Professional Documents
Culture Documents
2008
N° 01429782.1
EN
Instructions
SERIES AFV. AFB(P)
02.2008 - 01429782.1 - AFV . AFB series
Contents Page
Introduction
• 1.1 – Description 1
Receipt, Handling, Installation
• 2.1 – Receipt 1
• 2.2 – Handling 1
• 2.3 – Installation 2
• 2.4 – Assembling the device 3
• 2.5 – Refrigeration connections 3
• 2.5.1 – Connecting a remote unit 4
• 2.5.2 – Connection on central refrigerating plant 4
• 2.6 – Water connection 5
• 2.7 – Electrical connections 6
• 2.8 – Installing the sliding rails 6
• 2.9 – Installing the probes and the moisture sensor 7
Use, safety
• 3.1 - Safety 7
• 3.2 – Presentation of the automatic control system control panel 8
• 3.3 – Operation of the automatic control system panel 9
• 3.3.1 – Panel start/stop 9
• 3.3.2 – Adjusting the current day and time 9
• 3.3.3 – Programming a RETARDER PROOFING CYCLE 10
• 3.3.4 – Starting a RETARDER PROOFING CYCLE already Programmed 14
• 3.3.5 – Starting a DIRECT HEATING AND HUMIDITY PROGRAMME (proofing) 15
• 3.3.6 – Simplified programming of the automatic control system panel 16
• 3.4 – Operation of the simple electronic control panel 17
• 3.4.1 – Starting the holding phase 18
• 3.5 – Operating advice 19
• 3.5.1 – Loading, preliminary operations 19
• 3.5.2 – Loading the device 19
• 3.6 – Warning 19
• 3.7 – Retarder proofing 19
• 3.8 – Dough defects 21
Cleaning and Hygiene
• 4.1 – Cleaning instructions 22
• 4.2 – Daily cleaning 22
• 4.3 – Weekly cleaning 22
• 4.4 – Monthly cleaning 22
• 4.5 – Extended equipment shutdown 22
Breakdowns
• 5.1 – Troubleshooting 23
Maintenance
• 6.1 – Refrigeration regulator of the simple electronic control panel 24
• 6.2 – Holding timer of the simple electronic control panel 24
• 6.3 – Refrigeration regulator of the simple electronic control panel 24
• 6.4 – REFRIGERATION regulator parameters of the simple electronic control panel 25
• 6.5 – Parameters of the Holding timer of the simple electronic control panel 26
• 6.6 – HEATING regulator parameters of the simple electronic control panel 27
• 6.7 – Control panel, automatic control system board 28
• 6.8 – Parameters of the automatic control system control panel 29
Warranty 30
MEASURES TO LIMIT FLOUR DUST EMISSIONS 30
Declaration of conformity
• 9.1 – End of life of the equipment and waste management 31
Wiring diagrams
• 10.1 – Electromechanical Control Panel, Developed Diagram 32
• 10.1.1 – Electromechanical Control panel, Connection principle 33
• 10.2 – Automatic control system control panel, Developed diagram 34
• 10.2.1 – Automatic control system Control panel, Connection principle 35
1.1- Description
This equipment should only be used for the purpose it was designed for: namely, the controlled rising, full cycle
blocking and fermentation, or direct proofing. Any other use could result in operation problems.
AFB 68 1C 1P
A A – Refrigerating unit
B
C B – Control panel and power distribution panel
2.1 - Receipt
The good condition of the device at the time of receipt is the recipient’s responsibility. For these reasons, as of
its receipt, it is mandatory to check: the name of the recipient, the correspondence between the number of
packages received and shipped, the general good condition of the packaging and possibly the device.
These checks must be carried out in the presence of the carrier in order to notify any defects observed on the
transport receipt before signing it and make the necessary complaints, if any, to the carrier. These complaints
will have to be sent to the carrier by registered letter with confirmation of receipt within a deadline of 48 hours,
with a copy of this letter to the sender.
2.2 - Handling
The device can be transported with a pallet truck or directly on its castors after having removed only the handling
pallet and by taking all the necessary precautions.
It is recommended to keep the packaging of the device till its final installation location.
The device must be stored at a temperature between 0°C and 50°C, away from humidity, UV rays and all
sources of corrosive agents.
; The floor surface on which the equipment is to be set up must be as level as possible.
; The equipment must be installed in a ventilated space, away from heat sources.
; We recommend that you keep plenty of free space around the enclosure allowing air circulation and access
to all the panels for cleaning. This will ensure the longevity of the equipment.
When the refrigerating unit is installed inside a room, aeration must be provided for.
The temperature of this room must not exceed 38°C in the case of a standard housed unit and 46°C in
the case of a High Ambient Temperature unit.
Preliminary operations:
In the case of remote connection of the refrigerating system, the selection of the suction piping is essential. It will
have to be calculated according to its special features, its length, as well as the difference in level between the
refrigerating system and the heat exchanger inside the device.
This piping section must ensure a sufficient speed for the return of oil to the compressor and not generate a
head loss greater than 1.5°C.
