V300R002
User Manual
Issue 01
Date 2014-04-23
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Purpose
This document describes the DC power system in terms of product overview, components,
installation, commissioning, and maintenance. This document also describes operations for
the site monitoring unit (SMU) and rectifiers.
The figures provided in this document are for reference only.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Symbol Description
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 01 (2014-04-23)
This issue is the first official release.
Contents
2 Overview......................................................................................................................................... 6
2.1 Introduction .................................................................................................................................................................. 6
2.2 Model Number Description .......................................................................................................................................... 6
2.3 System Features ............................................................................................................................................................ 6
2.4 Working Principles ....................................................................................................................................................... 7
2.5 Configurations .............................................................................................................................................................. 8
3 Appearance ..................................................................................................................................... 9
3.1 Interior .......................................................................................................................................................................... 9
3.2 PDU ............................................................................................................................................................................ 10
3.3 Rectifier ...................................................................................................................................................................... 10
3.4 SMU02B ..................................................................................................................................................................... 12
3.5 UIM02D...................................................................................................................................................................... 16
4 Installation.................................................................................................................................... 20
4.1 Installation Preparations ............................................................................................................................................. 20
4.1.1 Tools ........................................................................................................................................................................ 20
4.1.2 Installation Dimensions ........................................................................................................................................... 21
4.1.3 Requirements for Cable Routing ............................................................................................................................. 22
4.1.4 Unpacking and Acceptance ...................................................................................................................................... 22
4.2 Installing a Subrack .................................................................................................................................................... 23
4.3 Installing Ground Cable .............................................................................................................................................. 23
4.4 Installing Components ................................................................................................................................................ 24
4.4.1 Installing a Rectifier ................................................................................................................................................ 24
4.5 (Optional) Installing Dry Contact Signal Cables ........................................................................................................ 25
4.6 Installing the Communications Cables ....................................................................................................................... 26
6 Commissioning............................................................................................................................ 33
6.1 Connecting the AC Power Supply .............................................................................................................................. 33
6.2 Setting the Display Language ..................................................................................................................................... 34
6.3 Setting the Date and Time ........................................................................................................................................... 34
6.4 Setting Battery Parameters.......................................................................................................................................... 34
6.5 (Optional) Setting Sensor Parameters ......................................................................................................................... 35
6.6 (Optional) Setting the Hibernation Parameter ............................................................................................................ 36
6.7 Setting Communications Parameters .......................................................................................................................... 36
6.7.1 Setting Parameters Before Using WebUI Management ........................................................................................... 36
6.7.2 (Optional) Setting Parameters Before Using the NetEco Management ................................................................... 37
6.7.3 Setting Parameters Before Using the SNMP Management ...................................................................................... 38
6.8 Connecting the Battery Supply ................................................................................................................................... 41
6.9 Subsequent Operations ............................................................................................................................................... 42
7 Maintenance ................................................................................................................................. 43
7.1 Routine Maintenance .................................................................................................................................................. 43
7.2 Rectifying Common Faults ......................................................................................................................................... 44
7.2.1 Mains Failure ........................................................................................................................................................... 44
7.2.2 AC Over Volt ........................................................................................................................................................... 44
7.2.3 AC Under Volt ......................................................................................................................................................... 44
7.2.4 DC Over Volt ........................................................................................................................................................... 44
7.2.5 DC Under Volt ......................................................................................................................................................... 45
7.2.6 Batt Chg.Overcur. .................................................................................................................................................... 45
7.2.7 LLVD Disconnected ................................................................................................................................................ 46
7.2.8 BLVD Disconnected ................................................................................................................................................ 46
7.2.9 Battery Fuse Break .................................................................................................................................................. 46
7.2.10 High Amb. Temp.................................................................................................................................................... 47
7.2.11 Low Amb. Temp. ................................................................................................................................................... 47
7.2.12 High Amb. Humi. .................................................................................................................................................. 48
7.2.13 Low Amb. Humi. ................................................................................................................................................... 48
7.2.14 Batt. High Temp. .................................................................................................................................................... 48
7.2.15 Batt. Low Temp. .................................................................................................................................................... 49
1 Safety Precautions
The power system is powered by high-voltage power sources. Direct or indirect contact
(through damp objects) with high-voltage power sources may result in serious danger.
