NEMA Compliant Load Center Specifications

This document describes a load center that provides safe and reliable distribution of electrical power for residential, commercial, and light industrial applications. Key features include an enclosure made of electro-galvanized steel, tin plated copper busbars, ample terminals for neutral and earth connections, and adjustable wiring compartments. It is available in plug-in and bolt-on designs for indoor or outdoor use, and can be configured with various main circuit breakers up to 400 amps to serve between 1 and 54 electrical circuits.

Uploaded by

Daniyal Parvez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views16 pages

NEMA Compliant Load Center Specifications

This document describes a load center that provides safe and reliable distribution of electrical power for residential, commercial, and light industrial applications. Key features include an enclosure made of electro-galvanized steel, tin plated copper busbars, ample terminals for neutral and earth connections, and adjustable wiring compartments. It is available in plug-in and bolt-on designs for indoor or outdoor use, and can be configured with various main circuit breakers up to 400 amps to serve between 1 and 54 electrical circuits.

Uploaded by

Daniyal Parvez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

APPLICATION

Load Centers have been designed for safe and reliable distribution and
control of electrical power as service entrance in residential, commercial and light
industrial premises. The Load Center type LA is available in Plug-in and Bolt-on
designs for indoor and outdoor applications and also available with main as MCB,
MCCB or ELCB.

KNOCKOUTS OF VARIOUS SIZES


AND REMOVABLE TOP AND BOTTOM
GLAND PLATE FOR EASE OF CABLE
ENTRY

Made in KSA KEYHOLE FIXING FOR


EASE OF WALL MOUNTING

FULLY SHROUDED BUSBARS DEPTH OF PAN ASSEMBLY IS ADJUSTABLE

MATT-FINISH POLYESTER POWDER


TIN PLATED ETP COPPER BUSBARS COATED IN RAL-7035 LIGHT GREY COLOUR
WITHOUT ANY JOINTS

POLYCARBONATE FOR
BUSBAR SUPPORT AND INSULATION
SPACIOUS ENCLOSURE FOR EASY WIRING

AMPLE NEUTRAL TERMINALS

AMPLE EARTH TERMINALS

ENCLOSURE MADE OF HIGH QUALITY


MAIN BREAKER
ELECTRO-GALVANIZED STEEL SHEET

Figure 1

1
APPLICATION

Load Centers have been designed for safe and reliable distribution and
control of electrical power as service entrance in residential, commercial and light
industrial premises. The Load Center type LA is available in Plug-in and Bolt-on
designs for indoor and outdoor applications and also available with main as MCB,
MCCB or ELCB.

KNOCKOUTS OF VARIOUS SIZES


AND REMOVABLE TOP AND BOTTOM
GLAND PLATE FOR EASE OF CABLE
ENTRY

Made in KSA KEYHOLE FIXING FOR


EASE OF WALL MOUNTING

FULLY SHROUDED BUSBARS DEPTH OF PAN ASSEMBLY IS ADJUSTABLE

MATT-FINISH POLYESTER POWDER


TIN PLATED ETP COPPER BUSBARS COATED IN RAL-7035 LIGHT GREY COLOUR
WITHOUT ANY JOINTS

POLYCARBONATE FOR
BUSBAR SUPPORT AND INSULATION
SPACIOUS ENCLOSURE FOR EASY WIRING

AMPLE NEUTRAL TERMINALS

AMPLE EARTH TERMINALS

ENCLOSURE MADE OF HIGH QUALITY


MAIN BREAKER
ELECTRO-GALVANIZED STEEL SHEET

Figure 1

1
FEATURES 1- INDOOR TYPE
Made of high quality electro-galvanized steel sheet Standard Load Center (Type LA)

Tin plated ETP copper busbar without any joints NEMA Compliant Distribution Board
NEMA Standards (UL 50 & UL 67)
Polyester powder coating RAL-7035
Figure 5
Available cable tie & cable holding for easy wiring installations

Single-Phase LC With MCB Main 30-63 AF


NO. OF
SPECIFICATIONS WAYS ORDERING NUMBER AND TYPE

1 POLE FLUSH H h W w D SURFACE H h W w D


4 42-0604063IEC 327 298 250 220 95 42-0604063IECS 303 298 225 220 95
ITEM DESCRIPTION 6 42-0606063IEC 380 350 250 220 95 42-0606063IECS 355 350 225 220 95
Standard NEMA PB1* 8 42-0608063IEC 380 350 250 220 95 42-0608063IECS 355 350 225 220 95
Busbar Rating 100 to 400A MAX 10 42-0610063IEC 471 441 250 220 95 42-0610063IECS 446 441 225 220 95
Busbar Type ETP copper flat fully shrouded 12 42-0612063IEC 522 492 250 220 95 42-0612063IECS 522 492 225 220 95
Voltage Rating 120-440V AC 50/60 Hz 14 42-0614063IEC 573 543 250 220 95 42-0614063IECS 548 543 225 220 95
No. of Ways 3PH : 12,18, 24, 30, 36, 42, 48, 54 16 42-0616063IEC 624 594 250 220 95 42-0616063IECS 599 594 225 220 95
2PH : 4, 6, 8, 10 Main Breaker: Ranges from 30-63A
Figure 6
1PH : 4, 6, 8, 10, 12, 14,16 For example:
42-0604040IEC Represents load center 4 way with 40A main flush mounted
Degree Of Protection IP40 (NEMA 1) & IP54 (NEMA 3R)
42-0604063IECS Represents load center 4 way with 63A main surface mounted
Enclosure Material Electro-galvanized steel sheet (corrosion resistant) Figure 2