Remote installation: in certain cases of installation with long pipes, you may be compelled to add oil to
compensate for the quantity of oil that may be continuously circulating or stuck to the walls of the tubes.
Add the absolute minimum as an excess of oil in the compressor can be as disastrous as a lack of oil. Beyond
10 m, it may be permitted to add oil according to the table below:
- Ø 1/2’’ 10 ml/m - Ø 5/8’’ 20 ml/m - Ø 3/4’’ 30 ml/m - Ø 7/8’’ 40 ml/m - Ø 1’’ 50 ml/m
(R-134a or R-404A compressors: polyolester 8685015
The various accessories provided for this purpose must be connected as shown in the views below:
Legend
A – Refrigerating Compressor H – Evaporator/Battery
B – High pressure, pressure switch I – Low pressure, pressure switch
C – Condenser J – Liquid line solenoid valve
D – Liquid buffer cylinder K – Constant pressure valve
E – Dehydrating filter L – Low pressure isolation valve
F – Fluid indicator M – High pressure Isolation valve
G – Thermostatic expansion valve
I A B C
The refrigerating unit condenser must be installed at a minimum distance of 300 mm of any obstacle that
could affect the air circulation.
The G expansion valve overheating is set from the factory. However, certain cases require additional adjustment
to obtain dryer or damper cold as required.
The general rule is to have a suction temperature between -14°C and -10°C for an ambient temperature of the
chamber of + 0°C for an installation equipped with a refrigerating unit. The compressor head must never be
allowed to freeze.
K I L
H
Inside theAdevice
Intérieur ppareil
G J F E B M
The expansion valve overheat does not need to be adjusted if it is connected to the central refrigerating plant.
The constant pressure valve K must be set to an evaporation temperature between –10°C and –15°C for an
ambient temperature in the chamber of +0°C.
In all cases: Choose the diameter of the refrigeration piping so that it does not affect the unit’s operation,
while making sure the suction piping is insulated.
• Supply
The device must be connected to the drinking water network of the town, (optional on “AFV” type Viennese
cabinets).
Solenoid valve leak to be inserted into the Pipe 4/6 to be connected on the quick
hole of the discharge plug fixed at the rear coupler of solenoid valve on the device
of the device.
B
D
Fix the water intake filter A close to the water supply pipe. This filter is delivered as an accessory with the
device.
The pipe provided for the water supply of the device must be provided for in 10x12. It is connected to the water
filter A by means of an olive union of diameter 3/8.
The pipe 4/6 B must be connected to the quick coupler of the water intake solenoid valve C fixed at the back of
the device’s ceiling.
The leak pipe D must be inserted into the discharge plug E of 32mm diameter fixed on the rear panel of the
device.
The solenoid valve includes a shut-off valve, which is used either to isolate the circuit, or to reduce
the water pressure.
• Discharge
All devices must be connected to a defrost water discharge pipe.
The ringed tube fixed at the back of the device is used to connect to a pipe with a diameter of 32 mm. A siphon
will have to be installed if required.
• Protect the equipment’s upstream main supply line with a suitable ground fault circuit interrupter according to
the standard in force (NC 15-100) and to the instructions on the manufacturer’s plate. The blue wire of the
equipment’s power cable must be connected to the neutral conductor of the electrical installation.
• Check that the equipment’s electrical power supply is compatible with the selected power source.
• Connect the wires of the various components to the terminals of the electrical cabinet according to the
installation and packaging of the equipment delivered. The representation of the electrical layout of electrical
components to be connected is glued inside the control panel.
• Install the sliding rails on the racks while keeping the different levels sufficiently apart to ensure proper air
circulation.
• Engage the lugs of slides through the front perforation of the rack. Rest this lug on the bottom field of this
perforation. Slide the slide towards the rear of the rack until it engages in the bottom housing at the back of
the perforation.
A half-moon present on top of certain perforations is used as a positioning mark for slides. This mark
is provided for a spacing of 63 mm between slides.
The rack pitch is 21mm between each perforation. The equipment is delivered with 48 slides to obtain
24 levels spaced out by 63 mm following the “half-moon” mark.
Fix the moisture sensor to the ceiling and carry out the electrical connections.
Insert the temperature probes from above the equipment, inside the box-out
made in the right-hand side of the equipment.
Pass the probes through the wire channel from within the right-hand side of the
equipment.
Fix the moisture sensors to the fan supports and carry out the electrical
connections.
Insert the temperature probes from above the equipment, inside the box-out made
in the right-hand and left-hand side of the equipment.
Pass the probes through the wire channels from within the right-hand and left-hand
side of the equipment.
Fix the humidity probe to the ceiling and carry out the electrical connection.
Insert the temperature probe from above the equipment, inside the box-out
made in the right-hand side of the equipment.
Pass the probe through the wire channel from within the right-
hand side of the device.
Fix the humidity probes to the lower surface of the ceiling and the partition wall.