Non-standard and improper operations may result in fire and electric shocks.
Before electrical connections, turn off the upstream protection switch for the device.
Before connecting the AC power supply, ensure that electrical connections are complete.
Before you connect cables to loads or battery cables, check cable and terminal polarities,
preventing reverse connections.
ESD Requirements
To prevent electrostatic-sensitive components from being damaged by the static on
human bodies, wear a well-grounded ESD wrist strap or gloves when touching circuit
boards.
When holding a board, hold its edge without components. Do not touch chips.
Removed boards must be packaged with ESD packaging materials before storage and
transportation.
Basic Requirements
Before installation and maintenance, wear goggles, rubber gloves, and protective clothes
to prevent injury caused by electrolyte overflow.
When handling a battery, ensure that its electrodes are upward. Leaning or reversing
batteries is prohibited.
Keep the battery loop disconnected during installation and maintenance.
Secure battery cables to a torque specified in battery documentation. Loose connections
will result in excessive voltage drop or cause batteries to burn out when the current is
large.
Short circuits will generate high transient currents and release a great deal of energy, which
may cause personal injury.
If conditions permit, disconnect the batteries in use before performing any other operations.
Lead-acid batteries in use emit flammable gas. Therefore, store the batteries in a place with
good ventilation, and take measures against fire.
High temperatures may result in battery distortion, damage, and electrolyte overflow.
When the battery temperature is higher than 60°C, check the battery for electrolyte overflow.
If the electrolyte overflows, absorb and counteract the electrolyte immediately. When moving
or handling a battery whose electrolyte leaks, exercise caution because the leaking electrolyte
may hurt human bodies. When you find electrolyte leaks, use sodium bicarbonate (NaHCO3)
or sodium carbonate (Na2CO3) to counteract and absorb the leaking electrolyte.
Signal cables must be bound separately from strong-current cables and high-voltage
cables.
Cables prepared by the customer must have the fire resistance capability.
Cables must not pass behind the air exhaust vents of rectifiers in the cabinet.
Drilling Holes
Do not drill holes on the subrack without permission. Non-standard drilling may affect
electromagnetic shielding performance of the subrackand damage the internal cables, and
metal scraps generated during drilling may short-circuit a circuit board.
Before drilling holes on the subrack, remove the cables inside the rack.
Wear goggles and protective gloves when drilling holes.
After drilling, clean up metal shavings.
2 Overview
2.1 Introduction
ETP48200-C2A1 is an embedded telecom power system that supplies power to –48 V DC
communications equipment with a maximum current of 200 A.
2.5 Configurations
Table 2-1 lists ETP48200-C2A1 configurations.
Item Configuration
3 Appearance
3.1 Interior
Figure 3-1, Figure 3-2, and Figure 3-3 show the ETP48200-C2A1 interior.
(1) Ground screw (2) LLVD wiring terminal (3) BLVD wiring terminal
(4) Battery wiring terminals (5) AC input terminals
Before delivery, the RTN+ busbar is short-circuited with the subrack PE terminal by default.
The two rightmost terminals among the AC input terminals shown in Figure 3-3 are N wiring
terminals.
3.2 PDU
Table 3-1 lists power distribution specifications for the ETP48200-C2A1.
Item Specifications
3.3 Rectifier
Rectifiers convert AC input into stable DC output.
Appearance
Figure 3-4 shows a rectifier.
Panel
Figure 3-5 shows the rectifier panel.
Indicators
Table 3-2 describes the indicators on the rectifier panel.
3.4 SMU02B
Appearance
Figure 3-6 shows an SMU02B.
Panel
Figure 3-7 shows an SMU02B panel.
(1) Run indicator (2) Minor alarm indicator (3) Major alarm indicator
(4) Buttons (5) USB port (reserved, the (6) RS485/RS232 port
port is protected by a
security mechanism.)
(7) Handle (8) Locking latch (9) FE port
(10) Liquid crystal display
(LCD)
Indicators
Table 3-3 describes the indicators on the SMU02B panel.
