You are on page 1of 19

1 material facts

1.1 overview
This manual is used for the 2SA5 series electric actuator installation, adjustment, operation and maintain.
Warning : Everyone must reads this manual carefully before starting the installation, adjustment, o peration and
maintenance. Do not run this actuator until you familiar with this product and read this manual.
Warning: When staff is near the valve and electric actuator, please be careful the high temperature, high pressure,
inflammable and explosive goods, toxic and corrosive materials which may present safety hazards.
Warning: The staff must install, connect, adjust, operate, store and maintain the actuator strictly according to the
operation procedure, drawings and manual. Otherwise, it may result in serious injury, equipment damaged and loss
of quality guarantee.
1.2 Safety Instruction
In order to avoid possible or potential physical harm, operation trouble, equipment breakdown and loss of quality
guarantee, we use the following logo in this manual to indicate those possible or potential problems. Please read this
manual carefully!
Warning: Any false operation may result in serious injury or death
Important: Any false operation may result in mild injury or minor wound and damages on product
Notice: the key messages remind users to understand and master the installation, adjustment and operation of 2SA5
series electric actuator.
1.3 Storage Note
If the actuator is not installed and used on-site immediately, please follow the steps below to storage it. Those steps
will guarantee optimum performance of the actuator, otherwise might be lead to degrade the performance and loss
quality guarantee.
2SA5 series electric actuator adopted Non-intrusive design, so it has strong moisture resistance. All covers and cable
entrances were sealed completely when the actuator leave the factory. Therefore the actuator should be stored in dry
and clean warehouse directly. Please avoid the vibration shock and the rapid variation of temperature.
If the 2SA5 series electric actuators were placed outside, they should be stored off the ground, and thoroughly covered
with waterproof plastic sheeting to avoid being soaked in the water or buried in snow.
If the actuator has not connected with the valve, please make sure the motor axis of the actuator is located in the
horizontal position.
If the actuator has connected with the valve, please install suitable valve rod case immediately to prevent debris into
drive sleeve and subject to corrosion.
2 Technical Data
2.1 ordering direction
2.1.1 Model Selecting Guide on Multi-Turn Electric Actuator
model:
1 2 3 4 5 6 7 - 8 9 10 11 Additional

2 S A 5 - -

ECOTRON (Switching type) 0

PROFITRON (Adjustable type) 5 See P2

No additional function 0

Relay Board with five relay dry contact output signals 1

with RPOFIBUS DP bus board 2

with MODBUS RTU bus board 3

1
2.1.2 Model selecting guide on Linear Electric Actuator

2
2.1.3 Model Selecting guide on Quarter-Turn Electric Actuator

3
4
2.2 Technical Data
Item Item Description
Input signal 4~20mA;0~10V(optional)Four binary signals (OPEN, CLOSE, STOP, EMERGENCY)
Output signal 4~20mA(Load impedance≤750Ω)5 relay dry contact signals (contact capacity
220V/1A)
Power supply AC200V/380V±15% (others can be customized)
DC4~20mA analog control
Control mode Switching control (OPEN,CLOSE, STOP, EMERGENCY)
PROFIBUS DP Modbus (optional)
Basic Error ≤0.5%
Return difference ≤0.5%
Dead Band 0.3~5% adjustable
Operating Mode S4-1200 times per hour. S2-15min; S2-30min
Protecting Function Over-torque,overvoltage,overcurrent,remote control of signal breaking
Additional Function Torque, speed adjustable, flexible start and stop
Environment
-25°C~+70°C
Temperature
Environment
Environment 5~95%
Humidity
Conditions
with frequency rate within 10~200HZ, the acceleration rate can reach a lasting
Mechanical
oscillation of 0.5g
Oscillation

Degree of Protection IP67 (IP68 is customizable)

3 Installation guide

Warning: When staff is near the valve and electric actuator, please be careful the high temperature, high
pressure, inflammable and explosive goods, toxic and corrosive materials which may present safety hazards.
Warning: Please install the actuator, connect the wiring, set the parameter, operate and maintain the actuator
in strict accordance with this manual. Otherwise, it may result in serious injury, equipment damaged and loss of
quality guarantee.

