Ceiling
to scan the entire HEPA filter
Negative (-ve)
surface for pinhole leaks that
could allow the transmission SPARGE PIPE
Important considerations:
• Access is required to the air off side of EXHAUST
the HEPA filter (within the exhaust duct),
so that a NATA technician is able to
view and scan the HEPA filter surface
at 25mm from the installation for traces
of the test aerosol.
• Access to the exhaust duct via access
panel may cause a decrease in air
pressure within the exhaust stream,
affecting the required flow of test
aerosol that is pulled through the HEPA.
In this instance it is sometimes necessary
to use blower fans to provide a flow of
air across the filters.