DRAKE & SCULL

HEAT LOAD CALCULATION


PROJECT :- VIP GOLF CLU VILLAS.
LOCATION FRESH AIR - KITCHEN - NORTH LATERAL WING
AREA :- 736 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 0.08 60 0
16 PARTITION 0.3 20 0
17 CEILING 0.4 30 0
18 FLOOR 0.322 15 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 0 1.1 35 0
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 4 PEOPLE X 245 980
32 LIGHTS WATTS Sqftx1.0x3.4xFACTOR 1.25 0
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM 6664 X DEG. F X 1.08 X B.F 0.176 44334.2592
35 SENSIBLE HEAT(SUB TOTAL) 45314.2592
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 4531.42592
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 49845.68512
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 10 % 61.5
43 EFFECTIVE ROOM LATENT LOAD(2) 676.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 50522.18512
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 49845.68512 0.986609842816712
46 ERSH(2) 50522.18512
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 1697.316
49 EFFECTIVE ROOM TOTAL HEAT (3) 50522.18512
50 Outside Air Sensible Ld 6664 X DegFX1.08X(1-B.F) 0.824 207564.9408
51 Outside Air Latent Ld 6664 XGR/LBX 0.68X(1- B.F) 0.824 235240.26624
52 SUB TOTAL 493327.39216
53 RETURN DUCT GAIN + HP PUMP 10 % 49332.739216
54 GRAND TOTAL HEAT 542660.131376
55 TONNES OF REFRIGERATION 45.2216776146667
56 FLOOR AREA - SQ.FT. 736 ON COIL DBT (DEG.F) 212.416970594545
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 148.376381516571
58 ON COIL H (BTU/LB) 111.991141684603
59 CFM/TR 37.5332345716095
60 SQ.FT./TR 16.2753802782693
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 542.660131376
66 SMBH 49.84568512
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION PASSAGE - NORTH LATERAL WING
AREA :- 736 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 335 0.06 33 663.3
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 820 0.06 40 1968
14 N.W. WALL 0.06 34 0
15 ROOF 736 0.08 60 3532.8
16 PARTITION 0.3 20 0
17 CEILING 0.4 30 0
18 FLOOR 736 0.322 15 3554.88
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 0 1.1 35 0
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 4 PEOPLE X 245 980
32 LIGHTS WATTS 300 Sqftx1.0x3.4xFACTOR 1.25 1275
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 11973.98
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 1197.398
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 13171.378
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 10 % 61.5
43 EFFECTIVE ROOM LATENT LOAD(2) 676.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 13847.878
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 13171.378 0.951147749857415
46 ERSH(2) 13847.878
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 448.504
49 EFFECTIVE ROOM TOTAL HEAT (3) 13847.878
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 13847.878
53 RETURN DUCT GAIN + HP PUMP 10 % 1384.7878
54 GRAND TOTAL HEAT 15232.6658
55 TONNES OF REFRIGERATION 1.26938881666667
56 FLOOR AREA - SQ.FT. 736 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 353.322779819902
60 SQ.FT./TR 579.806589073857
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 15.2326658
66 SMBH 13.171378
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION- NORTH LATERAL WING
AREA :- 559 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 195 0.06 46 538.2
10 S.E. WALL 0.06 46 0
11 S. WALL 352 0.06 44 929.28
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 559 0.08 60 2683.2
16 PARTITION 135 0.3 20 810
17 CEILING 0.4 30 0
18 FLOOR 559 0.322 15 2699.97
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 92 11 0.37 374.44
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 92 1.1 35 3542
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 6 PEOPLE X 245 1470
32 LIGHTS WATTS 1500 Sqftx1.0x3.4xFACTOR 1.25 6375
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 19422.09
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 1942.209
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 21364.299
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 10 % 61.5
43 EFFECTIVE ROOM LATENT LOAD(2) 676.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 22040.799
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 21364.299 0.969306920316273
46 ERSH(2) 22040.799
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 727.484
49 EFFECTIVE ROOM TOTAL HEAT (3) 22040.799
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 22040.799
53 RETURN DUCT GAIN + HP PUMP 10 % 2204.0799
54 GRAND TOTAL HEAT 24244.8789
55 TONNES OF REFRIGERATION 2.020406575
56 FLOOR AREA - SQ.FT. 559 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 360.068365441809
60 SQ.FT./TR 276.67698517562
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 24.2448789
66 SMBH 21.364299
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION RECEIVING- NORTH LATERAL WING
AREA :- 303 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 252.75 0.06 33 500.445
8 N.E. WALL 0.06 38 0
9 E. WALL 106 0.06 46 292.56