3.1 Installing the Electric Actuator to the Valve

1 Notice: the flange plate of valve and electric actuator should be cleaned thoroughly with greasy dirtying,
wiped off surface oil.
2Small amount of oil should be applied to the connection part
3 The electric actuator should be accurately installed to the valve
4 Bolts should be at least 8.8 in respect of level of performance (spring shims should be used to fixed bolts).
5 Torque of swivel bolt is M8 (23Nm) ; MlO (68Nm) ; M16 (305Nm) ; M20 (500Nm)

5
Figure 1 Type A output shaft
Type A output shaft should be first processed. If not, please process according to the following steps:
(1) Locating ring D should be unscrewed from flange plate
(2)Thread bushing A, needle bearing C and bearing shim B should be taken down together.
(3)Needle bearing C and bearing shim B should be taken down from thread busing A. Then the thread should
be taped out (check concentricity and beating rate after installation) and cleaned.
(4)Ball bearing greasy should be applied to needle bearing C and bearing shim B and attach them to thread
bushing A.
(5)Thread bushing A and the bearing should be inserted into the flange of output shaft.
(6)Screw locating ring D in until it is fixed.
(7)Ball bearing greasy should be applied through zerk with greasy gun until oil runs out of the centering ring.
(8)Then hand shank or hand heel should be used to rotated electric actuator so the thread will move to the
drive bolts of the valve.
(9)Finally, the flange mounting surface of electric actuator and that of valve should be fastened by bolt when
they are next to each other.
Important : please screw the fixing screw nut to make sure the valve-stem drive nut won’t fall off.
3.2 Separated Installation
Attention:
1. During installation, make sure ring O has been fixed well so as to meet the required protection level.
2 The motor power line and control line should be installed separately with shielded cables.
For any smart electric actuator, before or after delivery, separate installation of its control unit and mechanical
part can be carried out through separate installation components.
The following four conditions are suitable for separate installation:
(1)Installation environment with too high temperature
(2)Installation environment with too much oscillation
(3)Installation environment not suitable for debugging
(4)Installation environment with limited space

3.3 Electrical Connection Fighure3-1 Separated Installation

Warning: please cut off the main power supply before remove the independent terminal cover.
(1)Loosen four bolts from the electric warehouse, take off the junction box. See picture 3-2

6
Fighure3-2 take off the junction box.
(2)Screwing cable sealing joint and through the cable.
Caution: power cable: Main circuit wirings should be using metallic sealed pipe joint. Control cables: must be using
shielded cables with metallic sealed pipe joint to prevent electromagnetic interference.
Filed bus cable: the shield can be earthed on the circuit board of bus interface .
(3) Take XI terminal off the control board. If it with relay board, take X2 terminal off relay board and X3 terminal
off driver board. Using screwdriver to push/pull out the terminal from the plug board, if need be.
(4)According to the connection diagram (pic 3-4), connect the power supply and control line. Make sure the
protective earth (PE) connected with the ground point in internal actuator.
(5)Install terminal XI on the control board, terminal X2 on the replay board, terminal X3 on the driver board.
(6)Put the junction box back on the electronic storehouse, cable service entrance should be installed horizontal
downward at the moment.
(7)Screw the cable seal pipe joint
Important: during installation, the most important of all is make sure the sealed tube cable joint and sealed ring (O-
type ring) have been assembled well so as to meet the required protection level. For details of allowed diameter of
conductor, refer to wiring diagram.
3.4 Electrical connection
3.4.1 direct connection

3.4.1.1 Definition for terminals and requirements for wiring


Terminal Definition
Terminal block terminal Name Functions and Directions

Fighure3-3
Terminal block terminal Name Functions and Directions
X1.1 1(+)、 2(-) 4~20mA AO
X1.2 14(+)、 15(-) 4~20mA AI