Buttons
Table 3-4 describes the buttons on the SMU02B panel.
Communication Ports
Table 3-5 describes the communication ports on the SMU02B panel.
NOTE
All the ports mentioned are protected by a security mechanism.
3.5 UIM02D
Panel
The user interface module (UIM02D) supports twelve dry contact outputs, nine dry contact
inputs (including six universal dry contact inputs, one smoke sensor input, one water sensor
input, and one door status sensor input), and four analog parameter inputs (including one
ambient temperature and humidity input, two ambient temperature inputs, and one battery
temperature input).
Figure 3-9 shows a UIM02D panel.
Ports
DIN3
DIN4
DIN5
DIN6
ALM3
ALM4
ALM5
ALM6
ALM7
ALM8
ALM9
ALM10
ALM11
ALM12
Communications port COM RS485 port
Communication Port
COM port Baud rate: 9600 bit/s M/S and Modbus Connects to
protocol lower-level
devices
such as the
battery
voltage
detector,
DC Air
Conditioner
Note:
The COM port supports the security mechanism.
Pins
Figure 3-11 shows the pin numbers of the sensor ports. Table 3-11 defines the pins.
TEM-HUM 1 12 V
2 ENV_TEMP
3 12V
4 ENV_HUM
WATER 1 12 V
2 WATER
3 GND
4 -
TEMP1 1 GND
2 TEMP1
TEMP2 1 GND
2 TEMP2
GATE 1 GATE+
2 GATE-
SMOKE 1 SMOKE
2 12 V
BTEMP 1 GND
2 BTEMP
4 Installation
----End
Ensure that ground cables are installed securely. If devices are not properly grounded, electric
shocks may occur.
Do not put your hands into rectifier slots, avoiding electric shocks.
When a rectifier is running, a high temperature is generated around the air exhaust vent at
the rear. Do not touch the vent or cover the vent with cables or other objects.
Procedure
Step 1 Push the locking latch towards the left.
Step 2 Draw the handle downwards.
Step 3 Gently push a rectifier into its slot along the guide rail.
Step 4 Push the handle upwards.
Step 5 Push the locking latch towards the right to secure the handle.
----End
----End
(1) FE port
----End
(1) FE port
----End
Step 2 Connect the other end to the MON1 port on the BBU, as shown in Figure 4-10.
----End
(1) FE port
----End
Ensure that the upstream AC input circuit breaker is OFF, and attach labels such as "No
operations allowed."
Switch off all circuit breakers before installing power cables.
Procedure
Step 1 Remove the rear cover from the subrack.
Step 2 Lay out DC output power cables. Connect the negative power cable to a DC output terminal.
Step 3 Connect the positive power cable to the corresponding screw on the RTN+ busbar.
(1) DC load
----End
Procedure
Step 1 Lay out battery cables. Secure the negative battery cables to the battery wiring terminals.
Step 2 Connect the positive battery cables to the RTN+ busbar, as shown in Figure 4-13.
----End
Ensure that the upstream AC input circuit breaker is OFF, and attach labels such as "No
operations allowed."
Switch off all circuit breakers before installing power cables.
Procedure
Step 1 Lay out AC input power cables based on site requirements.
Step 2 Secure AC input power cables to AC input terminals.
Figure 4-14 Installing 220/380 V AC three-phase, four-wire input power cables (L1, L2, L3, and
N)
(1) ACDB
Figure 4-15 Installing 220/380 V AC three-phase, four-wire input power cables (L1, L2, L3, N,
and PE)
(1) ACDB
----End
6 Commissioning
The following commissioning procedure may result in power failure or alarms. Inform the
alarm center before and after the procedure.
Commissioning involves various technologies, requires trained personnel, and requires
compliance with commissioning instructions.
Commissioning is performed with the power on. Remove metal items such as watches and
necklaces, stand on dry insulating material, and use insulated tools.
Do not contact two electric bodies that have different currents during operations.
During commissioning, check that the status of the related unit or component meets
requirements before turning on any switch.