Steel Thickness Up to 1.2 mm


Knockout sizes See details on page 10, Figure 27
Two-Phase LC With MCB Main 30-100 AF
Enclosure Colour Polyester powder coated in RAL-7035 Grey colour NO. OF ORDERING NUMBER AND TYPE
Paint Thickness 70-90 microns WAYS
Main Breaker (incomer) MCB, MCCB, ELCB, ISOLATOR & DIRECT CONNECTION 1 POLE FLUSH H h W w D SURFACE H h W w D
Terminal Capacity MCB Frame Size 100 A : 50 [Link] 4 42-0404100 330 298 250 220 98 42-0404100S 303 298 225 220 98
MCCB Frame Size 100A : 95 [Link] 6 42-0406100 380 350 250 220 98 42-0406100S 355 350 225 220 98
MCCB Frame Size 225A : 185 [Link] 8 42-0408100 380 350 250 220 98 42-0408100S 355 350 225 220 98
MCCB Frame Size 250A : 185 [Link] 10 42-0410100 471 441 250 220 98 42-0410100S 446 441 225 220 98
MCCB Frame Size 400A : 300+125 [Link] Main Breaker: Ranges from 30-100A
Change last four digits for required ratings and mounting Figure 7
ELCB Frame Size 100A : 35 [Link]
For example:
Branches 1, 2 & 3 Pole Plug In MCBs 42-0408060 Represents load center 8 way with 60A main flush mounted
Neutral Terminal Bar Incoming Cable Lug :50,150 [Link] Figure 3
42-0408100S Represents load center 8 way with 100A main surface mounted

Outgoing Terminals : 16 [Link]


No. of Outgoing Terminals : Equivalent or more than No. of ways Two-Phase LC Without Main
Earth Terminal Bar Incoming Cable Lug :50,150 [Link]
NO. OF
Outgoing Terminals :16 [Link] ORDERING NUMBER AND TYPE
WAYS
No. of Outgoing Terminals : Equivalent or more than No. of ways
1 POLE FLUSH H h W w D SURFACE H h W w D
Rated Insulation Voltage 690 V AC
4 42-0304000 330 298 250 220 98 42-0304000S 303 298 225 220 98
Ambient Temperature 50 ºC
6 42-0306000 330 298 250 220 98 42-0306000S 303 298 225 220 98
* 'UL' compliance panels available upon request. 250 220 98 220 98
Figure 4 8 42-0308000 380 350 42-0308000S 355 350 225
10 42-0310000 420 390 250 220 98 42-0310000S 395 390 225 220 98
Busbar Rating: 100A
Figure 8
Change last four digits for required ratings and mounting
For example:
42-0308000 Represents load center 8 way 100A flush mounted
42-0308000s Represents load center 8 way 100A surface mounted
2 3
FEATURES 1- INDOOR TYPE
Made of high quality electro-galvanized steel sheet Standard Load Center (Type LA)

Tin plated ETP copper busbar without any joints NEMA Compliant Distribution Board
NEMA Standards (UL 50 & UL 67)
Polyester powder coating RAL-7035
Figure 5
Available cable tie & cable holding for easy wiring installations

Single-Phase LC With MCB Main 30-63 AF


NO. OF
SPECIFICATIONS WAYS ORDERING NUMBER AND TYPE

1 POLE FLUSH H h W w D SURFACE H h W w D


4 42-0604063IEC 327 298 250 220 95 42-0604063IECS 303 298 225 220 95
ITEM DESCRIPTION 6 42-0606063IEC 380 350 250 220 95 42-0606063IECS 355 350 225 220 95
Standard NEMA PB1* 8 42-0608063IEC 380 350 250 220 95 42-0608063IECS 355 350 225 220 95
Busbar Rating 100 to 400A MAX 10 42-0610063IEC 471 441 250 220 95 42-0610063IECS 446 441 225 220 95
Busbar Type ETP copper flat fully shrouded 12 42-0612063IEC 522 492 250 220 95 42-0612063IECS 522 492 225 220 95
Voltage Rating 120-440V AC 50/60 Hz 14 42-0614063IEC 573 543 250 220 95 42-0614063IECS 548 543 225 220 95
No. of Ways 3PH : 12,18, 24, 30, 36, 42, 48, 54 16 42-0616063IEC 624 594 250 220 95 42-0616063IECS 599 594 225 220 95
2PH : 4, 6, 8, 10 Main Breaker: Ranges from 30-63A
Figure 6
1PH : 4, 6, 8, 10, 12, 14,16 For example:
42-0604040IEC Represents load center 4 way with 40A main flush mounted
Degree Of Protection IP40 (NEMA 1) & IP54 (NEMA 3R)
42-0604063IECS Represents load center 4 way with 63A main surface mounted
Enclosure Material Electro-galvanized steel sheet (corrosion resistant) Figure 2

Steel Thickness Up to 1.2 mm


Knockout sizes See details on page 10, Figure 27
Two-Phase LC With MCB Main 30-100 AF
Enclosure Colour Polyester powder coated in RAL-7035 Grey colour NO. OF ORDERING NUMBER AND TYPE
Paint Thickness 70-90 microns WAYS
Main Breaker (incomer) MCB, MCCB, ELCB, ISOLATOR & DIRECT CONNECTION 1 POLE FLUSH H h W w D SURFACE H h W w D
Terminal Capacity MCB Frame Size 100 A : 50 [Link] 4 42-0404100 330 298 250 220 98 42-0404100S 303 298 225 220 98
MCCB Frame Size 100A : 95 [Link] 6 42-0406100 380 350 250 220 98 42-0406100S 355 350 225 220 98
MCCB Frame Size 225A : 185 [Link] 8 42-0408100 380 350 250 220 98 42-0408100S 355 350 225 220 98
MCCB Frame Size 250A : 185 [Link] 10 42-0410100 471 441 250 220 98 42-0410100S 446 441 225 220 98
MCCB Frame Size 400A : 300+125 [Link] Main Breaker: Ranges from 30-100A
Change last four digits for required ratings and mounting Figure 7
ELCB Frame Size 100A : 35 [Link]
For example:
Branches 1, 2 & 3 Pole Plug In MCBs 42-0408060 Represents load center 8 way with 60A main flush mounted
Neutral Terminal Bar Incoming Cable Lug :50,150 [Link] Figure 3
42-0408100S Represents load center 8 way with 100A main surface mounted

Outgoing Terminals : 16 [Link]