X1.1、X1.2 3、18 internal output 24V

X1.1
4、5、6、7、19、20 four Switching value input: OPEN,CLOSE, STOP, EMERGENCY
X1.2

1、2、3、4 corresponding relay 1:1、2 normal close,3、4 normal open;


1、2、3、4/5、6、
5、6、7、8 corresponding relay 2:5、6 normal close,7、8 normal open;
7、8/9、10、11、
X2 9、10、11、12 corresponding relay 3:9、10 normal close,11、12 normal open;
12/13、14、15、
13、14、15、16 corresponding relay 4:13、14 normal close,15、16;normal open
16/17、18、19、20
17、18、19、20 corresponding relay 5:17、18 normal close,19、20 normal open

7
regulated wiring
power line signal control line
Motor power ≤1.5kW, recommend 1.0mm², MAX 2.5mm²
0.5mm²
Motor power ≥3.0Kw, recommend 1.5mm²,MAX 4.0mm²
cable stealing thread size
Terminal(standard ) standard(Metric) Recommended wire diameter(mm)
2-M25x1.5 2-M25x1.5 12-14
1-M20x1.5 1-M20x1.5 10-12
in the process of transportation, the threaded hole of cable sealing lip should be coverd by plug screw 。
Protection level is provide by the seal of the cable after on-site installation. Please using the incoming line cover
with the product and collocating the suitable cable which is matching the external diameter. And apply seal on the
cable entry so as to meet the required protection level when necessary.

4 Operation
4.1 Local operation
Local operation includes the following contents: see picture 4-1 Operation Faceplate Diagram
8
information center
operation button
LED light
4.1.1 information center
LCD screen provides the actuator’s information of operation
mode, position, parameter setting choices, parameter input,
information feedback and alarm information.
4.1.2 operation buttons
You can choose the control operation sites of actuator
(local/remote) via the operation buttons, and running
the actuator locally at the same time. There are four
buttons provide different functions (see table 4-1).
4.1.3 LED Light
LED blue light blinking indicates the actuator is opening or closing, red light indicates the actuator fails to work
properly.
4.2 remote operation
Remote operating command depends on the parameter switching value and setting of switching value mode,
through:
Operate by switching input terminals (on, off, stop and emergency) and analog input channels.
Operate by Profibus DP or modbus RTU
manual operate
Warning: hand shrank (hand wheel) can be connected to the interior worm when the actuator is not operating.
Warning: After debugging, the operating of actuator with hand shrank should be confined to the scope of
terminal position set before. Otherwise, the scope has to be reset.
Clockwise rotation of the hand shrank (hand wheel) will lead to:
Anticlockwise rotation of Multi-Turn actuator
Distance rod’s outward extension in Linear actuator, which is close the value
Clockwise rotation (seen from the side of worm-gear box marked with arrow) of Quarter-Turn actuator when
the worm-gear box is RR.
1Press the handle/handwheel in the direction towards gearbox and overcome the resistance of the spring,
then users can switch the motor operation mode to manual opeartion mode.
2 Manual operation is preferential compared to motor operation. Motor operation is possible only when hand
shrank is loose.

5 customize electric actuator parameter

short-press: switch between local and remote,

LOCAL/REMOTE return to previous menu in the mode of parameter setting.


Long-press: enter or exit the mode of parameter setting

Local mode: hold the button less than 5 seconds, actuator operates towards “on” direction.
Parameter setting mode: short press : parameter modification and switch between the menu.

