Automation Portal

7UT87_220kV M3GSUT
7UT87_220kV M3GSUT

Creation time: 06/09/2020 06:56:50


Last modified time: 06/15/2020 13:14:32
Modified by: Unnamed User
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Device information
Device details
Name Value
Name 7UT87_220kV M3GSUT
IEC 61850 name SIP2
IEC 61850 Edition IEC 61850 Edition 2.1
Type 7UT87
Serial number BM2002008838
Configuration version V08.01.12
Communication configuration version V08.01.12
Product code 7UT87-DAAA-AA0-0AAAA0-AF0111-12111B-BAA000-000AC0-CC1BA1-CC1CF0
Short product code P1F404312
CPU type CP300

Function points
Function-points consumption: Used 50 out of 50

Function-chart (CFC) statistics


Name Value
Ticks for task Interlocking and Measurement 0 out of 127426
Ticks for task Event-Triggered 241 out of 13537
Ticks for task Fast Event-Triggered 0 out of 1000
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Hardware and protocols
Binary inputs
Binary input Terminals Module User label Threshold value
1.1 1D11-1D9 Base module BI 1.1 Low: 44 V, High: 88 V
1.2 1D12-1D10 Base module BI 1.2 Low: 44 V, High: 88 V
1.3 1D11-1D13 Base module BI 1.3 Low: 44 V, High: 88 V
1.4 1D12-1D14 Base module BI 1.4 Low: 44 V, High: 88 V
2.1 2B11-2B12 Base module BI 2.1 Low: 44 V, High: 88 V
2.2 2B11-2B14 Base module BI 2.2 Low: 44 V, High: 88 V
2.3 2B11-2B13 Base module BI 2.3 Low: 44 V, High: 88 V
3.1 3D11-3D9 Expansion module 3 BI 3.1 Low: 44 V, High: 88 V
3.2 3D12-3D10 Expansion module 3 BI 3.2 Low: 44 V, High: 88 V
3.3 3D11-3D13 Expansion module 3 BI 3.3 Low: 44 V, High: 88 V
3.4 3D12-3D14 Expansion module 3 BI 3.4 Low: 44 V, High: 88 V
4.1 4A1-4A3 Expansion module 4 BI 4.1 Low: 44 V, High: 88 V
4.2 4A2-4A4 Expansion module 4 BI 4.2 Low: 44 V, High: 88 V
4.3 4A5-4A7 Expansion module 4 BI 4.3 Low: 44 V, High: 88 V
4.4 4A6-4A8 Expansion module 4 BI 4.4 Low: 44 V, High: 88 V
4.5 4A9-4A11 Expansion module 4 BI 4.5 Low: 44 V, High: 88 V
4.6 4A10-4A12 Expansion module 4 BI 4.6 Low: 44 V, High: 88 V

Binary outputs
Binary output Terminals Module User label
1.1 1D1-1D2 Base module BO-F make 1.1
1.2 1D3-1D4 Base module BO-F make 1.2
1.3 1D5-1D6 Base module BO-F make 1.3
1.4 1D7-1D8 Base module BO-F make 1.4
2.1 2B3-2B4 Base module BO make 2.1
2.2 2B5-2B6-2B8 Base module BO change-over 2.2
3.1 3D1-3D2 Expansion module 3 BO-F make 3.1
3.2 3D3-3D4 Expansion module 3 BO-F make 3.2
3.3 3D5-3D6 Expansion module 3 BO-F make 3.3
3.4 3D7-3D8 Expansion module 3 BO-F make 3.4
4.1 4D1-4D2 Expansion module 4 BO make 4.1
4.2 4D3-4D4 Expansion module 4 BO make 4.2
4.3 4D5-4D6 Expansion module 4 BO make 4.3
4.4 4D7-4D8 Expansion module 4 BO make 4.4
4.5 4D9-4D10 Expansion module 4 BO make 4.5
4.6 4D11-4D12 Expansion module 4 BO make 4.6
4.7 4D13-4D14 Expansion module 4 BO make 4.7

Current transformers
Current transformer Terminals Module User label
1A1 1A1-1A2 Base module I P 1A1
1A2 1A3-1A4 Base module I P 1A2
1A3 1A5-1A6 Base module I P 1A3
1A4 1A7-1A8 Base module I P 1A4
1B1 1B1-1B2 Base module I P 1B1
1B2 1B3-1B4 Base module I P 1B2
1B3 1B5-1B6 Base module I P 1B3
1B4 1B7-1B8 Base module I P 1B4
3A1 3A1-3A2 Expansion module 3 I P 3A1
3A2 3A3-3A4 Expansion module 3 I P 3A2
3A3 3A5-3A6 Expansion module 3 I P 3A3
3A4 3A7-3A8 Expansion module 3 I P 3A4
3B1 3B1-3B2 Expansion module 3 I P 3B1
3B2 3B3-3B4 Expansion module 3 I P 3B2
3B3 3B5-3B6 Expansion module 3 I P 3B3
3B4 3B7-3B8 Expansion module 3 I P 3B4

Function keys
Function key Module User label
1 Base module Function key
2 Base module Function key
3 Base module Function key
4 Base module Function key
5 Base module Function key
6 Base module Function key
7 Base module Function key
8 Base module Function key

LEDs
LED Module User label
1.1 Base module LED 1.1
1.2 Base module LED 1.2
1.3 Base module LED 1.3
Totally Integrated
Automation Portal

LED Module User label


1.4 Base module LED 1.4
1.5 Base module LED 1.5
1.6 Base module LED 1.6
1.7 Base module LED 1.7
1.8 Base module LED 1.8
1.9 Base module LED 1.9
1.10 Base module LED 1.10
1.11 Base module LED 1.11
1.12 Base module LED 1.12
1.13 Base module LED 1.13
1.14 Base module LED 1.14
1.15 Base module LED 1.15
1.16 Base module LED 1.16

Ethernet configurations
Interfaces
Slot Module Protocol info
J Onboard Ethernet Ethernet-interface settings: DCP
E ETH-BB-2FO Channel 1: DCP,Line Mode

IP Interface 1 (J\Onboard Ethernet\Channel 1): IP Interface 1


Number Settings Value
101.1031.5281.101 IP address 172.16.60.60
101.1031.5281.102 Subnet mask 255.255.255.0
101.1031.5281.103 Default Gateway IP Addr 0.0.0.0
101.1031.5281.104 Configuration mode static
101.1031.5281.105 DCP enabled on
101.1031.5281.116 ShowVLAN false

IP Interface 1 (E\ETH-BB-2FO\Channel 1): IP Interface 1


Number Settings Value
102.1031.0.101 IP address 10.16.60.60
102.1031.0.102 Subnet mask 255.255.255.0
102.1031.0.103 Default Gateway IP Addr 0.0.0.0
102.1031.0.104 Configuration mode static
102.1031.0.105 DCP enabled on
102.1031.0.116 ShowVLAN false
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Measuring-points routing
Current-measuring points
Measuring point Connection type Terminals
Meas.point I-3ph 1 3-phase I A: 1B1-1B2
I B: 1B3-1B4
I C: 1B5-1B6
Meas.point I-3ph 2 3-phase I A: 1A1-1A2
I B: 1A3-1A4
I C: 1A5-1A6
Meas.point I-3ph 3 3-phase I A: 3A1-3A2
I B: 3A3-3A4
I C: 3A5-3A6
Meas.point I-3ph 4 3-phase I A: 3B1-3B2
I B: 3B3-3B4
I C: 3B5-3B6
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Function-group connections
Measuring point to function-group connections
Measuring point Measuring point
Meas.point I-3ph 1[ID 1] Transformer side 1:I 3ph
Meas.point I-3ph 1[ID 1] Circuit breaker 1:I 3ph
Meas.point I-3ph 2[ID 2] Transformer side 2:I 3ph
Meas.point I-3ph 2[ID 2] Circuit breaker 2:I 3ph
Meas.point I-3ph 3[ID 3] Circuit breaker 3:I 3ph
Meas.point I-3ph 3[ID 3] Transformer side 3:I 3ph
Meas.point I-3ph 4[ID 4] Circuit breaker 4:I 3ph
Meas.point I-3ph 4[ID 4] Transformer side 4:I 3ph

Function group to circuit-breaker group connections


Protection group Circuit-breaker group(s)
Transformer side 1 Circuit breaker 1
Transformer side 2 Circuit breaker 2
Transformer diff. 1 Circuit breaker 2
Transformer diff. 1 Circuit breaker 3
Transformer diff. 1 Circuit breaker 1
Transformer diff. 1 Circuit breaker 4
Transformer side 3 Circuit breaker 1
Transformer side 4 Circuit breaker 4

Protection-function group to protection-function group connections


Protection group Transformer group(s)
Transformer side 1 Transformer diff. 1:side
Transformer side 2 Transformer diff. 1:side
Transformer diff. 1 Transformer side 1:side
Transformer diff. 1 Transformer side 2:side
Transformer diff. 1 Transformer side 3:side
Transformer diff. 1 Transformer side 4:side
Transformer side 3 Transformer diff. 1:side
Transformer side 4 Transformer diff. 1:side
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Information routing
Legend
Abbreviation Description
BI Binary input
FK Function keys
BO Binary output
D Display
L Logs
FR Fault recorder

General
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
91.500 General >SG choice bit 1 SPS O
91.501 General >SG choice bit 2 SPS O
91.502 General >SG choice bit 3 SPS O
91.503 General >Sw. authority local SPS O
91.504 General >Sw. authority remote SPS O
91.505 General >Sw. mode interlocked SPS O
91.506 General >Sw. mode non-interl. SPS O
91.510 General >Test mode on SPS O
91.511 General >Test mode off SPS O
91.507 General >Dev. funct.logout on SPS O
91.508 General >Dev. funct.logout off SPS O
91.509 General >Block monitoring dir. SPS O
91.315 General Device logged off SPS O
91.53 General Health ENS O
General Health\warning SPS X
General Health\alarm SPS X
91.54 General Protection inactive SPS O
91.309 General Sw.authority key/set ENS O
91.310 General Sw.mode key/set ENS O
91.311 General Switching authority ENS O
91.312 General Switching mode ENS O
91.317 General Block monitoring dir. SPS O
91.318 General Active settings group INS O
91.329 General Functions in Test mode SPS U1.16 O
91.51 General Test mode ENC O
91.321 General Protection on SPC O
91.319 General Device logout SPC O
91.308 General Switching auth. station SPC O
91.300 General Act. settings group 1 SPC O
91.301 General Act. settings group 2 SPC O
91.302 General Act. settings group 3 SPC O
91.303 General Act. settings group 4 SPC O
91.304 General Act. settings group 5 SPC O
91.305 General Act. settings group 6 SPC O
91.306 General Act. settings group 7 SPC O
91.307 General Act. settings group 8 SPC O