When you are performing operations and do not want others to operate, attach the label
"Do not turn on the switch because operations are in process." to the power distribution
device.
During commissioning, shut down the device immediately if any fault is detected. Rectify
the fault and proceed with the commissioning.
If you select an undesired language, remove and then insert the SMU. Select a language again after the
SMU restarts.
Setting Wizard Date and Time Date and Time - Set to the local
NOTE date and time.
The date and Time Zone UTC +08:00 Set to the local
time vary
according to Beijing time zone.
time zones. Set
the time zone, NTP Enable No Yes/No
date, and time NOTE
based on the Set the
local situation. parameter to
Yes if you need
to synchronize
the SMU time
and the site
network server
time.
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Rated Capacity to 150 Ah.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set Rated
Capacity to 300 Ah.
Ambient None
Humi.
Sensor
Batt. Temp. None
Sensor 1
Batt. Temp. None
Sensor 2
Second- Third-Level
Main Menu Level Menu Menu Default Value Setting Value
Second- Third-Level
Main Menu Level Menu Menu Default Value Setting Value
----End
Step 3 Set the IP Addresses and Ports for the active and standby servers of the NetEco on the LCD,
as described in Table 6-7.
----End
----End
Information Description
SNMP version SNMP version and port number used by the SMU and NMS. The SNMP
versions include SNMPv1, SNMPv2c, and SNMPv3.
SNMP Port Number
Read Community Name If you use SNMPv1 or SNMPv2c, enter the read community name and write
community name that comply with the NMS. Otherwise, the SMU will not
Write Community Name connect to the NMS.
Information Description
User Name To enhance the security, you need a user name and password for
authentication if you use SNMPv3. After the authentication succeeds, the
MD5 Password SMU can communicate with the NMS.
DES Password
Trap Target Address IP address and port number reported in the alarm trap.
Trap Port
Procedure
Step 1 Apply to the site or equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 6-10.
Second-
Level Third-Level
Main Menu Menu Menu Default Value Setting
Step 3 Enter the IP address for the SMU in the address box of Internet Explorer. Log in to the
WebUI on the login page shown in Figure 6-1.
The preset user name is admin and the preset password is Changeme.
You can set SNMP parameters on the WebUI locally or remotely.
If the SNMP version is SNMPv3, set SNMP Version to SNMPv3 under SNMP, click
Add under SNMPv3, and then set User Name, MD5 Password, and DES Password, as
shown in Figure 6-3.
Step 5 Under SNMP Trap, set Trap Target Address and Trap Port.
Step 6 Under Mib files, click Export to export the Mib file and import it to the NMS.
----End
Follow-up Procedure
You can query the power system operating status, active alarms, and the names of
user-defined dry contact inputs, and configure dry contact outputs on the NMS that is
connected over the SNMP.
To avoid damage to batteries, switch on the battery circuit breaker only after correctly setting
the battery parameters.
Procedure
Step 1 Switch off the upstream AC input circuit breakers.
7 Maintenance
Electricity The AC input Clamp meter. The AC input For details, see
voltage is voltage is 7.2 Rectifying
normal. beyond the Common Faults
normal range. and 7.3
Identifying
The output The battery Component
voltage is branch or load Faults.
normal. branch voltage
exceeds the
specified range
(-42 V DC to
-58 V DC).
Preventive The indicators Observing Alarms are
maintenance are in the indicators. generated.
inspection normal status.
(PMI)
Grounding The ground Clamp meter. The resistance Secure the
point properly between the ground cable to
connects to the ground point the ground
ground bar in and the ground point again or
the cabinet. bar is greater replace the
than 0.1 ohm. ground cable.
Measures
1. Check whether the AC input cable is loose. If yes, secure the AC input cable.
2. Check whether the upstream AC input circuit breaker is OFF. If yes, rectify the back-end
circuit fault and then switch on the circuit breaker.
3. Check whether the AC input voltage is lower than 50 V AC. If yes, handle the mains
grid fault.
Measures
1. Check whether the AC overvoltage alarm threshold is properly set. If no, adjust it to a
proper value.
2. Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V
AC by default). If yes, handle the AC input fault.