Hold the button more than 5 seconds, actuator operates towards “off” direction with self hold.
Parameter setting mode: short press : parameter modification and switch between the menu.

parameter setting mode: long press: confirmation and save of parameter modification. Short-press: Enter the next level menu
ENTER
Local mode and stroke calibration mode: stop the actuator

9
Warning: the internal actuator with high voltage. When debugging, take operation panel off the control unit
without touching the print lines or component on circuit boards using fingers, and prevent print lines or component
contact with metal objects.
Warning:Consulting with the responsible person firstly, and make sure the debugging would not interfere
with the factory’s regular production and cause personal injury.
Warning: if the shutdown mode at the terminal position isn’t suitable for this value, it might be harmful to
the value.
5.1 Enter parameter setting mode
Under the parameter setting mode, you can modify the parameters of actuator to achieve the optimum control
and optimum using effect.
1 Under normal control mode, short press LOCAL/REMOTE button, enter the mode of local control.
2 Under normal control mode, long press LOCAL/REMOTE button, enter the mode of parameter setting
3 Under parameter setting mode, short press LOCAL/REMOTE button, and LCD screen shows a series of
parameter setting elements, see picture 5-1.
4 Short press ↑or ↓ for choosing new parameter values, long press ENTER button for saving new parameter
values.
5 When parameter setting is completed, long press LOCAL/REMOTE button to exit the parameter setting and
back to local control mode.
5.1 parameter setting

10
5.2 modify parameter setting
5.2.1 Language menu setting
Users can change display language of 2SA5 series electric actuator based on actual requirements, details please
refer to Figure 5-2 language setting.
1: LCD screen shows “language setting”,
2 Short press ↑or ↓, chose the language in “Chinese” or “English” .
3 long press ENTER button to confirm modified values, and the screen shows“dead-zone setting” at the
moment.
4. To return the normal control mode, please long press LOCAL/REMOTE button.
Figure 5-2 language setting

Enter

5.2.2 Dead band setting


Control accuracy can be improved by production technology requirements without oscillatory response. Details
please refer to Figure 5-3 Dead band setting.
1: LCD screen displayed “Dead band setting”
2: modify parameter values through short press ↑or ↓button, default value: 0.5%, Scope: 0.3%-30%
3: long press ENTER button to save modified values, and the screen shows“off-signal setting” at the moment.
4. To return the normal control mode, please long press LOCAL/REMOTE button.
Figure 5-3 Dead Band Setting

Enter

5.2.3 off-signal setting


Users can set the actuator based on the safeguard procedures on the appearance of off-signal during the valve
control, Details please refer to figure 5-4 off-signal setting.
1: LCD screen displayed “off- signal setting”
2: short press ↑or ↓button to modify parameter values. Default value: hold, parameter value: hold, all-on, all-
off.
Hold: stay at the original position
All-on : the value fully open.
All-off: the value fully close.
3: long press ENTER button to confirm modified values, and the screen shows“decelerated position setting”
at the moment.
To return the normal control mode, please long press LOCAL/REMOTE button.
figure 5-4 off-signal setting

11
Enter

5.2.4 decelerated position setting


Value control can be optimized through decelerated position setting. Details please refer to figure 5-5 decelerated
position setting.
1: LCD screen shows “decelerated position setting”
2: modify parameter values through short press ↑or ↓. Default value: 5.0%, range: 1.0%-10%
3: long press ENTER to confirm modified values, and the screen shows“off-terminal position setting” at the
moment.
To return the normal control mode, please long press LOCAL/REMOTE button.
figure 5-5 decelerated position setting

Enter

5.2.5 Valve stroke setting (must calibrated the stroke when the user first use it)
Warning: the internal actuator with high voltage. When debugging, take operation panel off the control unit
without touching the print lines or component on circuit boards using fingers, and prevent print lines or component
contact with metal objects.
Warning:Consulting with the responsible person firstly, and make sure the debugging would not interfere with
the factory’s regular production and cause personal injury.
Warning: if the shutdown mode at the terminal position isn’t suitable for this value, it might be harmful to
the value.

