Professional Documents
Culture Documents
0-7803-5035-9/'98/$10.0001998IEEE.
makes the potential distribution more even between the both under continuous fog condition. Dimensions of the plymer
ends of the insulator string. insulators used for the corona discharge test are shown in Fig.1.
In the case of the polymer insulator with the SiR housing,
potential distribution under water spray condition is equal to that Table 1 Fillers in silicone rubber swimens
of clean and dry condition, since water film can not be Specimen Fillers
--
continuously formed due to it’s hydrophobicity. Therefore the s1 Silica, ATH 1
electrical stress concentrates most at the line end of the polymer --s2 I
Silica, ATH2
insulator even under wetting oondition. Water drops on the s3 I silica A T H ~
surface of the polymer insulator are deformed along with the s4 I Silica, ATH3, QC03
direction of the electrical field and elehcal field at the edge of s.5 I silica A T H ~ . CXO,
the deformed water drops t m m e much higher [11,12]. -- Si6 1
Silica, ATH3, CaCO,
Corona discharges are tend to be generated around the ATH 1,P X H 2, and ATH 3 are different in kinds
deformed water drops. Nitric acid is generated by the corona &CO3 contained in SI,S5, and S6 is the same kind.
discharge. These phenomena become more remarkable when Order of the amount of GC03is SI>S5>S6.
the system voltage becomes higher. It is reported that the
elecfrical stress of the central p t i o n of the polymer insulator
for 735 kV line is about 30 kV/m and that of the line side I 2 0 0 m n 7
reaches 200-300 kV/m [13].
This paper describes changa of alppearance of the rubber of
the polymer insulator by cnrona discharges which was
generated under high electrical stress under fog condition.
Some kinds of silicone rubber :sheets containing different types
I--
of fillers were immersed in nitric acid solution, and changes of
Leakage distance : 560”
their mechanical properties were studied to confirm the effects
of nitric acid generated by the corona discharge. Fig.1 Polymeric insulator uxd for the corona discharge test.
73
oven. Weight loss, appearance changes, hardness, elongation the S1 and S4 insulators kept good hydrophobicity even after
and tensile strength were investigated. 400 hours test duration. Photographs of the trunk portion of
the S2 insulator where the corona discharges were observed are
3. Test results and discussion shown in Fig.2. Leakage current was measured by less than
3mA on all three insulators. However dfierences of the
3-1 Corona discharge test behavior of generation of the corona dkharges were
Observation results of the corona discharges and the considered as due to the differences of the behavior of surface
changes of appearance of the insulators by the corona discharge hydrophobicity. Further researches should be needed to
test are summarized in Table 2. After 24 hours, the corona understand these behavior.
dixharges due to water drops were observed visually at the 1' The concentration of hydrogen ion in water drops on the
shed from the earth side of the S2 insulator. After 72 hours, shed surface under the discolored trunk portion was pH0-2.0
the corona discharges were observed on the trunk portion by measuring with pH testing paper. We consider this high
between the 2d and 3"' shed from the earth side of the S2 concentration of hydrogen ion is due to the corona discharges.
insulator. The trunk portion of the S2 insulator on which the Analytical results of anions in the water drops are shown in
corona discharges were observed slightly discolored whitish. Table 3. Nitride ion concentration was 700 in giml which was
This phenomenon was considered to agree with the previous much higher than that of chloride ion and sulfate ion. The
ones reported by Cash et a1 [9]. After 250 hours, the corona nitride ion concentration in the water drops around area
discharges were observed at around the end-fitting of the earth subjected no corona discharges was only 40 U giml. These
side, and the trunk portion between the 1"and 3' sheds from the results show the acid generated by the corona discharges is
earth side of the S2 insulator. The discoloration area of the S2 mainly nitric acid.
insulator was spread, and a small amount of deposition of white Ozone was generated in the test chamber. Concentration
powder-like material was observed on the discolored trunk of the ozone was 0.1-lppm by measuring with gas detector tube,
portion. After 400 hours, the corona discharges were of which sensitivity ranges from 0.025 to 3 p.p.m. Since
continuously observed, on the S2 insulator, at all around of the solubility of ozone to water is much lower than nitride ion and it
trunk portion between the l*and 2d sheds from the earth side. easily disperses in the air, the phenomenon of discoloration to
The area of the corona discharges observed on the S2 white and depositing of the white powder-like material, which
insulator was spread as about 3 times as the area of after 2.50 were observed at the trunk portion was suggested to be taken
hours. However the corona discharges could not be observed place by nitric acid.
on the S1 and S4 insulators. This reason was considered that
Table 2 Appearance of corona activity and surface changes during corona discharge test
edge edge
72 No corona discharge -
Corona discharge on the hunk portion. - No corona discharge
Slight discoloration on the trunk portion.
t
250 No corona discharge Corona discharges on the trunk portion, between shcds No corona discharge
and around the end-fitting at he earth side.