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 154 0.06 40 369.6
14 N.W. WALL 0.06 34 0
15 ROOF 303 0.08 60 1454.4
16 PARTITION 151 0.3 30 1359
17 CEILING 0.4 30 0
18 FLOOR 303 0.322 15 1463.49
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 109 11 0.37 443.63
21 N.E 11 0.37 0
22 E 45 11 0.37 183.15
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 154 1.1 35 5929
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 500 Sqftx1.0x3.4xFACTOR 1.25 2125
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 14855.275
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 1485.5275
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 16340.8025
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 10 % 61.5
43 EFFECTIVE ROOM LATENT LOAD(2) 676.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 17017.3025
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 16340.8025 0.960246343390793
46 ERSH(2) 17017.3025
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 556.427
49 EFFECTIVE ROOM TOTAL HEAT (3) 17017.3025
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 17017.3025
53 RETURN DUCT GAIN + HP PUMP 10 % 1701.73025
54 GRAND TOTAL HEAT 18719.03275
55 TONNES OF REFRIGERATION 1.55991939583333
56 FLOOR AREA - SQ.FT. 303 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 356.702633644028
60 SQ.FT./TR 194.240805524527
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 18.71903275
66 SMBH 16.3408025
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION KITCHEN-NORTH LATERAL WING
AREA :- 2432 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 353 0.06 33 698.94
8 N.E. WALL 0.06 38 0
9 E. WALL 756 0.06 46 2086.56
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 2432 0.08 60 11673.6
16 PARTITION 723.5 0.3 20 4341
17 CEILING 0.4 30 0
18 FLOOR 2432 0.322 15 11746.56
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 460 11 0.37 1872.2
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 460 1.1 35 17710
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 20 PEOPLE X 245 4900
32 LIGHTS WATTS 3000 Sqftx1.0x3.4xFACTOR 1.25 12750
33 APPLIANCES 8110 W X 3.4 27574
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 95352.86
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 9535.286
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 104888.146
38 PEOPLE 20 PEOPLE X 205 4100
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 4100
42 SAFETY FACTOR 10 % 410
43 EFFECTIVE ROOM LATENT LOAD(2) 4510
44 EFFECTIVE ROOM TOTAL LOAD (3) 109398.146
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 104888.146 0.958774438462604
46 ERSH(2) 109398.146
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 3571.589
49 EFFECTIVE ROOM TOTAL HEAT (3) 109398.146
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 109398.146
53 RETURN DUCT GAIN + HP PUMP 10 % 10939.8146
54 GRAND TOTAL HEAT 120337.9606
55 TONNES OF REFRIGERATION 10.0281633833333
56 FLOOR AREA - SQ.FT. 2432 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 356.155865236138
60 SQ.FT./TR 242.516990104285
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 120.3379606
66 SMBH 104.888146
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-8
AREA :- 217 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 133 0.06 46 367.08
10 S.E. WALL 0.06 46 0
11 S. WALL 234 0.06 44 617.76
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 217 0.08 60 1041.6
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 21 11 0.37 85.47
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 4675.41
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-8
AREA :- 217 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 233.7705
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 4909.1805
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 5554.9305
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 4909.1805 0.883751920928624
46 ERSH(2) 5554.9305
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 167.165
49 EFFECTIVE ROOM TOTAL HEAT (3) 5554.9305
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 5554.9305
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 5554.9305
55 TONNES OF REFRIGERATION 0.462910875
56 FLOOR AREA - SQ.FT. 217 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 361.115982204171
60 SQ.FT./TR 468.77274162116
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 7.22140965
66 SMBH 6.38193465
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-7
AREA :- 350 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 190 0.06 44 501.6
12 S.W. WALL 0.06 42 0
13 W. WALL 133 0.06 40 319.2
14 N.W. WALL 0.06 34 0
15 ROOF 350 0.08 60 1680
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 21 165 0.37 1282.05
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 6346.35
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-7
AREA :- 350 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 317.3175
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 6663.6675
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 7309.4175
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 6663.6675 0.911655066905126
