Inciso a)
-----------------------------------------------------------------------------------------------------------------------------------
| | | DIgSILENT | Project: |
| | | PowerFactory |-------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable Load Flow Error for |
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
| |
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
| No. of 2-w Trfs. 3 No. of 3-w Trfs. 0 No. of syn. Machines 3 No. of asyn.Machines 0 |
| |
| |
| |
|---------------------------------------------------------------------------------------------------------------------------------|
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
c:firel = 58.77438 deg (Rotor angle with reference to reference machine angle)
Inciso b)
Indicar ¿cuál es la falla más crítica? y ¿Cuál es la máxima capacidad interruptiva que debe tener
cualquier interruptor que se desee tener como enlace de la barra?
R// La falla más crítica es Φ-Ground con 2.676 kA.
La máxima capacidad interruptiva que debe tener cualquier interruptor que se desee tener como enlace a la
barra, deberá ser mayor a 2.676 kA. Se recomienda una capacidad interruptora de 3.000 kA.
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
Inciso c)
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
El tiempo critico se encuentra en 14 ciclos, t=0.233 seg. En una falla trifásica para evitar que
la máquina se dispare en esos valores del Angulo interno de delta=178.433° debemos elegir un valor
menor a 14 ciclos.
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
Inciso d)
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
| |
| No. of 2-w Trfs. 3 No. of 3-w Trfs. 0 No. of syn. Machines 3 No. of asyn.Machines 0 |
| |
| |
| |
|---------------------------------------------------------------------------------------------------------------------------------|
-----------------------------------------------------------------------------------------------------------------------------------
| | | DIgSILENT | Project: |
| | | PowerFactory |-------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
| AC Load Flow, balanced, positive sequence | Automatic Model Adaptation for Convergence No |
| Automatic Tap Adjust of Transformers No | Max. Acceptable Load Flow Error for |
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------------------------
| |
| No. of 2-w Trfs. 3 No. of 3-w Trfs. 0 No. of syn. Machines 3 No. of asyn.Machines 0 |
| |
| |
| |
Universidad Nacional Autónoma de Honduras
Examen II de Estabilidad de Sistemas de Potencia
|---------------------------------------------------------------------------------------------------------------------------------|