.62 7 131 157 0.24 6 4.03
50 0.38 7 0.46 4 159 185 0.24 7 5.75
70 0.26 8 0.32 1 202 228 0.23 8 8.05
95 0.19 3 0.23 2 244 275 0.23 3 10.9 3
12 0 0.15 3 0.18 4 282 313 0.23 3 13.8 0
15 0 0.12 4 0.15 0 324 353 0.23 3 17.2 5
18 5 0.0991 0.12 1 371 399 0.23 3 21.2 8
24 0 0.0754 0.09 3 436 464 0.23 2 27.6 0
30 0 0.0601 0.07 5 481 524 0.23 1 34.5 0

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYRY/NYRGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conducto r, PVC Insulated, Galvanized
Stee l Round Wire Armoured with or without Steel Tape
,
PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone or operation.

CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter. Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate

mm² mm Mm mm kg/km mm

1. 5 0.8 0.8 1.8 15.8 463


2. 5 0.8 0.8 1.8 17.5 626
4 1.0 1.0 1.8 19.7 792
6 1.0 1.0 1.8 21.1 927
10 1.0 1.0 1.8 24.0 1,315
16 0.8 1.0 1.8 26.5 1,657
25 0.8 1.2 1.9 30.8 2,268
35 1.0 1.2 2.1 34.9 3,046
50 1.0 1.4 2.2 39.6 3,817
70 1.0 1.4 2.4 44.3 4,885
95 1.0 1.6 2.6 51.6 6,757
12 0 1.2 1.6 2.8 55.9 8,070
15 0 1.2 1.8 2.9 61.2 9,628
18 5 1.4 2.0 3.1 66.8 1 1,467
24 0 1.4 2.2 3.4 76.1 15,230
30 0 1.6 2.4 3.7 84.2 18,594

ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Induct anc e
Size c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.4 78 19 26 0.32 8 0.17
2.5 7.41 8.86 6 25 34 0.30 4 0.29
4 4.61 5.51 6 34 44 0.30 3 0.46
6 3.08 3.68 5 43 56 0.28 8 0.69
10 1.83 2.19 0 60 75 0.26 9 1.15
16 1.15 1.37 6 80 98 0.25 5 1.84
25 0.72 7 0.87 0 106 128 0.25 5 2.88
35 0.52 4 0.62 7 131 157 0.24 6 4.03
50 0.38 7 0.46 4 159 185 0.24 7 5.75
70 0.26 8 0.32 1 202 228 0.23 8 8.05
95 0.19 3 0.23 2 244 275 0.23 3 10.9 3
120 0.15 3 0.18 4 282 313 0.23 3 13.8 0
150 0.12 4 0.15 0 324 353 0.23 3 17.2 5
185 0.09 91 0.12 1 371 399 0.23 3 21.2 8
240 0.07 54 0.09 3 436 464 0.23 2 27.6 0
300 0.06 01 0.07 5 481 524 0.23 1 34.5 0

www.extranacable.com
®
EXTRANA
CABLE

5 CORE NYRY/NYRGbY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conducto r, PVC Insulated, Galvanized
Stee l Round Wire Armoured with or without Steel Tape
,
PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanica l protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DA TA
O ver all
Nominal Thic kness Net W eig ht
Diam eter Bending
Size Radius
Ins ulation Sheath Approximat e

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 17.4 606 312

2. 5 0.8 1.8 18.6 708 334

4 1.0 1.8 21.1 899 379

6 1.0 1.8 23.3 1,197 419

10 1.0 1.8 25.7 1,510 462

16 1.0 1.9 28.7 1,947 516

25 1.2 2.1 34.7 2,939 624

35 1.2 2.2 38.3 3,655 689

50 1.4 2.3 43.2 4,501 777

ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Induct anc e
Size c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.4 78 19 26 0.328 0.17

2.5 7.41 8.86 6 25 34 0.304 0.29

4 4.61 5.51 6 34 44 0.303 0.46

6 3.08 3.68 5 43 56 0.288 0.69

10 1.83 2.19 0 60 75 0.269 1.15

16 1.15 1.37 6 80 98 0.255 1.84

25 0.72 7 0.87 0 106 128 0.255 2.88

35 0.52 4 0.62 7 131 157 0.246 4.03

50 0.38 7 0.46 4 159 185 0.247 5.75

www.extranacable.com
®
EXTRANA
CABLE
NYB(Al)Y 0.6/1 kV
1 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Aluminium Tape Ar moured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders
and street lighting.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight Bending
Size Diameter
Radius
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