No. of Outgoing Terminals : Equivalent or more than No. of ways Two-Phase LC Without Main
Earth Terminal Bar Incoming Cable Lug :50,150 [Link]
NO. OF
Outgoing Terminals :16 [Link] ORDERING NUMBER AND TYPE
WAYS
No. of Outgoing Terminals : Equivalent or more than No. of ways
1 POLE FLUSH H h W w D SURFACE H h W w D
Rated Insulation Voltage 690 V AC
4 42-0304000 330 298 250 220 98 42-0304000S 303 298 225 220 98
Ambient Temperature 50 ºC
6 42-0306000 330 298 250 220 98 42-0306000S 303 298 225 220 98
* 'UL' compliance panels available upon request. 250 220 98 220 98
Figure 4 8 42-0308000 380 350 42-0308000S 355 350 225
10 42-0310000 420 390 250 220 98 42-0310000S 395 390 225 220 98
Busbar Rating: 100A
Figure 8
Change last four digits for required ratings and mounting
For example:
42-0308000 Represents load center 8 way 100A flush mounted
42-0308000s Represents load center 8 way 100A surface mounted
2 3
INDOOR TYPE
Three-Phase LC With MCB Main 30-100 AF Three-Phase LC With MCCB Main 250 A
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
6 2 42-06100 445 415 370 343 105 42-06100S 430 415 355 343 105 18 6 42-18250 926 896 430 400 140 42-18250S 911 896 415 400 140
9 3 42-09100 332 302 370 343 105 42-09100S 317 302 355 343 105 24 8 42-24250 1002 972 430 400 140 42-24250S 987 972 415 400 140
12 4 42-12100 542 515 367 343 105 42-12100S 527 515 352 343 105 30 10 42-30250 1078 1048 430 400 140 42-30250S 1063 1048 415 400 140
18 6 42-18100 618 591 367 343 105 42-18100S 603 591 352 343 105 36 12 42-36250 1154 1124 430 400 140 42-36250S 1139 1124 415 400 140
24 8 42-24100 697 667 367 343 105 42-24100S 682 667 352 343 105 42 14 42-42250 1230 1200 430 400 140 42-42250S 1215 1200 415 400 140
30 10 42-30100 773 743 370 343 105 42-30100S 758 743 355 343 105 48 16 42-48250 1305 1275 430 400 140 42-48250S 1290 1275 415 400 140
36 12 42-36100 878 848 370 343 105 42-36100S 863 848 355 343 105 Main Breaker: 250A
42 14 42-42100 960 930 370 343 105 42-42100S 945 930 355 343 105 Change last four digits for required ratings and mounting
For example:
Main Breaker: Ranges from 30-100A Figure 13
42-42250 Represents load center 42 way with 250A main flush mounted
Change last four digits for required ratings and mounting 42-42250S Represents load center 42 way with 250A main surface mounted
For example: Figure 9
42-12060 Represents load center 12 way with 60A main flush mounted
42-12100S Represents load center 12 way with 100A main surface mounted Three-Phase LC With MCCB Main 300-400 AF
Three-Phase LC With MCCB Main 30-100 AF NO. OF WAYS ORDERING NUMBER AND TYPE

NO. OF WAYS ORDERING NUMBER AND TYPE 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
24 8 42-24400 1186 1156 530 500 160 42-24400S 1171 1156 515 500 160
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
30 10 42-30400 1262 1232 530 500 160 42-30400S 1247 1232 515 500 160
12 4 42-L12100 620 590 370 343 105 42-L12100S 605 590 355 343 105
36 12 42-36400 1338 1308 530 500 160 42-36400S 1323 1308 515 500 160
18 6 42-L18100 700 670 370 343 105 42-L18100S 685 670 355 343 105
42 14 42-42400 1414 1384 530 500 160 42-42400S 1399 1384 515 500 160
24 8 42-L24100 773 743 370 343 105 42-L24100S 758 743 355 343 105
48 16 42-48400 1490 1460 530 500 160 42-48400S 1475 1460 515 500 160
30 10 42-L30100 878 848 370 343 105 42-L30100S 863 848 355 343 105
54 18 42-54400 1570 1540 530 500 160 42-54400S 1555 1540 515 500 160
36 12 42-L36100 960 930 370 343 105 42-L36100S 945 930 355 343 105
42 14 42-L42100 1040 1010 370 343 105 42-L42100S 1025 1010 355 343 105 Main Breaker: Ranges from 300-400A
Change last four digits for required ratings and mounting
Main Breaker: Ranges from 30-100A For example:
Change last four digits for required ratings and mounting 42-42300 Represents load center 42 way with 300A main flush mounted
For example: Figure 10 Figure 14
42-42400S Represents load center 42 way with 400A main surface mounted
42-L12060 Represents load center 12 way with 60A main flush mounted
42-L12100S Represents load center 12 way with 100A main surface mounted

One-Phase LC With 2 Pole ELCB Main


Three-Phase LC With MCCB Main 125-225 AF
NO. OF
ORDERING NUMBER AND TYPE
NO. OF WAYS ORDERING NUMBER AND TYPE WAYS
1 POLE FLUSH H h W w D SURFACE H h W w D
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
4 46-E104063030 327 298 250 220 95 46-E104063030S 303 298 225 220 95
12 4 42-L12225 620 590 370 343 105 42-L12225S 605 590 355 343 105
6 46-E106063030 380 350 250 220 95 46-E106063030S 355 350 225 220 95
18 6 42-L18225 700 670 370 343 105 42-L18225S 685 670 355 343 105
8 46-E108063030 380 350 250 220 95 46-E108063030S 355 350 225 220 95
24 8 42-L24225 773 743 370 343 105 42-L24225S 758 743 355 343 105
10 46-E110063030 471 441 250 220 95 46-E110063030S 446 441 225 220 95
30 10 42-L30225 878 848 370 343 105 42-L30225S 863 848 355 343 105
12 46-E112063030 522 492 250 220 95 46-E112063030S 522 492 225 220 95
36 12 42-L36225 960 930 370 343 105 42-L36225S 945 930 355 343 105
14 46-E114063030 573 543 250 220 95 46-E114063030S 548 543 225 220 95
42 14 42-L42225 1040 1010 370 343 105 42-L42225S 1025 1010 355 343 105
16 46-E116063030 624 594 250 220 95 46-E116063030S 599 594 225 220 95
48 16 42-L48225 1120 1090 370 343 105 42-L48225S 1105 1090 355 343 105

Main Breaker: Ranges from 125-225A


Change last four digits for required ratings and mounting Figure 11 46 - E 1 06 063 030 S
For example: AVAILABLE RANGE:
TYPE SURFACE
42-L42125 Represents load center 42 way with 125A main flush mounted 1- 2P, 63A, 30mA
42-L42225S Represents load center 42 way with 225A main surface mounted SENSITIVITY 2- 2P, 63A, 100mA Figure 15
3- 2P, 63A, 300mA*
RATING
4- 2P, 63A, 500mA*
NO. OF WAYS
*Will be manufactured on special request
ONE PHASE