Measures
1. Check whether the AC undervoltage alarm threshold is properly set. If no, adjust it to a
proper value.
2. Check whether the AC input voltage is below the AC undervoltage alarm threshold (180
V AC by default). If yes, handle the AC input fault.
Measures
1. Check whether the DC overvoltage alarm threshold (58 V DC by default) is properly set.
If no, adjust it to a proper value.
2. Check whether the system voltage is set too high in manual mode. If yes, confirm the
reason and adjust the voltage to normal after the operation.
3. Remove the rectifiers one by one and check whether the alarm is cleared. If the alarm
still exists, reinstall the rectifier. If the alarm is cleared, replace the rectifier.
Measures
1. Check whether an AC power failure occurs. If yes, resume the AC power supply.
2. Check whether the DC undervoltage alarm threshold (45 V DC by default) is properly
set. If no, adjust it to a proper value.
3. Check whether the load current is greater than the current power system capacity. If yes,
expand the power system capacity or reduce the load power.
4. Check whether the system voltage is set too low in manual mode. If yes, confirm the
reason and adjust the voltage to a proper value after the operation.
5. Check whether the power system capacity is insufficient for the loads due to rectifier
failures. If yes, replace the faulty rectifier.
Measures
1. Check whether an alarm is generated for rectifier communication interruption. If yes,
remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm
still exists, replace the rectifier.
2. Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still
exists, replace the SMU.
Measures
1. Check whether an AC power failure occurs. If yes, resume the AC power supply.
2. Check whether loads are manually disconnected. If yes, confirm the reason of the
manual disconnection, and reconnect the loads after the operation.
3. Check whether the load disconnection voltage (44 V DC by default) is set too high on
the SMU. If yes, adjust it to a proper value.
4. Check whether the power system capacity is insufficient for the loads due to rectifier
failures. If yes, replace the faulty rectifier.
5. Check whether the load current is greater than the current power system capacity. If yes,
expand the power system capacity or reduce the load power.
Measures
1. Check whether an AC power failure occurs. If yes, resume the AC power supply.
2. Check whether batteries are manually disconnected. If yes, confirm the reason of the
manual disconnection, and reconnect the batteries after the operation.
3. Check whether the battery disconnection voltage (43.2 V DC by default) is set too high
on the SMU. If yes, adjust it to a proper value.
4. Check whether the power system capacity is insufficient for the loads due to rectifier
failures. If yes, replace the faulty rectifier.
5. Check whether the load current is greater than the current power system capacity. If yes,
expand the power system capacity or reduce the load power.
Measures
1. Check whether the battery fuse detection cable is disconnected. If it is disconnected,
reconnect it.
2. Check whether the battery circuit breaker is disconnected or the battery fuse is blown. If
the battery breaker is disconnected or the battery fuse is blown, rectify the battery loop
fault and then switch on the circuit breaker or replace the fuse.
This alarm is generated only for the power system that has ambient temperature sensors installed.
Possible Causes
The ambient overtemperature alarm threshold is not set properly on the SMU.
The temperature control system is faulty in the cabinet where the ambient temperature
sensor is located.
The ambient temperature sensor is faulty.
Measures
1. Check whether the ambient temperature alarm threshold (55°C by default) is properly set
on the SMU. If no, adjust it based on site requirements.
2. Check whether the temperature control system in the cabinet is faulty. If yes, rectify the
fault. The alarm is cleared when the cabinet temperature falls within the allowed range.
3. Check whether the ambient temperature sensor is faulty. If yes, replace the temperature
sensor.
This alarm is generated only for the power system that has ambient temperature sensors installed.
Possible Causes
The ambient undertemperature alarm threshold is not set properly on the SMU.
The temperature control system is faulty in the cabinet where the ambient temperature
sensor is located.
The ambient temperature sensor is faulty.
Measures
1. Check whether the ambient undertemperature alarm threshold (-20°C by default) is
properly set on the SMU. If no, adjust it based on site requirements.
2. Check whether the temperature control system in the cabinet is faulty. If yes, rectify the
fault. The alarm is cleared when the cabinet temperature falls within the allowed range.
