EXTRANA
CABLE
www.extranacable.com
®
EXTRANA
CABLE
NYA 450/750 V
SNI 04-6629.3; SNI 0225;
(Copper Conductor, PVC Insulated)
For building wire installed in conduit in dry location and interwiring in swich board and
control panel.
CONSTRUCTION DATA
Nominal Ov erall
Net Weight Bending Standard
Size Insulation Di a meter
Radius delivery length
Thi ckness Approximate
ELECTRICAL DATA
Mi n. DC Ins ulation Ma x. Current Carr yi ng Ma x. Short
Max . Conductor Resistance
Size Resistance Capacity at 30ºC Inductance circuit current
DC at 20ºC AC at 70 ºC DC at 20ºC AC at 70 ºC in air in pi pe at 1 sec.
www.extranacable.com
®
EXTRANA
CABLE
For building wire installed in conduit in dry location and interwiring in switch board and
control panel, inherently flame retardant in compliance with IEC 60332-1.
CONSTRUCTION DATA
- mm² mm mm mm kg/km mm
ELECTRICAL DA TA
Min. DC Ma x. Current Carr yi ng
Max . Co nductor Resistance Ins ul ation Ma x. Short circuit
Core Size Capacity at 30ºC Inductance
Resis tance current at 1 sec.
DC at 20ºC AC at 70 ºC at 20ºC in air in ground
www.extranacable.com
®
EXTRANA
CABLE
NYY 0.6/1 kV
1 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, PVC Sheathed)
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Ov erall
Nominal Thi ckness Net Weight Bending
Size Di a meter
Radius
Insulation Sheath Approximate
mm² mm mm mm kg/km mm
1. 5 0.8 1.4 6.0 55 48
2. 5 0.8 1.4 6.5 70 52
4 1.0 1.4 7.4 97 59
6 1.0 1.4 8.0 121 64
10 1.0 1.4 9.4 168 75
16 1.0 1.4 9.9 234 79
25 1.2 1.4 1 1.6 344 93
35 1.2 1.4 12.7 445 102
50 1.4 1.4 14.3 578 114
70 1.4 1.4 16.0 793 128
95 1.6 1.5 18.5 1,079 148
120 1.6 1.6 20.0 1,319 160
150 1.8 1.7 22.2 1,622 178
185 2.0 1.7 24.6 2,009 197
240 2.2 1.8 27.7 2,612 222
300 2.4 1.9 30.7 3,236 246
400 2.6 2.1 34.2 4,077 274
500 2.8 2.2 38.1 5,139 305
630 2.8 2.3 42.4 6,712 339
ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Ov erall
Nominal Thi ckness Net Weight
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal Thi ckness Net Weight
Diam eter Bending
Size Radius
Insulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight Bending
Size Dia m eter
Radius
In s ulation Sheath Approximate
mm² mm mm mm kg/km mm
1. 5 0.7 1.4 6.0 48 48
2. 5 0.7 1.4 6.5 62 52
4 0.7 1.4 7.4 81 59
6 0.7 1.4 8.0 104 64
10 0.7 1.4 9.4 150 75
16 0.7 1.4 9.9 213 79
25 0.9 1.4 1 1.6 318 93
35 0.9 1.4 12.7 419 102
50 1.0 1.4 14.3 546 114
70 1.1 1.4 16.0 766 128
95 1.1 1.6 18.5 1,033 148
120 1.2 1.6 20.0 1,287 160
150 1.4 1.6 22.2 1,575 178
185 1.6 1.8 24.6 1,965 197
240 1.7 1.8 27.7 2,552 222
300 1.8 1.8 30.7 3,071 246
400 2.0 2.0 34.2 4,028 274
500 2.2 2.1 38.1 5,051 305
630 2.4 2.2 42.4 6,478 339
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 3 0ºC
M ax. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 2 0ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
N2XY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 27 33 0.315 0.21
2.5 7.41 8.866 36 44 0.293 0.36
4 4.61 5.516 48 58 0.275 0.57
6 3.08 3.685 61 72 0.263 0.86
10 1.83 2.190 83 97 0.248 1.43
16 1.15 1.376 113 128 0.238 2.29
25 0.727 0.870 150 167 0.240 3.58