Device
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
4171.501 Device >GOOSE Stop SPS O
Device Process mode inactive SPS X U1.16
4171.301 Device Physical health ENS O
4171.303 Device Device startup SPS O
4171.304 Device Life contact SPS O
4171.305 Device Battery failure SPS O
4171.306 Device Clock fail SPS O
4171.310 Device Error meas. trans. ENS O
4171.312 Device Compensation error ENS O
4171.314 Device Offset error ENS O
4171.316 Device DIGSI active SPS O X
4171.317 Device Simulation mode active SPS O X
4171.318 Device Commiss. mode active SPS O X
4171.319 Device Error memory SPS O
4171.320 Device Auxiliary Power Fail SPS O
4171.321 Device Cyber Security state ENS O
4171.322 Device Cyber-security event ENS O
4171.323 Device Event lost SPS O
4171.324 Device Chatter blocking SPS O
4171.325 Device Flash disk health ENS O
4171.342 Device GOOSE/SV sim.mode SPC O
Totally Integrated
Automation Portal

Alarm handling
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
5971.503 Alarm handling >Group Alarm SPS X O
5971.504 Alarm handling >Group Warning SPS X O
5971.505 Alarm handling >Group indication SPS O
5971.300 Alarm handling Group alarm SPS O
5971.301 Alarm handling Group warning SPS U1.15 O
5971.302 Alarm handling Group indication SPS O
5971.52 Alarm handling Behavior ENS O
5971.53 Alarm handling Health ENS O

Time sync.
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
8851.305 Time sync. Time sync. error SPS O

Power system
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
11.2311.500 General >Phs-rotation reversal SPS O
11.2311.501 General >Invert Phases SPS O
11.2311.321 General Freq.out of oper.range SPS O
11.931.8881.319 Meas.point I-3ph 1\CT 3-phase Phases AB inverted SPS O
11.931.8881.320 Meas.point I-3ph 1\CT 3-phase Phases BC inverted SPS O
11.931.8881.321 Meas.point I-3ph 1\CT 3-phase Phases AC inverted SPS O
11.931.8881.325 Meas.point I-3ph 1\CT 3-phase Meas.point mult.config. SPS O
11.931.3841.300 Meas.point I-3ph 1\CT 1 Sampled val. current SAV X
11.931.3842.300 Meas.point I-3ph 1\CT 2 Sampled val. current SAV X
11.931.3843.300 Meas.point I-3ph 1\CT 3 Sampled val. current SAV X
11.931.2491.82 Meas.point I-3ph 1\Supv. balan. I >Block function SPS O
11.931.2491.52 Meas.point I-3ph 1\Supv. balan. I Behavior ENS O
11.931.2491.54 Meas.point I-3ph 1\Supv. balan. I Inactive SPS O
11.931.2491.53 Meas.point I-3ph 1\Supv. balan. I Health ENS O
11.931.2491.71 Meas.point I-3ph 1\Supv. balan. I Failure SPS O X
11.931.2551.82 Meas.point I-3ph 1\Supv. ph.seq.I >Block function SPS O
11.931.2551.52 Meas.point I-3ph 1\Supv. ph.seq.I Behavior ENS O
11.931.2551.54 Meas.point I-3ph 1\Supv. ph.seq.I Inactive SPS O
11.931.2551.53 Meas.point I-3ph 1\Supv. ph.seq.I Health ENS O
11.931.2551.71 Meas.point I-3ph 1\Supv. ph.seq.I Failure SPS O X
11.932.8881.319 Meas.point I-3ph 2\CT 3-phase Phases AB inverted SPS O
11.932.8881.320 Meas.point I-3ph 2\CT 3-phase Phases BC inverted SPS O
11.932.8881.321 Meas.point I-3ph 2\CT 3-phase Phases AC inverted SPS O
11.932.8881.325 Meas.point I-3ph 2\CT 3-phase Meas.point mult.config. SPS O
11.932.3841.300 Meas.point I-3ph 2\CT 1 Sampled val. current SAV X
11.932.3842.300 Meas.point I-3ph 2\CT 2 Sampled val. current SAV X
11.932.3843.300 Meas.point I-3ph 2\CT 3 Sampled val. current SAV X
11.932.2491.82 Meas.point I-3ph 2\Supv. balan. I >Block function SPS O
11.932.2491.52 Meas.point I-3ph 2\Supv. balan. I Behavior ENS O
11.932.2491.54 Meas.point I-3ph 2\Supv. balan. I Inactive SPS O
11.932.2491.53 Meas.point I-3ph 2\Supv. balan. I Health ENS O
11.932.2491.71 Meas.point I-3ph 2\Supv. balan. I Failure SPS O X
11.932.2551.82 Meas.point I-3ph 2\Supv. ph.seq.I >Block function SPS O
11.932.2551.52 Meas.point I-3ph 2\Supv. ph.seq.I Behavior ENS O
11.932.2551.54 Meas.point I-3ph 2\Supv. ph.seq.I Inactive SPS O
11.932.2551.53 Meas.point I-3ph 2\Supv. ph.seq.I Health ENS O
11.932.2551.71 Meas.point I-3ph 2\Supv. ph.seq.I Failure SPS O X
11.933.8881.319 Meas.point I-3ph 3\CT 3-phase Phases AB inverted SPS O
11.933.8881.320 Meas.point I-3ph 3\CT 3-phase Phases BC inverted SPS O
11.933.8881.321 Meas.point I-3ph 3\CT 3-phase Phases AC inverted SPS O
11.933.8881.325 Meas.point I-3ph 3\CT 3-phase Meas.point mult.config. SPS O
11.933.3841.300 Meas.point I-3ph 3\CT 1 Sampled val. current SAV X
11.933.3842.300 Meas.point I-3ph 3\CT 2 Sampled val. current SAV X
11.933.3843.300 Meas.point I-3ph 3\CT 3 Sampled val. current SAV X
11.933.2491.82 Meas.point I-3ph 3\Supv. balan. I >Block function SPS O
11.933.2491.52 Meas.point I-3ph 3\Supv. balan. I Behavior ENS O
11.933.2491.54 Meas.point I-3ph 3\Supv. balan. I Inactive SPS O
11.933.2491.53 Meas.point I-3ph 3\Supv. balan. I Health ENS O
11.933.2491.71 Meas.point I-3ph 3\Supv. balan. I Failure SPS O X
11.933.2551.82 Meas.point I-3ph 3\Supv. ph.seq.I >Block function SPS O
11.933.2551.52 Meas.point I-3ph 3\Supv. ph.seq.I Behavior ENS O
11.933.2551.54 Meas.point I-3ph 3\Supv. ph.seq.I Inactive SPS O
11.933.2551.53 Meas.point I-3ph 3\Supv. ph.seq.I Health ENS O
11.933.2551.71 Meas.point I-3ph 3\Supv. ph.seq.I Failure SPS O X
11.934.8881.319 Meas.point I-3ph 4\CT 3-phase Phases AB inverted SPS O
11.934.8881.320 Meas.point I-3ph 4\CT 3-phase Phases BC inverted SPS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
11.934.8881.321 Meas.point I-3ph 4\CT 3-phase Phases AC inverted SPS O
11.934.8881.325 Meas.point I-3ph 4\CT 3-phase Meas.point mult.config. SPS O
11.934.3841.300 Meas.point I-3ph 4\CT 1 Sampled val. current SAV X
11.934.3842.300 Meas.point I-3ph 4\CT 2 Sampled val. current SAV X
11.934.3843.300 Meas.point I-3ph 4\CT 3 Sampled val. current SAV X
11.934.2491.82 Meas.point I-3ph 4\Supv. balan. I >Block function SPS O
11.934.2491.52 Meas.point I-3ph 4\Supv. balan. I Behavior ENS O
11.934.2491.54 Meas.point I-3ph 4\Supv. balan. I Inactive SPS O
11.934.2491.53 Meas.point I-3ph 4\Supv. balan. I Health ENS O
11.934.2491.71 Meas.point I-3ph 4\Supv. balan. I Failure SPS O
11.934.2551.82 Meas.point I-3ph 4\Supv. ph.seq.I >Block function SPS O
11.934.2551.52 Meas.point I-3ph 4\Supv. ph.seq.I Behavior ENS O
11.934.2551.54 Meas.point I-3ph 4\Supv. ph.seq.I Inactive SPS O
11.934.2551.53 Meas.point I-3ph 4\Supv. ph.seq.I Health ENS O
11.934.2551.71 Meas.point I-3ph 4\Supv. ph.seq.I Failure SPS O

Recording
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
81.7441.310 Grnd.-flt log Fault number INS O,G
81.7441.311 Grnd.-flt log Ground-fault log is full INS G
81.791.2761.502 Fault recorder\Control >External start SPS O
81.791.2761.503 Fault recorder\Control >Manual start SPS O
81.791.2761.310 Fault recorder\Control Fault number INS O,F
81.791.2761.327 Fault recorder\Control Tmax reduced SPS O
81.791.2761.324 Fault recorder\Control Fault log is full INS F
81.791.2761.300 Fault recorder\Control Start record SPC O
81.791.2761.305 Fault recorder\Control Reset memory SPC O
81.791.2761.306 Fault recorder\Control Clear memory SPC O

J:Onboard Ethernet
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
101.2311.53 General Health ENS O

Transformer side 1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
911.1131.4681.3 Process monitor\Closure detec. Closure SPS F
00
300.0 Operational values\RMS Iph:A CMV X
300.0 Operational values\RMS Iph:B CMV X
300.0 Operational values\RMS Iph:C CMV X
911.1941.661.81 50/51 OC-3ph-B1\Definite-T 1 >Block stage SPS O
911.1941.661.50 50/51 OC-3ph-B1\Definite-T 1 >Block delay & op. SPS F
0
911.1941.661.52 50/51 OC-3ph-B1\Definite-T 1 Behavior ENS O
911.1941.661.53 50/51 OC-3ph-B1\Definite-T 1 Health ENS O
911.1941.661.54 50/51 OC-3ph-B1\Definite-T 1 Inactive SPS O
911.1941.661.55 50/51 OC-3ph-B1\Definite-T 1 Pickup ACD F
50/51 OC-3ph-B1\Definite-T 1 Pickup\general SPS U1.8
911.1941.661.57 50/51 OC-3ph-B1\Definite-T 1 Operate ACT F
50/51 OC-3ph-B1\Definite-T 1 Operate\general SPS U1.4
911.1941.691.81 50/51 OC-3ph-B1\Inverse-T 1 >Block stage SPS O
911.1941.691.50 50/51 OC-3ph-B1\Inverse-T 1 >Block delay & op. SPS F
0
911.1941.691.52 50/51 OC-3ph-B1\Inverse-T 1 Behavior ENS O
911.1941.691.53 50/51 OC-3ph-B1\Inverse-T 1 Health ENS O
911.1941.691.54 50/51 OC-3ph-B1\Inverse-T 1 Inactive SPS O
911.1941.691.55 50/51 OC-3ph-B1\Inverse-T 1 Pickup ACD F
50/51 OC-3ph-B1\Inverse-T 1 Pickup\general SPS U1.8
911.1941.691.57 50/51 OC-3ph-B1\Inverse-T 1 Operate ACT F
50/51 OC-3ph-B1\Inverse-T 1 Operate\general SPS U1.4
911.1941.691.59 50/51 OC-3ph-B1\Inverse-T 1 Disk emulation running SPS F
911.1731.751.81 50N/51N OC-gnd-B1\Definite-T 1 >Block stage SPS O
911.1731.751.50 50N/51N OC-gnd-B1\Definite-T 1 >Block delay & op. SPS F
0
911.1731.751.52 50N/51N OC-gnd-B1\Definite-T 1 Behavior ENS O
911.1731.751.53 50N/51N OC-gnd-B1\Definite-T 1 Health ENS O
911.1731.751.54 50N/51N OC-gnd-B1\Definite-T 1 Inactive SPS O
911.1731.751.55 50N/51N OC-gnd-B1\Definite-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Definite-T 1 Pickup\general SPS U1.10
911.1731.751.57 50N/51N OC-gnd-B1\Definite-T 1 Operate ACT F
50N/51N OC-gnd-B1\Definite-T 1 Operate\general SPS U3.1
911.1731.781.81 50N/51N OC-gnd-B1\Inverse-T 1 >Block stage SPS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
911.1731.781.50 50N/51N OC-gnd-B1\Inverse-T 1 >Block delay & op. SPS F
0
911.1731.781.52 50N/51N OC-gnd-B1\Inverse-T 1 Behavior ENS O
911.1731.781.53 50N/51N OC-gnd-B1\Inverse-T 1 Health ENS O
911.1731.781.54 50N/51N OC-gnd-B1\Inverse-T 1 Inactive SPS O
911.1731.781.55 50N/51N OC-gnd-B1\Inverse-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Inverse-T 1 Pickup\general SPS U1.10
911.1731.781.57 50N/51N OC-gnd-B1\Inverse-T 1 Operate ACT F
50N/51N OC-gnd-B1\Inverse-T 1 Operate\general SPS U3.1
911.1731.781.59 50N/51N OC-gnd-B1\Inverse-T 1 Disk emulation running SPS F
911.1871.2311.3 51Ns Sens. GFP 1\General Ground fault ACD F,G
01
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block stage SPS O
81
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block delay & op. SPS F
500
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Behavior ENS O
52
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Health ENS O
53
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Inactive SPS O
54
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Pickup ACD F,G
55
51Ns Sens. GFP 1\3I0> 1 Pickup\general SPS U1.13
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate ACT F,G
57
51Ns Sens. GFP 1\3I0> 1 Operate\general SPS U1.1
911.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate delay expired ACT G
56

