DOC N0 SEPL-NRP-IOCL-150-CIV-DOC-02
Sr.NO Comments
Drawing & design calculations are not Senchronised few parameter in drawings is
1 shown different whatever assumed in design calculations
5 RCC tank is Fixed Base ,R shall be considered as 2 & I value shall be 1.5
Wall shall be designed for most critical case along Y & along X direction.The wall
9 shall be designed for cumulative effect hydrostatic & Hydrodynamic effect
10 Wall Stability,pressure check,sliding check not performed
11 Crack width for base slabshall also be checked
Sr.NO Comments
3 Show Calculaions
Actual Distribution & linear Distribution diagram for Impulsive & convective
4 pressure
5 Slashing wave height Calculation it shall be more than free board please check
6 Minimum Reinforcement of wall shall be 0.35%
Date-18-03-2021
Rev -B
Reply
Drawing & design calculations are not Senchronised few parameter in drawings is
1 shown different whatever assumed in design calculations
5 RCC tank is Fixed Base ,R shall be considered as 2 & I value shall be 1.5
Wall shall be designed for most critical case along Y & along X direction.The wall
9 shall be designed for cumulative effect hydrostatic & Hydrodynamic effect
10 Wall Stability,pressure check,sliding check not performed
11 Crack width for base slabshall also be checked
Reply