35 0.524 0.627 186 201 0.233 5.01
50 0.387 0.464 226 239 0.232 7.15
70 0.268 0.321 290 295 0.229 10.01
95 0.193 0.232 353 355 0.224 13.59
120 0.153 0.184 413 404 0.223 17.16
150 0.124 0.150 468 458 0.224 21.45
185 0.0991 0.121 540 516 0.225 26.46
240 0.0754 0.093 590 600 0.223 34.32
300 0.0601 0.075 745 695 0.221 42.90
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21
2.5 7.41 8.866 32 38 0.293 0.36
4 4.61 5.516 41 49 0.275 0.57
6 3.08 3.685 52 60 0.263 0.86
10 1.83 2.190 71 97 0.248 1.43
16 1.15 1.376 96 108 0.238 2.29
25 0.727 0.870 130 141 0.240 3.58
35 0.524 0.627 159 170 0.233 5.01
50 0.387 0.464 193 201 0.232 7.15
70 0.268 0.321 245 249 0.229 10.01
95 0.193 0.232 302 299 0.224 13.59
120 0.153 0.184 349 340 0.223 17.16
150 0.124 0.150 400 381 0.224 21.45
185 0.0991 0.121 464 434 0.225 26.46
240 0.0754 0.093 552 506 0.223 34.32
300 0.0601 0.075 640 585 0.221 42.90
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21
2.5 7.41 8.866 32 38 0.293 0.36
4 4.61 5.516 41 49 0.275 0.57
6 3.08 3.685 52 60 0.263 0.86
10 1.83 2.190 71 97 0.248 1.43
16 1.15 1.376 96 108 0.238 2.29
25 0.727 0.870 130 141 0.240 3.58
35 0.524 0.627 159 170 0.233 5.01
50 0.387 0.464 193 201 0.232 7.15
70 0.268 0.321 245 249 0.229 10.01
95 0.193 0.232 302 299 0.224 13.59
120 0.153 0.184 349 340 0.223 17.16
150 0.124 0.150 400 381 0.224 21.45
185 0.0991 0.121 464 434 0.225 26.46
240 0.0754 0.093 552 506 0.223 34.32
300 0.0601 0.075 640 585 0.221 42.90
www.extranacable.com
®
EXTRANA
CABLE
Used as power cable for indoors, outdoors, cable trunking, and burried in the ground.
Also used for power stations, industries and switchgear as well as for urban supply
networks, where there is low exposure to mechanical damage.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 29 0.315 0.21
www.extranacable.com
®
EXTRANA
CABLE
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size
Radius
Insulation Sheath Approxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 27 33 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 36 44 0.29 3 0.36
4/4 4.61 5.51 6 48 58 0.27 5 0.57
6/6 3.08 3.685 61 72 0.26 3 0.86
10/ 10 1.83 2.19 0 83 97 0.24 8 1.43
16/16 1.15 1.376 113 128 0.23 8 2.29
25/16 0.72 7 0.87 0 150 167 0.24 0 3.58
35/16 0.52 4 0.62 7 186 201 0.23 3 5.01
50/25 0.38 7 0.464 226 239 0.23 2 7.15
70/35 0.26 8 0.321 290 295 0.22 9 10.0 1
95/50 0.19 3 0.232 353 355 0.22 4 13.5 9
120/70 0.15 3 0.18 4 413 404 0.22 3 17.1 6
150/70 0.12 4 0.15 0 468 458 0.22 4 21.4 5
185/95 0.09 91 0.121 540 516 0.22 5 26.4 6
240/12 0 0.07 54 0.093 590 600 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 745 695 0.22 1 42.9 0
www.extranacable.com
®
EXTRANA
CABLE
N2XCY 0.6/1 kV
3 CORE SNI IEC 60502-1; SNI 0255
(Copper Conducto r, XLPE Insulated, Copper Wire Screen,
PVC Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Carryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 23 29 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 32 38 0.29 3 0.36
4/4 4.61 5.51 6 41 49 0.27 5 0.57
6/6 3.08 3.685 52 60 0.26 3 0.86
10/ 10 1.83 2.19 0 71 97 0.24 8 1.43