35 1.2 1.8 17.0 677 305

50 1.4 1.8 18.8 833 338

70 1.4 1.8 20.5 1,068 368

95 1.6 1.8 22.8 1,382 410

120 1.6 1.8 24.4 1,660 438

150 1.8 1.8 26.4 1,985 474

185 2.0 1.9 28.7 2,399 516

240 2.2 2.0 32.0 3,073 575

300 2.4 2.1 35.5 3,833 638

400 2.6 2.2 39.0 4,746 701

500 2.6 2.3 42.9 5,996 771

630 2.6 2.5 47.2 7,394 849

ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC

mm² Ω/km Ω/km A A A A mH/km kA

25 0.727 0.870 140 137 206 153 0.358 2.88

35 0.524 0.627 174 169 249 183 0.345 4.03

50 0.387 0.464 212 206 296 216 0.336 5.75

70 0.268 0.321 269 261 365 265 0.326 8.05

95 0.193 0.232 331 321 438 316 0.321 10.93

120 0.153 0.184 386 374 499 359 0.316 13.80

150 0.124 0.150 442 428 561 402 0.313 17.25

185 0.0991 0.121 511 494 637 454 0.310 21.28

240 0.0754 0.093 612 590 743 527 0.307 27.60

300 0.0601 0.075 707 678 843 544 0.305 34.50

400 0.0470 0.061 859 817 986 686 0.302 46.02

500 0.0366 0.049 1000 940 1 125 774 0.299 57.53

630 0.0283 0.041 1 124 1060 1 198 846 0.293 72.52

www.extranacable.com
®
EXTRANA
CABLE

2 CORE
NYBY 0.6/1 kV
SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Gal vanized Steel Tape Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 13.6 372 244


2. 5 0.8 1.8 14.5 423 260
4 1.0 1.8 16.3 524 293
6 1.0 1.8 17.4 602 312
10 1.0 1.8 19.3 749 347
16 1.0 1.8 21.3 935 383
25 1.2 1.8 24.7 1,248 444
35 1.2 1.8 27.0 1,517 485
50 1.4 1.9 30.6 1,879 550
70 1.4 2.1 34.9 2,477 627
95 1.6 2.2 39.7 3,190 714
120 1.6 2.3 43.1 3,817 775
150 1.8 2.5 47.8 4,638 860
185 2.0 2.6 52.4 5,543 942
240 2.2 2.9 59.5 7,132 1,070
300 2.4 3.1 65.7 8,716 1,182

ELECTRICAL DATA
Max. Cond uctor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 2 0 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

3 CORE NYBY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Galvanized Steel Tape Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders
and street lighting.

CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e

mm² mm mm mm kg/km mm

1. 5 0.8 1.8 14.1 453 253


2. 5 0.8 1.8 15.1 529 271
4 1.0 1.8 17.1 686 307
6 1.0 1.8 18.3 809 329
10 1.0 1.8 20.2 1,037 363
16 1.0 1.8 22.5 1,343 404
25 1.2 1.8 26.1 1,864 469
35 1.2 1.9 28.7 2,328 516
50 1.4 2.0 33.1 3,005 595
70 1.4 2.1 37.1 3,917 667
95 1.6 2.3 42.4 5,176 762
120 1.6 2.5 46.7 6,350 840
150 1.8 2.6 51.1 7,653 919
185 2.0 2.8 56.6 9,358 1,018
240 2.2 3.0 63.6 1 1,990 1,144
300 2.4 3.2 70.3 14,798 1,265

ELECTRICAL DATA
M ax. Cond uctor Resistance Ma x. Current Carr yi n g Capacity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

