Professional Documents
Culture Documents
Abstract--This paper describes a method for the robustness 2) Speed reference step applied to the speed-governor
assessment of the generator-voltage regulator-stabilizer set of (GOV) of a generator supplying a local load, and operating in
individual power plants in large scale systems. This is carried out isolated mode;
using a 2-bus synthetic system, whose parameters are varied to
simulate the presence of electromechanical oscillations over a 3) Voltage reference step applied to AVR of a generator,
wide range of frequencies. The method helps predicting the equipped with AVR, PSS and GOV controls, and connected to
generator-voltage regulator-stabilizer performance, when the infinite bus through either a low impedance (equal to the
submitted to electromechanical oscillations of different nature step-up transformer impedance) or a high impedance (twice
(inter-area, local and intra-plant) in the actual multimachine the value of Xd’ or larger);
environment.
4) Mechanical reference step applied to the GOV of a
Index Terms--Power System Stabilizer, Small-Signal Stability, generator and associated controls, as in 3), to assess the
Controller Robustness. adverse transients to terminal voltage and reactive power
I. INTRODUCTION induced by the presence of the PSS [4];
5) Frequency response plot of the GEP transfer function of
R OBUSTNESS assessment of Power System Stabilizers
(PSS), to aid PSS tuning, may be carried out by
simulating their performance for numerous events and
the generator and AVR, prior and after PSS addition, to verify
whether the established frequency domain guidelines for PSS
probable system operation scenarios [1]. Robust control design have not been infringed [5, 6, 7].
methods are of limited use in large power system models [2, 3] The synthetic test system method described in this paper,
due to the computational burden imposed by the available should also be added to this set of tests on individual plants,
robust control design algorithms. widening the spectrum of preliminary tests to data validation
This paper describes a fairly simple method for assessing and adequacy, besides allowing an assessment of controller
the small-signal stability robustness of the generator-automatic robustness and also indicating possible improvements to PSS
voltage regulator (AVR) and PSS set, which is expected to be design.
of practical value. A generating plant and associated controls II. SYNTHETIC SYSTEM
must have a robust performance over a wide range of
scenarios, events, and for electromechanical modes of The synthetic system, pictured in Fig. 1, consists of a
different nature. The proposed method involves the automatic generator injecting constant power S at constant power factor
generation of a large set of conditions on the 2-bus synthetic (cosφ) into Bus #1, which has a shunt variable load (Psh and
system that produce close to real-life electromechanical modes Qsh). Bus #1 is connected through a variable impedance to an
of different frequencies. The phase shaping of the stabilizer is infinite system (Bus #2), whose voltage magnitude is kept
obtained through use of the root locus departure angle constant at 1 pu. For brevity, and without compromising the
technique (e.g., the pole residues for the ∆ω/∆VREF transfer results and objectives of this paper, the series resistance (R12)
function) [2], to cater for the different phase compensation will be assumed always equal to zero.
needs for the intra-plant, local and inter-area modes. Sφ V1 θ1 1 0o
In the analysis of large-scale systems, it is good practice to R12 X12
carry out a series of tests on the individual components and
controllers, in a preliminary phase, for bad data detection in
these very large dynamic data files, and identification of #1 #2
inadequately designed (or tuned) controllers.
There is a set of data validation tests that may be carried
out on individual generators with associated controllers prior Psh Qsh
to running small-signal studies of interconnected systems [4]:
Fig. 1. Synthetic system for PSS robustness assessment.
1) Voltage reference step applied to AVR of a generator at
no-load; The frequency of the electromechanical mode in this
synthetic system is made to vary by changing the reactance
J. C. R. Ferraz and N. Martins are with CEPEL – PO Box 68007, 21944-
X12, becoming smaller as the line reactance X12 is raised.
970, Rio de Janeiro, RJ, Brazil. (e-mail: jcferraz@ieee.org, nelson@cepel.br) When changing the reactance X12 there is an associated
G. N. Taranto is with COPPE/UFRJ – PO Box 68564, 21945-970, Rio de change in the power flow through the transmission line. In
Janeiro, RJ, Brazil. (e-mail: tarang@coep.ufrj.br)
2
order to maintain the generation unchanged (both active and The parameters a and b in equation (6) are determined from
reactive), the difference in the transmitted power through the the minimum and maximum values of X12 and of the angular
variable impedance line, must be absorbed by the variable load difference θ12 (Fig. 2), and are given by:
connected to Bus #1 (Psh and Qsh). Therefore, when the power ⎛ θ12
Max ⎞
[ ( )] ; b =
⎜ ⎟
transfer through the line is small, the load absorbs practically θ Max
− arcsin P1 X Min 1 ⎜ a
⎝
⎟
⎠ .
a= 12 12 e
all the generated power. On the other hand, for small reactance X 12Max (7)
⎛ 1 ⎞ ⎛ 1 ⎞
values of the line, practically all the generated power is ln⎜⎜ ⎟ − ln⎜ ⎟
X Min ⎟ ⎜ X Max ⎟
transferred through the line and absorbed by the infinite bus, ⎝ 12 ⎠ ⎝ 12 ⎠
while the load at Bus #1 tends to zero.