16/16 1.15 1.376 96 108 0.23 8 2.29
25/16 0.72 7 0.87 0 130 141 0.24 0 3.58
35/16 0.52 4 0.62 7 159 170 0.23 3 5.01
50/25 0.38 7 0.464 193 201 0.23 2 7.15
70/35 0.26 8 0.321 245 249 0.22 9 10.0 1
95/50 0.19 3 0.232 302 299 0.22 4 13.5 9
120/70 0.15 3 0.18 4 349 340 0.22 3 17.1 6
150/70 0.12 4 0.15 0 400 381 0.22 4 21.4 5
185/95 0.09 91 0.121 464 434 0.22 5 26.4 6
240/12 0 0.07 54 0.093 552 506 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 640 585 0.22 1 42.9 0
www.extranacable.com
®
EXTRANA
CABLE
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di a meter Bending
Size Radius
Insulation Sheath Approxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Carryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.4 78 23 29 0.31 5 0.21
2.5/2. 5 7.41 8.86 6 32 38 0.29 3 0.36
4/4 4.61 5.51 6 41 49 0.27 5 0.57
6/6 3.08 3.685 52 60 0.26 3 0.86
10/ 10 1.83 2.19 0 71 97 0.24 8 1.43
16/16 1.15 1.376 96 108 0.23 8 2.29
25/16 0.72 7 0.87 0 130 141 0.24 0 3.58
35/16 0.52 4 0.62 7 159 170 0.23 3 5.01
50/25 0.38 7 0.464 193 201 0.23 2 7.15
70/35 0.26 8 0.321 245 249 0.22 9 10.0 1
95/50 0.19 3 0.232 302 299 0.22 4 13.5 9
120/70 0.15 3 0.18 4 349 340 0.22 3 17.1 6
150/70 0.12 4 0.15 0 400 381 0.22 4 21.4 5
185/95 0.09 91 0.121 464 434 0.22 5 26.4 6
240/12 0 0.0754 0.093 552 506 0.22 3 34.3 2
300/15 0 0.06 01 0.07 5 640 585 0.22 1 42.9 0
www.extranacable.com
®
EXTRANA
CABLE
CONSTRUCTION DA TA
O ver all
Nominal Thickness Net W eig ht
Diameter Bending
Size Radius
Insulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C Ma x . Sh ort circuit
Size Induct anc e
c urr ent at 1 s ec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1. 5 12.1 14.478 23 29 0.31 5 0.21
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Over all
Nominal Thi ckness Net Weight Bending
Size Dia m eter
Radius
Insulation Sheath Approximat e
mm² mm mm mm kg/km mm
1. 5 0.8 1.8 9.45 168 76
2. 5 0.8 1.8 9.85 188 79
4 1.0 1.8 10.75 230 86
6 1.0 1.8 1 1.35 265 91
10 1.0 1.8 12.25 328 98
16 1.0 1.8 13.35 416 107
25 1.2 1.8 14.95 549 120
35 1.2 1.8 16.05 673 128
50 1.4 1.8 17.95 847 144
70 1.4 1.8 19.65 1,078 157
95 1.6 1.8 21.85 1,383 175
120 1.6 1.8 23.45 1,655 188
150 1.8 1.8 25.45 1,992 204
185 2.0 1.8 27.45 2,360 220
240 2.2 1.9 30.85 3,025 247
300 2.4 2.1 34.35 3,785 275
400 2.6 2.2 37.65 4,639 301
500 2.6 2.3 41.65 5,893 333
630 2.6 2.4 46.15 7,439 369
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 3 0ºC
M ax. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 2 0ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
NYSY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated,
Copper Tape Screen, PVC Sheathed)
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter. Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net Weight Bending
Size Diamete r
Radius
In s ulation Sheath App roximate
mm² mm mm mm kg/km mm
1. 5/1.5 0.8 1.8 9.55 167 76
2. 5/2.5 0.8 1.8 9.95 195 80
4/4 1.0 1.8 10.85 248 87
6/6 1.0 1.8 1 1.45 300 92
10 /10 1.0 1.8 12.35 396 99
16/16 1.0 1.8 13.45 535 108
25/16 1.2 1.8 15.05 664 120
35/16 1.2 1.8 16.15 784 129
