Professional Documents
Culture Documents
Abstract—The demand of electricity transmission safe and reliable, such Substation should have
toward regions for society, industrial and other grounding system [2]. Grounding system plays
needs are increasing hence, making electricity important role in a Substation operation.
transmission and distribution increased as well. Grounding system provides connected neutral
The increase in electricity transmission and
point system, equipment, and support for
distribution requires addition of Substation
construction. Substation constructions are crucial structure into the earth. Grounding system
for economic growth in Indonesia. This research ensures safety for every one that work inside
aims to design two models of grounding system, to Substation. Grounding system also eases
determine permissible touch voltages and interference finding into the earth and helps
permissible step voltages, and to simulate both controlling and protecting system [1].
designs using CYMGrd Software, whereby both Grounding system has crucial roles a
designs were compared to obtain optimal Substation, amongst them are to ensure people
grounding system at 275 KV Betung Substation. or animal nearby grounded facilities not
With touch voltages and step voltages values of
affected by hazard from electric shock and to
1387.97 V and 364.6 KV in first model, and touch
voltages and step voltages of 1247.2 V and 112.39 provide means to carry electric currents into the
V in second model, both model did not exceed earth under normal and fault conditions without
permissible touch voltages of 1409.58 V and exceeding any operating and equipment limits
permissible step voltages of 5050.1 V. Final result or adversely affecting continuity of service [3].
of this research showed that second design model With this crucial role of grounding
was more optimal compared with the first design system, we conducted grounding system design
model. optimization on 275 KV Betung Substation
Project which aims to design two models of
Keywords—Substation; grounding system; CYMGrd
grounding system by determining permissible
software; touch voltage and step voltage; IEEE 80-
2000 Standard. touch voltages and permissible step voltages on
275 Betung KV Substation, and simulating both
design models with CYMGrd Software.
I. INTRODUCTION Afterwards, both designs were compared to
Substation is an integrated part of obtain optimal design. Grounding system design
electricity distribution and transmission. In on 275 KV Betung Substation discussed in this
which certain power system centered in a place paper is grounding on equipment, and such
containing transmission and distribution, design carried out only on outdoor side which is
distribution tools, transformer, and safety tools simulated using CYMGrd Software.
and control tools. The success of a power
system operation depends on efficient and
II. RESEARCH METHOD
satisfying performance of a Substation.
Therefore, Substation could be said as core of a A. Design Flowchart
power system [1]. Safety and reliability are the Fig. 1. shows design flowchart on how to
two main matters in operation and design of an design grounding system according to IEEE
electricity power system, including in Standard 80-2000:
Substation design. To ensure that Substation is
978-602-50431-1-6/17/$31.00 ©2017 IEEE 400 2017 15th Intl. Conf. QiR: Intl. Symp. Elec. and Com. Eng
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
Fig.1. Design Flowchart According to IEEE 80-2000 [3]
401
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
If protective surface layer is not used, then Cs = 1 and ȡs=ȡ.
ȡs earth surface resistivity in tf fault duration in s
ȍ.m Ta dc time offset constant in s
ts duration of shock current in Ig symmetrical grid current in A, in which
seconds. Ig is [4]
3I(0)A 3I(0)B
3I(0)C
I”k
3I(0)B
B C
A
ZEB
ZEA ZEC
UEB
Fig. 2. Partial Short-Circuit Current on Short Circuit Phase into the Ground on Substation B [4]
402
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
(10) with
In which, in which
ZP driving point impedance in ȍ resistance per unit length from earth
ZW earth wire impedance between two wires
towers, where ZW [4] rWW equivalent earth wire radius
rW earth wire radius
(11) for 1 earth wire: rWW = rW
for 2 earth wires:
• Reduction Factor for Overhead Line v total earth wire
(OHL) dWL geometric mean distance between earth
The following equation used to calculate wire and phase conductor L1, L2, and
reduction factor for OHL [4] L3
Ȧ angular frequency: Ȧ = 2ʌf
(12) permeability in the air:
403
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
TABLE 2. FIGURE OF BOTH DESIGN MODEL
Model 1
Model 2
In first design model, Bare Copper 276 rods were used. Table 3 shows potential
Conductor (BCC) used were 5,334.35 m and 12 contour simulation result on both design model
rods were used. Meanwhile on the second
design model, 5,089.49 m BCC were used and
404
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
TABLE 3. CONTOUR SIMULATION RESULT ON BOTH DESIGN MODEL
Model 1
Model 2
405
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
TABLE 4. POTENTIAL PROFILE SIMULATION RESULT ON BOTH DESIGN MODEL
Model 1
Model 2
406
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.
TABLE 5. OPTIMALIZATION OF BOTH GROUNDING SYSTEM DESIGN OF 275 KV BETUNG
SUBSTATION
Rg 0.588699 ȍ 0.530937 ȍ
IV. CONCLUSION
1. There were two grounding design models ACKNOWLEDGMENT
simulated in this research of grounding Researcher would like to thank source person
system design optimization on 275 kV and all supporting parties in data collection and
Betung Substation. First model used 12 processing in this research. Eventually,
rods and 5,334.5 m BCC. Meanwhile researcher hope that Allah SWT would grant
second model made with more rods, 276 His grace and blessing for all parties supporting
rods and grounding BCC was made the completion of this article.
loose, 5,089.49 m
2. In first model, Etouch actual and Estep
actual was 1,387.97 V and 364.6 V REFERENCES
respectively. Meanwhile on the second [1] K. A. Vyas; J. G. Jamnani, “Optimal Design
model, Etouch actual and Estep actual were of Grounding System for HV/EHV
1,247.2 V and 112.39 V respectively. On Substations in Two Layered Soil”,
permissible Etouch and Estep and manually International Journal of Emerging
calculated, permissible Etouch and Estep Technology and Advanced Engineering,
value was 1,409.58 V and 5,050.1 V Gujarat, 2012, pp. 383 – 392, Vol. 2 (5).
respectively. These showed that both
[2] M. A. Adelian, “Improvement of Substation
design model had complied with the
Earthing”, International Journal of
permissible Etouch and Estep or both design
Engineering and Advanced Technology,
was safe.
3. Upon the comparison of both design, 2014, pp. 100 – 104, Vol. 3 (4).
economically it was predicted that cost [3] IEEE Guide for Safety in AC Substation
needed to construct second grounding Grounding, IEEE Standard 80-2000, 2000.
system design model on 275 kV Betung
Substation was Rp 3,810,225,872.65, [4] S. Ishak, “Module Earthing Calculation Note
cheaper than cost estimation for first Using Excel Spread Sheet and CYMGrd
grounding system design model of Rp Software”, Jakarta : -, 2014, Chapter 2
4,561,053,777.78.
407
Authorized licensed use limited to: Universidad Antonio Narino. Downloaded on May 30,2020 at 17:57:48 UTC from IEEE Xplore. Restrictions apply.