You are on page 1of 4

A B C D E F G H I J

5 [0.20]
(4) Mounting Holes
68 [2.68] for M5 [#10] Screws. Cooling fan location 5 [0.20]
Air

42 [1.65]
2

VERTICAL MTG DIM


118 [4.65]
128 [5.04]

Keypad

0.5 [0.02]
Nameplate
3
5 [0.20]

5 [0.20]
Air
20.2 [0.80] 53.8 [2.12]
4 2.7 [0.11] 137.5 [5.41]
6 [0.24] 96 [3.78] 6 [0.24]
HORIZONTAL MTG DIM

108 [4.27]

6
56.5 [2.22]

C/C: INPUT VOLTAGE WEIGHT COOLING


GA50□ (VAC) Kg (lb) FANS

200 TO 240 1.5 (3.3)


B006□□□ 0
1-PHASE
7 200 TO 240
2012□□□ 1.5 (3.3) 1
3-PHASE
380 TO 480 1.5 (3.3)
4004□□□ 0
3-PHASE
□ denotes A-Z

8 DRWN. J. MATTAS 5-28-19 TITLE SIZE A PAGE 1 OF 4 REV


CHKD. J. PIOTROWSKI 7-29-19 GA500 DIMENSION DRAWING DWG.NO.
UNITS MM [IN] TECH. L. UDDIN 8-7-19 FRAME SIZE 2.4 0
SCALE 1:3 APRV. J. CAIRO 8-22-19
IP20 ENCLOSURE DD.GA50.FR2.4.IP20
A B C D E F G H I J

Terminal and Wiring Information for GA50□B006


1

FRONT VIEW BOTTOM VIEW

2
98 [3.86]

7.6 [0.30]
3
Refer to DD.GA50.CONTROLBOARD
drawing for Control Circuit Board details

(Control Circuit Board)


Base Point of

117.4 [4.62]
Control Circuit Board
Main Circuit Terminals

81.3 [3.20]
4 with M3 Screws;

Terminals)
(Grounding
63.5 [2.50]
Slotted (-)

53 [2.09]

10.7 [0.42] 6.35 [0.25]

Grounding Terminals
with M4 Screws; 36.3 [1.43] 6.35 [0.25]
Phillips(+)/Slotted(-) combo
6
58 [2.28] 4xP6.35=25.4 [1.00]

C/C: TERMINAL WIRE RANGE TERMINAL CLAMPING TORQUE


2
GA50□ SYMBOL AWG (mm ) SCREW N.m. (lb.in.)
L/L1, N/L2 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
7 U/T1, V/T2, W/T3 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
B006□□□ -, +1 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
B1, B2 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
14 - 10 (2.5 - 6) M4 1.2 - 1.5 (11 - 13)
□ Denotes A-Z
Note: Refer to applicable codes and standards for proper wire type and size.

8 DRWN. J. MATTAS 5-28-19 TITLE SIZE A PAGE 2 OF 4 REV


CHKD. J. PIOTROWSKI 7-29-19 GA500 DIMENSION DRAWING DWG.NO.
UNITS MM [IN] TECH. L. UDDIN 8-7-19 FRAME SIZE 2.4 0
SCALE 1:2 APRV. J. CAIRO 8-22-19
IP20 ENCLOSURE DD.GA50.FR2.4.IP20
A B C D E F G H I J

Terminal and Wiring Information for GA50□2012 and GA50□4004


1

FRONT VIEW BOTTOM VIEW

2
98 [3.86]

7.6 [0.30]
3
Refer to DD.GA50.CONTROLBOARD
drawing for Control Circuit Board details

(Control Circuit Board)


Base Point of

117.4 [4.62]
Control Circuit Board
Main Circuit Terminals

81.3 [3.20]
4 with M3 Screws;

Terminals)
(Grounding
63.5 [2.50]
Slotted (-)

53 [2.09]

10.7 [0.42] 2xP6.35=12.7 [0.50]

Grounding Terminals
with M4 Screws; 36.3 [1.43] 2xP6.35=12.7 [0.50]
Phillips(+)/Slotted(-) combo
6
58 [2.28] 4xP6.35=25.4 [1.00]

C/C: TERMINAL WIRE RANGE TERMINAL CLAMPING TORQUE


2
GA50□ SYMBOL AWG (mm ) SCREW N.m. (lb.in.)
R/L1, S/L2, T/L3 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
7 U/T1, V/T2, W/T3 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
2012□□□
-, +1, +2 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
4004□□□
B1, B2 14 - 10 (2.5 - 6) M3 0.6 - 0.8 (5 - 7)
14 - 10 (2.5 - 6) M4 1.2 - 1.5 (11 - 13)
□ Denotes A-Z
Note: Refer to applicable codes and standards for proper wire type and size.

8 DRWN. J. MATTAS 5-28-19 TITLE SIZE A PAGE 3 OF 4 REV


CHKD. J. PIOTROWSKI 7-29-19 GA500 DIMENSION DRAWING DWG.NO.
UNITS MM [IN] TECH. L. UDDIN 8-7-19 FRAME SIZE 2.4 0
SCALE 1:2 APRV. J. CAIRO 8-22-19
IP20 ENCLOSURE DD.GA50.FR2.4.IP20
A B C D E F G H I J

Minimum Installation Clearances Panel Cutout


For External Heatsink Mounting Configuration
1

(4)-M4(#8) 96 [3.78]
2 Threaded Hole

50 [1.97]
Customer Panel
Air Air

100 [3.94]
3

CUTOUT

144 [5.67]

128 [5.04]

146 [5.75]
4
30 [1.18] 30 [1.18]

80 [3.15]
100 [3.94]

106 [4.17]
50 [1.97]

6 Air Air

7
Notes:
Note: Exposed heatsink minimum clearance = 61.5 [2.42].
For alternate mounting configurations, consult manual. Refer to external heatsink instructions document for additional details.

8 DRWN. J. MATTAS 5-28-19 TITLE SIZE A PAGE 4 OF 4 REV


CHKD. J. PIOTROWSKI 7-29-19 GA500 DIMENSION DRAWING DWG.NO.
UNITS MM [IN] TECH. L. UDDIN 8-7-19 FRAME SIZE 2.4 0
SCALE 1:3 APRV. J. CAIRO 8-22-19
IP20 ENCLOSURE DD.GA50.FR2.4.IP20