Transformer side 2
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
912.1131.4681.3 Process monitor\Closure detec. Closure SPS F
00
300.0 Operational values\RMS Iph:A CMV X
300.0 Operational values\RMS Iph:B CMV X
300.0 Operational values\RMS Iph:C CMV X
912.1941.661.81 50/51 OC-3ph-B1\Definite-T 1 >Block stage SPS O
912.1941.661.50 50/51 OC-3ph-B1\Definite-T 1 >Block delay & op. SPS F
0
912.1941.661.52 50/51 OC-3ph-B1\Definite-T 1 Behavior ENS O
912.1941.661.53 50/51 OC-3ph-B1\Definite-T 1 Health ENS O
912.1941.661.54 50/51 OC-3ph-B1\Definite-T 1 Inactive SPS O
912.1941.661.55 50/51 OC-3ph-B1\Definite-T 1 Pickup ACD F
50/51 OC-3ph-B1\Definite-T 1 Pickup\general SPS U1.8
912.1941.661.57 50/51 OC-3ph-B1\Definite-T 1 Operate ACT F
50/51 OC-3ph-B1\Definite-T 1 Operate\general SPS U1.4
912.1941.691.81 50/51 OC-3ph-B1\Inverse-T 1 >Block stage SPS O
912.1941.691.50 50/51 OC-3ph-B1\Inverse-T 1 >Block delay & op. SPS F
0
912.1941.691.52 50/51 OC-3ph-B1\Inverse-T 1 Behavior ENS O
912.1941.691.53 50/51 OC-3ph-B1\Inverse-T 1 Health ENS O
912.1941.691.54 50/51 OC-3ph-B1\Inverse-T 1 Inactive SPS O
912.1941.691.55 50/51 OC-3ph-B1\Inverse-T 1 Pickup ACD F
912.1941.691.57 50/51 OC-3ph-B1\Inverse-T 1 Operate ACT F
50/51 OC-3ph-B1\Inverse-T 1 Operate\general SPS U1.4
50/51 OC-3ph-B1\Inverse-T 1 Operate delay expired\general SPS U1.8
912.1941.691.59 50/51 OC-3ph-B1\Inverse-T 1 Disk emulation running SPS F
912.1731.751.81 50N/51N OC-gnd-B1\Definite-T 1 >Block stage SPS O
912.1731.751.50 50N/51N OC-gnd-B1\Definite-T 1 >Block delay & op. SPS F
0
912.1731.751.52 50N/51N OC-gnd-B1\Definite-T 1 Behavior ENS O
912.1731.751.53 50N/51N OC-gnd-B1\Definite-T 1 Health ENS O
912.1731.751.54 50N/51N OC-gnd-B1\Definite-T 1 Inactive SPS O
912.1731.751.55 50N/51N OC-gnd-B1\Definite-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Definite-T 1 Pickup\general SPS U1.10
912.1731.751.57 50N/51N OC-gnd-B1\Definite-T 1 Operate ACT F
50N/51N OC-gnd-B1\Definite-T 1 Operate\general SPS U3.1
912.1731.781.81 50N/51N OC-gnd-B1\Inverse-T 1 >Block stage SPS O
912.1731.781.50 50N/51N OC-gnd-B1\Inverse-T 1 >Block delay & op. SPS F
0
912.1731.781.52 50N/51N OC-gnd-B1\Inverse-T 1 Behavior ENS O
912.1731.781.53 50N/51N OC-gnd-B1\Inverse-T 1 Health ENS O
912.1731.781.54 50N/51N OC-gnd-B1\Inverse-T 1 Inactive SPS O
912.1731.781.55 50N/51N OC-gnd-B1\Inverse-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Inverse-T 1 Pickup\general SPS U1.10
912.1731.781.57 50N/51N OC-gnd-B1\Inverse-T 1 Operate ACT F
50N/51N OC-gnd-B1\Inverse-T 1 Operate\general SPS U3.1
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
912.1731.781.59 50N/51N OC-gnd-B1\Inverse-T 1 Disk emulation running SPS F
912.1871.2311.3 51Ns Sens. GFP 1\General Ground fault ACD F,G
01
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block stage SPS O
81
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block delay & op. SPS F
500
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Behavior ENS O
52
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Health ENS O
53
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Inactive SPS O
54
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Pickup ACD F,G
55
51Ns Sens. GFP 1\3I0> 1 Pickup\general SPS U1.13
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate ACT F,G
57
51Ns Sens. GFP 1\3I0> 1 Operate\general SPS U1.1
912.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate delay expired ACT G
56

Transformer diff. 1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
87T diff. prot. 1\General I diff.\phs A MV R(X)
87T diff. prot. 1\General I diff.\phs B MV R(X)
87T diff. prot. 1\General I diff.\phs C MV R(X)
87T diff. prot. 1\General I restr.\phs A MV R(X)
87T diff. prot. 1\General I restr.\phs B MV R(X)
87T diff. prot. 1\General I restr.\phs C MV R(X)
901.1691.2311.3 87T diff. prot. 1\General I diff. operate phA MV F
11
901.1691.2311.3 87T diff. prot. 1\General I diff. operate phB MV F
12
901.1691.2311.3 87T diff. prot. 1\General I diff. operate phC MV F
13
901.1691.2311.3 87T diff. prot. 1\General I restr. operate phA MV F
14
901.1691.2311.3 87T diff. prot. 1\General I restr. operate phB MV F
15
901.1691.2311.3 87T diff. prot. 1\General I restr. operate phC MV F
16
901.1691.11041. 87T diff. prot. 1\I-DIFF >Block stage SPS O
81
901.1691.11041. 87T diff. prot. 1\I-DIFF Behavior ENS O
52
901.1691.11041. 87T diff. prot. 1\I-DIFF Health ENS O
53
901.1691.11041. 87T diff. prot. 1\I-DIFF Inactive SPS O
54
901.1691.11041. 87T diff. prot. 1\I-DIFF Pickup ACD F
55
87T diff. prot. 1\I-DIFF Pickup\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Pickup\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Pickup\phs C SPS R(X)
901.1691.11041. 87T diff. prot. 1\I-DIFF Operate ACT F
57
87T diff. prot. 1\I-DIFF Operate\general SPS U3.2 U1.1
87T diff. prot. 1\I-DIFF Operate\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Operate\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Operate\phs C SPS R(X)
901.1691.11041. 87T diff. prot. 1\I-DIFF Slope 1 MV F
301
901.1691.11041. 87T diff. prot. 1\I-DIFF Incr. of char. (Start) SPS R(X) O,F
302
901.1691.11041. 87T diff. prot. 1\I-DIFF Increase of char. (DC) SPS R(X) F
303
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by inrush SPS F
304
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by 2.Harmon. ACT F
305
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 2.Harmon.\phs C SPS R(X)
901.1691.11041. 87T diff. prot. 1\I-DIFF Crossblock by 2.Harm. SPS R(X) F
306
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by CWA SPS R(X) F
307
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by 3.Harmon. ACT F
308
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
901.1691.11041. 87T diff. prot. 1\I-DIFF Crossblock by 3.Harm. SPS F
309
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by 5.Harmon. ACT F
310
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by 5.Harmon.\phs C SPS R(X)
901.1691.11041. 87T diff. prot. 1\I-DIFF Crossblock by 5.Harm. SPS R(X) F
311
901.1691.11041. 87T diff. prot. 1\I-DIFF Blocked by ext. fault ACT F
312
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs A SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs B SPS R(X)
87T diff. prot. 1\I-DIFF Blocked by ext. fault\phs C SPS R(X)
901.1691.11041. 87T diff. prot. 1\I-DIFF Crossbl. by ext. fault SPS R(X) F
313
901.1691.11041. 87T diff. prot. 1\I-DIFF CWA int. fault detected SPS R(X) F
316
901.1691.11071. 87T diff. prot. 1\I-DIFF fast >Block stage SPS O
81
901.1691.11071. 87T diff. prot. 1\I-DIFF fast Behavior ENS O
52
901.1691.11071. 87T diff. prot. 1\I-DIFF fast Health ENS O
53
901.1691.11071. 87T diff. prot. 1\I-DIFF fast Inactive SPS O
54
901.1691.11071. 87T diff. prot. 1\I-DIFF fast Pickup ACD F
55
87T diff. prot. 1\I-DIFF fast Pickup\phs A SPS R(X)
87T diff. prot. 1\I-DIFF fast Pickup\phs B SPS R(X)
87T diff. prot. 1\I-DIFF fast Pickup\phs C SPS R(X)
901.1691.11071. 87T diff. prot. 1\I-DIFF fast Operate ACT F
57
87T diff. prot. 1\I-DIFF fast Operate\phs A SPS R(X)
87T diff. prot. 1\I-DIFF fast Operate\phs B SPS R(X)
87T diff. prot. 1\I-DIFF fast Operate\phs C SPS R(X)

E:ETH-BB-2FO
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
102.2311.53 General Health ENS O
102.1031.0.304 Channel 1\Line Mode Channel Live SPS O
102.1031.0.53 Channel 1\Line Mode Health ENS O
102.1031.0.305 Channel 1\Line Mode Redund. Channel Live SPS O