46 ERSH(2) 7309.4175
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 226.907
49 EFFECTIVE ROOM TOTAL HEAT (3) 7309.4175
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 7309.4175
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 7309.4175
55 TONNES OF REFRIGERATION 0.609118125
56 FLOOR AREA - SQ.FT. 350 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 372.517679589228
60 SQ.FT./TR 574.601190860968
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 9.50224275
66 SMBH 8.66276775
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-6
AREA :- 217 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 234 0.06 33 463.32
8 N.E. WALL 0.06 38 0
9 E. WALL 133 0.06 46 367.08
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 217 0.08 60 1041.6
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 21 11 0.37 85.47
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 4520.97
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-6
AREA :- 217 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 226.0485
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 4747.0185
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 5392.7685
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 4747.0185 0.880256309908352
46 ERSH(2) 5392.7685
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 161.643
49 EFFECTIVE ROOM TOTAL HEAT (3) 5392.7685
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 5392.7685
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 5392.7685
55 TONNES OF REFRIGERATION 0.449397375
56 FLOOR AREA - SQ.FT. 217 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 359.687616418371
60 SQ.FT./TR 482.868864109409
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 7.01059905
66 SMBH 6.17112405
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-5
AREA :- 315 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 234 0.06 33 463.32
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 133 0.06 40 319.2
14 N.W. WALL 0.06 34 0
15 ROOF 315 0.08 60 1512
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 21 165 0.37 1282.05
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 6140.07
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-5
AREA :- 315 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 307.0035
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 6447.0735
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 7092.8235
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 6447.0735 0.908957272093405
46 ERSH(2) 7092.8235
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 219.532
49 EFFECTIVE ROOM TOTAL HEAT (3) 7092.8235
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 7092.8235
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 7092.8235
55 TONNES OF REFRIGERATION 0.591068625
56 FLOOR AREA - SQ.FT. 315 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 371.415315000084
60 SQ.FT./TR 532.933041404456
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 9.22067055
66 SMBH 8.38119555
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION OPERATOR BED ROOM / OFFICE
AREA :- 248 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 121 0.06 33 239.58
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 100 0.06 40 240
14 N.W. WALL 0.06 34 0
15 ROOF 248 0.08 60 1190.4
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 22 11 0.37 89.54
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 65 165 0.37 3968.25
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 87 1.1 35 3349.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 2 PEOPLE X 245 490
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 10587.27
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION OPERATOR BED ROOM / OFFICE
AREA :- 248 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 529.3635
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 11116.6335
38 PEOPLE 2 PEOPLE X 205 410
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 410
42 SAFETY FACTOR 5 % 20.5
43 EFFECTIVE ROOM LATENT LOAD(2) 430.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 11547.1335
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 11116.6335 0.962718020017695
46 ERSH(2) 11547.1335
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 378.537
49 EFFECTIVE ROOM TOTAL HEAT (3) 11547.1335
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 11547.1335
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 11547.1335
55 TONNES OF REFRIGERATION 0.962261125
56 FLOOR AREA - SQ.FT. 248 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 393.382865882815
60 SQ.FT./TR 257.726300644225
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 15.01127355
66 SMBH 14.45162355
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION MAIN CONTROL ROOM/PASSAGE
AREA :- 462 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 61 0.06 33 120.78
8 N.E. WALL 0.06 38 0
9 E. WALL 251 0.06 46 692.76
10 S.E. WALL 0.06 46 0
11 S. WALL 224 0.06 44 591.36
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 462 0.08 60 2217.6