3. Check whether the ambient temperature sensor is faulty. If yes, replace the ambient
temperature sensor.
This alarm is generated only for the power system that has humidity sensors installed.
Possible Causes
The ambient overhumidity alarm threshold is not set properly on the SMU.
The humidity is too high in the cabinet where the humidity sensor is located.
The humidity sensor is faulty.
Measures
1. Check whether the ambient overhumidity alarm threshold (95% RH by default) is
properly set on the SMU. If no, adjust it based on site requirements.
2. Check whether water intrudes into the cabinet. If yes, wipe the water with dry cotton or
other tools and rectify the fault.
3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor.
This alarm is generated only for the power system that has humidity sensors installed.
Possible Causes
The ambient underhumidity alarm threshold is not properly set on the SMU.
The humidity is too low in the cabinet where the humidity sensor is located.
The humidity sensor is faulty.
Measures
1. Check whether the ambient underhumidity alarm threshold (5% RH by default) is
properly set on the SMU. If no, adjust it based on site requirements.
2. Check whether the cabinet humidity is too low. If yes, adjust the cabinet humidity. The
alarm is cleared when the humidity falls within the allowed range.
3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor.
This alarm is generated only for the power system that has battery temperature sensor installed.
Possible Causes
The battery overtemperature alarm threshold is not set properly on the SMU.
The battery temperature controlling system is faulty.
The battery temperature sensor is faulty.
Measures
1. Check whether the battery overtemperature alarm threshold (50°C by default) is properly
set. If no, adjust it to a proper value.
2. Check whether the battery temperature controlling system is faulty. If yes, rectify the
fault. The alarm is cleared when the battery temperature falls within the allowed range.
3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature
sensor.
This alarm is generated only for the power system that has battery temperature sensor installed.
Possible Causes
The battery undertemperature alarm threshold is not set properly on the SMU.
The battery temperature controlling system is faulty.
The battery temperature sensor is faulty.
Measures
1. Check whether the battery undertemperature alarm threshold (-10°C by default) is
properly set. If no, adjust it to a proper value.
2. Check whether the battery temperature controlling system is faulty. If yes, rectify the
fault. The alarm is cleared when the battery temperature falls within the allowed range.
3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature
sensor.
This alarm is generated only for the power system that has door status sensor installed.
Possible Causes
The cabinet doors are open.
The door status sensor is faulty.
Measures
1. Close cabinet doors.
2. Check whether the door status sensor is faulty. If yes, replace the door status sensor.
This alarm is generated only for the power system that has water sensors installed.
Possible Causes
Water intrudes into the cabinet.
The water sensor is faulty.
Measures
1. Check whether water intrudes into the cabinet. If yes, wipe the water with dry cotton or
other tools and rectify the fault.
2. Check whether the water sensor is faulty. If yes, replace the water sensor.
This alarm is generated only for the power system that has smoke sensors installed.
Possible Causes
There is smoke inside the cabinet.
The smoke sensor is faulty.
Measures
1. Check whether there is smoke inside the cabinet. If yes, disconnect the power supply
from the cabinet, handle the fault, and then resume system operation and clear the alarm
on the SMU.
2. Check whether the smoke sensor is faulty. If yes, replace the smoke sensor.
Measures
1. Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier,
and then reinstall it after the indicator turns off.
2. If the alarm still exists, replace the rectifier.
Measures
1. Check whether the AC input voltage exceeds the upper threshold of the rectifier working
voltage. If yes, rectify the power supply fault and then resume the power supply.
2. Check whether the AC input voltage is below the lower threshold of the rectifier working
voltage. If yes, rectify the power supply fault and then resume the power supply.
3. Check whether the ambient temperature is higher than the normal operating temperature
of the rectifier. If yes, check and rectify the temperature unit fault.
4. Remove the rectifier that generates the alarm and reinstall it after the indicator turns off.
If the alarm still exists, replace the rectifier.
Measures
1. Check whether the rectifier is removed. If yes, reinstall it.
2. If the rectifier is in position, remove the rectifier and reinstall it.
3. If the alarm still exists, replace the rectifier.
Ensure that loads are supplied with power when replacing major components. For example,
keep the switches for primary loads in the ON position, and do not turn off the battery
switch and AC input switch at the same time.
