Professional Documents
Culture Documents
Mechanical Consultants
TOTAL 0 0 0 0 0 0 0 43
HADDAD
Mechanical Consultants
Input Data
Th System Highest Temp (Deg F): 80.0
Tl System Lowest Temp (Deg F): 44.0
P1 Static Pressure at Expansion Tank (Ft): 13.2
P2 Critical Equipment Max Operating Pressure (Psig): 146.0
DH Difference in Altitude between Expansion Tank and Critical Equipment (Ft): 0.0
DP Additive Pump Operating Pressure Effect at Critical Equipment (Ft): 62.4
Computed Data
P3 Relief Valve Setting (Psig): P3 = P2 - 7 = 139.0
P4 Adopted Max Op.Pressure at Critical Equip. (Psig): P4 = P3 x 0.9 = 125.1
Pf Min Operating Pressure at Expansion Tank (Psia): Pf = Ceiling of (P1/2.31) + 14.5 = 21.8
Pa Air Precharge To Expansion Tank (Bars): Pa = Pf / 14.5 = 1.5
Po Max Operating Pressure at Expansion Tank (Psia): Po = P5 - (DH+DP)/2.31 +14.5 = 112.6
E Percent Increase in Water Volume E (%): E= Function of (Th & Tl) = 0.242
Vs System Water Content (Gal): Vs = S Volumes = 619
Input Data
Th System Highest Temp (Deg F): 80.0
Tl System Lowest Temp (Deg F): 44.0
Computed Data
E Percent Increase in Water Volume E (%): E= Function of (Th & Tl) = 0.242
Vs System Water Content (Gal): Vs = S Volumes = 619.2