50/25 1.4 1.8 18.05 953 144
70/35 1.4 1.8 19.75 1,262 158
95/50 1.6 1.8 21.95 1,651 176
120/7 0 1.6 1.8 23.55 2,056 188
150/7 0 1.8 1.8 25.55 2,567 204
185/9 5 2.0 1.8 27.55 2,929 220
240/1 20 2.2 1.9 30.95 4,055 248
300/1 50 2.4 2.1 34.45 5,063 276
400/1 20 2.6 2.2 37.75 6,226 302
500/2 40 2.6 2.3 41.75 7,968 334
630/3 00 2.6 2.4 46.25 10,045 370
ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net W eight
Diamete r Bending
Size Radius
Ins ulation Sheath App roximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 20 31 0.328 0.17
2.5/2.5 7.41 8.866 27 41 0.304 0.29
4/4 4.61 5.516 37 54 0.303 0.46
6/6 3.08 3.685 48 68 0.288 0.69
10/10 1.83 2.190 66 92 0.269 1.15
16/16 1.15 1.376 89 121 0.255 1.84
25/16 0.727 0.870 118 153 0.255 2.88
35/16 0.524 0.627 145 187 0.246 4.03
50/25 0.387 0.464 176 222 0.247 5.75
70/35 0.268 0.321 224 272 0.238 8.05
95/50 0.193 0.232 271 328 0.233 10.93
120/70 0.153 0.184 314 375 0.233 13.80
150/70 0.124 0.150 361 419 0.233 17.25
185/95 0.0991 0.121 412 475 0.233 21.28
240/120 0.0754 0.093 484 550 0.232 27.60
300/150 0.0601 0.075 590 525 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Ov erall
Nominal Thicknes s Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max . Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 19 26 0.328 0.17
2.5/2.5 7.41 8.866 25 34 0.304 0.29
4/4 4.61 5.516 34 44 0.303 0.46
6/6 3.08 3.685 43 56 0.288 0.69
10/10 1.83 2.190 60 75 0.269 1.15
16/16 1.15 1.376 80 98 0.255 1.84
25/16 0.727 0.870 106 128 0.255 2.88
35/16 0.524 0.627 131 157 0.246 4.03
50/25 0.387 0.464 159 185 0.247 5.75
70/35 0.268 0.321 202 228 0.238 8.05
95/50 0.193 0.232 244 275 0.233 10.93
120/70 0.153 0.184 282 313 0.233 13.80
150/70 0.124 0.150 324 353 0.233 17.25
185/95 0.0991 0.121 371 399 0.233 21.28
240/120 0.0754 0.093 436 464 0.232 27.60
300/150 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Ov erall
Nominal T hicknes s Net Weight
Diamete r Bending
Size Radius
Ins ulation Sheath App roximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Conductor Resistance Ma x. Current Carr yi n g Capacit y at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 7 0 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5/1.5 12.1 14.478 19 26 0.328 0.17
2.5/2.5 7.41 8.866 25 34 0.304 0.29
4/4 4.61 5.516 34 44 0.303 0.46
6/6 3.08 3.685 43 56 0.288 0.69
10/10 1.83 2.190 60 75 0.269 1.15
16/16 1.15 1.376 80 98 0.255 1.84
25/16 0.727 0.870 106 128 0.255 2.88
35/16 0.524 0.627 131 157 0.246 4.03
50/25 0.387 0.464 159 185 0.247 5.75
70/35 0.268 0.321 202 228 0.238 8.05
95/50 0.193 0.232 244 275 0.233 10.93
120/70 0.153 0.184 282 313 0.233 13.80
150/70 0.124 0.150 324 353 0.233 17.25
185/95 0.0991 0.121 371 399 0.233 21.28
240/120 0.0754 0.093 436 464 0.232 27.60
300/150 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For power plants and switchgears as well as for installation of substations; for
installation indoors in confined spaces and cable channels because of small bending
radius. As buried cable, because of its light weight and preferably in places where
installation conditions are difficult.