Circuit breaker 2
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
202.4261.500 Circuit break. >Ready SPS O
202.4261.501 Circuit break. >Acquisition blocking SPS O
202.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
202.4261.502 Circuit break. >Reset switch statist. SPS O
202.4261.503 Circuit break. External health ENS O
202.4261.53 Circuit break. Health ENS O
202.4261.300 Circuit break. Trip/open cmd. SPS O,F
202.4261.301 Circuit break. Close command SPS O,F
202.4261.303 Circuit break. Definitive trip SPS F
202.4261.311 Circuit break. Break.-current phs A MV F
202.4261.312 Circuit break. Break.-current phs B MV F
202.4261.313 Circuit break. Break.-current phs C MV F
202.4261.317 Circuit break. Break. current 3I0/IN MV F
202.4261.58 Circuit break. Position DPC O
202.6541.500 Manual close >Input SPS O
202.6541.501 Manual close >Block manual close SPS O
202.6541.300 Manual close Detected SPS O
202.4201.53 Control Health ENS O
202.4201.58 Control Cmd. with feedback DPC O
202.4231.53 Interlocking Health ENS O
202.6151.53 CB test Health ENS O
202.6151.301 CB test Test execution ENS O
202.6151.302 CB test Trip command issued ENS O
202.6151.303 CB test Close command issued ENS O
202.6151.304 CB test Test canceled ENS O
Totally Integrated
Automation Portal

Circuit breaker 3
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
203.4261.500 Circuit break. >Ready SPS O
203.4261.501 Circuit break. >Acquisition blocking SPS O
203.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
203.4261.502 Circuit break. >Reset switch statist. SPS O
203.4261.503 Circuit break. External health ENS O
203.4261.53 Circuit break. Health ENS O
203.4261.300 Circuit break. Trip/open cmd. SPS O,F
203.4261.301 Circuit break. Close command SPS O,F
203.4261.303 Circuit break. Definitive trip SPS F
203.4261.311 Circuit break. Break.-current phs A MV F
203.4261.312 Circuit break. Break.-current phs B MV F
203.4261.313 Circuit break. Break.-current phs C MV F
203.4261.317 Circuit break. Break. current 3I0/IN MV F
203.4261.58 Circuit break. Position DPC O
203.6541.500 Manual close >Input SPS O
203.6541.501 Manual close >Block manual close SPS O
203.6541.300 Manual close Detected SPS O
203.4201.53 Control Health ENS O
203.4201.58 Control Cmd. with feedback DPC O
203.4231.53 Interlocking Health ENS O
203.6151.53 CB test Health ENS O
203.6151.301 CB test Test execution ENS O
203.6151.302 CB test Trip command issued ENS O
203.6151.303 CB test Close command issued ENS O
203.6151.304 CB test Test canceled ENS O

Circuit breaker 1
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
301.4261.500 Circuit break. >Ready SPS O
301.4261.501 Circuit break. >Acquisition blocking SPS O
301.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
301.4261.502 Circuit break. >Reset switch statist. SPS O
301.4261.503 Circuit break. External health ENS O
301.4261.53 Circuit break. Health ENS O
301.4261.300 Circuit break. Trip/open cmd. 3-pole SPS O,F
301.4261.401 Circuit break. Trip only pole A SPS F
301.4261.402 Circuit break. Trip only pole B SPS F
301.4261.403 Circuit break. Trip only pole C SPS F
301.4261.301 Circuit break. Close command SPS O,F
301.4261.303 Circuit break. Definitive trip SPS F
301.4261.311 Circuit break. Break.-current phs A MV F
301.4261.312 Circuit break. Break.-current phs B MV F
301.4261.313 Circuit break. Break.-current phs C MV F
301.4261.317 Circuit break. Break. current 3I0/IN MV F
301.4261.58 Circuit break. Position 3-pole DPC O
301.6541.500 Manual close >Input SPS O
301.6541.501 Manual close >Block manual close SPS O
301.6541.300 Manual close Detected SPS O
301.4201.53 Control Health ENS O
301.4201.58 Control Cmd. with feedback DPC O
301.4231.53 Interlocking Health ENS O
301.6151.53 CB test Health ENS O
301.6151.301 CB test Test execution ENS O
301.6151.302 CB test Trip command issued ENS O
301.6151.303 CB test Close command issued ENS O
301.6151.304 CB test Test canceled ENS O

Transformer side 3
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
914.1131.4681.3 Process monitor\Closure detec. Closure SPS F
00
914.1941.661.81 50/51 OC-3ph-B1\Definite-T 1 >Block stage SPS O
914.1941.661.50 50/51 OC-3ph-B1\Definite-T 1 >Block delay & op. SPS F
0
914.1941.661.52 50/51 OC-3ph-B1\Definite-T 1 Behavior ENS O
914.1941.661.53 50/51 OC-3ph-B1\Definite-T 1 Health ENS O
914.1941.661.54 50/51 OC-3ph-B1\Definite-T 1 Inactive SPS O
914.1941.661.55 50/51 OC-3ph-B1\Definite-T 1 Pickup ACD F
50/51 OC-3ph-B1\Definite-T 1 Pickup\general SPS U1.7
914.1941.661.57 50/51 OC-3ph-B1\Definite-T 1 Operate ACT F
50/51 OC-3ph-B1\Definite-T 1 Operate\general SPS U1.4
914.1941.691.81 50/51 OC-3ph-B1\Inverse-T 1 >Block stage SPS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
914.1941.691.50 50/51 OC-3ph-B1\Inverse-T 1 >Block delay & op. SPS F
0
914.1941.691.52 50/51 OC-3ph-B1\Inverse-T 1 Behavior ENS O
914.1941.691.53 50/51 OC-3ph-B1\Inverse-T 1 Health ENS O
914.1941.691.54 50/51 OC-3ph-B1\Inverse-T 1 Inactive SPS O
914.1941.691.55 50/51 OC-3ph-B1\Inverse-T 1 Pickup ACD F
50/51 OC-3ph-B1\Inverse-T 1 Pickup\general SPS U1.7
914.1941.691.57 50/51 OC-3ph-B1\Inverse-T 1 Operate ACT F
50/51 OC-3ph-B1\Inverse-T 1 Operate\general SPS U1.4
914.1941.691.59 50/51 OC-3ph-B1\Inverse-T 1 Disk emulation running SPS F
914.1731.751.81 50N/51N OC-gnd-B1\Definite-T 1 >Block stage SPS O
914.1731.751.50 50N/51N OC-gnd-B1\Definite-T 1 >Block delay & op. SPS F
0
914.1731.751.52 50N/51N OC-gnd-B1\Definite-T 1 Behavior ENS O
914.1731.751.53 50N/51N OC-gnd-B1\Definite-T 1 Health ENS O
914.1731.751.54 50N/51N OC-gnd-B1\Definite-T 1 Inactive SPS O
914.1731.751.55 50N/51N OC-gnd-B1\Definite-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Definite-T 1 Pickup\general SPS U1.9
914.1731.751.57 50N/51N OC-gnd-B1\Definite-T 1 Operate ACT F
50N/51N OC-gnd-B1\Definite-T 1 Operate\general SPS U3.1
914.1731.781.81 50N/51N OC-gnd-B1\Inverse-T 1 >Block stage SPS O
914.1731.781.50 50N/51N OC-gnd-B1\Inverse-T 1 >Block delay & op. SPS F
0
914.1731.781.52 50N/51N OC-gnd-B1\Inverse-T 1 Behavior ENS O
914.1731.781.53 50N/51N OC-gnd-B1\Inverse-T 1 Health ENS O
914.1731.781.54 50N/51N OC-gnd-B1\Inverse-T 1 Inactive SPS O
914.1731.781.55 50N/51N OC-gnd-B1\Inverse-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Inverse-T 1 Pickup\general SPS U1.9
914.1731.781.57 50N/51N OC-gnd-B1\Inverse-T 1 Operate ACT F
50N/51N OC-gnd-B1\Inverse-T 1 Operate\general SPS U3.1
914.1731.781.59 50N/51N OC-gnd-B1\Inverse-T 1 Disk emulation running SPS F
914.1871.2311.3 51Ns Sens. GFP 1\General Ground fault ACD F,G
01
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block stage SPS O
81
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block delay & op. SPS F
500
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Behavior ENS O
52
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Health ENS O
53
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Inactive SPS O
54
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Pickup ACD F,G
55
51Ns Sens. GFP 1\3I0> 1 Pickup\general SPS U1.14
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate ACT F,G
57
51Ns Sens. GFP 1\3I0> 1 Operate\general SPS U1.1
914.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate delay expired ACT G
56

Circuit breaker 4
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
201.4261.500 Circuit break. >Ready SPS O
201.4261.501 Circuit break. >Acquisition blocking SPS O
201.4261.504 Circuit break. >Reset AcqBlk&Subst SPS O
201.4261.502 Circuit break. >Reset switch statist. SPS O
201.4261.503 Circuit break. External health ENS O
201.4261.53 Circuit break. Health ENS O
201.4261.300 Circuit break. Trip/open cmd. SPS O,F
201.4261.301 Circuit break. Close command SPS O,F
201.4261.303 Circuit break. Definitive trip SPS F
201.4261.311 Circuit break. Break.-current phs A MV F
201.4261.312 Circuit break. Break.-current phs B MV F
201.4261.313 Circuit break. Break.-current phs C MV F
201.4261.317 Circuit break. Break. current 3I0/IN MV F
201.4261.58 Circuit break. Position DPC O
201.6541.500 Manual close >Input SPS O
201.6541.501 Manual close >Block manual close SPS O
201.6541.300 Manual close Detected SPS O
201.4201.53 Control Health ENS O
201.4201.58 Control Cmd. with feedback DPC O
201.4231.53 Interlocking Health ENS O
201.6151.53 CB test Health ENS O
201.6151.301 CB test Test execution ENS O
201.6151.302 CB test Trip command issued ENS O
201.6151.303 CB test Close command issued ENS O
Totally Integrated
Automation Portal