5.2.5.1 Preparations before valve stroke setting


After installation, please check and make sure that:

1The actuator and valve have been installed and connected with each other correctly
2 All set screws, adapting piece and electrical connection part have been screwed up
3 Ground connection and equipotential bonding have been carried out correctly.
4 Electrical connection is right
5 Adopt all measures to prevent the fingers touch the moving parts
6 The actuator and valve must be in perfect condition
7 The environment temperature should be within the required scope for actuator operation. (The impact of
the heat transmitted from control targets should be taken into account).
Certain further checking is necessary according to the specific condition of the factory.
5.2.5.2 Adjusting the Rate of signal Gear Unit (It is needed only when the valve is fitted).

12
We will adjust it if users have clearly illustrated the stroke scope of control target when they ordered the
actuator. If not, follow the operation steps below to adjust the rate of signal gear unit:
1 Take the cover down from signal gear unit.
2 Decide the full stroke rotating turns of actuator, stroke length (mm) or angle (the defining rotating turns of
the whole positioning stroke output shaft should be include)
3 Count the upward rotating turns of the full stroke and stroke length(mm). Adjust the angle to one that most
close to the parameter in the next grade. (Diagram 1 for parameter. e.g. when rotating turns is 30, grade 36 should
be chosen.)
4 Adjust slip wheel with locking mechanism until the edge of its wheel align to the parameter on its cover. (Four
set screws of signal gear unit can be taken down to allow the signal gear unit to be taken out when necessary. And
reset it after readjustment.)
5 Install the exterior cover of the signal gear unit.
Adjustable rate of signal gear unit Table 5-1 Multi-turn actuator
Model Unit
0.8 2.1 5.5 14 36 93 240 610 1575 4020 adjustable ratio of the signal gear unit
0.8- 2.1- 5.5- 14- 36- 93- 240- 610- 1575-
2SA5… ONS ≤0.8
2.1 5.5 14 36 93 240 610 1575 4020

Adjustable rate of signal gear unit


Model Unit Table 5-2 Linear actuator
0.8 2.1 5.5 14 36 93
adjustable ratio of the signal gear unit
Revoluti- 27.5-
2SA5…+LE12.1 ≤4 4-10.5 10.5-27.5 70-180 180-465
ons/stroke 70

Revoluti- 27.5-
2SA5…+LE25.1 ≤4 4-10.5 10.5-27.5 70-180 180-465
ons/stroke 70

Revoluti-
2SA5…+LE50.1 ≤4.8 4.8-12.6 12.6-33 33-84 84-216 216-558
ons/stroke

Revoluti- 38.5-
2SA5…+LE70.1 ≤5.6 5.6-14.7 14.7-38.5 98-252 252-651
ons/stroke 98

Revoluti- 38.5-
2SA5…+LE100.1 ≤5.6 5.6-14.7 14.7-38.5 98-252 252-651
ons/stroke 98

Revoluti- 112-
2SA5…+LE200.1 ≤6.4 6.4-16.8 16.8-44 44-112 288-741
ons/stroke 288

Table 5-3 Quarter-turn actuator adjustable ratio of the signal gear unit
Adjustable rate of Adjustable rate of
Model Model
signal gear unit signal gear unit
2SA5…+GS40.2/GF40.2 5.5 2SA5…+GS160-GZ14(4:1)/GF160-GZ14(4:1) 93
2SA5…+GS50.3/GF50.3 14 2SA5…+GS160-GZ14(8:1)/GF160-GZ14(8:1) 240
2SA5…+GS63.3/GF63.3 14 2SA5…+GS200/GF200 14
2SA5…+GS80.3/GF80.3 14 2SA5…+GS200-GZ14(4:1)/GF200-GZ14(4:1) 93
2SA5…+GS100.3/GF100.3 14 2SA5…+GS200-GZ14(8:1)/GF200-GZ14(8:1) 240
2SA5…+GS100.3-VZ4.3/GF100.3-VZ4.3 93 2SA5…+GS200-GZ14(16:1)/GF200-GZ14(16:1) 240
2SA5…+GS125.3/GF125.3 14 2SA5…+GS250-GZ14(4:1)/GF250-GZ14(4:1) 93
2SA5…+GS125.3-VZ4.3/GF125.3-VZ4.3 93 2SA5…+GS250-GZ14(8:1)/GF250-GZ14(8:1) 240
2SA5…+GS160/GF160 14 2SA5…+GS250-GZ14(16:1)/GF250-GZ14(16:1) 240