Select The Main Sensitivity As Mentioned Above

4 Figure 12
5
INDOOR TYPE
Three-Phase LC With MCB Main 30-100 AF Three-Phase LC With MCCB Main 250 A
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
6 2 42-06100 445 415 370 343 105 42-06100S 430 415 355 343 105 18 6 42-18250 926 896 430 400 140 42-18250S 911 896 415 400 140
9 3 42-09100 332 302 370 343 105 42-09100S 317 302 355 343 105 24 8 42-24250 1002 972 430 400 140 42-24250S 987 972 415 400 140
12 4 42-12100 542 515 367 343 105 42-12100S 527 515 352 343 105 30 10 42-30250 1078 1048 430 400 140 42-30250S 1063 1048 415 400 140
18 6 42-18100 618 591 367 343 105 42-18100S 603 591 352 343 105 36 12 42-36250 1154 1124 430 400 140 42-36250S 1139 1124 415 400 140
24 8 42-24100 697 667 367 343 105 42-24100S 682 667 352 343 105 42 14 42-42250 1230 1200 430 400 140 42-42250S 1215 1200 415 400 140
30 10 42-30100 773 743 370 343 105 42-30100S 758 743 355 343 105 48 16 42-48250 1305 1275 430 400 140 42-48250S 1290 1275 415 400 140
36 12 42-36100 878 848 370 343 105 42-36100S 863 848 355 343 105 Main Breaker: 250A
42 14 42-42100 960 930 370 343 105 42-42100S 945 930 355 343 105 Change last four digits for required ratings and mounting
For example:
Main Breaker: Ranges from 30-100A Figure 13
42-42250 Represents load center 42 way with 250A main flush mounted
Change last four digits for required ratings and mounting 42-42250S Represents load center 42 way with 250A main surface mounted
For example: Figure 9
42-12060 Represents load center 12 way with 60A main flush mounted
42-12100S Represents load center 12 way with 100A main surface mounted Three-Phase LC With MCCB Main 300-400 AF
Three-Phase LC With MCCB Main 30-100 AF NO. OF WAYS ORDERING NUMBER AND TYPE

NO. OF WAYS ORDERING NUMBER AND TYPE 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
24 8 42-24400 1186 1156 530 500 160 42-24400S 1171 1156 515 500 160
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
30 10 42-30400 1262 1232 530 500 160 42-30400S 1247 1232 515 500 160
12 4 42-L12100 620 590 370 343 105 42-L12100S 605 590 355 343 105
36 12 42-36400 1338 1308 530 500 160 42-36400S 1323 1308 515 500 160
18 6 42-L18100 700 670 370 343 105 42-L18100S 685 670 355 343 105
42 14 42-42400 1414 1384 530 500 160 42-42400S 1399 1384 515 500 160
24 8 42-L24100 773 743 370 343 105 42-L24100S 758 743 355 343 105
48 16 42-48400 1490 1460 530 500 160 42-48400S 1475 1460 515 500 160
30 10 42-L30100 878 848 370 343 105 42-L30100S 863 848 355 343 105
54 18 42-54400 1570 1540 530 500 160 42-54400S 1555 1540 515 500 160
36 12 42-L36100 960 930 370 343 105 42-L36100S 945 930 355 343 105
42 14 42-L42100 1040 1010 370 343 105 42-L42100S 1025 1010 355 343 105 Main Breaker: Ranges from 300-400A
Change last four digits for required ratings and mounting
Main Breaker: Ranges from 30-100A For example:
Change last four digits for required ratings and mounting 42-42300 Represents load center 42 way with 300A main flush mounted
For example: Figure 10 Figure 14
42-42400S Represents load center 42 way with 400A main surface mounted
42-L12060 Represents load center 12 way with 60A main flush mounted
42-L12100S Represents load center 12 way with 100A main surface mounted

One-Phase LC With 2 Pole ELCB Main


Three-Phase LC With MCCB Main 125-225 AF
NO. OF
ORDERING NUMBER AND TYPE
NO. OF WAYS ORDERING NUMBER AND TYPE WAYS
1 POLE FLUSH H h W w D SURFACE H h W w D
1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D
4 46-E104063030 327 298 250 220 95 46-E104063030S 303 298 225 220 95
12 4 42-L12225 620 590 370 343 105 42-L12225S 605 590 355 343 105
6 46-E106063030 380 350 250 220 95 46-E106063030S 355 350 225 220 95
18 6 42-L18225 700 670 370 343 105 42-L18225S 685 670 355 343 105
8 46-E108063030 380 350 250 220 95 46-E108063030S 355 350 225 220 95
24 8 42-L24225 773 743 370 343 105 42-L24225S 758 743 355 343 105
10 46-E110063030 471 441 250 220 95 46-E110063030S 446 441 225 220 95
30 10 42-L30225 878 848 370 343 105 42-L30225S 863 848 355 343 105
12 46-E112063030 522 492 250 220 95 46-E112063030S 522 492 225 220 95
36 12 42-L36225 960 930 370 343 105 42-L36225S 945 930 355 343 105
14 46-E114063030 573 543 250 220 95 46-E114063030S 548 543 225 220 95
42 14 42-L42225 1040 1010 370 343 105 42-L42225S 1025 1010 355 343 105
16 46-E116063030 624 594 250 220 95 46-E116063030S 599 594 225 220 95
48 16 42-L48225 1120 1090 370 343 105 42-L48225S 1105 1090 355 343 105

Main Breaker: Ranges from 125-225A


Change last four digits for required ratings and mounting Figure 11 46 - E 1 06 063 030 S
For example: AVAILABLE RANGE:
TYPE SURFACE
42-L42125 Represents load center 42 way with 125A main flush mounted 1- 2P, 63A, 30mA
42-L42225S Represents load center 42 way with 225A main surface mounted SENSITIVITY 2- 2P, 63A, 100mA Figure 15
3- 2P, 63A, 300mA*
RATING
4- 2P, 63A, 500mA*
NO. OF WAYS
*Will be manufactured on special request
ONE PHASE