4 CORE NYBY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Galvanized Steel Tape Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e

mm² mm Mm mm kg/km mm

1. 5 0.8 1.8 15.0 561 269


2. 5 0.8 1.8 16.0 663 287
4 1.0 1.8 18.2 886 327
6 1.0 1.8 19.6 1,064 352
10 1.0 1.8 21.8 1,395 392
16 1.0 1.8 24.3 1,837 437
25 1.2 1.9 28.6 2,628 514
35 1.2 2.0 31.5 3,306 566
50 1.4 2.1 36.2 4,305 651
70 1.4 2.3 40.9 5,682 735
95 1.6 2.5 47.2 7,630 849
120 1.6 2.6 51.3 9,260 923
150 1.8 2.8 56.8 1 1,333 1,022
185 2.0 3.0 62.4 13,800 1,122
240 2.2 3.2 70.2 17,776 1,263
300 2.4 3.5 78.3 22,166 1,409

ELECTRICAL DATA
Max . Conduc tor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50

www.extranacable.com
®
EXTRANA
CABLE

5 CORE NYBY 0.6/1 kV


SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Galvanized Steel Tape Armoured, PVC Sheathed)

For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

1.5 0.8 1.8 15.9 684 285

2.5 0.8 1.8 17.1 823 307

4 1.0 1.8 19.6 1,127 352

6 1.0 1.8 21.1 1,365 379

10 1.0 1.8 23.5 1,811 422

16 1.0 1.8 26.3 2,412 473

25 1.2 2.0 31.3 3,514 563

35 1.2 2.1 34.9 4,485 627

50 1.4 2.2 39.8 5,826 716

ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi ng Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17

2.5 7.41 8.866 25 34 0.304 0.29

4 4.61 5.516 34 44 0.303 0.46

6 3.08 3.685 43 56 0.288 0.69

10 1.83 2.190 60 75 0.269 1.15

16 1.15 1.376 80 98 0.255 1.84

25 0.727 0.870 106 128 0.255 2.88

35 0.524 0.627 131 157 0.246 4.03

50 0.387 0.464 159 185 0.247 5.75

www.extranacable.com
®
EXTRANA
CABLE

DERATING FACTORS

Table 1. Correction fact ors for ambient air temperatures other than 30 ºC

Maximum conductor Ambient air temperature


temperature ºC
ºC
20 25 35 40 45 50 55 60
90 1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71

Table 2. Correction factors for ambient ground temperatures other than 20 ºC


Maximum conductor Ambient ground temperature
temperature ºC
ºC
10 15 25 30 35 40 45 50
90 1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76

Table 3. Correction factors for depths of laying other than 0.8 m for
direct buried cables
Single-core cables
Depth of laying Nominal Conductor size Three-core
mm
2 cables
mtr
2 2
≤ 185 mm > 185 mm
0.5 1.04 1.06 1.04
0.6 1.02 1.04 1.03
1.0 0.98 0.97 0.98
1.25 0.96 0.95 0.96
1.5 0.95 0.93 0.95
1.75 0.94 0.91 0.94
2 0.93 0.90 0.93
2.5 0.91 0.88 0.91
3 0.90 0.86 0.90

www.extranacable.com
®
EXTRANA
CABLE

Table 4. Correction factors for depths of laying other than 0,8 m for
cables in ducts
Single-core cables
Depth of laying Nominal Conductor size Three-core
2 cables
mtr mm
2 2
≤ 185 mm > 185 mm

0.5 1.04 1.05 1.03


0.6 1.02 1.03 1.02
1 0.98 0.97 0.99
1.25 0.96 0.95 0.97
1.5 0.95 0.93 0.96
1.75 0.94 0.92 0.95
2 0.93 0.91 0.94
2.5 0.91 0.89 0.93
3 0.90 0.88 0.92

Table 5. Correction factor for soil thermal resistivities other than 1,5 K.m/W for
direct buried single-core cables

Nominal Values of soil thermal resistivity


area of
K.m/W
conductor
mm² 0.7 0.8 0.9 1 2 2.5 3
16 1.29 1.24 1.19 1.15 0.89 0.82 0.75
25 1.30 1.25 1.20 1.16 0.89 0.81 0.75
35 1.30 1.25 1.21 1.16 0.89 0.81 0.75
50 1.32 1.26 1.21 1.16 0.89 0.81 0.74
70 1.33 1.27 1.22 1.17 0.89 0.81 0.74
95 1.34 1.28 1.22 1.18 0.89 0.80 0.74
120 1.34 1.28 1.22 1.18 0.89 0.80 0.74
150 1.35 1.29 1.23 1.18 0.88 0.80 0.74
185 1.35 1.29 1.23 1.18 0.88 0.80 0.74
240 1.36 1.29 1.23 1.18 0.88 0.80 0.73
300 1.36 1.30 1.24 1.19 0.88 0.80 0.73
400 1.37 1.30 1.24 1.19 0.88 0.79 0.73

www.extranacable.com
®
EXTRANA
CABLE

Table 6. Correction factor for soil thermal resistivities other than 1,5 K.m/W
single-core cables in buried duct