CONSTRUCTION DATA
Ov erall
Nominal Thicknes s Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Conductor Resistance Max. Current Carr yi n g Capacit y at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC A C at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1. 5/1.5 12.1 14.478 19 26 0.328 0.17
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0º C AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
3 CORE
NYFGbY 0.6/1 kV
SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Galvanized
Steel Flat Armoured, PVC Sheathed)
For installation in the ground, indoors, cable trunking and outdoors if increased mechanical
protection is required or where high-pulling stresses ma y occur during installation or operation.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm Mm mm kg/km mm
ELECTRICAL DATA
Max . Cond uctor Resistance Ma x. Current Carr yi n g Cap acity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximate
mm² mm Mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Over all
Nominal T hi ckness Net Weight
Dia m eter Bending
Size Radius
Ins ulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax . Cond uctor Resistance Ma x. Current Carr yi ng Cap acity at 3 0ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders and
street lighting.
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht Bending
Size Di ameter
Radius
Ins ulation Sheath App roxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Ma x. Con ductor Resistance Max. Current Car ryin g Cap acity at 30º C
Ma x . Sh ort circuit
Size in air in ground Induct anc e
curr en t at 1 sec.
DC at 20ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
NYRY/NYRGbY 0.6/1 kV
2 CORE SNI IEC 60502-1; SNI 0255
(Copper Conducto r, PVC Insulated, Galvanized
Stee l Round Wire Armoured with or without Steel Tape
,
PVC Sheathed)
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Size Induct anc e
c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.32 8 0.17
2.5 7.41 8.86 6 27 41 0.30 4 0.29
4 4.61 5.51 6 37 54 0.30 3 0.46
6 3.08 3.68 5 48 68 0.28 8 0.69
10 1.83 2.19 0 66 92 0.26 9 1.15
16 1.15 1.37 6 89 121 0.25 5 1.84
25 0.72 7 0.87 0 118 153 0.25 5 2.88
35 0.52 4 0.62 7 145 187 0.24 6 4.03
50 0.38 7 0.46 4 176 222 0.24 7 5.75
70 0.26 8 0.32 1 224 272 0.23 8 8.05
95 0.19 3 0.23 2 271 328 0.23 3 10.9 3
120 0.15 3 0.18 4 314 375 0.23 3 13.8 0
150 0.12 4 0.15 0 361 419 0.23 3 17.2 5
185 0.09 91 0.12 1 412 475 0.23 3 21.2 8
240 0.07 54 0.09 3 484 550 0.23 2 27.6 0
300 0.06 01 0.07 5 590 525 0.23 1 34.5 0
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate
mm² mm Mm mm kg/km mm
ELECTRICAL DATA
M a x. C on ductor Resistance Max. Current Carrying Cap acity at 30º C M a x . Sh ort circuit
Size Induct anc e
c urrent at 1 sec..
D C at 20ºC A C at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1. 5 12.1 14.478 19 26 0.32 8 0.17
2. 5 7.41 8.86 6 25 34 0.30 4 0.29
4 4.61 5.51 6 34 44 0.30 3 0.46
6 3.08 3.68 5 43 56 0.28 8 0.69
10 1.83 2.19 0 60 75 0.26 9 1.15
16 1.15 1.37 6 80 98 0.25 5 1.84
25 0.72 7 0.87 0 106 128 0.25 5 2.88
35 0.52 4 0.62 7 131 157 0.24 6 4.03
50 0.38 7 0.46 4 159 185 0.24 7 5.75
70 0.26 8 0.32 1 202 228 0.23 8 8.05
95 0.19 3 0.23 2 244 275 0.23 3 10.9 3
12 0 0.15 3 0.18 4 282 313 0.23 3 13.8 0
15 0 0.12 4 0.15 0 324 353 0.23 3 17.2 5
18 5 0.0991 0.12 1 371 399 0.23 3 21.2 8
24 0 0.0754 0.09 3 436 464 0.23 2 27.6 0
30 0 0.0601 0.07 5 481 524 0.23 1 34.5 0
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone or operation.