Select The Main Sensitivity As Mentioned Above

4 Figure 12
5
INDOOR TYPE
Three-Phase LC With 4 Pole ELCB Main

NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


12 4 46-E312063030 542 515 367 343 105 46-E312063030S 527 515 352 343 105
18 6 46-E318063030 618 591 367 343 105 46-E318063030S 603 591 352 343 105
24 8 46-E324063030 697 667 367 343 105 46-E324063030S 682 667 352 343 105
30 10 46-E330063030 773 743 370 343 105 46-E330063030S 758 743 355 343 105
36 12 46-E336063030 878 848 370 343 105 46-E336063030S 863 848 355 343 105
42 14 46-E342063030 960 930 370 343 105 46-E342063030S 945 930 355 343 105
Figure16
46 - E 3 12 063 030 S AVAILABLE RANGE:
1- 4P, 63A, 30mA
TYPE SURFACE 2- 4P, 63A,100mA
3- 4P, 63A, 300mA*
SENSITIVITY 4- 4P, 63A, 500mA*
RATING 5- 4P, 100A, 30mA
6- 4P, 100A,100mA
NO. OF WAYS
7- 4P, 100A, 300mA*
THREE PHASE 8- 4P, 100A, 500mA*
Select The Main Rating and Sensitivity As Mentioned Above *Will be manufactured on special request

Three-Phase 2 Sections LC With 3 Pole Main Isolator Or MCB Three-Phase 2 Sections LC With 3 Pole Main Isolator Or MCB
And Both Sections Protected By 2 Nos. Of 4 Pole ELCBs And One Sections Protected By 4 Pole ELCB
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


1 POLE 3 POLE FLUSH H h W w SURFACE
D H h W w D
6+6 2+2 46-I06061002020 46-I06061002020S 605 590 355 343 105 6+6 2+2 46-I060610020 620 590 370 343 105 46-I060610020S 605 590 355 343 105
620 590 370 343 105
12+6 4+2 46-I12061002020 12+6 4+2 46-I120610020 696 666 370 343 105 46-I120610020S 681 666 355 343 105
696 666 370 343 105 46-I12061002020S 681 666 355 343 105
12+12 4+4 46-I12121002020 12+12 4+4 46-I121210020 780 750 370 343 105 46-I121210020S 765 750 355 343 105
780 750 370 343 105 46-I12121002020S 765 750 355 343 105
18+12 6+4 46-I18121002020 18+12 6+4 46-I181210020 848 818 370 343 105 46-I181210020S 833 818 355 343 105
848 818 370 343 105 46-I18121002020S 833 818 355 343 105
18+18 6+6 46-I18181002020 18+18 6+6 46-I181810020 928 898 370 343 105 46-I181810020S 913 898 355 343 105
928 898 370 343 105 46-I18181002020S 913 898 355 343 105
24+18 8+6 46-I24181002020 24+18 8+6 46-I241810020 1004 974 370 343 105 46-I241810020S 989 974 355 343 105
1004 974 370 343 105 46-I24181002020S 989 974 355 343 105
Figure17 Figure19

Three-Phase 2 Sections LC With 3 Pole Main MCCB Three-Phase 2 Sections LC With 3 Pole Main MCCB
And Both Sections Protected By 2 Nos. Of 4 Pole ELCBs And One Sections Protected By 4 Pole ELCB
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


6+6 2+2 46-L06061002020 816 786 430 400 105 46-L06061002020S 800 786 414 400 105 6+6 2+2 46-L060610020 816 786 430 400 105 46-L060610020S 800 786 414 400 105
12+6 4+2 46-L12061002020 892 862 430 400 105 46-L12061002020S 876 862 414 400 105 12+6 4+2 46-L120610020 892 862 430 400 105 46-L120610020S 876 862 414 400 105
12+12 4+4 46-L12121002020 968 938 430 400 105 46-L12121002020S 952 938 414 400 105 12+12 4+4 46-L121210020 968 938 430 400 105 46-L121210020S 952 938 414 400 105
18+12 6+4 46-L18121002020 1044 1014 430 400 105 46-L18121002020S 1028 1014 414 400 105 18+12 6+4 46-L181210020 1044 1014 430 400 105 46-L181210020S 1028 1014 414 400 105
18+18 6+6 46-L18181002020 1120 1090 430 400 105 46-L18181002020S 1104 1090 414 400 105 18+18 6+6 46-L181810020 1120 1090 430 400 105 46-L181810020S 1104 1090 414 400 105
24+18 8+6 46-L24181002020 1196 1166 430 400 105 46-L24181002020S 1180 1166 414 400 105 24+18 8+6 46-L241810020 1196 1166 430 400 105 46-L241810020S 1180 1166 414 400 105

46 - L 06 06 100 20 20 S 46 - L 06 06 100 20 S
Type Surface * MAIN BREAKER RATING ** ELCB RATING Type Surface * MAIN BREAKER RATING ** ELCB RATING Figure20
ELCB Rating Section-2 ** ELCB Rating
CODE # RATING CODE # RATING CODE # RATING CODE # RATING
** ELCB Rating Section-1 063-100 63, 100A ISOLATOR “I” 20 63A 30mA Figure18 * Main Breaker Rating 063-100 63, 100A ISOLATOR “I” 20 63A 30mA
* Main Breaker Rating 030-100 FOR 30, 40,50,60,70,100A MCB “T” 30 100A 30mA No. Of Ways Section-2 030-100 FOR 30, 40, 50, 60, 70, 100A MCB “T” 30 100A 30mA
No. Of Ways Section-2 030-100 FOR 30, 40,50,60,75,100A MCCB “L” 40 63A 100mA No. Of Ways Section-1 030-100 FOR 30, 40, 50, 60, 75, 100A MCCB “L” 40 63A 100mA
No. Of Ways Section-1 125-225 FOR 125,150,175,200,225A MCCB “L” 50 100A 100mA Main Breaker Type -‘’ L’’ For MCCB ‘’ T ‘’ For MCB, ‘’ I ‘’ For Isolator 125-225 FOR 125. 150. 175. 200. 225A MCCB “L” 50 100A 100mA
Main Breaker Type”L” For MCCB, “T” For MCB, “I” For Isolator Please Select Your Product As Mentioned Above
Please Select Your Product As Mentioned Above