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 65 11 0.37 264.55
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 0 121 0.37 0
26 W 0 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 65 1.1 35 2502.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 600 Sqftx1.0x3.4xFACTOR 1.25 2550
33 APPLIANCES 3000 W X 3.4 10200
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 19874.55
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION MAIN CONTROL ROOM/PASSAGE
AREA :- 462 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 993.7275
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 20868.2775
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 21514.0275
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 20868.2775 0.969984699517559
46 ERSH(2) 21514.0275
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 710.594
49 EFFECTIVE ROOM TOTAL HEAT (3) 21514.0275
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 21514.0275
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 21514.0275
55 TONNES OF REFRIGERATION 1.792835625
56 FLOOR AREA - SQ.FT. 462 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 396.352154031234
60 SQ.FT./TR 257.69233584925
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 27.96823575
66 SMBH 27.12876075
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION METAL DETECTOR&WAITING/RECEPTION
AREA :- 448 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 325 0.06 44 858
12 S.W. WALL 0.06 42 0
13 W. WALL 86 0.06 40 206.4
14 N.W. WALL 0.06 34 0
15 ROOF 448 0.08 60 2150.4
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 80 12 0.37 355.2
25 S.W 121 0.37 0
26 W 65 165 0.37 3968.25
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 145 1.1 35 5582.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 8 PEOPLE X 245 1960
32 LIGHTS WATTS 600 Sqftx1.0x3.4xFACTOR 1.25 2550
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 17630.75
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION METAL DETECTOR&WAITING/RECEPTION
AREA :- 448 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 881.5375
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 18512.2875
38 PEOPLE 8 PEOPLE X 205 1640
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 1640
42 SAFETY FACTOR 5 % 82
43 EFFECTIVE ROOM LATENT LOAD(2) 1722
44 EFFECTIVE ROOM TOTAL LOAD (3) 20234.2875
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 18512.2875 0.914896929284019
46 ERSH(2) 20234.2875
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 630.369
49 EFFECTIVE ROOM TOTAL HEAT (3) 20234.2875
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 20234.2875
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 20234.2875
55 TONNES OF REFRIGERATION 1.686190625
56 FLOOR AREA - SQ.FT. 448 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 373.84235938839
60 SQ.FT./TR 265.687635405991
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 26.30457375
66 SMBH 24.06597375
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION LOBBY
AREA :- 326 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 110 0.06 33 217.8
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 326 0.08 60 1564.8
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 65 11 0.37 264.55
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 65 1.1 35 2502.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 4 PEOPLE X 245 980
32 LIGHTS WATTS 400 Sqftx1.0x3.4xFACTOR 1.25 1700
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 7229.65
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION LOBBY
AREA :- 326 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 361.4825
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 7591.1325
38 PEOPLE 4 PEOPLE X 205 820
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 820
42 SAFETY FACTOR 5 % 41
43 EFFECTIVE ROOM LATENT LOAD(2) 861
44 EFFECTIVE ROOM TOTAL LOAD (3) 8452.1325
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 7591.1325 0.898132216928686
46 ERSH(2) 8452.1325
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 258.489
49 EFFECTIVE ROOM TOTAL HEAT (3) 8452.1325
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 8452.1325
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 8452.1325
55 TONNES OF REFRIGERATION 0.704344375
56 FLOOR AREA - SQ.FT. 326 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 366.99201437052
60 SQ.FT./TR 462.841773954679
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 10.98777225
66 SMBH 9.86847225
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION PALACE GUARD BEDROOM/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 103 0.06 33 203.94
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 203 0.08 60 974.4
16 PARTITION 0.3 30 0
17 CEILING 0.4 30 0
18 FLOOR 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 0 1.1 35 0
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 2 PEOPLE X 245 490
32 LIGHTS WATTS 200 Sqftx1.0x3.4xFACTOR 1.25 850
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 2518.34