Seek the customer's prior consent if load disconnection is required.
Do not maintain devices on raining days, preventing water from entering and damaging
devices.
Protect yourself from being burnt when moving the rectifier because the rectifier has a high
temperature.
Procedure
Step 1 Put on protective gloves.
Step 2 Push the locking latch at the right side of the panel towards the left.
Step 3 Gently draw the handle outwards, and then remove the rectifier from the subrack, as shown in
Figure 7-1.
Step 4 Push the locking latch on the new rectifier towards the left, and pull out the handle.
Step 5 Place the new rectifier at the entry to the correct slot.
Step 6 Gently slide the converter into the slot along guide rails until it is engaged. Close the handle,
and push the locking latch towards the right to lock the handle, as shown in Figure 7-2.
Follow-up Procedure
Pack the removed component, and return it to Huawei local warehouse.
Procedure
Step 1 Push the locking latch towards the left.
Step 2 Pull the handle outwards to remove the SMU, as shown in Figure 7-3.
Step 3 Insert a new SMU into the subrack, push the locking latch towards the left, and pull out the
handle.
Step 4 Slide the new SMU into the subrack slowly along the guide rail, pull in the handle, and then
push the locking latch towards the right.
Step 5 Reset parameters on the SMU.
----End
Follow-up Procedure
Pack the removed component, and return it to Huawei local warehouse.
The UIM02D consists of two user interface boards. This topic describes how to replace the boards.
Procedure
Step 1 Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2 Remove the UIM02D.
1. Record the positions of signal cables on the UIM02D panel, and then disconnect the
signal cables.
2. Unscrew and remove the UIM02D, as shown in Figure 7-5.
2. Disconnect the cables between upper and lower boards in the UIM02D.
Step 4 Remove the lower board from the UIM02D.
1. Record the positions of signal cables and communications cables connected to the lower
board, and disconnect the cables.
2. Unscrew and remove the lower board from the UIM02D, as shown in Figure 7-7.
Follow-up Procedure
Return the faulty boards for repair.
A Technical Specifications
Electrostatic IEC61000-4-2
discharge (ESD) Shell ports: contact discharge of 6 kV and air
discharge of 8 kV; signal ports: contact discharge
of 2 kV
Electrical fast IEC61000-4-4
transient (EFT) Signal port: 1 kV; power port: 2 kV
Radiated IEC61000-4-3
susceptibility (RS) Level 3; field strength: 10 V/m
Conducted IEC61000-4-6
susceptibility (CS) Signal port: 3 V; power port: 10 V
Surge immunity IEC61000-4-5
AC and DC power ports: Differential mode: 2 kV
(8/20 µs); common mode: 4 kV (8/20 µs)
Voltage dips IEC 61000-4-11
immunity (DIP)
Others Safety design Complies with IEC/EN60950-1 and GB4943
Mean time between 200,000 hours
failures (MTBF)
Structure Power system (H x 87.1 mm x 482 mm x 450 mm
W x D)
Weight ≤ 15 kg (excluding rectifiers)
Protection level IP20
Installation mode Equipped with mounting ears to adapt to 19-inch
cabinets
Cable routing Signal cables and communications cables are
routed from the front, and power cables are routed
from the rear.
Maintenance mode Maintained from the front or rear
Heat dissipation Natural cooling
ALM8 Reserved
ALM9 Reserved
ALM10 Reserved
ALM11 Reserved
ALM12 Reserved
A
ACDB alternating current distribution box
B
BLVD battery low voltage disconnection
E
EFT electrical fast transient
EMC electromagnetic compatibility
ESD electrostatic discharge
H
HTTPS Hypertext Transfer Protocol Secure
I
IP Internet Protocol
L
LCD liquid crystal display
LLVD load low voltage disconnection
M
MTBF mean time between failures
P
PDU power distribution unit
R
RS radiated susceptibility
S
SMU site monitoring unit
SNMP Simple Network Management Protocol
T
THD total harmonic distortion