Bba2 Ril30 (2015)
Bba2 Ril30 (2015)
469 SETUP
PREFERENCES
Default Message Cycle Time 2.0 s
Default Message Timeout 300 s
Average Motor Load Calculation Period 15 min
Temperature Display Units Celsius
Trace Memory Trigger Position 90 %
Trace Memory Buffers 2 x 42 cycles
Display Update Interval 0.4 s
Motor Load Filter Interval 0 cycles
MESSAGE SCRATCHPAD
First Scratchpad Message Seteado 15-07-02 Por Roberto Muratore
Second Scratchpad Message Est. Ingieneria SNC-Lavalin
Third Scratchpad Message Text 3
Fourth Scratchpad Message RIL30
Fifth Scratchpad Message Bomba 2
SYSTEM SETUP
CURRENT SENSING
Phase CT Primary 200 A
Motor Full Load Amps 76 A
Ground CT Type 5 A Secondary
Ground CT Primary 50 A
Phase Differential CT Type None
VOLTAGE SENSING
VoltageTransformer Connection Type Open Delta
Voltage Transformer Ratio 35.00 :1
Motor Nameplate Voltage 4000 V
POWER SYSTEM
Nominal System Frequency 50 Hz
System Phase Sequence ABC
DIGITAL INPUTS
STARTER
Starter Status Switch Start Aux a
OUTPUT RELAYS
TRIP RELAY
Force R1 Operate Time 0s
ALARM RELAY
Force R4 Operate Time 0s
AUX RELAY 2
Force R2 Output Operate Time 0s
AUX RELAY 3
Force R3 Operate Time 0s
PROTECTION
THERMAL MODEL
469 THERMAL MODEL
Curve Style Standard
Overload Pickup Level 1.15 FLA
Unbalance k Factor 5
Cool Time Constant Running 30 min
Cool Time Constant Stopped 45 min
Hot/Cold Safe Stall Ratio 0.50
Thermal Capacity Alarm Relays Alarm
Thermal Capacity Alarm Level 75 % used
Overload Trip Relays Trip
OVERLOAD CURVE
Standard Overload Curve Number 2
Tue Aug 06 12:44:37 2019 Settings (Enabled Features) PAGE 2
CURRENT ELEMENTS
SHORT CIRCUIT TRIP
Short Circuit Trip Latched
Short Circuit Trip Relays Trip
Short Circuit Trip Pickup 4.0 CT
Intentional Short Circuit Trip Delay 0 ms
MECHANICAL JAM
Mechanical Jam Trip Latched
Mechanical Jam Trip Relays Trip
Mechanical Jam Pickup 1.50 xFLA
Mechanical Jam Delay 1s
UNDERCURRENT
Block Undercurrent from Start 0s
Undercurrent Trip Latched
Undercurrent Trip Relays Trip
Undercurrent Trip Pickup 0.50 xFLA
Undercurrent Trip Delay 15 s
CURRENT UNBALANCE
Current Unbalance Trip Latched
Current Unbalance Trip Relays Trip
Current Unbalance Trip Pickup 20 %
Current Unbalance Trip Delay 5s
GROUND FAULT
Ground Fault Alarm Events On/Yes
Ground Fault Trip Latched
Ground Fault Trip Relays Trip
Ground Fault Trip Pickup 0.20 CT
Intentional GF Trip Delay 0 ms
MOTOR STARTING
ACCELERATION TIMER
Accleration Timer Trip Latched
Acceleration Timer Trip Relays Trip
Acceleration Timer from Start 10.0 s
JOGGING BLOCK
Jogging Block On/Yes
Maximum Starts/Hour Permissible 5
Time Between Starts 10 min
RTD TEMPERATURE
RTD TYPES
Stator RTD Type 100 Ohm Platinum
Bearing RTD Type 100 Ohm Platinum
Ambient RTD Type 100 Ohm Platinum
Other RTD Type 100 Ohm Platinum
RTD #1
RTD #1 Application Stator
RTD #1 Name
RTD #1 Alarm Latched
RTD #1 Alarm Relays Alarm
RTD #1 Alarm Temperature 105 °C