Number Group Signal Type Source Destination


BI FK CFC BO LED FR L CFC D
201.6151.304 CB test Test canceled ENS O

Transformer side 4
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
913.1131.4681.3 Process monitor\Closure detec. Closure SPS F
00
913.1941.661.81 50/51 OC-3ph-B1\Definite-T 1 >Block stage SPS O
913.1941.661.50 50/51 OC-3ph-B1\Definite-T 1 >Block delay & op. SPS F
0
913.1941.661.52 50/51 OC-3ph-B1\Definite-T 1 Behavior ENS O
913.1941.661.53 50/51 OC-3ph-B1\Definite-T 1 Health ENS O
913.1941.661.54 50/51 OC-3ph-B1\Definite-T 1 Inactive SPS O
913.1941.661.55 50/51 OC-3ph-B1\Definite-T 1 Pickup ACD F
50/51 OC-3ph-B1\Definite-T 1 Pickup\general SPS U1.7
913.1941.661.57 50/51 OC-3ph-B1\Definite-T 1 Operate ACT F
50/51 OC-3ph-B1\Definite-T 1 Operate\general SPS U1.4
913.1941.691.81 50/51 OC-3ph-B1\Inverse-T 1 >Block stage SPS O
913.1941.691.50 50/51 OC-3ph-B1\Inverse-T 1 >Block delay & op. SPS F
0
913.1941.691.52 50/51 OC-3ph-B1\Inverse-T 1 Behavior ENS O
913.1941.691.53 50/51 OC-3ph-B1\Inverse-T 1 Health ENS O
913.1941.691.54 50/51 OC-3ph-B1\Inverse-T 1 Inactive SPS O
913.1941.691.55 50/51 OC-3ph-B1\Inverse-T 1 Pickup ACD F
50/51 OC-3ph-B1\Inverse-T 1 Pickup\general SPS U1.7
913.1941.691.57 50/51 OC-3ph-B1\Inverse-T 1 Operate ACT F
50/51 OC-3ph-B1\Inverse-T 1 Operate\general SPS U1.4
913.1941.691.59 50/51 OC-3ph-B1\Inverse-T 1 Disk emulation running SPS F
913.1731.751.81 50N/51N OC-gnd-B1\Definite-T 1 >Block stage SPS O
913.1731.751.50 50N/51N OC-gnd-B1\Definite-T 1 >Block delay & op. SPS F
0
913.1731.751.52 50N/51N OC-gnd-B1\Definite-T 1 Behavior ENS O
913.1731.751.53 50N/51N OC-gnd-B1\Definite-T 1 Health ENS O
913.1731.751.54 50N/51N OC-gnd-B1\Definite-T 1 Inactive SPS O
913.1731.751.55 50N/51N OC-gnd-B1\Definite-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Definite-T 1 Pickup\general SPS U1.9
913.1731.751.57 50N/51N OC-gnd-B1\Definite-T 1 Operate ACT F
50N/51N OC-gnd-B1\Definite-T 1 Operate\general SPS U3.1
913.1731.781.81 50N/51N OC-gnd-B1\Inverse-T 1 >Block stage SPS O
913.1731.781.50 50N/51N OC-gnd-B1\Inverse-T 1 >Block delay & op. SPS F
0
913.1731.781.52 50N/51N OC-gnd-B1\Inverse-T 1 Behavior ENS O
913.1731.781.53 50N/51N OC-gnd-B1\Inverse-T 1 Health ENS O
913.1731.781.54 50N/51N OC-gnd-B1\Inverse-T 1 Inactive SPS O
913.1731.781.55 50N/51N OC-gnd-B1\Inverse-T 1 Pickup ACD F
50N/51N OC-gnd-B1\Inverse-T 1 Pickup\general SPS U1.9
913.1731.781.57 50N/51N OC-gnd-B1\Inverse-T 1 Operate ACT F
50N/51N OC-gnd-B1\Inverse-T 1 Operate\general SPS U3.1
913.1731.781.59 50N/51N OC-gnd-B1\Inverse-T 1 Disk emulation running SPS F
913.1871.2311.3 51Ns Sens. GFP 1\General Ground fault ACD F,G
01
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block stage SPS O
81
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 >Block delay & op. SPS F
500
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Behavior ENS O
52
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Health ENS O
53
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Inactive SPS O
54
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Pickup ACD F,G
55
51Ns Sens. GFP 1\3I0> 1 Pickup\general SPS U1.14
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate ACT F,G
57
51Ns Sens. GFP 1\3I0> 1 Operate\general SPS U1.1
913.1871.12421. 51Ns Sens. GFP 1\3I0> 1 Operate delay expired ACT G
56

Main menu
Number Group Signal Type Source Destination
BI FK CFC BO LED FR L CFC D
Logs Operational log X1.1
Logs Fault log X1.3
Measurements\Transformer side 1 Fund./sym.comp. X1.2
Measurements\Transformer side 2 Fund./sym.comp. X1.4
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Communication mapping
This folder is empty.
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Settings
Device settings
Settings Value
Edit mode secondary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 172.16.60.60 (Port J)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Hide all settings
Hide SIPROTEC extensions in IEC 61850 structure Hide all SIPROTEC extensions
Reserv.time for com.prot. 120 s
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.
Station name Project1 (Substation name)

General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.138 Block monitoring dir. All: off
91.164 Station name All: Project1

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Control
Number Settings Value
91.162 Blk setting change Settings group 1: false
91.163 Reserv.time for com.prot. All: 120 s
91.118 Enable sw.auth. station All: false

General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false

General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false

General \Test support


Number Settings Value
91.139 Fault-display All: with pickup
91.161 CFC chart quality handling All: manual

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 none
Time source 2 none
Time zone time source 1 All: local
Time zone time source 2 All: local
Totally Integrated
Automation Portal

Settings Value
Sync. latency time src.1 All: 0 µs
Sync. latency time src.2 All: 0 µs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: 60 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time true
Start of daylight sav. time Last Sunday in March at 2:00 AM
End of daylight sav. time Last Sunday in October at 3:00 AM

Pulse per second (Port G)


Settings Value
Sync. latency PPS All: 0 µs

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

Power system \Meas.point I-3ph 1


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 1

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 20000 A
11.931.8881.102 Rated secondary current All: 5 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: yes
11.931.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 2.50 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay failure indication Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay failure indication Settings group 1: 5 s

Power system \Meas.point I-3ph 2


CT 3-phase \General
Number Settings Value
11.932.8881.115 CT connection All: 3-phase
Totally Integrated
Automation Portal

Number Settings Value


11.932.8881.127 Tracking All: active
11.932.8881.130 Measuring-point ID All: 2

CT 3-phase \CT phases


Number Settings Value
11.932.8881.101 Rated primary current All: 2500 A
11.932.8881.102 Rated secondary current All: 5 A
11.932.8881.117 Current range All: 100 x IR
11.932.8881.118 Internal CT type All: CT protection
11.932.8881.116 Neutr.point in dir.of ref.obj All: yes
11.932.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.932.3841.103 Magnitude correction All: 1
11.932.3841.117 Phase All: I A

CT 2
Number Settings Value
11.932.3842.103 Magnitude correction All: 1
11.932.3842.117 Phase All: I B

CT 3
Number Settings Value
11.932.3843.103 Magnitude correction All: 1
11.932.3843.117 Phase All: I C

Supv. balan. I
Number Settings Value
11.932.2491.1 Mode Settings group 1: on
11.932.2491.101 Release threshold Settings group 1: 2.50 A
11.932.2491.102 Threshold min/max Settings group 1: 0.5
11.932.2491.6 Delay failure indication Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.932.2551.1 Mode Settings group 1: on
11.932.2551.6 Delay failure indication Settings group 1: 5 s

Power system \Meas.point I-3ph 3


CT 3-phase \General
Number Settings Value
11.933.8881.115 CT connection All: 3-phase
11.933.8881.127 Tracking All: active
11.933.8881.130 Measuring-point ID All: 3

CT 3-phase \CT phases


Number Settings Value
11.933.8881.101 Rated primary current All: 3000 A
11.933.8881.102 Rated secondary current All: 5 A
11.933.8881.117 Current range All: 100 x IR
11.933.8881.118 Internal CT type All: CT protection
11.933.8881.116 Neutr.point in dir.of ref.obj All: yes
11.933.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.933.3841.103 Magnitude correction All: 1
11.933.3841.117 Phase All: I A

CT 2
Number Settings Value
11.933.3842.103 Magnitude correction All: 1
11.933.3842.117 Phase All: I B

CT 3
Number Settings Value
11.933.3843.103 Magnitude correction All: 1
11.933.3843.117 Phase All: I C
Totally Integrated
Automation Portal

Supv. balan. I
Number Settings Value
11.933.2491.1 Mode Settings group 1: on
11.933.2491.101 Release threshold Settings group 1: 2.50 A
11.933.2491.102 Threshold min/max Settings group 1: 0.5
11.933.2491.6 Delay failure indication Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.933.2551.1 Mode Settings group 1: off
11.933.2551.6 Delay failure indication Settings group 1: 5 s

Power system \Meas.point I-3ph 4


CT 3-phase \General
Number Settings Value
11.934.8881.115 CT connection All: 3-phase
11.934.8881.127 Tracking All: active
11.934.8881.130 Measuring-point ID All: 4

CT 3-phase \CT phases


Number Settings Value
11.934.8881.101 Rated primary current All: 3000 A
11.934.8881.102 Rated secondary current All: 5 A
11.934.8881.117 Current range All: 100 x IR
11.934.8881.118 Internal CT type All: CT protection
11.934.8881.116 Neutr.point in dir.of ref.obj All: yes
11.934.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.934.3841.103 Magnitude correction All: 1
11.934.3841.117 Phase All: I A

CT 2
Number Settings Value
11.934.3842.103 Magnitude correction All: 1
11.934.3842.117 Phase All: I B

CT 3
Number Settings Value
11.934.3843.103 Magnitude correction All: 1
11.934.3843.117 Phase All: I C

Supv. balan. I
Number Settings Value
11.934.2491.1 Mode Settings group 1: off
11.934.2491.101 Release threshold Settings group 1: 2.50 A
11.934.2491.102 Threshold min/max Settings group 1: 0.5
11.934.2491.6 Delay failure indication Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.934.2551.1 Mode Settings group 1: off
11.934.2551.6 Delay failure indication Settings group 1: 5 s

Recording \Fault recorder


Control
Number Settings Value
81.791.2761.130 Fault recording All: with pickup
81.791.2761.131 Storage All: always
81.791.2761.111 Maximum record time All: 5 s
81.791.2761.112 Pre-trigger time All: 0.5 s
81.791.2761.113 Post-trigger time All: 0.5 s
81.791.2761.116 Manual record time All: 0.5 s
81.791.2761.140 Sampling frequency All: 2 kHz
81.791.2761.141 Sampl. freq. IEC 61850 rec. All: 1 kHz
81.791.2761.151 COMTRADE revision year All: COMTRADE 1999
81.791.2761.128 Scaling COMTRADE All: Secondary values
81.791.2761.129 Cal.zero.seq.cur.channel All: no
81.791.2761.132 Cal.zero seq.volt.channel All: no
Totally Integrated
Automation Portal

Transformer side 1 \General


General \Rated values
Number Settings Value
911.91.103 Rated apparent power All: 475 MVA
911.91.102 Rated voltage All: 19 kV
911.91.101 Rated current All: 14434 A

General \Side data


Number Settings Value
911.91.149 Neutral point Settings group 1: grounded
911.91.104 Winding configuration Settings group 1: D (Delta)
911.91.163 Vector group numeral All: 0
911.91.130 Side number All: Side 1
911.91.210 MI3ph1 usesMeasP with ID All: 1
911.91.215 CT mismatch M I-3ph 1 All: 1.386

Transformer side 1 \Process monitor


Transformer side 1 \50/51 OC-3ph-B1
Definite-T 1
Number Settings Value
911.1941.661.1 Mode Settings group 1: off
911.1941.661.2 Operate & flt.rec. blocked Settings group 1: no
911.1941.661.8 Method of measurement Settings group 1: fundamental comp.
911.1941.661.3 Threshold Settings group 1: 10.00 A
911.1941.661.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
911.1941.691.1 Mode Settings group 1: off
911.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
911.1941.691.8 Method of measurement Settings group 1: fundamental comp.
911.1941.691.3 Threshold Settings group 1: 5.00 A
911.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
911.1941.691.131 Reset Settings group 1: disk emulation
911.1941.691.101 Time dial Settings group 1: 1