13
5.2.5.3 valve stroke setting
Please follow these steps to set the valve stroke, details refer to the figure 5-8 valve stroke setting.
1 Loosen the valve manually (direction refers to section 4.3), keep the valve not tightened.
2 Taking off cover from signal gear unit, and adjusting the ratio of the signal gear unit based on the value’s
requirements.
3 LCD screen shows “off-terminal position setting”
4 Setting the off-terminal position when the LCD screen shows “closure terminal position setting” (calibrate
zero position).
(1)operational method:
a) Motor operation method: operate the actuator towards closed terminal position through press ↑or ↓ key.
When the actuator run to the suitable closed position, then do the step 2.

b) Hand shank/hand wheel operation method: Press the hand shank /hand wheel in the direction towards
gearbox and overcome the resistance of the spring, operate the actuator toward closed terminal position through
rotate the hand wheel (refer to section 4.3). When the actuator run to the suitable closed position, then do the
step 2.
(2)Hold on the extension part D, (refer to picture 5-6) of signal gear unit, rotate E part manually until the
potentiometer angle in the table 5-4 position.
(3)Long press the ENTER to confirm closed terminal position (zero position), and LCD shows “OK” at the
moment, LCD screen shows “opened-closed terminal position setting”
5 Sets the opened terminal position when the LCD screen shows “opened terminal position setting” (calibrate full
position).
(1)Operational method
a)Motor operation method: operate the actuator towards opened terminal position through press ↑or ↓.
When the actuator run to the suitable opened position, then do the step 2.
b)Hand shank/hand wheel operation method: Press the hand shank/hand wheel in the direction towards
gearbox and overcome the resistance of the spring, operate the actuator toward opened terminal position through
rotate the hand wheel (refer to section 4.3). When the actuator run to the suitable opened position, then do the
step 2.
(2)Long press the ENTER to confirm opened terminal position (full position), and show a notice “OK” at the
moment, LCD screen shows “operating speed setting”
Figure 5-4 potentiometer pointer angle of closed terminal position

14
6 Return to normal control mode, please long press LOCAL/REMOTE button.
7 Adjusting Indicator of Mechanical position
DO NOT rotate central wheel anymore once terminal position is set up (adjust manually or take the whole signal
gear unit out)! Otherwise, a reset is unavoidable!
Adjust the indicator of mechanical position according to the following guides to match the actual terminal position:
(1) Move actuator to full-off position
(2)Rotate wafer G until the red mark align to the arrow on the observing window of the cover.
(3)The actuator should operate to fully opened position.
(4)With white wafer G still, turn transparent wafer H until the green mark align to the arrow on the observing
window of the cover
(5)Coat the cover of signal gear unit. Make sure that the cover’s seal ring is correctly installed.
Figure 5-7 signal gear unit

Attention:1)If the ratio of signal gear unit is readjusted, the opened-closed terminal position should be reset.
2)If the potentiometer is reinstalled, the opened-closed terminal position should be reset.
3)Reset the stroke standardization when the control board is replaced
Figure 5-8 value stroke setting

15
Angle of pot enliome must not exceed 0
5.2.6 operating speed setting
Through operating speed setting, users can change the control speed of value. Details please refer figure 5-9
operating speed setting
1LCD screen shows “operating speed setting”
2 Modify parameter values through short press ↑or ↓. Default values and range are related to the specific model.
3 long press ENTER to save the new modified values, and the screen shows“shut off torque setting” at the
moment.
4 Return to normal control mode, please long press LOCAL/REMOTE button.
Figure 5-9 operating speed setting