Nominal Values of soil thermal resistivity


area of
K.m/W
conductor
mm² 0.7 0.8 0.9 1 2 2.5 3
16 1.20 1.17 1.14 1.11 0.92 0.85 0.79
25 1.21 1.17 1.14 1.12 0.91 0.85 0.79
35 1.21 1.18 1.15 1.12 0.91 0.84 0.79
50 1.21 1.18 1.15 1.12 0.91 0.84 0.79
70 1.22 1.19 1.15 1.12 0.91 0.84 0.78
95 1.23 1.19 1.16 1.13 0.91 0.84 0.78
120 1.123 1.20 1.16 1.13 0.91 0.84 0.78
150 1.24 1.20 1.16 1.13 0.91 0.83 0.78
185 1.24 1.20 1.17 1.13 0.91 0.83 0.78
240 1.25 1.21 1.17 1.14 0.90 0.83 0.77
300 1.25 1.21 1.17 1.14 0.90 0.83 0.77
400 1.25 1.21 1.17 1.14 0.90 0.83 0.77

Table 7. Correction factor for soil thermal resistivities other than 1,5 K.m/W
for direct buried three-core cables

Nominal Values of soil thermal resistivity


area off
K.m/W
conductor
mm² 0.7 0.8 0.9 1 2 2.5 3
16 1.23 1.19 1.16 1.13 0.91 0.84 0.78
25 1.24 1.20 1.16 1.13 0.91 0.84 0.78
35 1.25 1.21 1.17 1.13 0.91 0.83 0.78
50 1.25 1.21 1.17 1.14 0.91 0.83 0.77
70 1.26 1.21 1.18 1.14 0.90 0.83 0.77
95 1.26 1.22 1.18 1.14 0.90 0.83 0.77
120 1.26 1.22 1.18 1.15 0.90 0.83 0.77
150 1.27 1.22 1.18 1.15 0.90 0.83 0.77
185 1.27 1.23 1.18 1.15 0.90 0.83 0.77
240 1.28 1.23 1.19 1.15 0.90 0.83 0.77
300 1.28 1.23 1.19 1.15 0.90 0.82 0.77
400 1.28 1.23 1.19 1.15 0.90 0.82 0.76

www.extranacable.com
®
EXTRANA
CABLE

Table 8. Correction factor for soil thermal resistivities other than 1,5 K.m/W
three-core cables in buried duct

Nominal Values of soil thermal resistivity


area of
K.m/W
conductor
mm² 0.7 0.8 0.9 1 2 2.5 3
16 1.12 1.11 1.09 1.08 0.94 0.89 0.84
25 1.14 1.12 1.10 1.08 0.94 0.89 0.84
35 1.14 1.12 1.10 1.08 0.94 0.88 0.84
50 1.14 1.12 1.10 1.08 0.94 0.88 0.84
70 1.15 1.13 1.11 1.09 0.94 0.88 0.83
95 1.15 1.13 1.11 1.09 0.94 0.88 0.83
120 1.15 1.13 1.11 1.09 0.93 0.88 0.83
150 1.16 1.13 1.11 1.09 0.93 0.88 0.83
185 1.16 1.14 1.11 1.09 0.93 0.87 0.83
240 1.16 1.14 1.12 1.10 0.93 0.87 0.82
300 1.17 1.14 1.12 1.10 0.93 0.87 0.82
400 1.17 1.14 1.12 1.10 0.92 0.86 0.81