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION PALACE GUARD BEDROOM/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 125.917
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 2644.257
38 PEOPLE 2 PEOPLE X 205 410
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 410
42 SAFETY FACTOR 5 % 20.5
43 EFFECTIVE ROOM LATENT LOAD(2) 430.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 3074.757
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 2644.257 0.859988935711017
46 ERSH(2) 3074.757
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 90.041
49 EFFECTIVE ROOM TOTAL HEAT (3) 3074.757
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 3074.757
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 3074.757
55 TONNES OF REFRIGERATION 0.25622975
56 FLOOR AREA - SQ.FT. 203 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 351.406024529689
60 SQ.FT./TR 792.25772963522
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 3.9971841
66 SMBH 3.4375341
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION PALAVE GUARD OFFICE/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 106 0.06 33 209.88
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 145 0.06 40 348
14 N.W. WALL 0.06 34 0
15 ROOF 203 0.08 60 974.4
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 65 165 0.37 3968.25
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 65 1.1 35 2502.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 2 PEOPLE X 245 490
32 LIGHTS WATTS 300 Sqftx1.0x3.4xFACTOR 1.25 1275
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM 0 X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 9768.03
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION PALAVE GUARD OFFICE/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 488.4015
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 10256.4315
38 PEOPLE 2 PEOPLE X 205 410
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 410
42 SAFETY FACTOR 5 % 20.5
43 EFFECTIVE ROOM LATENT LOAD(2) 430.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 10686.9315
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 10256.4315 0.959717155480972
46 ERSH(2) 10686.9315
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 349.246
49 EFFECTIVE ROOM TOTAL HEAT (3) 10686.9315
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 10686.9315
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 10686.9315
55 TONNES OF REFRIGERATION 0.890577625
56 FLOOR AREA - SQ.FT. 203 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 392.156661878074
60 SQ.FT./TR 227.941949473523
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 13.89301095
66 SMBH 13.33336095
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION SPECIAL GUARD BEDROOM/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 106 0.06 33 209.88
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 203 0.08 60 974.4
16 PARTITION 77 0.3 30 693
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 0 1.1 35 0
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 2 PEOPLE X 245 490
32 LIGHTS WATTS 300 Sqftx1.0x3.4xFACTOR 1.25 1275
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM 0 X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 3642.28
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION SPECIAL GUARD BEDROOM/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 182.114
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 3824.394
38 PEOPLE 2 PEOPLE X 205 410
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 410
42 SAFETY FACTOR 5 % 20.5
43 EFFECTIVE ROOM LATENT LOAD(2) 430.5
44 EFFECTIVE ROOM TOTAL LOAD (3) 4254.894
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 3824.394 0.898822391345119
46 ERSH(2) 4254.894
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 130.226
49 EFFECTIVE ROOM TOTAL HEAT (3) 4254.894
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 4254.894
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 4254.894
55 TONNES OF REFRIGERATION 0.3545745
56 FLOOR AREA - SQ.FT. 203 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 367.27403131032
60 SQ.FT./TR 572.517200193471
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 5.5313622
66 SMBH 4.9717122
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION SPECIAL GUARD OFFICE/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 145 0.06 46 400.2
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 106 0.06 34 216.24
15 ROOF 203 0.08 60 974.4
16 PARTITION 77 0.3 30 693
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 65 11 0.37 264.55
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 65 1.1 35 2502.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM 0 X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 6805.89
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION SPECIAL GUARD OFFICE/PASSAGE
AREA :- 203 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 340.2945
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 7146.1845
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 7791.9345
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 7146.1845 0.917125843396143