By keeping constant the value of the injected generation θ12
θ12 = a ln(bX12)
and the machine terminal conditions, one ensures that the
machine limits for safe operation are not violated. The θMax
12
generator, associated controls, and the PSS may then have
their small signal stability performance assessed when facing
the different electromechanical frequencies produced by the
parameter changes in the synthetic system. Note that the
synthetic system has one independent parameter (X12) and
three dependent parameters (θ1, Psh and Qsh). Being comprised
of only two buses, the synthetic system has an analytic power
flow solution.
The robustness assessment of the generator and associated
θMin
controls relies on the analysis of the system eigenvalues 12
Fig. 3. Active power changes in the line (P12) and in the load (Psh).
V1V2 sin (θ 12 ) ; (V ) − V1V2 cos(θ 12 ) .
2
ξ2 ξ1 Imag 60
(degrees)
x 40
x
Without PSS
12
30
θ
x
x
20
x x
XMax
12
10
x x
0
0 5 10 15 20 25
X12 (pu)
Imag
0.76
utilized, having a gain of 100 and a time constant of 50 ms. 6
Table 2 shows the MVA capacity of the hydro plant, the Fig. 6. System poles for different values X12 (from 0.1 pu to 25 pu).
constant-P and constant-Z parts of the load. The logarithmic Root Locus
15
function describing the angle θ12 changes with the line 0.5 0.36 0.24 0.12 14
-8 -6 -4 -2 0 2
Fig. 6 shows the loci described by two system poles of Real
Real(1/s)
interest, as the line reactance X12 is varied from 0.1pu up to Fig. 7. Root-loci for ten different values of X12 (between 0.1 pu and 25pu)
25pu. The electromechanical mode of oscillation is poorly obtained with a direct gain feedback.
damped or negatively damped for most values of line Fig. 8 shows an enlarged detail of Fig. 7, focusing on the
reactance, except for low values of X12, which corresponds to behavior of the electromechanical pole. One should note that
the highest frequencies of oscillation (e.g., frequencies of for low values of electromechanical oscillation frequency
intra-plant modes). (associated with higher values of X12) there is no need for
Fig. 7 presents the root-loci plots for ten different values of phase compensation in the stabilizing loop, since the departure
X12 when each stabilizing transfer function (∆ω/∆VREF) is angle is already at 180o. However, for higher
closed through a feedback loop comprising a pure gain, with electromechanical frequencies (lower values of X12), there is
no phase compensation. The blue arrows are the pole residues need to phase advance this departure angle.
of the transfer function (∆ω/∆VREF) associated with a fixed In summary, the analysis of Fig. 8 shows the need for phase
value of X12, each one defining the departure angle of the root- advance compensation for higher frequency electromechanical
locus diagram. modes (local and intra-plant), while the lower frequency,
4
poorly (or negatively) damped inter-area modes, only require a poles related to intra-plant and exciter modes do not get their
direct gain in the stabilizing loop to increase the damping damping ratios unduly reduced. A second stabilizer design,
ratios of these poles, without significantly changing their PSS2 (see Table 4), whose phase advance blocks have center
imaginary parts. These PSS phase compensation needs for frequencies about 30 rad/s, is now assessed.
modes of different frequencies, identified from the inspection 15
0.5 0.36 0.24 0.12 14
of Fig. 8, are in agreement with the established guidelines for
PSS tuning. 12
Root Locus
12 0.64 10
0.16 0.08 10
0.25
(rad/s)
10 8
10
0.76
ImagImag
8 6
8
0.36 5 0.88
4
(rad/s)
6
6
ImagImag
0.48 2
0.97
4
4
0.62
0
0.78 2
2 -8 -6 -4 -2 0 2
0.94 Real
Real (1/s)
at 6.5 rad/s.
6
6
Table 3. Parameters for PSS1.
0.88 4
Frequency of Maximum 4
PSS1(s)
Phase Advance 0.96 2
2
2
⎛ 1 + 0.300s ⎞ ⎛ 3s ⎞
PSS 1 (s ) = (5) ⋅ ⎜ ⎟ ⋅⎜ ⎟ ωMax = 6.5 rad/s 0
⎝ 1 + 0.075s ⎠ ⎝ 1 + 3s ⎠ -8 -6 -4 -2 0 2
Real (1/s)
Real
Fig. 10. Root-loci diagrams obtained by increasing the PSS1 gain.
Fig. 9 shows the departure angles for the ten root-loci
Root Locus
diagrams (residues for the electromechanical poles of 15
0.5 0.36 0.24 0.12 14
(∆ω/∆VREF)) for the system without (red arrows) and with the
12
PSS1 (black arrows). One may note that the PSS1 phase
compensated residues are close to ideal (departure angles 0.64 10
10
about 180º) only for electromechanical modes with
(rad/s)
8
frequencies between 6 rad/s and 9 rad/s. 0.76
Imag
Fig. 12 shows the departure angles for the same set of ten blocks with center frequencies about 30 rad/s and a phase-lag
root-loci (residues of transfer function (∆ω/∆VREF)) for the block which cancels out the phase advance at the lower
original system (red arrows) and with the PSS2 (black arrows). frequencies. Note that Fig. 8 showed that the departure angles
for the root-loci for pure gain feedbacks at lower frequencies
Root Locus
15
0.5 0.36 0.24 0.12 14
were about 180o, indicating there is no need for phase
compensation.