Table 9. Correction factor for groups of three-core cables in horizontal


formation laid direct in the ground

Spacing between cable centres


Number of
cables in mm
group
T ouching 200 400 600 800
2 0.8 0.86 0.90 0.92 0.94
3 0.69 0.77 0.82 0.86 0.89
4 0.62 0.72 0.79 0.83 0.87
5 0.57 0.68 0.76 0.81 0.85
6 0.54 0.65 0.74 0.80 0.84
7 0.51 0.63 0.72 0.78 0.83
8 0.49 0.61 0.71 0.77 -
9 0.47 0.60 0.70 - -
10 0.46 0.59 0.69 - -
11 0.45 0.57 0.69 - -
12 0.43 0.56 0.68 - -

www.extranacable.com
®
EXTRANA
CABLE

Table 10. Correction factor for groups of three-phase circuits of


single-core cables laid direct in the ground

Spacing between cable centres


Number of
cables in mm
group
T ouching 200 400 600 800
2 0.73 0.83 0.88 0.90 0.92
3 0.60 0.73 0.79 0.83 0.86
4 0.54 0.68 0.75 0.80 0.84
5 0.49 0.63 0.72 0.78 0.82
6 0.46 0.61 0.70 0.76 0.81
7 0.43 0.58 0.68 0.75 0.80
8 0.41 0.57 0.67 0.74 -
9 0.39 0.55 0.66 0.73 -
10 0.37 0.54 0.65 - -
11 0.36 0.53 0.64 - -
12 0.35 0.52 0.64 - -

Table 11. Correction factor for groups of three-core cables in single


way ducts in horizontal formation

Spacing between cable centres


Number of
cables in mm
group
T ouching 200 400 600 800
2 0.85 0.88 0.92 0.94 0.95
3 0.75 0.80 0.85 0.88 0.91
4 0.69 0.75 0.82 0.86 0.89
5 0.65 0.72 0.79 0.84 0.87
6 0.62 0.69 0.77 0.83 0.87
7 0.59 0.67 0.76 0.82 0.86
8 0.57 0.65 0.75 0.81 -
9 0.55 0.64 0.74 0.80 -
10 0.54 0.63 0.73 - -
11 0.52 0.62 0.73 - -
12 0.51 0.61 0.72 - -

www.extranacable.com
®
EXTRANA
CABLE

Table 12. Correction factor for groups of three-phase circuits of


single-core cables in single-way ducts

Spacing between cable centres


Number of
cables in mm
group
T ouching 200 400 600 800
2 0.78 0.85 0.89 0.91 0.93
3 0.66 0.75 0.81 0.85 0.88
4 0.59 0.70 0.77 0.82 0.86
5 0.55 0.66 0.74 0.80 0.84
6 0.51 0.64 0.72 0.78 0.83
7 0.48 0.61 0.71 0.77 0.82
8 0.46 0.60 0.70 0.76 -
9 0.44 0.58 0.69 0.76 -
10 0.43 0.57 0.68 - -
11 0.42 0.56 0.67 - -
12 0.40 0.55 0.67 - -

www.extranacable.com
®
EXTRANA
CABLE

Table 13. Reduction factors for groups of more than one multi-core cable in air - T o be applied to the
current-carrying capacity for one multi-core cable in free air

Number Number of cables


Method of Installation
of trays 1 2 3 4 6 9
1 1.00 0.88 0.82 0.79 0.76 0.73

2 1.00 0.87 0.80 0.77 0.73 0.68


≥ 20 mm

3 1.00 0.86 0.79 0.76 0.71 0.66


Cables on
perforated trays
D D
1 1.00 1.00 0.98 0.95 0.91 -

2 1.00 0.99 0.96 0.92 0.87 -


≥ 20 mm
3 1.00 0.98 0.95 0.91 0.85 -

1 1.00 0.88 0.82 0.78 0.73 0.72

2 1.00 0.88 0.81 0.76 0.71 0.70


Cables on
vertical
perforated trays ≥
225 mm
1 1.00 0.91 0.89 0.88 0.87 -

2 1.00 0.91 0.88 0.87 0.85 -

1 1.00 0.87 0.82 0.80 0.79 0.78

2 1.00 0.86 0.80 0.78 0.76 0.73


≥ 20 mm
Cables on ladder 3 1.00 0.85 0.79 0.76 0.73 0.70
supports, cleats,
etc D D 1 1.00 1.00 1.00 1.00 1.00 -