6 7
INDOOR TYPE
Three-Phase LC With 4 Pole ELCB Main

NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


12 4 46-E312063030 542 515 367 343 105 46-E312063030S 527 515 352 343 105
18 6 46-E318063030 618 591 367 343 105 46-E318063030S 603 591 352 343 105
24 8 46-E324063030 697 667 367 343 105 46-E324063030S 682 667 352 343 105
30 10 46-E330063030 773 743 370 343 105 46-E330063030S 758 743 355 343 105
36 12 46-E336063030 878 848 370 343 105 46-E336063030S 863 848 355 343 105
42 14 46-E342063030 960 930 370 343 105 46-E342063030S 945 930 355 343 105
Figure16
46 - E 3 12 063 030 S AVAILABLE RANGE:
1- 4P, 63A, 30mA
TYPE SURFACE 2- 4P, 63A,100mA
3- 4P, 63A, 300mA*
SENSITIVITY 4- 4P, 63A, 500mA*
RATING 5- 4P, 100A, 30mA
6- 4P, 100A,100mA
NO. OF WAYS
7- 4P, 100A, 300mA*
THREE PHASE 8- 4P, 100A, 500mA*
Select The Main Rating and Sensitivity As Mentioned Above *Will be manufactured on special request

Three-Phase 2 Sections LC With 3 Pole Main Isolator Or MCB Three-Phase 2 Sections LC With 3 Pole Main Isolator Or MCB
And Both Sections Protected By 2 Nos. Of 4 Pole ELCBs And One Sections Protected By 4 Pole ELCB
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


1 POLE 3 POLE FLUSH H h W w SURFACE
D H h W w D
6+6 2+2 46-I06061002020 46-I06061002020S 605 590 355 343 105 6+6 2+2 46-I060610020 620 590 370 343 105 46-I060610020S 605 590 355 343 105
620 590 370 343 105
12+6 4+2 46-I12061002020 12+6 4+2 46-I120610020 696 666 370 343 105 46-I120610020S 681 666 355 343 105
696 666 370 343 105 46-I12061002020S 681 666 355 343 105
12+12 4+4 46-I12121002020 12+12 4+4 46-I121210020 780 750 370 343 105 46-I121210020S 765 750 355 343 105
780 750 370 343 105 46-I12121002020S 765 750 355 343 105
18+12 6+4 46-I18121002020 18+12 6+4 46-I181210020 848 818 370 343 105 46-I181210020S 833 818 355 343 105
848 818 370 343 105 46-I18121002020S 833 818 355 343 105
18+18 6+6 46-I18181002020 18+18 6+6 46-I181810020 928 898 370 343 105 46-I181810020S 913 898 355 343 105
928 898 370 343 105 46-I18181002020S 913 898 355 343 105
24+18 8+6 46-I24181002020 24+18 8+6 46-I241810020 1004 974 370 343 105 46-I241810020S 989 974 355 343 105
1004 974 370 343 105 46-I24181002020S 989 974 355 343 105
Figure17 Figure19

Three-Phase 2 Sections LC With 3 Pole Main MCCB Three-Phase 2 Sections LC With 3 Pole Main MCCB
And Both Sections Protected By 2 Nos. Of 4 Pole ELCBs And One Sections Protected By 4 Pole ELCB
NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING NUMBER AND TYPE

1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D 1 POLE 3 POLE FLUSH H h W w D SURFACE H h W w D


6+6 2+2 46-L06061002020 816 786 430 400 105 46-L06061002020S 800 786 414 400 105 6+6 2+2 46-L060610020 816 786 430 400 105 46-L060610020S 800 786 414 400 105
12+6 4+2 46-L12061002020 892 862 430 400 105 46-L12061002020S 876 862 414 400 105 12+6 4+2 46-L120610020 892 862 430 400 105 46-L120610020S 876 862 414 400 105
12+12 4+4 46-L12121002020 968 938 430 400 105 46-L12121002020S 952 938 414 400 105 12+12 4+4 46-L121210020 968 938 430 400 105 46-L121210020S 952 938 414 400 105
18+12 6+4 46-L18121002020 1044 1014 430 400 105 46-L18121002020S 1028 1014 414 400 105 18+12 6+4 46-L181210020 1044 1014 430 400 105 46-L181210020S 1028 1014 414 400 105
18+18 6+6 46-L18181002020 1120 1090 430 400 105 46-L18181002020S 1104 1090 414 400 105 18+18 6+6 46-L181810020 1120 1090 430 400 105 46-L181810020S 1104 1090 414 400 105
24+18 8+6 46-L24181002020 1196 1166 430 400 105 46-L24181002020S 1180 1166 414 400 105 24+18 8+6 46-L241810020 1196 1166 430 400 105 46-L241810020S 1180 1166 414 400 105

46 - L 06 06 100 20 20 S 46 - L 06 06 100 20 S
Type Surface * MAIN BREAKER RATING ** ELCB RATING Type Surface * MAIN BREAKER RATING ** ELCB RATING Figure20
ELCB Rating Section-2 ** ELCB Rating
CODE # RATING CODE # RATING CODE # RATING CODE # RATING
** ELCB Rating Section-1 063-100 63, 100A ISOLATOR “I” 20 63A 30mA Figure18 * Main Breaker Rating 063-100 63, 100A ISOLATOR “I” 20 63A 30mA
* Main Breaker Rating 030-100 FOR 30, 40,50,60,70,100A MCB “T” 30 100A 30mA No. Of Ways Section-2 030-100 FOR 30, 40, 50, 60, 70, 100A MCB “T” 30 100A 30mA
No. Of Ways Section-2 030-100 FOR 30, 40,50,60,75,100A MCCB “L” 40 63A 100mA No. Of Ways Section-1 030-100 FOR 30, 40, 50, 60, 75, 100A MCCB “L” 40 63A 100mA
No. Of Ways Section-1 125-225 FOR 125,150,175,200,225A MCCB “L” 50 100A 100mA Main Breaker Type -‘’ L’’ For MCCB ‘’ T ‘’ For MCB, ‘’ I ‘’ For Isolator 125-225 FOR 125. 150. 175. 200. 225A MCCB “L” 50 100A 100mA
Main Breaker Type”L” For MCCB, “T” For MCB, “I” For Isolator Please Select Your Product As Mentioned Above
Please Select Your Product As Mentioned Above