Transformer side 1 \50N/51N OC-gnd-B1


Definite-T 1
Number Settings Value
911.1731.751.1 Mode Settings group 1: off
911.1731.751.2 Operate & flt.rec. blocked Settings group 1: no
911.1731.751.8 Method of measurement Settings group 1: fundamental comp.
911.1731.751.3 Threshold Settings group 1: 5.00 A
911.1731.751.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
911.1731.781.1 Mode Settings group 1: off
911.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
911.1731.781.8 Method of measurement Settings group 1: fundamental comp.
911.1731.781.3 Threshold Settings group 1: 1.00 A
911.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
911.1731.781.109 Reset Settings group 1: disk emulation
911.1731.781.101 Time dial Settings group 1: 1

Transformer side 1 \51Ns Sens. GFP 1


General
Number Settings Value
911.1871.2311.101 Dropout delay Settings group 1: 1 s
911.1871.2311.119 Block. group indications Settings group 1: no

3I0> 1
Number Settings Value
911.1871.12421.1 Mode Settings group 1: on
911.1871.12421.2 Operate & flt.rec. blocked Settings group 1: no
911.1871.12421.8 Method of measurement Settings group 1: fundamental comp.
911.1871.12421.3 Threshold Settings group 1: 1.00 A
911.1871.12421.102 Pickup delay Settings group 1: 0 s
911.1871.12421.6 Operate delay Settings group 1: 0.3 s
Totally Integrated
Automation Portal

Transformer side 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 1\ 50/51 OC-3ph-B1\ Definite-T 1 Circuit breaker 1:Trip
Transformer side 1\ 50/51 OC-3ph-B1\ Inverse-T 1 Circuit breaker 1:Trip
Transformer side 1\ 50N/51N OC-gnd-B1\ Definite-T 1 Circuit breaker 1:Trip
Transformer side 1\ 50N/51N OC-gnd-B1\ Inverse-T 1 Circuit breaker 1:Trip
Transformer side 1\ 51Ns Sens. GFP 1\ 3I0> 1 Circuit breaker 1:Trip

Transformer side 2 \General


General \Rated values
Number Settings Value
912.91.103 Rated apparent power All: 417 MVA
912.91.102 Rated voltage All: 132 kV
912.91.101 Rated current All: 1824 A

General \Side data


Number Settings Value
912.91.149 Neutral point Settings group 1: grounded
912.91.104 Winding configuration Settings group 1: Y (Wye)
912.91.163 Vector group numeral All: 1
912.91.130 Side number All: Side 2
912.91.210 MI3ph1 usesMeasP with ID All: 2
912.91.215 CT mismatch M I-3ph 1 All: 1.371

Transformer side 2 \Process monitor


Transformer side 2 \50/51 OC-3ph-B1
Definite-T 1
Number Settings Value
912.1941.661.1 Mode Settings group 1: off
912.1941.661.2 Operate & flt.rec. blocked Settings group 1: no
912.1941.661.8 Method of measurement Settings group 1: fundamental comp.
912.1941.661.3 Threshold Settings group 1: 10.00 A
912.1941.661.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
912.1941.691.1 Mode Settings group 1: off
912.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
912.1941.691.8 Method of measurement Settings group 1: fundamental comp.
912.1941.691.3 Threshold Settings group 1: 5.00 A
912.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
912.1941.691.131 Reset Settings group 1: disk emulation
912.1941.691.101 Time dial Settings group 1: 1

Transformer side 2 \50N/51N OC-gnd-B1


Definite-T 1
Number Settings Value
912.1731.751.1 Mode Settings group 1: off
912.1731.751.2 Operate & flt.rec. blocked Settings group 1: no
912.1731.751.8 Method of measurement Settings group 1: fundamental comp.
912.1731.751.3 Threshold Settings group 1: 5.00 A
912.1731.751.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
912.1731.781.1 Mode Settings group 1: off
912.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
912.1731.781.8 Method of measurement Settings group 1: fundamental comp.
912.1731.781.3 Threshold Settings group 1: 1.00 A
912.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
912.1731.781.109 Reset Settings group 1: disk emulation
912.1731.781.101 Time dial Settings group 1: 1

Transformer side 2 \51Ns Sens. GFP 1


General
Number Settings Value
912.1871.2311.101 Dropout delay Settings group 1: 1 s
912.1871.2311.119 Block. group indications Settings group 1: no
Totally Integrated
Automation Portal

3I0> 1
Number Settings Value
912.1871.12421.1 Mode Settings group 1: off
912.1871.12421.2 Operate & flt.rec. blocked Settings group 1: no
912.1871.12421.8 Method of measurement Settings group 1: fundamental comp.
912.1871.12421.3 Threshold Settings group 1: 1.00 A
912.1871.12421.102 Pickup delay Settings group 1: 0 s
912.1871.12421.6 Operate delay Settings group 1: 0.3 s

Transformer side 2\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 2\ 50/51 OC-3ph-B1\ Definite-T 1 Circuit breaker 2:Trip
Transformer side 2\ 50/51 OC-3ph-B1\ Inverse-T 1 Circuit breaker 2:Trip
Transformer side 2\ 50N/51N OC-gnd-B1\ Definite-T 1 Circuit breaker 2:Trip
Transformer side 2\ 50N/51N OC-gnd-B1\ Inverse-T 1 Circuit breaker 2:Trip
Transformer side 2\ 51Ns Sens. GFP 1\ 3I0> 1 Circuit breaker 2:Trip

Transformer side 3 \General


General \Rated values
Number Settings Value
914.91.103 Rated apparent power All: 24 MVA
914.91.102 Rated voltage All: 6.6 kV
914.91.101 Rated current All: 2099 A

General \Side data


Number Settings Value
914.91.149 Neutral point Settings group 1: grounded
914.91.104 Winding configuration Settings group 1: Y (Wye)
914.91.163 Vector group numeral All: 11
914.91.130 Side number All: Side 3
914.91.210 MI3ph1 usesMeasP with ID All: 3
914.91.215 CT mismatch M I-3ph 1 All: 1.429

Transformer side 3 \Process monitor


Transformer side 3 \50/51 OC-3ph-B1
Definite-T 1
Number Settings Value
914.1941.661.1 Mode Settings group 1: off
914.1941.661.2 Operate & flt.rec. blocked Settings group 1: no
914.1941.661.8 Method of measurement Settings group 1: fundamental comp.
914.1941.661.3 Threshold Settings group 1: 10.00 A
914.1941.661.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
914.1941.691.1 Mode Settings group 1: off
914.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
914.1941.691.8 Method of measurement Settings group 1: fundamental comp.
914.1941.691.3 Threshold Settings group 1: 5.00 A
914.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
914.1941.691.131 Reset Settings group 1: disk emulation
914.1941.691.101 Time dial Settings group 1: 1

Transformer side 3 \50N/51N OC-gnd-B1


Definite-T 1
Number Settings Value
914.1731.751.1 Mode Settings group 1: off
914.1731.751.2 Operate & flt.rec. blocked Settings group 1: no
914.1731.751.8 Method of measurement Settings group 1: fundamental comp.
914.1731.751.3 Threshold Settings group 1: 5.00 A
914.1731.751.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
914.1731.781.1 Mode Settings group 1: off
914.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
914.1731.781.8 Method of measurement Settings group 1: fundamental comp.
914.1731.781.3 Threshold Settings group 1: 1.00 A
914.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
914.1731.781.109 Reset Settings group 1: disk emulation
914.1731.781.101 Time dial Settings group 1: 1
Totally Integrated
Automation Portal

Transformer side 3 \51Ns Sens. GFP 1


General
Number Settings Value
914.1871.2311.101 Dropout delay Settings group 1: 1 s
914.1871.2311.119 Block. group indications Settings group 1: no

3I0> 1
Number Settings Value
914.1871.12421.1 Mode Settings group 1: off
914.1871.12421.2 Operate & flt.rec. blocked Settings group 1: no
914.1871.12421.8 Method of measurement Settings group 1: fundamental comp.
914.1871.12421.3 Threshold Settings group 1: 1.00 A
914.1871.12421.102 Pickup delay Settings group 1: 0 s
914.1871.12421.6 Operate delay Settings group 1: 0.3 s

Transformer side 3\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 3\ 50/51 OC-3ph-B1\ Definite-T 1 Circuit breaker 1:Trip
Transformer side 3\ 50/51 OC-3ph-B1\ Inverse-T 1 Circuit breaker 1:Trip
Transformer side 3\ 50N/51N OC-gnd-B1\ Definite-T 1 Circuit breaker 1:Trip
Transformer side 3\ 50N/51N OC-gnd-B1\ Inverse-T 1 Circuit breaker 1:Trip
Transformer side 3\ 51Ns Sens. GFP 1\ 3I0> 1 Circuit breaker 1:Trip

Transformer side 4 \General


General \Rated values
Number Settings Value
913.91.103 Rated apparent power All: 24 MVA
913.91.102 Rated voltage All: 6.6 kV
913.91.101 Rated current All: 2099 A

General \Side data


Number Settings Value
913.91.149 Neutral point Settings group 1: grounded
913.91.104 Winding configuration Settings group 1: Y (Wye)
913.91.163 Vector group numeral All: 11
913.91.130 Side number All: Side 4
913.91.210 MI3ph1 usesMeasP with ID All: 4
913.91.215 CT mismatch M I-3ph 1 All: 1.429

Transformer side 4 \Process monitor


Transformer side 4 \50/51 OC-3ph-B1
Definite-T 1
Number Settings Value
913.1941.661.1 Mode Settings group 1: off
913.1941.661.2 Operate & flt.rec. blocked Settings group 1: no
913.1941.661.8 Method of measurement Settings group 1: fundamental comp.
913.1941.661.3 Threshold Settings group 1: 10.00 A
913.1941.661.6 Operate delay Settings group 1: 0 s

Inverse-T 1
Number Settings Value
913.1941.691.1 Mode Settings group 1: off
913.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
913.1941.691.8 Method of measurement Settings group 1: fundamental comp.
913.1941.691.3 Threshold Settings group 1: 5.00 A
913.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
913.1941.691.131 Reset Settings group 1: disk emulation
913.1941.691.101 Time dial Settings group 1: 1

Transformer side 4 \50N/51N OC-gnd-B1


Definite-T 1
Number Settings Value
913.1731.751.1 Mode Settings group 1: off
913.1731.751.2 Operate & flt.rec. blocked Settings group 1: no
913.1731.751.8 Method of measurement Settings group 1: fundamental comp.
913.1731.751.3 Threshold Settings group 1: 5.00 A
913.1731.751.6 Operate delay Settings group 1: 0 s
Totally Integrated
Automation Portal

Inverse-T 1
Number Settings Value
913.1731.781.1 Mode Settings group 1: off
913.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
913.1731.781.8 Method of measurement Settings group 1: fundamental comp.
913.1731.781.3 Threshold Settings group 1: 1.00 A
913.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
913.1731.781.109 Reset Settings group 1: disk emulation
913.1731.781.101 Time dial Settings group 1: 1

Transformer side 4 \51Ns Sens. GFP 1


General
Number Settings Value
913.1871.2311.101 Dropout delay Settings group 1: 1 s
913.1871.2311.119 Block. group indications Settings group 1: no

3I0> 1
Number Settings Value
913.1871.12421.1 Mode Settings group 1: off
913.1871.12421.2 Operate & flt.rec. blocked Settings group 1: no
913.1871.12421.8 Method of measurement Settings group 1: fundamental comp.
913.1871.12421.3 Threshold Settings group 1: 1.00 A
913.1871.12421.102 Pickup delay Settings group 1: 0 s
913.1871.12421.6 Operate delay Settings group 1: 0.3 s