2 1.00 0.99 0.98 0.97 0.96 -


≥ 20 mm

3 1.00 0.98 0.97 0.96 0.93 -

Note 1. Values given are averages for the cable types and range of conductor size considered. The spread
of values is generally less than 5 %.
Note 2. Factors apply to single layer groups of cables as shown above and do not apply when cables are
installed in more than one layer touching each other. Values for such installations may be siginificantly lower
and must be determined by an appropriate method.
Note 3. Values are given for vertical spacing between trays of 300 mm and least 20 mm between trays and
wall. For closer spacing, the factors should be reduced.
Note 4. Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back.
For closer spacing, the factors should be reduced.

www.extranacable.com
®
EXTRANA
CABLE

Table 14. Reduction factors for groups of more than one circuit of single-core cables – T o be applied
to the current-carying capacit y for one circuit of single-core cables in free air

Number Number of three-phase Use as a


Method of Installation of trays circuit (Note 5) multiplier to
1 2 3 rating for

1 0.98 0.91 0.87


Perforated
trays
2 0.96 0.87 0.81
(Note 3) ≥ 20 mm
3 0.95 0.85 0.78 Three cables in
horizontal
Ladder 1 1.00 0.97 0.96 formation
supports,
cleats, etc 2 0.98 0.93 0.89
≥ 20 mm
(Note 3) 3 0.97 0.90 0.86

D 1 1.00 0.98 0.96


Perforated 2D
trays
2 0.97 0.93 0.89
(Note 3) ≥ 20 mm 3 0.96 0.92 0.86

V ertical 225 mm
1 1.00 0.91 0.89
perforated
Three cables in
trays
trefoil formation
2 1.00 0.90 0.86
(Note 4)

Ladder D 1 1.00 1.00 1.00


supports, 2D

cleats, etc 2 0.97 0.95 0.93

(Note 3) ≥ 20 mm 3 0.96 0.94 0.90

Note 1. Values given are averages for the cable types and range of conductor size considered. The spread
of values is generally less than 5 %.
Note 2. Factors are given for single layers of cables (or trefoil groups) as shownin the table and do not apply
when cables are installed in more than one layer touching each other. Values for such installations
may be siginificantly lower and must be d etermined by an appropriate method.
Note 3. Values are given for vertical spacing between trays of 300 mm. For closer spacing, the factors should
be reduced.
Note 4. Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back.
For closer spacing, the factors should be reduced.
Note 5. For circuit having more than one cable in parallel per phase, each three phase set of conductors
should be considered as a circuit for the purpose of this table.

www.extranacable.com
APPROXIMATE VOLTAGE DROP
(Copper Conductor)
(mV/A/m)

Conductor XLPE Insulated PVC Insulated


cross
sectional Single Phase @ 90°C Single Phase @ 70°C
3 Phase 3 Phase
area
@ 90°C @ 70°C
mm² Unarmoured Armoured Unarmoured Armoured

1.5 31.0259 - 26.8156 29.001 - 25.0857

2.5 18.9959 - 16.4013 17.8016 - 15.3981

4 1 1.8414 - 10.2083 11.0424 - 9.5513

6 7.9264 - 6.8180 7.3833 - 6.3860

10 4.7324 - 4.0509 4.3850 - 3.7920

16 2.9469 - 2.5470 2.7672 2.7081 2.3922

25 1.8706 2.9409 1.6151 1.7512 1.7523 1.5125

35 1.3559 1.8706 1.1689 1.2746 1.2759 1.0994

50 1.0083 1.3359 0.8673 0.9479 0.9492 0.8157

70 0.7097 1.0083 0.6075 0.6673 0.6088 0.5715

95 0.5250 0.7097 0.4458 0.4981 0.4997 0.4232

120 0.4296 0.5250 0.3616 0.4084 0.4102 0.3441

150 0.3640 0.4290 0.3028 0.3487 0.3510 0.2908

185 0.3085 0.3640 0.2532 0.2994 0.3014 0.2463

240 0.2593 0.3085 0.2082 0.2555 0.2756 0.2061

300 0.2302 0.2593 0.1812 0.2297 0.2319 0.1823

400 0.2061 0.2302 0.1604 0.2110 0.2135 0.1639

500 0.1914 0.2091 0.1461 0.1985 0.2013 0.1524

630 0.1808 0.1942 0.1359 0.1890 0.1927 0.1438