74
After 72 hours After400hours
Fig2 Photographs of the trunk portion of the S2insulator,
which was subjected to corona discharges
4000 2’000 1500 1000 650
Wavenumber (cm-‘)
Table 3 Analytical results of water droplets around corona
discharge
Measuring Ions
-
Ion Concentmtions( ,U g/d)
Fig3 hh-red spectra of the silicone rubber
housing before the corona discharge test, (a)
NO; 700 (4) and the deposited material at the trunk
Cl- 50 (30) portion oE the S2 specimen, @).
so,” ~~ ~~~ ~~~
Values in parenthcses show concentrations of each component teriomtion of ,&cone rubber by nitric acid
of water drops around the m a without lthe corona discharges. It is clarified that nitric acid generated by corona discharges
in humid condition c a m deterioration of the housing rubber
The white powder-like material was scratchdoff and surface as discoloration and deposition of the powder-like
analyzed by diffraction-refraction FT-R (Fourier Transform material. Therefore the deterioration behaviors of the silicone
Infra-red Spectroscopy). Spat” of the silicone rubber rubbers used for the polymer insulators by nitric acid wa5
housing surface beforc tested (a), and that of the white powder- studied a$ d w n i in the section 2-3, that is the acid
like material @) are shown in Fig. 3. Assignments of major immersion test. Nitric acid concentration for the immersion
peak are also given in the figure. Since the peaks of spectrum test w z specified as 1 N, because the lowest pH of the water
(b) at 1370 cm-’and 1630 cm-’ indicate nitride compounds, drops on the shtd surface subjected to the corona discharges
this proves generation of nitric acid by corona discharges. was zero. This concentration of nitric acid was considered very
Although four peaks were obsewed based on ATH around high, since the nitric acid may be immediately disperxd and
about 3400 m-’in spcctrum (a), only one peak was observed diluted by rain and wind in the actual field.
at same portion in spectrum (b). This peak was assigned to The specimens immersed in 1N-nitric acid solution for 24
AI(?IO,), (Aluminum nitride). The Feaks at about 1350 cm-’ to 96 hours were taken out of it and continuously they were
and 1650 m-’of spectnrm (b) are also assigned to AI(N03);. immersed in deionized water for 24 hours to stop the progress
The peak at 1250 mi’ based on Si-C silicone side chain in of deterioration by the residual nitric acid. Then the specimens
spectrum (a) was disappeared in s p w m @). The peaks were dried in a vacuum oven at 35c for 48 hours. This
around 1100cm-’based on Si-0-Si, silicone back-bom chain in drying removes the absorbed water , and eliminates the errors
spectrum (a) became broad and one peak in spectrum @). due to the weight of the residual water. Then the weight loss
This means the white powder-like material contains silica.. and mechanical properties of the immersed rubber specimens
These results suggests that white powder-like material were measured.
deposited on the surface of the insulator by decomposition and
oxidation of siliconc polymer of housing rubber, and that 3-2-1 Weight IQSS of the specimens by immersion in nitric
dissolution and nitration of ATE3 were taken place with nitric acid
acid generated by the corona discharges. Weight loss ratio of the spccimens by immersion in the 1N-
nitric acid solution for 24,@ and 96 hours wcre shown in Fig.4.
Tbe weights of the spccimens arc reduced lincarlv with
immcrsion period. The wcighk of the s4, S5 and SO
75
containing both ATH and CaC03 were remarkably reduced.
Especially 17% of weight loss was observed on the specimen,
S5 after 96 hours immersion. Weight loss ratio of the S1, S2
and S3, not containing CaCQ were smaller comparing to the
specimens containing CaCQ. The weight loss of the S1 after
96 hours immersion was only 7%. The amount of A I and Ca
in the IN-nitric acid solution which was used for immersion of
the specimen, S4 for 96 hours were measured by Inductively
Coupled Plasma-Atomic Emission Spectroscopy (ICP-AES).
As a result, the concentration of A
I and Ca in the solution were
180 and 2700 ,U dml, respectively. This results showed
CaCO, is more easily dissolved than ATH with nitric acid.
-20 '
0 20 40 60 80 100
[discolored
76
3-23Changes of hardness OS the spechemby
immersion in nittic acid
Although the fillers in the housing rubber is dissolved by
nitric acid generated by the moria discharges, it may be
predicted that surface hardness of the specimens increase by
oxidation with nitric acid. Therefore changes of hardness of
the specimens were measured by the micro durometer which
can detect the hardness up to 0.5mm ffom the surfaces. The
measurement results are shown in Fig.7. Hardness of the
specimens, S1, S2 and S3 not containing CaCO?increased with
immersion period. Increase of harclness of the S1, S2 and S3
specimenswere 10,12, and 4 pints respectively after 96 hours -15 L
immersion. Especially, hardness of the specimen, S2 0 20 40 60 80 100
increased about by 90 as absolute value after 96 hours immersion duration (hrs)
immersion. As a result, the S2 lost elasticity and became
brittle. Hardness of the specimens, M, S5 and S6 containing Fig.7 Clangis of hardness of silicone rubber specimen during
&CO3 filler decreased after 24 hours immersion once, but after immersion in IN-nitric acid
96 hours immersion the hardness increased to 0,2, and 5 points
respectively. This behaviors are considered due to the
formation of the sponge-like layer by dissolving of the almost +s1
amount of CaCO, filler in the bulk of the Sa.
77
References
78
[Ill A J. Phillips, D. J. Child, H. M. Schneider :“Water Drop
Corona Effectson Fulk-Scall 500kV Non-Cm”c
Insulators”, Paper PE-23501-1998, Paper submitted
to IEEEPES Winter Meeting, Tampa, Florida, February
1-5,1998.
[12]A J. Phillips, D. J. Child,H. M. Schneider : “Agmg of
Non-Ceramic Insulator; due to the Corona from Water
Drops”, Paper PE-236-PWRD-0-11-1997, Paper submitted
to IEEE PES Winter Meeting, Tampa, Horida, February
1-5,1998.
[13]G. H. Vallancourt, S. Cangnan and C. Jean : ‘Experience
with the Detection of Faulty Composite Insulators on
High-Voltage Power Lines by the:ElectricField
Measurement Method‘’, PE-932-.PWRD-O5-19!97,Paper
submitted to IEEEPES, Summer Meeting in Berlin., 1997.
79