Transformer side 4\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 4\ 50/51 OC-3ph-B1\ Definite-T 1 Circuit breaker 4:Trip
Transformer side 4\ 50/51 OC-3ph-B1\ Inverse-T 1 Circuit breaker 4:Trip
Transformer side 4\ 50N/51N OC-gnd-B1\ Definite-T 1 Circuit breaker 4:Trip
Transformer side 4\ 50N/51N OC-gnd-B1\ Inverse-T 1 Circuit breaker 4:Trip
Transformer side 4\ 51Ns Sens. GFP 1\ 3I0> 1 Circuit breaker 4:Trip

Transformer diff. 1 \87T diff. prot. 1


General
Number Settings Value
901.1691.2311.105 CT mismatch side 1 M3ph 1 All: 1.386
901.1691.2311.110 CT mismatch side 2 M3ph 1 All: 1.203
901.1691.2311.115 CT mismatch side 3 M3ph 1 All: 0.072
901.1691.2311.120 CT mismatch side 4 M3ph 1 All: 0.072
901.1691.2311.191 Reference side is All: Side 1
901.1691.2311.151 MU-ID Side 1 Mp3ph 1 All: 1
901.1691.2311.156 MU-ID Side 2 Mp3ph 1 All: 2
901.1691.2311.161 MU-ID Side 3 Mp3ph 1 All: 3
901.1691.2311.166 MU-ID Side 4 Mp3ph 1 All: 4

I-DIFF \General
Number Settings Value
901.1691.11041.1 Mode Settings group 1: off
901.1691.11041.2 Operate & flt.rec. blocked Settings group 1: no
901.1691.11041.6 Operate delay Settings group 1: 0 s

I-DIFF \Operate curve


Number Settings Value
901.1691.11041.3 Threshold Settings group 1: 0.2 I/IrObj
901.1691.11041.100 Slope 1 Settings group 1: 0.3
901.1691.11041.101 Intersection 1 Irest Settings group 1: 0.67 I/IrObj
901.1691.11041.102 Slope 2 Settings group 1: 0.7
901.1691.11041.103 Intersection 2 Irest Settings group 1: 2.5 I/IrObj

I-DIFF \Starting detection


Number Settings Value
901.1691.11041.106 Starting detection Settings group 1: no
901.1691.11041.107 Thresh. startup detection Settings group 1: 0.1 I/IrObj
901.1691.11041.108 Factor increasing char. Settings group 1: 2
901.1691.11041.109 Max. perm. Start. time Settings group 1: 5 s

I-DIFF \DC offset detection


Number Settings Value
901.1691.11041.110 Factor increasing char. DC Settings group 1: 2.3
Totally Integrated
Automation Portal

I-DIFF \Inrush blocking


Number Settings Value
901.1691.11041.115 Blocking with 2. harmonic Settings group 1: yes
901.1691.11041.116 2nd harmonic content Settings group 1: 15 %
901.1691.11041.117 Crossblock. time 2nd har. Settings group 1: 0 s
901.1691.11041.118 Blocking with CWA Settings group 1: yes

I-DIFF \Overexcit. blocking


Number Settings Value
901.1691.11041.121 Blocking with 3rd harm. Settings group 1: no
901.1691.11041.122 3rd harmonics content Settings group 1: 30 %
901.1691.11041.123 Crossblock. time 3rd har. Settings group 1: 0 s
901.1691.11041.124 Blocking with 5th harm. Settings group 1: no
901.1691.11041.125 5th harmonics content Settings group 1: 30 %
901.1691.11041.126 Crossblock. time 5th har. Settings group 1: 0 s
901.1691.11041.127 Limit Idiff 3., 5. harmonics Settings group 1: 1.5 I/IrObj

I-DIFF \Ext. fault detection


Number Settings Value
901.1691.11041.128 Threshold add-on stabiliz. Settings group 1: 2 I/IrObj
901.1691.11041.129 Time of add-on stabiliz. Settings group 1: 0.3 s
901.1691.11041.130 Crossblk. time add-on st. Settings group 1: 0.3 s

I-DIFF fast
Number Settings Value
901.1691.11071.1 Mode Settings group 1: off
901.1691.11071.3 Threshold Settings group 1: 7.5 I/IrObj
901.1691.11071.6 Operate delay Settings group 1: 0 s
901.1691.11071.100 Operate & flt.rec. blocked Settings group 1: no

Transformer diff. 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF Circuit breaker 2:Trip, Circuit breaker 3:Trip, Circuit breaker 1:Trip, Circuit breaker 4:Trip
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF fast Circuit breaker 2:Trip, Circuit breaker 3:Trip, Circuit breaker 1:Trip, Circuit breaker 4:Trip

Circuit breaker 2 \General


General \Ref. for %-values
Number Settings Value
202.2311.101 Rated normal current All: 2500 A

General \Breaker settings


Number Settings Value
202.2311.112 Current thresh. CB open All: 1.60 A

Circuit breaker 2 \Trip logic


Trip logic
Number Settings Value
202.5341.103 Reset of trip command All: with I<

Circuit breaker 2 \Circuit break.


Circuit break.
Number Settings Value
202.4261.101 Output time All: 0.1 s
202.4261.105 Indicat. of breaking values All: always

Circuit breaker 2 \Manual close


Manual close
Number Settings Value
202.6541.101 Action time Settings group 1: 0.3 s
202.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 2 \Control


Control
Number Settings Value
202.4201.101 Control model All: SBO w. enh. security
202.4201.102 SBO time-out All: 30 s
202.4201.103 Feedback monitoring time All: 1 s
Totally Integrated
Automation Portal

Number Settings Value


202.4201.104 Check switching authority All: yes
202.4201.105 Check if pos. is reached All: yes
202.4201.106 Check double activat. blk. All: yes
202.4201.107 Check blk. by protection All: yes

Circuit breaker 2 \CB test


CB test
Number Settings Value
202.6151.101 Dead time All: 0.1 s
202.6151.102 Trip only All: false
202.6151.103 Consider current criterion All: false

Circuit breaker 3 \General


General \Ref. for %-values
Number Settings Value
203.2311.101 Rated normal current All: 3000 A

General \Breaker settings


Number Settings Value
203.2311.112 Current thresh. CB open All: 1.33 A

Circuit breaker 3 \Trip logic


Trip logic
Number Settings Value
203.5341.103 Reset of trip command All: with I<

Circuit breaker 3 \Circuit break.


Circuit break.
Number Settings Value
203.4261.101 Output time All: 0.1 s
203.4261.105 Indicat. of breaking values All: always

Circuit breaker 3 \Manual close


Manual close
Number Settings Value
203.6541.101 Action time Settings group 1: 0.3 s
203.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 3 \Control


Control
Number Settings Value
203.4201.101 Control model All: SBO w. enh. security
203.4201.102 SBO time-out All: 30 s
203.4201.103 Feedback monitoring time All: 1 s
203.4201.104 Check switching authority All: yes
203.4201.105 Check if pos. is reached All: yes
203.4201.106 Check double activat. blk. All: yes
203.4201.107 Check blk. by protection All: yes

Circuit breaker 3 \CB test


CB test
Number Settings Value
203.6151.101 Dead time All: 0.1 s
203.6151.102 Trip only All: false
203.6151.103 Consider current criterion All: false

Circuit breaker 1 \General


General \Ref. for %-values
Number Settings Value
301.2311.101 Rated normal current All: 20000 A

General \Breaker settings


Number Settings Value
301.2311.112 Current thresh. CB open All: 5.00 A
301.2311.113 1-pole operate allowed All: yes
Totally Integrated
Automation Portal

Circuit breaker 1 \Trip logic


Trip logic
Number Settings Value
301.5341.101 Trip at 2ph short circuit All: 3-pole
301.5341.102 3-pole coupling All: with trip
301.5341.103 Reset of trip command All: with I<

Circuit breaker 1 \Circuit break.


Circuit break.
Number Settings Value
301.4261.101 Output time All: 0.1 s
301.4261.105 Indicat. of breaking values All: always

Circuit breaker 1 \Manual close


Manual close
Number Settings Value
301.6541.101 Action time Settings group 1: 0.3 s
301.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 1 \Control


Control
Number Settings Value
301.4201.101 Control model All: SBO w. enh. security
301.4201.102 SBO time-out All: 30 s
301.4201.103 Feedback monitoring time All: 1 s
301.4201.104 Check switching authority All: yes
301.4201.105 Check if pos. is reached All: yes
301.4201.106 Check double activat. blk. All: yes
301.4201.107 Check blk. by protection All: yes

Circuit breaker 1 \CB test


CB test
Number Settings Value
301.6151.101 Dead time All: 0.1 s
301.6151.102 Trip only All: false
301.6151.103 Consider current criterion All: false

Circuit breaker 4 \General


General \Ref. for %-values
Number Settings Value
201.2311.101 Rated normal current All: 3000 A

General \Breaker settings


Number Settings Value
201.2311.112 Current thresh. CB open All: 1.33 A

Circuit breaker 4 \Trip logic


Trip logic
Number Settings Value
201.5341.103 Reset of trip command All: with I<

Circuit breaker 4 \Circuit break.


Circuit break.
Number Settings Value
201.4261.101 Output time All: 0.1 s
201.4261.105 Indicat. of breaking values All: always

Circuit breaker 4 \Manual close


Manual close
Number Settings Value
201.6541.101 Action time Settings group 1: 0.3 s
201.6541.102 CB open dropout delay Settings group 1: 0 s
Totally Integrated
Automation Portal

Circuit breaker 4 \Control


Control
Number Settings Value
201.4201.101 Control model All: SBO w. enh. security
201.4201.102 SBO time-out All: 30 s
201.4201.103 Feedback monitoring time All: 1 s
201.4201.104 Check switching authority All: yes
201.4201.105 Check if pos. is reached All: yes
201.4201.106 Check double activat. blk. All: yes
201.4201.107 Check blk. by protection All: yes

Circuit breaker 4 \CB test


CB test
Number Settings Value
201.6151.101 Dead time All: 0.1 s
201.6151.102 Trip only All: false
201.6151.103 Consider current criterion All: false
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Group warning
or10_1 build_sps_1
OR10 BUILD_SPS
OR BUILD_SPS
Totally Integrated

Power system.Meas.point I-3ph 1.Supv. balan. I.Failure [BOOL] X1 Y VAL OUT


Automation Portal

Power system.Meas.point I-3ph 1.Supv. ph.seq.I.Failure [BOOL] X2 QL


Power system.Meas.point I-3ph 1.Supv. sum I.Failure [BOOL] X3
0 X4
build_q_1
BUILD_Q
BUILD_Q
1 GOOD QL
0 BAD

or10_2 build_sps_2
OR10 BUILD_SPS
OR BUILD_SPS
Power system.Meas.point I-3ph 2.Supv. balan. I.Failure [BOOL] X1 Y VAL OUT
Power system.Meas.point I-3ph 2.Supv. ph.seq.I.Failure [BOOL] X2 QL
Power system.Meas.point I-3ph 2.Supv. sum I.Failure [BOOL] X3
build_q_2
BUILD_Q
BUILD_Q
1 GOOD QL
0 BAD
Group warning - Data flow /Task: Event-triggered (1.1 / 3.2)

or_sps_1
or10_3 build_sps_3 OR_SPS
OR10 BUILD_SPS OR_SPS
OR BUILD_SPS IN1 OUT Alarm handling.>Group Warning [SSPS]
Power system.Meas.point I-3ph 3.Supv. balan. I.Failure [BOOL] X1 Y VAL OUT IN2 VALID
Power system.Meas.point I-3ph 3.Supv. ph.seq.I.Failure [BOOL] X2 QL IN3
Power system.Meas.point I-3ph 3.Supv. sum I.Failure [BOOL] X3 0 IN4
Power system.Meas.point I-3ph 3.Supv.ADC sum I.Failure [BOOL] X4
build_q_3
BUILD_Q
BUILD_Q
1 GOOD QL
0 BAD