6 7
Three-Phase LC With MCCB Main 125-225 AF

NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D

2- OUTDOOR TYPE
12 4 42-WPL12225 615 350 160
18 6 42-WPL18225 692 350 160
24 8 42-WPL24225 768 350 160
30 10 42-WPL30225 845 350 160
36 12 42-WPL36225 921 350 160
42 14 42-WPL42225 998 350 160
48 16 42-WPL48225 1074 350 160
Figure 21
Main Breaker: Ranges from 125-225A
Change last three digits for required ratings
For example:
42-WPL42125 Represents load centr 42 way with 125A main
42-WPL42225 Represents load center 42 way with 225A main Figure 24

Three-Phase LC With MCB Main 30-100 AF Three-Phase LC With MCCB Main 250 A

NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D 1 POLE 3 POLE CODE H W D


12 4 42-WP12100 515 350 160 24 8 42-WP24250 800 400 180
18 6 42-WP18100 592 350 160 30 10 42-WP30250 877 400 180
24 8 42-WP24100 668 350 160 36 12 42-WP36250 953 400 180
30 10 42-WP30100 745 350 160 42 14 42-WP42250 1030 400 180
36 12 42-WP36100 821 350 160 48 16 42-WP48250 1106 400 180
42 14 42-WP42100 898 350 160
Main Breaker: 250A
Change last three digits for required ratings
Main Breaker: Ranges from 30-100A Figure 22 For example:
Change last three digits for required ratings 42-WP42250 Represents load center 42 way with 250A main
For example: 42-WP48250 Represents load center 48 way with 250A main
42-WP12030 Represents load center 12 way with 30A main Figure 25
42-WP12100 Represents load center 12 way with 100A main

Three-Phase LC With MCCB Main 30-100 AF Three-Phase LC With MCCB Main 300-400 AF

NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D 1 POLE 3 POLE CODE H W D


12 4 42-WPL12100 555 350 160 30 10 42-WP30400 1232 500 200
18 6 42-WPL18100 632 350 160 36 12 42-WP36400 1309 500 200
24 8 42-WPL24100 708 350 160 42 14 42-WP42400 1385 500 200
30 10 42-WPL30100 785 350 160 48 16 42-WP48400 1462 500 200
36 12 42-WPL36100 861 350 160
Main Breaker: Ranges from 300-400A
42 14 42-WPL42100 938 350 160 Change last three digits for required rating
For example:
Main Breaker: Ranges from 30-100A 42-WP42300 Represents load center 42 way with 300A main
Change last three digits for required ratings 42-WP42400 Represents load center 42 way with 400A main
For example:
42-WPL18030 Represents load center 18 way with 30A main Figure 26
42-WPL18100 Represents load center 18 way with 100A main Figure 23

8 9
Three-Phase LC With MCCB Main 125-225 AF

NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D

2- OUTDOOR TYPE
12 4 42-WPL12225 615 350 160
18 6 42-WPL18225 692 350 160
24 8 42-WPL24225 768 350 160
30 10 42-WPL30225 845 350 160
36 12 42-WPL36225 921 350 160
42 14 42-WPL42225 998 350 160
48 16 42-WPL48225 1074 350 160
Figure 21
Main Breaker: Ranges from 125-225A
Change last three digits for required ratings
For example:
42-WPL42125 Represents load centr 42 way with 125A main
42-WPL42225 Represents load center 42 way with 225A main Figure 24

Three-Phase LC With MCB Main 30-100 AF Three-Phase LC With MCCB Main 250 A

NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D 1 POLE 3 POLE CODE H W D


12 4 42-WP12100 515 350 160 24 8 42-WP24250 800 400 180
18 6 42-WP18100 592 350 160 30 10 42-WP30250 877 400 180
24 8 42-WP24100 668 350 160 36 12 42-WP36250 953 400 180
30 10 42-WP30100 745 350 160 42 14 42-WP42250 1030 400 180
36 12 42-WP36100 821 350 160 48 16 42-WP48250 1106 400 180
42 14 42-WP42100 898 350 160
Main Breaker: 250A
Change last three digits for required ratings
Main Breaker: Ranges from 30-100A Figure 22 For example:
Change last three digits for required ratings 42-WP42250 Represents load center 42 way with 250A main
For example: 42-WP48250 Represents load center 48 way with 250A main
42-WP12030 Represents load center 12 way with 30A main Figure 25
42-WP12100 Represents load center 12 way with 100A main

Three-Phase LC With MCCB Main 30-100 AF Three-Phase LC With MCCB Main 300-400 AF

NO. OF WAYS ORDERING NUMBER AND TYPE NO. OF WAYS ORDERING DETAILS AND TYPE

1 POLE 3 POLE CODE H W D 1 POLE 3 POLE CODE H W D


12 4 42-WPL12100 555 350 160 30 10 42-WP30400 1232 500 200
18 6 42-WPL18100 632 350 160 36 12 42-WP36400 1309 500 200
24 8 42-WPL24100 708 350 160 42 14 42-WP42400 1385 500 200
30 10 42-WPL30100 785 350 160 48 16 42-WP48400 1462 500 200
36 12 42-WPL36100 861 350 160
Main Breaker: Ranges from 300-400A
42 14 42-WPL42100 938 350 160 Change last three digits for required rating
For example:
Main Breaker: Ranges from 30-100A 42-WP42300 Represents load center 42 way with 300A main
Change last three digits for required ratings 42-WP42400 Represents load center 42 way with 400A main
For example:
42-WPL18030 Represents load center 18 way with 30A main Figure 26
42-WPL18100 Represents load center 18 way with 100A main Figure 23

8 9
Moulded Case Circuit Breaker (MCCB)
LA KNOCKOUTS ELETRA MOULDED CASE CIRCUIT BREAKER ELA
S/NO. Description
1 MCCB 3P(ELA) 30A
2 MCCB 3P(ELA) 40A
3 MCCB 3P(ELA) 50A
4 MCCB 3P(ELA) 60A
5 MCCB 3P(ELA) 75A
6 MCCB 3P(ELA)100A

