You are on page 1of 1

Last Measurement Deviation Report

*********************************

Database: FFC1-2019 New.rbm


Area: Uty-BU
Report Date: 28-Apr-20 11:46

Reference Value is the PREVIOUS DATA

POINT POINT CURRENT REF ABS. % ALR


ID DESCRIPTION VALUE VALUE UNITS DELTA DEV. SYM
----- ----------------------------- ------- ----- ------- ------- ---- ---

K-801B - Cooling Tower Fan (28-Apr-20) PARM = OVERALL


MAH=MOTOR O/B BRG HORIZONTAL 1.235 1.303 mm/Sec -.068 -5
MAV=MOTOR O/B BRG VERTICAL 1.178 1.239 mm/Sec -.061 -5
MAA=MOTOR O/B BRG AXIAL 1.421 1.455 mm/Sec -.034 -2
MBH=MOTOR I/B BRG HORIZONTAL 1.246 1.312 mm/Sec -.066 -5
MBV=MOTOR I/B BRG VERTICAL .828 .847 mm/Sec -.019 -2
MBA=MOTOR I/B BRG AXIAL 1.442 1.292 mm/Sec .150 12
M1P=MOTOR O/B BRG HORIZONTAL PKV .130 .129 G-s .0011 1
M2P=MOTOR I/B BRG HORIZONTAL PKV .155 .180 G-s -.025 -14

----------------------------------------------------------------------------

% - Maximum Percentage Alarm


+ - Maximum Delta Alarm
# - Maximum Value Alarm

Vibration values are normal.

For rectification of abnormal sound, greasing of motor bearing to be carried out.