2.1 ( Page9 - 4)
or10_4 build_sps_4
OR10 BUILD_SPS
OR BUILD_SPS
General.Health.warning [BOOL] X1 Y VAL OUT
General.Health.alarm [BOOL] X2 QL
build_q_4
BUILD_Q
BUILD_Q
1 GOOD QL
0 BAD

1.2 ( Page9 - 3)
Totally Integrated
Automation Portal

Group warning - Data flow /Task: Event-triggered (1.2 / 3.2)


1.1 ( Page9 - 2)

2.2 ( Page9 - 5)
Totally Integrated
Automation Portal

Group warning - Data flow /Task: Event-triggered (2.1 / 3.2)


1.1 ( Page9 - 2)

2.2 ( Page9 - 5)

3.1 ( Page9 - 6)
Totally Integrated
Automation Portal

Group warning - Data flow /Task: Event-triggered (2.2 / 3.2)


1.2 ( Page9 - 3)
2.1 ( Page9 - 4)

3.2 ( Page9 - 7)
Totally Integrated
Automation Portal

Group warning - Data flow /Task: Event-triggered (3.1 / 3.2)


2.1 ( Page9 - 4)

3.2 ( Page9 - 7)
Totally Integrated
Automation Portal

Group warning - Data flow /Task: Event-triggered (3.2 / 3.2)


2.2 ( Page9 - 5)
3.1 ( Page9 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

Group warning - Control flow /Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
OR10 or10_1 OR10 default OR

X1 Power system.Meas.point I-3ph 1.Supv. Bool X1


balan. I.Failure [BOOL]
X2 Power system.Meas.point I-3ph 1.Supv. Bool X2
ph.seq.I.Failure [BOOL]
X3 Power system.Meas.point I-3ph 1.Supv. Bool X3
sum I.Failure [BOOL]
X4 0 Bool X4

Y 0 Bool Y
.../build_sps_1.VAL

OR10 or10_2 OR10 default OR

X1 Power system.Meas.point I-3ph 2.Supv. Bool X1


balan. I.Failure [BOOL]
X2 Power system.Meas.point I-3ph 2.Supv. Bool X2
ph.seq.I.Failure [BOOL]
X3 Power system.Meas.point I-3ph 2.Supv. Bool X3
sum I.Failure [BOOL]
Y 0 Bool Y
.../build_sps_2.VAL

OR10 or10_3 OR10 default OR

X1 Power system.Meas.point I-3ph 3.Supv. Bool X1


balan. I.Failure [BOOL]
X2 Power system.Meas.point I-3ph 3.Supv. Bool X2
ph.seq.I.Failure [BOOL]
X3 Power system.Meas.point I-3ph 3.Supv. Bool X3
sum I.Failure [BOOL]
X4 Power system.Meas.point I-3ph Bool X4
3.Supv.ADC sum I.Failure [BOOL]
Y 0 Bool Y
.../build_sps_3.VAL

BUILD_Q build_q_1 BUILD_Q default BUILD_Q

GOOD 1 Bool GOOD

BAD 0 Bool DISTURBED

QL 16#0000 Struct QL
.../build_sps_1.QL

BUILD_SPS build_sps_1 BUILD_SP default BUILD_SPS


S
VAL .../or10_1.Y Bool VAL

QL .../build_q_1.QL Struct QL

OUT 0 Struct OUT

BUILD_Q build_q_2 BUILD_Q default BUILD_Q

GOOD 1 Bool GOOD

BAD 0 Bool DISTURBED

QL 16#0000 Struct QL
.../build_sps_2.QL

BUILD_SPS build_sps_2 BUILD_SP default BUILD_SPS


S
VAL .../or10_2.Y Bool VAL

QL .../build_q_2.QL Struct QL

OUT 0 Struct OUT


.../or_sps_1.IN1

BUILD_Q build_q_3 BUILD_Q default BUILD_Q

GOOD 1 Bool GOOD

BAD 0 Bool DISTURBED

QL 16#0000 Struct QL
.../build_sps_3.QL

BUILD_SPS build_sps_3 BUILD_SP default BUILD_SPS


S
VAL .../or10_3.Y Bool VAL

QL .../build_q_3.QL Struct QL

OUT 0 Struct OUT


.../or_sps_1.IN2

OR10 or10_4 OR10 default OR

X1 General.Health.warning [BOOL] Bool X1

X2 General.Health.alarm [BOOL] Bool X2

Y 0 Bool Y
Totally Integrated
Automation Portal

Run se‐ Object/parameter Operand Type Unit Task Additional Comment


quence tasks
.../build_sps_4.VAL

BUILD_Q build_q_4 BUILD_Q default BUILD_Q

GOOD 1 Bool GOOD

BAD 0 Bool DISTURBED

QL 16#0000 Struct QL
.../build_sps_4.QL

BUILD_SPS build_sps_4 BUILD_SP default BUILD_SPS


S
VAL .../or10_4.Y Bool VAL

QL .../build_q_4.QL Struct QL

OUT 0 Struct OUT


.../or_sps_1.IN3

OR_SPS or_sps_1 OR_SPS default OR_SPS

IN1 .../build_sps_2.OUT Struct X1

IN2 .../build_sps_3.OUT Struct X2

IN3 .../build_sps_4.OUT Struct X3

IN4 0 Struct X4

OUT 0 Struct OUT


Alarm handling.>Group Warning [SSPS]

VALID 0 Bool VALID


Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Process mode inactive
or10_1
OR10
OR
Device.Simulation mode active [BOOL] X1 Y Device.Process mode inactive [BOOL]
Totally Integrated

Device.Commiss. mode active [BOOL] X2


Automation Portal

and10_1 tlong_1
neg_1 AND10 TLONG
NEG AND TLONG
NEG X1 Y START Q Alarm handling.>Group Alarm [BOOL]
Device.DIGSI active [BOOL] IN OUT X2 RESET QT
4 HOUR
0 MIN
neg_2 10 100ms MS100
NEG
NEG
IN OUT
Process mode inactive - Data flow /Task: Event-triggered (1.1 / 3.2)

2.1 ( Page10 - 4)
1.2 ( Page10 - 3)
Totally Integrated
Automation Portal

Process mode inactive - Data flow /Task: Event-triggered (1.2 / 3.2)


1.1 ( Page10 - 2)

2.2 ( Page10 - 5)
Totally Integrated
Automation Portal

Process mode inactive - Data flow /Task: Event-triggered (2.1 / 3.2)


1.1 ( Page10 - 2)

2.2 ( Page10 - 5)

3.1 ( Page10 - 6)
Totally Integrated
Automation Portal

Process mode inactive - Data flow /Task: Event-triggered (2.2 / 3.2)


1.2 ( Page10 - 3)
2.1 ( Page10 - 4)

3.2 ( Page10 - 7)
Totally Integrated
Automation Portal

Process mode inactive - Data flow /Task: Event-triggered (3.1 / 3.2)


2.1 ( Page10 - 4)

3.2 ( Page10 - 7)
Totally Integrated
Automation Portal

Process mode inactive - Data flow /Task: Event-triggered (3.2 / 3.2)


2.2 ( Page10 - 5)
3.1 ( Page10 - 6)
Totally Integrated
Automation Portal
Totally Integrated
Automation Portal

Process mode inactive - Control flow /Task: Event-triggered


Run se‐ Object/parameter Operand Type Unit Task Additional Comment
quence tasks
OR10 or10_1 OR10 default OR

X1 Device.Simulation mode active [BOOL] Bool X1

X2 Device.Commiss. mode active [BOOL] Bool X2

Y 0 Bool Y
.../and10_1.X1
Device.Process mode inactive [BOOL]

NEG neg_1 NEG default NEG

IN Device.DIGSI active [BOOL] Bool IN

OUT 0 Bool OUT


.../and10_1.X2

AND10 and10_1 AND10 default AND

X1 .../or10_1.Y Bool X1

X2 .../neg_1.OUT Bool X2

Y 0 Bool Y
.../neg_2.IN
.../tlong_1.START

NEG neg_2 NEG default NEG

IN .../and10_1.Y Bool IN

OUT 0 Bool OUT


.../tlong_1.RESET

TLONG tlong_1 TLONG default TLONG

START .../and10_1.Y Bool START

RESET .../neg_2.OUT Bool RESET

HOUR 4 UInt HOUR


(0..65534
)
MIN 0 UInt MIN
(0..59)
MS100 10 UInt 100ms MS100
(0..599)
Q 0 Bool Q
Alarm handling.>Group Alarm [BOOL]

QT 0 Bool QT
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT / Display pages


Fault-display configuration
Circuit breaker 2
Display line Displayed information
Display line 1 Pickup indication
Display line 2 Operate indication
Display line 3 Trip indication
Display line 4 PU time
Display line 5 Trip time
Display line 6 No alarm

Circuit breaker 3
Display line Displayed information
Display line 1 Pickup indication
Display line 2 Operate indication
Display line 3 Trip indication
Display line 4 PU time
Display line 5 Trip time
Display line 6 No alarm

Circuit breaker 1
Display line Displayed information
Display line 1 Pickup indication
Display line 2 Operate indication
Display line 3 Trip indication
Display line 4 PU time
Display line 5 Trip time
Display line 6 No alarm
Totally Integrated
Automation Portal

7UT87_220kV M3GSUT
Safety and security
Operations safety and access control
Enter confirmation ID
Scope of operation Active Description
Settings / operation true Allows change of settings and access to process data.
Fct.Key/PB operation false Allows operating via function keys and push-buttons only with
confirmation ID (of Settings/Operation).
Switching (process) true Allow switching operations. Interlocking condition get consid‐
ered.
Switching (unlocked) true Allow switching operations. Interlocking condition get ignor‐
ed.
Switching authority true Definition of the authority for switching operations. LOCAL al‐
ways has higher priority than REMOTE.

Security event logging


Sec. Ev. Logg. \General
Number Settings Value
1331.2761.19021.120 Security log cap. warn. All: 80 %

Sec. Ev. Logg. \syslog server A


Number Settings Value
1331.2761.19021.101 Enable logging All: false

Sec. Ev. Logg. \syslog server B


Number Settings Value
1331.2761.19021.111 Enable logging All: false

Network access security


DIGSI access
Number Settings Value
1331.19831.101 Integrated Port J All: read and write access
1331.19831.102 Module Port E All: read and write access

Web access
Number Settings Value
1331.20431.101 Integrated Port J All: read and write access
1331.20431.102 Module Port E All: read and write access

Client Auth
Number Settings Value
1331.21001.102 Trusted CA All: SIPROTEC 5 trusted certificate authority