6 Installing the Subrack and Relevant Components

3. Push the fan unit into the subrack slowly, and fasten the screw on the fan unit
panel, as shown in Figure 6-20.

Figure 6-20 Installing the Fan Unit

6.6 Installing and Removing the Subrack Anti-


dust Screen

Generally, the anti-dust screen has been installed in the subrack before delivery,
and users need not install it on site. However, cleaning and maintenance of the anti-
dust screen is required at regular intervals. In this case, users need to remove and
install it on site.

See Figure 6-21 for the appearance of the subrack anti-dust screen.

Version: A/1 6-19


AN5116-06B Optical Line Terminal Equipment Installation Guide

Figure 6-21 The Appearance of the Anti-dust Screen

The handle of the subrack anti-dust screen is located on the bottom of the screen.
Figure 6-22 illustrates the components of the anti-dust screen.

Figure 6-22 The Anti-dust Screen Components (Bottom)

The anti-dust screen is used together with the shield plate. Figure 6-23 illustrates
the components of the shield plate.

6-20 Version: A/1


6 Installing the Subrack and Relevant Components

Figure 6-23 The Shield Plate Components

6.6.1 Removing the Subrack Anti-dust Screen

Procedure

1. Hold the handle on the bottom of the anti-dust screen, and pull the anti-dust
screen outward gently to squeeze the clips on the front baffle of the shield plate,
as illustrated in Figure 6-24.

Figure 6-24 Pulling the Anti-dust Screen Gently

Version: A/1 6-21


AN5116-06B Optical Line Terminal Equipment Installation Guide

2. When squeezed, the clips on the front baffle generate a reverse spring force.
Pull down the anti-dust screen gently so that the anti-dust screen can detach
from the rear baffle of the shield plate, as illustrated in Figure 6-25.

Figure 6-25 The Anti-dust Screen Detached from the Rear Baffle

3. Go on to pull down the anti-dust screen so that the screen can detach from the
front baffle of the shield plate, as illustrated in Figure 6-26.

Figure 6-26 Taking out the Anti-dust Screen

6-22 Version: A/1


6 Installing the Subrack and Relevant Components

6.6.2 Installing the Subrack Anti-dust Screen

Procedure

1. Hold the handle on the bottom of the anti-dust screen. Attach the front baffle
side of the anti-dust screen to the front battle of the shield plate. Then pull the
anti-dust screen outward gently to squeeze the clips on the front baffle of the
shield plate, so that the anti-dust screen can fit snugly into the front baffle, as
illustrated in Figure 6-27.

Figure 6-27 The Anti-dust Screen Fit into the Front Baffle

2. Push the anti-dust screen upward gently until it fits snugly into the rear baffle of
the shield plate, as illustrated in Figure 6-28.

Figure 6-28 The Anti-dust Screen Fit into the Rear Baffle