You are on page 1of 1

Unit 01-02, 31/F, New Trend Centre, No.

704 Prince Edward Road East, San Po Kong, Kowloon, Hong Kong.
Tel: (852)2787 5717; Fax: (852)2787 2983
sales@mesanct.com; www.mesanct.com
Version:20200812095005
Cooling Tower Data
Series: MXH Cross Flow Induced Draft, L Type
Model: MXH-2244-11 CTI Certification: C26C-08R09
Cell(s) Per Set: 1 Fan Motor Pole No.: 4p
Fan Type: Axial Fan Motor Power Per Cell: 11 kw
Fan Diameter: 2050 mm Fan Motor Power Total: 11 kw
Fans Per Cell: 1 Air Flow Per Cell: 132000 m3/h
Static Head: 3.87 m Air Flow Total: 132000 m3/h
Distribution Head: 0m
Performance Data
Water Flow Rate Per set: 152.1 m3/h Evaporation Loss: 1.667 %
Entering Water Temp.: 40°C Drift Loss: ≤ 0.005 %
Leaving Water Temp.: 30°C Capacity: 110.3 %
Ambient Wet Bulb Temp: 23.6°C Heat Rejection Capability: 1769 kw
Range: 10°C
Approach: 6.4°C This selection satisfies your design conditions.
Physical Data
Per Set Total Per Set
Length: 2280 mm Dry Weight: 2424 kg
Width: 4470 mm Operating Weight: 4334 kg
Height: 3725 mm
Note: Weights and dimensions do not include options.

Notes: The tower selection & performance are based on a well-ventilated condition and single set design. For multiple-set jobs or in
unfavorable conditions, please contact our engineering department for assistance with the towers layout.

Powered by TCPDF (www.tcpdf.org)