LA 3 PH 100A MCB 12W - 42W


ELETRA MOULDED CASE CIRCUIT BREAKER ELB
A- O21/O27 DOUBLE KNOCKOUT -2 Nos.
B- O38.5/O44 DOUBLE KNOCKOUT - 6 Nos S/NO. Description
C- O19/O25 TRIPLE KNOCKOUT -16 Nos.
D- O44/O54.5/O64 TRIPLE KNOCKOUT - 4 Nos. 1 MCCB 3P(ELB) 125A
E- O23/O28/O33 TRIPLE KNOCKOUT - 4 Nos. 2 MCCB 3P(ELB) 150A
F- O44/O50/O62 TRIPLE KNOCKOUT - 2 Nos.
G- WALL MOUNTING EMBOSS WITH KEY HOLE - 4 Nos. 3 MCCB 3P(ELB) 175A Figure 28
4 MCCB 3P(ELB) 200A
5 MCCB 3P(ELB) 225A
Notes:
All dimension are in mm
The details in this drawing indicate dimensions and
knockout positions for one Load Center.
Knockout details for other Load Center types, shown in this
catalogue, are available on request Dimensions

Figure 27

TESTING

MOUNTING
All load centers type (LA) are type tested for complete sequence as per international standards.

Each of our products under go strict quality control check and is routinely checked for:

Dielectric Test : A high voltage routine test

Electrical Continuity Test : To confirm correct assembly & operation

Insulation Resistance Test : To ensure high insulation resistance


Figure 29

10 11
Moulded Case Circuit Breaker (MCCB)
LA KNOCKOUTS ELETRA MOULDED CASE CIRCUIT BREAKER ELA
S/NO. Description
1 MCCB 3P(ELA) 30A
2 MCCB 3P(ELA) 40A
3 MCCB 3P(ELA) 50A
4 MCCB 3P(ELA) 60A
5 MCCB 3P(ELA) 75A
6 MCCB 3P(ELA)100A

LA 3 PH 100A MCB 12W - 42W


ELETRA MOULDED CASE CIRCUIT BREAKER ELB
A- O21/O27 DOUBLE KNOCKOUT -2 Nos.
B- O38.5/O44 DOUBLE KNOCKOUT - 6 Nos S/NO. Description
C- O19/O25 TRIPLE KNOCKOUT -16 Nos.
D- O44/O54.5/O64 TRIPLE KNOCKOUT - 4 Nos. 1 MCCB 3P(ELB) 125A
E- O23/O28/O33 TRIPLE KNOCKOUT - 4 Nos. 2 MCCB 3P(ELB) 150A
F- O44/O50/O62 TRIPLE KNOCKOUT - 2 Nos.
G- WALL MOUNTING EMBOSS WITH KEY HOLE - 4 Nos. 3 MCCB 3P(ELB) 175A Figure 28
4 MCCB 3P(ELB) 200A
5 MCCB 3P(ELB) 225A
Notes:
All dimension are in mm
The details in this drawing indicate dimensions and
knockout positions for one Load Center.
Knockout details for other Load Center types, shown in this
catalogue, are available on request Dimensions

Figure 27

TESTING

MOUNTING
All load centers type (LA) are type tested for complete sequence as per international standards.

Each of our products under go strict quality control check and is routinely checked for:

Dielectric Test : A high voltage routine test

Electrical Continuity Test : To confirm correct assembly & operation

Insulation Resistance Test : To ensure high insulation resistance


Figure 29

10 11
Moulded Case Circuit Breaker (MCCB)

TECHNICAL SPECIFICATION

MOULDED CASE CIRCUIT BREAKER


Frame size (AF) 100 225
Frame Type ELA ELB
Breaking capacity (kA), Icu at 415V AC 14 14
Number of poles 3 3
Type 3 pole ELA 100A ELB 225A
Rated current (A) at 50 ºC 30,40 125,150
50,60,75,100 175,200,225
Technical data conforming to IEC/EN60947-2
Rated operational voltage (V) Ue (50/60 Hz) 600 600
Rated operational voltage (V) Ue (DC) 250 250
Rated insulation voltage (V) Ui (50/60Hz) 690 690
Rated impulse withstand voltage (kv)uimp 6 6
Ultimate breaking capacity (kA)Icu
AC 50/60 Hz 220/240V 25 25
380/415V 14 14
440/460V 14 14
480/500V 7.5 7.5
600V 7.5 7.5
DC 125V 15 15
250V 10 10
Service breaking capacity(%Icu).Ics 50 50
Category of use A A
Endurance (number of operations) mechanical 8500 7000
electrical 1500 1000
Type of trip unit:
-Thermal-magnetic release fixed fixed
-Electronic release - -
-Pre-alarm via LED - -
-Hydraulic-magnetic release - -
Accessories - -
Dimensions (WxHxD) mm 90x155x60 105x165x68.5
Weight (kg) - MAX 1.1 1.3

,
12
Moulded Case Circuit Breaker (MCCB)

TECHNICAL SPECIFICATION

MOULDED CASE CIRCUIT BREAKER


Frame size (AF) 100 225
Frame Type ELA ELB
Breaking capacity (kA), Icu at 415V AC 14 14
Number of poles 3 3
Type 3 pole ELA 100A ELB 225A
Rated current (A) at 50 ºC 30,40 125,150
50,60,75,100 175,200,225
Technical data conforming to IEC/EN60947-2
Rated operational voltage (V) Ue (50/60 Hz) 600 600
Rated operational voltage (V) Ue (DC) 250 250
Rated insulation voltage (V) Ui (50/60Hz) 690 690
Rated impulse withstand voltage (kv)uimp 6 6
Ultimate breaking capacity (kA)Icu
AC 50/60 Hz 220/240V 25 25
380/415V 14 14
440/460V 14 14
480/500V 7.5 7.5
600V 7.5 7.5
DC 125V 15 15
250V 10 10
Service breaking capacity(%Icu).Ics 50 50
Category of use A A
Endurance (number of operations) mechanical 8500 7000
electrical 1500 1000
Type of trip unit:
-Thermal-magnetic release fixed fixed
-Electronic release - -
-Pre-alarm via LED - -
-Hydraulic-magnetic release - -
Accessories - -
Dimensions (WxHxD) mm 90x155x60 105x165x68.5
Weight (kg) - MAX 1.1 1.3

,
12