12
Fig. 15 shows the departure angles for the ten root-loci
10
0.64 10 diagrams (residues for the electromechanical pole of the set of
transfer functions (∆ω/∆VREF)) for the original system (red
(rad/s)
8
0.76 arrows) and with PSS3 (black arrows). The black arrow
Imag
(rad/s)
8
11), showing that the PSS2 stabilizer improves the damping 0.76
ratios for the electromechanical poles over the entire Imag
Imag 6
frequency range. Note, however, that between 1rad/s and
5 0.88
4 rad/s (frequencies which are typical of inter-area nodes), the 4
phase lead provided is excessive (Fig. 13), causing a reduction
2
in the frequency of the electromechanical mode, as the 0.97
stabilizer gain is increased.
0
Root Locus
15 -8 -6 -4 -2 0 2
0.5 0.36 0.24 0.12 14
Real (1/s)
Real
12
Fig. 14. Original system (red) and system with PSS2 (black) – K = 8 pu/pu.
0.64
Table 5. Parameters for PSS3.
10
10 Frequency of Maximum
PSS3(s)
Phase Advance
(rad/s)
8
0.76
Imag
2
⎛ 1 + 0.100s ⎞ ⎛ 1 + 0.250s ⎞ ⎛ 3s ⎞
6 PSS 3 (s ) = (30 ) ⋅ ⎜ ⎟ ⋅⎜ ⎟⋅⎜ ⎟ ωMax = 34 rad/s
Imag
⎝ 1 + 0.010s ⎠ ⎝ 1 + 1.000s ⎠ ⎝ 1 + 3s ⎠
5 0.88
4
15
0.97 2 0.5 0.36 0.24 0.12 14
0 12
-8 -6 -4 -2 0 2 0.64
Real
Real
(1/s)
10
10
Fig. 13. Root-loci diagrams obtained by increasing the PSS2 gain.
(rad/s)
8
0.76
Imag
(red curve) and with PSS3 (green curve) with a gain equal to
30pu/pu. Such gain is usually considered very high for PSSs 10
10
(rad/s)
of the third block, which is a phase-lag block centered at a low 8
Imag
frequency, a 30 pu/pu gain becomes acceptable. One may note
Imag
6
there are no problems with exciter modes, and that the
damping ratios for the electromechanical poles are acceptable 5
4
over the whole frequency range (from 1 rad/s to 14 rad/s).
Fig. 18 allows comparing the performances of the three 2
0.64
10
10 Fig. 19 shows the eigenvalue loci for the original system
with no PSS (red curve), PSS2 (black curve), PSS3 (green
(rad/s)
8
0.76 curve) and PSS4 (purple curve). It can be seen that PSS4
Imag
12
0
-8 -6 -4 -2 0 2 10
10
Real (1/s)
Real
(rad/s)
Root Locus
Imag
15 6
0.5 0.36 0.24 0.12 14
5
4
12
0.64 2
10
10
(rad/s)
8 0
0.76
Imag
−9 −8 −7 −6 −5 −4 −3 −2 −1 0 1 2
Imag
6 Real
Real (1/s)
5 0.88 Fig. 19. PSS performance comparison using the synthetic system
4
(Without PSS: red / PSS2: black / PSS3: green / PSS4: purple).
0.97 2 Other stabilizer tunings could be analyzed, to better assess
the benefits of having either the third phase-compensation
0
block or the advantages of having unequal phase-lead blocks.
-8 -6 -4 -2 0 2 Other stabilizer structures and the use of different input
Real (1/s)
Real
Fig. 17. Original system (red) and system with PSS3 (grern) – K = 30pu/pu.
variables, or multiple channels, etc. could also be assessed [6,
8, 9].
A close to optimal tuning of a stabilizer should have the Fig. 20 and Fig. 21 show the Bode diagrams for the four
performance of the PSS2 stabilizer at higher frequencies and stabilizers assessed in this paper.
the performance of the PSS3 stabilizer at lower frequencies.
An attempt to achieve a further improved design has lead to
the fourth stabilizer, PSS4 (Table 6), which has two phase-lead
blocks of different parameters and one phase-lag block.
7
Bode Diagram
60 few others, would be to make the constant impedance part of
40
the shunt load vary with the X12 value, so as to better reflect
the capability of a given generating plant to contribute to the
Magnitude (dB)
20
damping of inter-area modes through well-designed
0 PSS1 stabilizers.
PSS2
-20
PSS3 Another contribution of this paper is to bring new evidence
PSS4
to the discussion on the use of a third phase compensation
-40
135 block (phase-lag) to improve stabilizer performance for low
frequency (0.2 Hz), poorly damped, inter-area modes.
90
PSS gain tuning performed during commissioning tests is
Phase (deg)