RTD #1 Trip Latched
RTD #1 Trip Voting RTD #1
RTD #1 Trip Relays Trip
RTD #1 Trip Temperature 120 °C
RTD #2
RTD #2 Application Stator
RTD #2 Name
RTD #2 Alarm Latched
RTD #2 Alarm Relays Alarm
RTD #2 Alarm Temperature 105 °C
RTD #2 Trip Latched
RTD #2 Trip Voting RTD #2
RTD #2 Trip Relays Trip
Tue Aug 06 12:44:37 2019 Settings (Enabled Features) PAGE 3
RTD #3
RTD #3 Application Stator
RTD #3 Name
RTD #3 Alarm Latched
RTD #3 Alarm Relays Alarm
RTD #3 Alarm Temperature 105 °C
RTD #3 Trip Latched
RTD #3 Trip Voting RTD #3
RTD #3 Trip Relays Trip
RTD #3 Trip Temperature 120 °C
RTD #4
RTD #4 Application Stator
RTD #4 Name
RTD #4 Alarm Latched
RTD #4 Alarm Relays Alarm
RTD #4 Alarm Temperature 105 °C
RTD #4 Trip Latched
RTD #4 Trip Voting RTD #4
RTD #4 Trip Relays Trip
RTD #4 Trip Temperature 120 °C
RTD #5
RTD #5 Application Stator
RTD #5 Name
RTD #5 Alarm Latched
RTD #5 Alarm Relays Alarm
RTD #5 Alarm Temperature 105 °C
RTD #5 Trip Latched
RTD #5 Trip Voting RTD #5
RTD #5 Trip Relays Trip
RTD #5 Trip Temperature 120 °C
RTD #6
RTD #6 Application Stator
RTD #6 Name
RTD #6 Alarm Latched
RTD #6 Alarm Relays Alarm
RTD #6 Alarm Temperature 105 °C
RTD #6 Trip Latched
RTD #6 Trip Voting RTD #6
RTD #6 Trip Relays Trip
RTD #6 Trip Temperature 120 °C
RTD #7
RTD #7 Application Bearing
RTD #7 Name Rodam
RTD #7 Alarm Latched
RTD #7 Alarm Relays Alarm
RTD #7 Alarm Temperature 70 °C
RTD #7 Trip Latched
RTD #7 Trip Voting RTD #7
RTD #7 Trip Relays Trip
RTD #7 Trip Temperature 75 °C
RTD #8
RTD #8 Application Bearing
RTD #8 Name Rodam
RTD #8 Alarm Unlatched
RTD #8 Alarm Relays Alarm
RTD #8 Alarm Temperature 70 °C
RTD #8 Trip Latched
RTD #8 Trip Voting RTD #8
RTD #8 Trip Relays Trip
RTD #8 Trip Temperature 75 °C
RTD #9
RTD #9 Application Bearing
Tue Aug 06 12:44:37 2019 Settings (Enabled Features) PAGE 4
RTD #10
RTD #10 Application Bearing
RTD #10 Name
RTD #11
RTD #11 Application Other
RTD #11 Name
RTD #12
RTD #12 Application Ambient
RTD #12 Name
VOLTAGE ELEMENTS
UNDERVOLTAGE
Undervoltage Active Only If Bus Energized On/Yes
Undervoltage Trip Latched
Undervoltage Trip Relays Trip
Undervoltage Trip Pickup 0.80 Rated
Starting Undervoltage Trip Pickup 1.00 Rated
Undervoltage Trip Delay 3.0 s
POWER ELEMENTS
POWER FACTOR
Block Power Factor Element from Start 1s
REACTIVE POWER
Block kvar Element from Start 1s
UNDERPOWER
Block Underpower From Start 0s
REVERSE POWER
Block Reverse Power From Start 0s
TORQUE SETUP
Stator Resistance 0.004 mOhm
Pole Pairs 2
Torque Unit Newton-meter
OVERTORQUE SETUP
Overtorque Alarm Relays Alarm
Overtorque Alarm Level 4000.0 Nm
Overtorque Alarm Delay 1.0 s
CURRENT DEMAND
Current Demand Period 15 min
KW DEMAND
kW Demand Period 15 min
KVAR DEMAND
kvar Demand Period 15 min
KVA DEMAND
kVA Demand Period 15 min
ANALOG OUTPUTS
Analog Output 1 Selection None
Analog Output 2 Selection None
Analog Output 3 Selection None
Analog Output 4 Selection None