46 ERSH(2) 7791.9345
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 243.338
49 EFFECTIVE ROOM TOTAL HEAT (3) 7791.9345
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 7791.9345
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 7791.9345
55 TONNES OF REFRIGERATION 0.649327875
56 FLOOR AREA - SQ.FT. 203 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 374.753131393278
60 SQ.FT./TR 312.630964749511
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 10.12951485
66 SMBH 9.29003985
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ARMOUR STORE/OFFICE
AREA :- 220 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0 0.06 38 0
9 E. WALL 0 0.06 46 0
10 S.E. WALL 0 0.06 46 0
11 S. WALL 94 0.06 44 248.16
12 S.W. WALL 0 0.06 42 0
13 W. WALL 0 0.06 40 0
14 N.W. WALL 0 0.06 34 0
15 ROOF 220 0.08 60 1056
16 PARTITION 77 0.3 30 693
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 0 11 0.37 0
22 E 0 11 0.37 0
23 S.E 0 11 0.37 0
24 S 9 12 0.37 39.96
25 S.W 0 121 0.37 0
26 W 0 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 9 1.1 35 346.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 400 Sqftx1.0x3.4xFACTOR 1.25 1700
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 4818.62
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ARMOUR STORE/OFFICE
AREA :- 220 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 240.931
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 5059.551
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 5705.301
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 5059.551 0.886815787633291
46 ERSH(2) 5705.301
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 172.285
49 EFFECTIVE ROOM TOTAL HEAT (3) 5705.301
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 5705.301
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 5705.301
55 TONNES OF REFRIGERATION 0.47544175
56 FLOOR AREA - SQ.FT. 220 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 362.367929960319
60 SQ.FT./TR 462.727558107802
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 7.4168913
66 SMBH 6.5774163
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION STORAGE/PANTRY
AREA :- 144 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 85 0.06 44 224.4
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 144 0.08 60 691.2
16 PARTITION 77 0.3 30 693
17 CEILING 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 18 12 0.37 79.92
25 S.W 121 0.37 0
26 W 0 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 18 1.1 35 693
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 400 Sqftx1.0x3.4xFACTOR 1.25 1700
33 APPLIANCES 500 W X 3.4 1700
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 6516.52
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION STORAGE/PANTRY
AREA :- 144 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 325.826
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 6842.346
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 7488.096
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 6842.346 0.913763124831733
46 ERSH(2) 7488.096
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 232.992
49 EFFECTIVE ROOM TOTAL HEAT (3) 7488.096
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 7488.096
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 7488.096
55 TONNES OF REFRIGERATION 0.624008
56 FLOOR AREA - SQ.FT. 144 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 373.379067712617
60 SQ.FT./TR 230.766272227279
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 9.7345248
66 SMBH 8.8950498
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-4
AREA :- 217 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 173 0.06 33 342.54
8 N.E. WALL 0.06 38 0
9 E. WALL 133 0.06 46 367.08
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 217 0.08 60 1041.6
16 PARTITION 0.3 30 0
17 CEILING 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 21 11 0.37 85.47
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 4400.19
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-4
AREA :- 217 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 220.0095
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 4620.1995
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 5265.9495
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 4620.1995 0.877372542216746
46 ERSH(2) 5265.9495
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 157.324
49 EFFECTIVE ROOM TOTAL HEAT (3) 5265.9495
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 5265.9495
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 5265.9495
55 TONNES OF REFRIGERATION 0.438829125
56 FLOOR AREA - SQ.FT. 217 ON COIL DBT (DEG.F) 75
57 HEIGHT 2.4 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 358.509260165059
60 SQ.FT./TR 494.497715938977
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 6.84573435
66 SMBH 6.00625935
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-3
AREA :- 351 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 190 0.06 33 376.2
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 0.06 44 0
