You are on page 1of 1

Current Transformer

Window – Type MAG ELECTRIC Co.


0.72/ 3kV; 50 – 60 Hz

Type AL1

Secondary 1A,5A
Primary Class 0.5 Class 1 Class 3
Window Sizes A Max(VA) Max(VA) Max(VA)
50  5 5 7.5
Bars 75  10 10 12.5
30 × 10 or 100 5 5 7.5
150 10 10 12.5
20 × 10
200 10 12.5 15
250 12.5 15 17.5
Round conductors up to 23 ∅
300 15 17.5 20
400 15 17.5 22.5
Accessories on request:
500 15 17.5 27.5
Secondary terminal cover
600 15 17.5 27.5
Mounting feet
Other VA-Ratings, special ratios and CT’s class 0.2 on request

Dimensions in mm Only for cable conductors with primary 2 turns-for VA ≥ 1.25(CL0.5,1) VA ≥ 2.5 (CL 3)

Type AL2

Window Sizes

Bars Secondary 1A,5A


40 × 10 or Primary Class 0.5 Class 1 Class 3
30 × 10 A Max(VA) Max(VA) Max(VA)
200 5 7.5 10
Round conductors up to 25 ∅ 250 7.5 10 12.5
300 10 12.5 15
Accessories on request: 400 25 30 37.5
Secondary terminal cover 500 30 35 45
Mounting feet 600 30 35 50
800 35 40 50
Dimensions in mm Other VA-Ratings, special ratios and CT’s class 0.2 on request

! It is recommended to select the minimum required VA, otherwise the CTs security factor and price will increase.