Professional Documents
Culture Documents
© American Architectural
Manufacturers Association 2010
` Comparison of the AAMA/WDMA/CSA
101/I.S.2/A440 -08 lab test (referred to as
NAFS-08) to the AAMA 502 quality
assurance field test and the AAMA 511
forensic evaluation
manufacturer’s
instructions in a precise
test buck opening
Conversion as per NAFS-08
` 15% for R, LC, CW
` 20% for AW
Gateway Requirements
Performance Minimum Minimum Minimum
Class Design Structural test Water
Pressure, Pa pressure, Pa Resistance
(psf) (psf) Test Pressure,
Pa (psf)
R 15.0 22.5 2.90
LC 25.0 37.5 3.75
CW 30.0 45.0 4.50
AW 40.0 60.0 8.00
6.00 PSF (~50 mph)
Equivalent hydrostatic
water head
1.16”
NAFS Overview
7.50 PSF (~55 mph)
Equivalent hydrostatic
water head
1.44”
NAFS Overview
AAMA 502-08
AAMA 502
` AAMA 502-90
` Original publication by AAMA
` AAMA 502-02
` Added reference to AAMA accredited laboratory and
first introduced the 1/3 WTP reduction for water
resistance testing of installed products
AAMA 502
` AAMA 502-08
` Defined “newly” installed as prior to issuance of the
occupancy permit not to exceed 6 months after
installation of the fenestration product.
` ASTM E 783
◦ Field Measurement of Air Leakage through
Installed Exterior Windows and Doors
` ASTM E 1105
◦ Field Determination of Water Penetration of
AAMA 502
PRESSURE
MEASURING
ALTERNATE DEVICE
TEST
CHAMBER
TEST
CHAMBER
EXHAUST
VALVE
AAMA 502
AIR SYSTEM
INNERMOST PLANE
FOR WATER PENETRATION
(REFERENCE PARAGRAPH 4.3.4)
W
PRESSURE GAUGE
VALVE
CALIBRATED WATER
SPRAY RACK
AAMA 503
AAMA 503 Curtain Wall Chamber Arrangement
` Storefronts
` Curtain Wall
` Sloped Glazing
AAMA 503
Sloped Glazing Systems Chamber
Arrangement
AAMA 503
` Storefronts
` Curtain Wall
` Sloped Glazing
AAMA 503
Forensic Investigation
ASTM References in AAMA 511
¾ASTM E 2128, Standard Guide for
Evaluating Water Leakage of Building Walls
Forensic Investigation
• Architectural drawings
• Structural drawings
• Shop drawings
• Installation instructions
• Contracts
• Purchase orders
• Specifications
• Warranties
Step # 2: Evaluation of Design Concept
Forensic Investigation
• Exterior observations
• Observe workmanship
• Observe product
deficiency
• Develop a
hypothesis for the
source of the
water intrusion
Forensic Investigation
Determination is based on:
Forensic Investigation
◦ Field Standards
◦ Laboratory Standards
◦ Prior Testing
◦ Weather Data
◦ Experience
◦ Simulate the weather events
Forensic Investigation
◦ Exposure
◦ Height above grade
◦ Basic wind speed
(or weather data)
◦ Location of
specimen
within façade
Forensic Investigation
• The objective of testing is to identify the leak
Forensic Investigation
paths
Consistent leaks more than one year
AAMA 511- Example 1
`
` ASCE/SEI 7‐05 analysis is used with the
following information:
◦ Location of building (Newark, NJ)
◦ Building usage designation (Class II)
◦ Exposure level (Exposure B)
◦ Building design (enclosed structure with a flat roof )
◦ Building height (33 ft.)
◦ Window area (16 square ft.)
` From these features, the water resistance test
pressure is, theoretically, 2.4 psf.
AAMA 511- Example 1
` Local weather data is analyzed by daily
readings for September of 2005, allowing the
investigator to observe the weather condition,
amount of precipitation and maximum wind
speed for each day
AAMA 511 Example #1
AAMA 511- Example 1
` The maximum 5‐second gust wind speeds are
recorded for every day in September in which
measurable rainfall occurred
` Only two leak events are reported during
September 2005
` Average wind determined to be 34 mph
evaluate the window opening in question
` Weather data analysis is used to determine field water
penetration resistance pressure
` Table 3 of AAMA/WDMA/CSA 101/I.S. 2/A440‐05 shows
tested water penetration resistance pressure
` The result of the weather data analysis (2.2 psf ) is the
differential pressure used to evaluate the window
opening in question
` Leak Reported during storm on September
AAMA 511- Example 2
21, 2005
` Class II, Exposure C
` Building height is 60 ft., window (z) is 55
ft. above ground
` Window is 2’ high x 2’ wide, wind area (A)
of 4 ft2
` AAMA rating C35
AAMA 511- Example 2 Estimating the Test Pressure
` ASCE/SEI 7‐05 analysis is used with the following
information:
◦ Location of building (Chicago, Il)
◦ Building usage designation (Class II)
◦ Exposure level (Exposure C)
◦ Building design (enclosed structure with a flat roof )
◦ Building height (60 ft.)
◦ Window area (4 square ft.)
` From these features, the water resistance test pressure is,
theoretically, 3.2 psf.
AAMA 511- Example 2
` Referring to tabulated local weather data
above, the investigator can determine and
record the maximum 5‐second gust speeds on
the date of the reported leak
` 52 mph can now be used in Eq.‐ 6‐15 from SEI/ASCE 7‐05
to establish a wind pressure of 7.9 psf
` Since specimen height is above 60 feet above grade, this
wind pressure is inserted into Eq.‐ 6‐23 to calculate
maximum test pressure
` Result = 8.4 psf, which is greater than the laboratory
water penetration resistance test pressure of 5.25 psf as
prescribed for a C 35 product rating.
` Since calculated differential air test pressure exceeds the
rated performance value for the product, investigator
shall first perform at least 1 test at 2/3 of the product
performance rating prior to testing at calculated
pressure.
Interior Weep Holes Water shall cover all horizontal surfaces expected to be wet
`
each new water test
` Use isolation to protect features from water
spray
` Do not turn the water off at the first
moment a leak appears
` Try to trace the leak from the exterior to the
interior and use destructive wall probes as
required to identify this leak path
` Do not end non-leaking tests until you are
confident the specimen is not contributing
to leakage
` No or limited leak history
` Leak reported as window leak when leak
Recreating the Leak
documents