12 S.W. WALL 0.06 42 0
13 W. WALL 203 0.06 40 487.2
14 N.W. WALL 0.06 34 0
15 ROOF 351 0.08 60 1684.8
16 PARTITION 0.3 30 0
17 CEILING 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 21 165 0.37 1282.05
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 4 PEOPLE X 245 980
32 LIGHTS WATTS 320 Sqftx1.0x3.4xFACTOR 1.25 1360
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 6978.75
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-3
AREA :- 351 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 348.9375
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 7327.6875
38 PEOPLE 4 PEOPLE X 205 820
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 820
42 SAFETY FACTOR 5 % 41
43 EFFECTIVE ROOM LATENT LOAD(2) 861
44 EFFECTIVE ROOM TOTAL LOAD (3) 8188.6875
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 7327.6875 0.894854944702677
46 ERSH(2) 8188.6875
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 249.518
49 EFFECTIVE ROOM TOTAL HEAT (3) 8188.6875
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 8188.6875
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 8188.6875
55 TONNES OF REFRIGERATION 0.682390625
56 FLOOR AREA - SQ.FT. 351 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 365.652865508923
60 SQ.FT./TR 514.368145078195
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 10.64529375
66 SMBH 9.52599375
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-2
AREA :- 217 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 133 0.06 46 367.08
10 S.E. WALL 0.06 46 0
11 S. WALL 234 0.06 44 617.76
12 S.W. WALL 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0.06 34 0
15 ROOF 234 0.08 60 1123.2
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 0 0.322 30 0
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 21 11 0.37 85.47
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 165 0.37 0
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 21 1.1 35 808.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 240 Sqftx1.0x3.4xFACTOR 1.25 1020
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 4757.01
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-2
AREA :- 217 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 237.8505
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 4994.8605
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 5640.6105
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 4994.8605 0.885517711247745
46 ERSH(2) 5640.6105
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 170.082
49 EFFECTIVE ROOM TOTAL HEAT (3) 5640.6105
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 5640.6105
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 5640.6105
55 TONNES OF REFRIGERATION 0.470050875
56 FLOOR AREA - SQ.FT. 217 ON COIL DBT (DEG.F) 75
57 HEIGHT 2.4 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 361.837513994208
60 SQ.FT./TR 461.652156269255
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 7.33279365
66 SMBH 6.49331865
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-1
AREA :- 315 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 0.06 46 0
10 S.E. WALL 0.06 46 0
11 S. WALL 334 0.06 44 881.76
12 S.W. WALL 0.06 42 0
13 W. WALL 233 0.06 40 559.2
14 N.W. WALL 0.06 34 0
15 ROOF 315 0.08 60 1512
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 315 0.322 30 3042.9
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 11 0.37 0
21 N.E 11 0.37 0
22 E 11 0.37 0
23 S.E 11 0.37 0
24 S 12 0.37 0
25 S.W 121 0.37 0
26 W 31 165 0.37 1892.55
27 NW 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 31 1.1 35 1193.5
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 3 PEOPLE X 245 735
32 LIGHTS WATTS 340 Sqftx1.0x3.4xFACTOR 1.25 1445
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 11261.91
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-1
AREA :- 315 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 5 % 563.0955
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION ACCOMODATION-1
AREA :- 315 SQ. FT. Date 26.09.2011
PREPARED BY :- BM
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 11825.0055
38 PEOPLE 3 PEOPLE X 205 615
39 LATENT LOAD OUTDOOR AIR CFM X GR/LB X 0.68 X B.F 0.176 0
40
41 LATENT HEAT LOAD (SUB TOTAL) 615
42 SAFETY FACTOR 5 % 30.75
43 EFFECTIVE ROOM LATENT LOAD(2) 645.75
44 EFFECTIVE ROOM TOTAL LOAD (3) 12470.7555
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 11825.0055 0.94821885490418
46 ERSH(2) 12470.7555
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 402.658
49 EFFECTIVE ROOM TOTAL HEAT (3) 12470.7555
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 12470.7555
53 RETURN DUCT GAIN + HP PUMP 0 % 0
54 GRAND TOTAL HEAT 12470.7555
55 TONNES OF REFRIGERATION 1.039229625
56 FLOOR AREA - SQ.FT. 315 ON COIL DBT (DEG.F) 75
57 HEIGHT 2.4 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 387.45826178622
60 SQ.FT./TR 303.109142024314
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 16.21198215
66 SMBH 15.37250715
DRAKE & SCULL
HEAT LOAD CALCULATION
PROJECT :- VIP GOLF CLU VILLAS.