5.2.7 shut off torque setting


Through shut off torque setting, users can set the valve closing torque/thrust based on the valve’s requirements.
Details please refer Figure 5-10 shut off torque setting.
1 LCD screen shows “shut off torque setting”
2 Modify parameter values through short press ↑or ↓. Default values and scopes are related to the specific
model
3 long press ENTER to save the new modified values, and the screen shows“switching value setting” at the
moment
4Return to normal control mode, please long press LOCAL/REMOTE button.
Figure 5-10 shut off torque setting

5.2.8 switching value input setting


Through switching value input setting, users can change the control mode of the valve. Details please refer Figure
5-11 switching value input setting.
1 LCD screen shows “switching value input setting”
2 Modify parameter values through short press ↑or ↓. Default value is set as open.
3 Long press ENTER to save the new modified value, and the screen shows “switching value mode” at the moment
4 Modify parameter values through short press ↑or ↓. Default value is set as inching or self-hold.
Inching: the actuator will drive the valve towards the corresponding direction as long as keeping the on-off
commands. The actuator will stop without control command.
self-hold: through pulsed contact control function of switching value input terminal (on, off, stop), actuator starts
running after receiving on/off pulse command, it will stop until receiving a stop command or reaching the end
position. Pulse width is 10ms。
5 long press ENTER to save the new modified values, and the screen shows“shut-off mode” at the moment

16
6Return to normal control mode, please long press LOCAL/REMOTE button.
Figure 5-11 switching value input setting

5.2.9 switching value output setting


Switching value output of 2SA5 series electric actuator adopts programmable relay under trigger states. Relay always
used for getting feedback of device state hardwire. Every relay has multiple trigger states to set up. Details please
refer figure 5-12 switching value output setting
1 LCD screen shows “relay 1” hint
2 Modify parameter values through short press ↑or ↓. Details please refer Table 5-5 relay function list.
3 Long press ENTER to save the new modified values, and the screen shows “relay 2” at the moment
4 Modify parameter values through short press ↑or ↓. Details please refer table 5-5 relay function list.
5 Long press ENTER to save the new modified value, and the screen shows “relay 3” at the moment
6 Modify parameter values through short press ↑or ↓. Details please refer table 5-5 relay function list.
7 Long press ENTER to save the new modified values, and the screen shows “relay 4” at the moment

8 Modify parameter values through short press ↑or ↓. Details please refer table 5-5 relay function list.
9 Long press ENTER to save the new modified value, and the screen shows “relay 5” at the moment
10 Modify parameter values through short press ↑or ↓. Details please refer table 5-5 relay function list.
11 Long press ENTER to save the new modified values, and the screen shows “parameter setting” at the moment
12Return to normal control mode, please long press LOCAL/REMOTE button.

Figure 5-12 switching value output setting

17
6 maintains and after-sales support
6.1 Maintains
In normal condition, little maintenance is needed. But we recommend a normal check after operating for 24h
after debugging. The followings are included for check:
(1)Whether the actual operation of the actuator can meet manufacturing technique requirements.
(2)Whether there is abnormal oscillation or noise.
(3)Whether there is any fixed component loose.
The above can’t include all the maintenance items. The specific maintenance activity should take the actual
operation condition into account so as the carry out the least maintenance.
6.2 After-sale servicex
The following circumstance should be included into paid repair as they are caused by users’ false operation not
in line with directions.
(1)Damages caused by users’ use and operation which is not following the instructions.
(2)Man-made damage caused by self-remade
(3)Damages caused by users’ false operation that not in line with product specification
(4)Damages caused by accidental drop by users after purchase
(5)Damages caused by force majeure like nature disasters
When abnormal operation is noticed, the actuator should be checked and adjusted according to the instruction
manual. If failed to recover, users should contact our company in time. With warranty period, any failure caused by
design or production would receive our non-paid repair; if the warranty period has passed, our company would
carry out paid repair to the product according to users’ requirements.

7 Countermeasures and treatment of failures


Actuator’s faults and treatment of failures

18
19

You might also like