CONSTRUCTION DA TA
O ver all
Nominal Th ickness Net W eig ht
Di ameter. Ben ding
Size Rad ius
Ins ulation Sheath App roxim ate
mm² mm Mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Induct anc e
Size c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.4 78 19 26 0.32 8 0.17
2.5 7.41 8.86 6 25 34 0.30 4 0.29
4 4.61 5.51 6 34 44 0.30 3 0.46
6 3.08 3.68 5 43 56 0.28 8 0.69
10 1.83 2.19 0 60 75 0.26 9 1.15
16 1.15 1.37 6 80 98 0.25 5 1.84
25 0.72 7 0.87 0 106 128 0.25 5 2.88
35 0.52 4 0.62 7 131 157 0.24 6 4.03
50 0.38 7 0.46 4 159 185 0.24 7 5.75
70 0.26 8 0.32 1 202 228 0.23 8 8.05
95 0.19 3 0.23 2 244 275 0.23 3 10.9 3
120 0.15 3 0.18 4 282 313 0.23 3 13.8 0
150 0.12 4 0.15 0 324 353 0.23 3 17.2 5
185 0.09 91 0.12 1 371 399 0.23 3 21.2 8
240 0.07 54 0.09 3 436 464 0.23 2 27.6 0
300 0.06 01 0.07 5 481 524 0.23 1 34.5 0
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanica l protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DA TA
O ver all
Nominal Thic kness Net W eig ht
Diam eter Bending
Size Radius
Ins ulation Sheath Approximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Max. Current Carrying Capacity at 30º C Max. Short circuit
Induct anc e
Size c urr ent at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.4 78 19 26 0.328 0.17
www.extranacable.com
®
EXTRANA
CABLE
NYB(Al)Y 0.6/1 kV
1 CORE SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Aluminium Tape Ar moured, PVC Sheathed)
For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders
and street lighting.
CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight Bending
Size Diameter
Radius
Insulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi n g Capacity at 30ºC
Max. Short circuit
Size in air in ground Inductance
current at 1 sec.
DC at 20ºC AC at 70 ºC
www.extranacable.com
®
EXTRANA
CABLE
2 CORE
NYBY 0.6/1 kV
SNI IEC 60502-1; SNI 0255
(Copper Conductor, PVC Insulated, Double
Gal vanized Steel Tape Armoured, PVC Sheathed)
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max. Cond uctor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 2 0 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 31 0.328 0.17
2.5 7.41 8.866 27 41 0.304 0.29
4 4.61 5.516 37 54 0.303 0.46
6 3.08 3.685 48 68 0.288 0.69
10 1.83 2.190 66 92 0.269 1.15
16 1.15 1.376 89 121 0.255 1.84
25 0.727 0.870 118 153 0.255 2.88
35 0.524 0.627 145 187 0.246 4.03
50 0.387 0.464 176 222 0.247 5.75
70 0.268 0.321 224 272 0.238 8.05
95 0.193 0.232 271 328 0.233 10.93
120 0.153 0.184 314 375 0.233 13.80
150 0.124 0.150 361 419 0.233 17.25
185 0.0991 0.121 412 475 0.233 21.28
240 0.0754 0.093 484 550 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if ground conditions
are propone to mechanical demage. Also used in urban network, household feeders
and street lighting.
CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e
mm² mm mm mm kg/km mm
ELECTRICAL DATA
M ax. Cond uctor Resistance Ma x. Current Carr yi n g Capacity at 30ºC M ax. Short circuit
Inductance
Size current at 1 sec..
DC at 2 0 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Over all
Nominal T hick ness Net W eight
Diam eter Bending
Size Radius
Ins ulation Sheath Appro ximat e
mm² mm Mm mm kg/km mm
ELECTRICAL DATA
Max . Conduc tor Resistance Ma x. Current Carr yi n g Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec. .
DC at 20 ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
2.5 7.41 8.866 25 34 0.304 0.29
4 4.61 5.516 34 44 0.303 0.46
6 3.08 3.685 43 56 0.288 0.69
10 1.83 2.190 60 75 0.269 1.15
16 1.15 1.376 80 98 0.255 1.84
25 0.727 0.870 106 128 0.255 2.88
35 0.524 0.627 131 157 0.246 4.03
50 0.387 0.464 159 185 0.247 5.75
70 0.268 0.321 202 228 0.238 8.05
95 0.193 0.232 244 275 0.233 10.93
120 0.153 0.184 282 313 0.233 13.80
150 0.124 0.150 324 353 0.233 17.25
185 0.0991 0.121 371 399 0.233 21.28
240 0.0754 0.093 436 464 0.232 27.60
300 0.0601 0.075 481 524 0.231 34.50
www.extranacable.com
®
EXTRANA
CABLE
For installation in the ground, indoors, cable trunking and outdoors if increased
mechanical protection is required or where high-pulling stresses may occur during
installation or operation.
CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter Bending
Size Radius
Insulation Sheath Approximate
mm² mm mm mm kg/km mm
ELECTRICAL DATA
Max. Conductor Resistance Ma x. Current Carr yi ng Capacity at 30ºC Max. Short circuit
Inductance
Size current at 1 sec..
DC at 20ºC AC at 70 ºC in air in ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 26 0.328 0.17
www.extranacable.com
®
EXTRANA
CABLE
DERATING FACTORS
Table 1. Correction fact ors for ambient air temperatures other than 30 ºC
Table 3. Correction factors for depths of laying other than 0.8 m for
direct buried cables
Single-core cables
Depth of laying Nominal Conductor size Three-core
mm
2 cables
mtr
2 2
≤ 185 mm > 185 mm
0.5 1.04 1.06 1.04
0.6 1.02 1.04 1.03
1.0 0.98 0.97 0.98
1.25 0.96 0.95 0.96
1.5 0.95 0.93 0.95
1.75 0.94 0.91 0.94
2 0.93 0.90 0.93
2.5 0.91 0.88 0.91
3 0.90 0.86 0.90
www.extranacable.com
®
EXTRANA
CABLE
Table 4. Correction factors for depths of laying other than 0,8 m for
cables in ducts
Single-core cables
Depth of laying Nominal Conductor size Three-core
2 cables
mtr mm
2 2
≤ 185 mm > 185 mm
Table 5. Correction factor for soil thermal resistivities other than 1,5 K.m/W for
direct buried single-core cables
www.extranacable.com
®
EXTRANA
CABLE
Table 6. Correction factor for soil thermal resistivities other than 1,5 K.m/W
single-core cables in buried duct
Table 7. Correction factor for soil thermal resistivities other than 1,5 K.m/W
for direct buried three-core cables
www.extranacable.com
®
EXTRANA
CABLE
Table 8. Correction factor for soil thermal resistivities other than 1,5 K.m/W
three-core cables in buried duct
www.extranacable.com
®
EXTRANA
CABLE
www.extranacable.com
®
EXTRANA
CABLE
www.extranacable.com
®
EXTRANA
CABLE
Table 13. Reduction factors for groups of more than one multi-core cable in air - T o be applied to the
current-carrying capacity for one multi-core cable in free air
Note 1. Values given are averages for the cable types and range of conductor size considered. The spread
of values is generally less than 5 %.
Note 2. Factors apply to single layer groups of cables as shown above and do not apply when cables are
installed in more than one layer touching each other. Values for such installations may be siginificantly lower
and must be determined by an appropriate method.
Note 3. Values are given for vertical spacing between trays of 300 mm and least 20 mm between trays and
wall. For closer spacing, the factors should be reduced.
Note 4. Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back.
For closer spacing, the factors should be reduced.
www.extranacable.com
®
EXTRANA
CABLE
Table 14. Reduction factors for groups of more than one circuit of single-core cables – T o be applied
to the current-carying capacit y for one circuit of single-core cables in free air
Note 1. Values given are averages for the cable types and range of conductor size considered. The spread
of values is generally less than 5 %.
Note 2. Factors are given for single layers of cables (or trefoil groups) as shownin the table and do not apply
when cables are installed in more than one layer touching each other. Values for such installations
may be siginificantly lower and must be d etermined by an appropriate method.
Note 3. Values are given for vertical spacing between trays of 300 mm. For closer spacing, the factors should
be reduced.
Note 4. Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back.
For closer spacing, the factors should be reduced.
Note 5. For circuit having more than one cable in parallel per phase, each three phase set of conductors
should be considered as a circuit for the purpose of this table.
www.extranacable.com
APPROXIMATE VOLTAGE DROP
(Copper Conductor)
(mV/A/m)