LOCATION MEETING ROOM/ENTRANCE/BAR&TEA ROOM AT SOUTH WING
AREA :- 2770 SQ. FT. Date 24.09.2011
PREPARED BY :- BM
1 CONDITIONS DB(DEG.F) WB(DEG.F) %RH BTU/LB GR/LB
2 OUTSIDE 110 84 48.2 128
3 INSIDE 75 62 50 26.4 65
4 DIFF. 35 22 *** 21.8 63
5
6 ITEM AREA SQ.FT U FACTOR EQ. TEMP BTU/HR.
7 N.WALL 0 0.06 33 0
8 N.E. WALL 0.06 38 0
9 E. WALL 842 0.06 46 2323.92
10 S.E. WALL 0 0.06 46 0
11 S. WALL 206 0.06 44 543.84
12 S.W. WALL 0 0.06 42 0
13 W. WALL 0.06 40 0
14 N.W. WALL 0 0.06 34 0
15 ROOF 2770 0.08 60 13296
16 PARTITION 0.3 30 0
17 CEILING 0 0.4 30 0
18 FLOOR 2770 0.322 30 26758.2
19 ITEM AREA SQ.FT SOLAR GAIN FACTOR
20 N 0 11 0.37 0
21 N.E 11 0.37 0
22 E 543 11 0.37 2210.01
23 S.E 0 11 0.37 0
24 S 107 12 0.37 475.08
25 S.W 0 121 0.37 0
26 W 0 165 0.37 0
27 NW 0 109 0.37 0
28 TRANS HEAT GAIN AREA SQ.FT FACTOR TEMP DIFF.
29 ALL GLASS 650 1.1 35 25025
30 INTERNAL HEAT
31 INTERNAL HEAT PEOPLE 25 PEOPLE X 245 6125
32 LIGHTS WATTS 3000 Sqftx1.0x3.4xFACTOR 1.25 12750
33 APPLIANCES W X 3.4 0
34 OUTDOOR AIR CFM 0 X DEG. F X 1.08 X B.F 0.176 0
35 SENSIBLE HEAT(SUB TOTAL) 89507.05
36 SUPPLY DUCT GAIN + FAN H.P+ SAFETY 10 % 8950.705
37 EFFECTIVE ROOM SENSIBLE HEAT (1) 98457.755
38 PEOPLE 25 PEOPLE X 205 5125
39 LATENT LOAD OUTDOOR AIR CFM 400 X GR/LB X 0.68 X B.F 0.176 3015.936
40
41 LATENT HEAT LOAD (SUB TOTAL) 8140.936
42 SAFETY FACTOR 10 % 814.0936
43 EFFECTIVE ROOM LATENT LOAD(2) 8955.0296
44 EFFECTIVE ROOM TOTAL LOAD (3) 107412.7846
45 ESHF SENSIBLE HEAT FACTOR =ERSH(1) 98457.755 0.916629760290192
46 ERSH(2) 107412.7846
47 ADP 42
48 DEH. AIR (CFM) ERSH/1.08(TRM-TADP)(1-BF) 3352.625
49 EFFECTIVE ROOM TOTAL HEAT (3) 107412.7846
50 Outside Air Sensible Ld 0 X DegFX1.08X(1-B.F) 0.824 0
51 Outside Air Latent Ld 0 XGR/LBX 0.68X(1- B.F) 0.824 0
52 SUB TOTAL 107412.7846
53 RETURN DUCT GAIN + HP PUMP 10 % 10741.27846
54 GRAND TOTAL HEAT 118154.06306
55 TONNES OF REFRIGERATION 9.84617192166667
56 FLOOR AREA - SQ.FT. 2770 ON COIL DBT (DEG.F) 75
57 HEIGHT 4.1 ON COIL WBT (DEG.F) 62
58 ON COIL H (BTU/LB) 26.4
59 CFM/TR 340.500384950636
60 SQ.FT./TR 281.327608540388
61
62 Assumptions :
63
64 CAPACITY DETAILS CALCULATED CAPACITY
65 TMBH 118.15406306
66 SMBH 98.457755