GITET 500 kV MUARA ENIM

500 kV & 70 kV Single Phase Current Transformer

Isn Tp t'al t' Rb Rct Eal Burden


No. Bay Name Qty Ratio Class Kssc Tap Remark
(A) (ms) (ms) (ms) (Ω) (Ω) (V) (VA)

25.00
5.5 5# Kssc x Ktd x Isr x (5.00+RCT) at lower ratio
Core 1 : 2000-4000/1A TPX 1 120 20
24 62
65 12.5 5.00
3 - For Busbar Protection
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio

Core 2 : 2000-4000/1A TPX 1 120 20


24 62
65
25.00
12.5
5'5
5.00
3
5# Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Busbar Protection
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
DIAMETER 7 20 at lower ratio
1 3 units Core 3 : 2000-4000/1A 5P20 1 - - - - - - For Breaker Failure Protection
(CUT OFF B / BUS BAR B) 40 at higher ratio
25.00 5.5 5# Kssc x Ktd x Isr x ((5.00+RCT)) at lower ratio
Core 4 : 2000-4000/1A TPX 1 120 36
24 78
65 12.5 5.00
3 - For Circulating Current Protection
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio

Core 5 : 2000-4000/1A TPX 1 120 36 78


25.00 5.5
5.00
#5 Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Circulating Current Protection
24 65 12.5 3
12.50 #
10 Kssc x Ktd x Isr x (5.00+RCT) at higher ratio

Core 1 : 2000-4000/1A TPX 1 120 36


24 78
25.00 5.5
5.00
3
#5 Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Circulating Current Protection
65 12.5
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
25.00 5.5 5# Kssc x Ktd x Isr x (5.00+RCT) at lower ratio
Core 2 : 2000-4000/1A TPX 1 120 36
24 78
65 12.5 5.00
3 - For Circulating Current Protection
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
DIAMETER 7 20 at lower ratio
2 3 units Core 3 : 2000-4000/1A 5P20 1 - - - - - - For Breaker Failure Protection
(CUT OFF AB / CENTER) 40 at higher ratio

Core 4 : 2000-4000/1A TPX 1 120 36 78


25.00 5.5
5.00
5# Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Circulating Current Protection
24 65 12.5 3
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio

Core 5 : 2000-4000/1A TPX 1 120 36 78


25.00 5.5
5.00
5# Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Circulating Current Protection
24 65 12.5 3
12.50 10# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
8.33 6 4# Kssc x Ktd x Isr x (5.00+RCT) at lower ratio
Core 1 : 600-1200/1A TPX 1 120 36
24 78
65 6.72 5.00
3 - For Trafo Differential Protection
INTERBUS TRAFO 3 4.17 8# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
3 3 units
(COMMON WINDING) 8.33 6 4# Kssc x Ktd x Isr x (5.00+RCT)
( ) at lower ratio
Core 2 : 600-1200/1A TPX 1 120 36
24 78
65 6.72 5.00
3 - For Trafo Differential Protection
4.17 8# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
15.00 6 4# Kssc x Ktd x Isr x (5.00+RCT) at lower ratio
Core 1 : 600-1200/1A TPX 1 120 45
24 87
65 6.72 5.00
3 - For Trafo REF Protection
INTERBUS TRAFO 3 7.50 8# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio
4 1 units
(EARTHING SUMMATION POINT)
Core 2 : 600-1200/1A TPX 1 120 45
24 87
65
15.00
6.72
65.00
3
4# Kssc x Ktd x Isr x (5.00+RCT)
-
at lower ratio
For Trafo REF Protection
7.50 8# Kssc x Ktd x Isr x (5.00+RCT) at higher ratio