Insert the temperature probes from above the equipment, inside the box-out made
in the right-hand and left-hand side of the equipment.
Pass the probes through the wire channels from within the right-hand and left-hand
side of the equipment.
Use, safety
3.1 - Safety
Before turning the equipment on, check that there are no obstacles which can affect the proper operation of the
moving parts, like the utility duct and the refrigerating unit ventilators.
After turning the equipment on, check that the electrical network voltage does not vary more than 10% during the
hold and proofing phases.
Updating the day and time Direct call to programme P1 (e.g.: 12h)
Display and programming of the desired humidity rate Programming cycle and Validation key
DIRECT REFRIGERATION and DIRECT HEATING manual programme Cycle start and Validation
Reduction of the value during programming Increase of the value during programming
CURVE SIGNALLING
Programmes
Manual
DORMING phase
BLOCKING Phase PROOFING phase Return to
REFRIGERATION
The LEDs corresponding to the selected operating mode light up continuously in manual mode.
The 1st LED of the curve lights up continuously in the case of operation in controlled proofing cycle:
they will flash and come on as the programme proceeds.
Only the current day and time are displayed: standby mode.
Starting Up: press the key
The control panel is automatically set to DIRECT REFRIGERATION. The corresponding display indicates the
temperature inside the enclosure and the 2 corresponding LEDs light up.
The panel must be stopped or on standby: only the day and time must be displayed, otherwise press once
- Keep the key pressed for 5 seconds: the day of the week flashes
- Set the current day of the week with the or keys (Monday = 1, Tuesday = 2, etc.)
The “On” LED comes on as well as the one corresponding to the operation of the Manual Refrigeration
programme on the cycle, temperature curve.
; Set the day: press the keys or once then validate by pressing the key once
; To set the time press the keys or once then validate by pressing the key once
; To set the minutes press the keys or once then validate by pressing the key once
; To set the temperature: press the keys or once then validate by pressing the key once
st
The TEMPERATURE of the 1 PROOFING stage (heating), flashes: 12.
; To set the temperature: press the keys or once then validate by pressing the key once
st
The HUMIDITY LEVEL of the 1 PROOFING stage (heating), flashes: 80.
; To set the humidity: press the keys or once then validate by pressing the key once
nd
The TEMPERATURE of the 2 PROOFING stage (heating), flashes: 16.
; To set the temperature press the keys or once then validate by pressing the key once
nd
The HUMIDITY LEVEL of the 2 PROOFING stage (heating), flashes: 80.
; To set the humidity press the keys or once then validate by pressing the key once
; To set the temperature: press the keys or once then validate by pressing the key once
rd
The HUMIDITY LEVEL of the 3 PROOFING stage (heating), flashes: 80.
; To set the humidity: press the keys or once then validate by pressing the key once
; To set the humidity: press the keys or once then validate by pressing the key once
; To set the humidity: press the keys or once then validate by pressing the key once
The RETURN to REFRIGERATION after proofing TEMPERATURE “DORMING mode” flashes: 18.
; To set the humidity press the keys or once then validate by pressing the key once
; To set the humidity: press the keys or once then validate by pressing the key once
The panel returns to its initial display when changing to programming mode,
the BAKING DAY programmed previously flashes.
The panel beeps 5 times and starts the cycle thus programmed.
As the cycle progresses, the LEDs will flash and remain fixed. They indicate the phase in which the cycle is and
its progress status. The temperature displays will also come on according to the phase in which the programme
is.
In all cases, the day and time displayed are those of the end of proofing: The point in between the hours and
minutes is continuously lighted.
Pressing the key once displays the current day and time for 5 seconds (the point in between the hours and
minutes flashes during this real display).
If a power failure occurs during execution of the cycle, when the power is restored, if this
failure lasts more than 15 minutes, the baking day and time will flash in order to warn the
user that it is important to check the possible consequences on the products.
To stop the flashing, press the key once
; To STOP the current retarder proofing cycle press the key once
When this programme is selected the next day, its baking day will be automatically incremented by one day.
After having entered the respective temperature, humidity, duration values in the programme, it may be assigned
to a 12h cycle for P1, 24h for P2, 48h for P3 or for special products
The “On” LED lights up along with the one corresponding to the operation of the programme
Manual Refrigeration on the cycle, temperature curve.
; If the baking day and time correspond to the desired values, press the key once
The retarder proofing cycle is immediately started with the values already entered.
The panel beeps 5 times and starts the cycle thus programmed.
; Otherwise: press the keys or once then validate by pressing the key once
To modify the following desired values, follow the procedure of the paragraph:
As soon as modifications have been made press the key once = the cycle starts.
; Select the direct HEATING and HUMIDITY programme: Press the 2nd key once starting from the left
The inside TEMPERATURE and the HUMIDITY LEVEL are displayed: 12°C and 80%
Press the key once and the or keys then validate by pressing the key once or wait for 5 seconds
Press the key once and the or keys then validate by pressing the key once or wait for 5 seconds
Set or Check the actual day and time before commissioning (see paragraph 3.3.2 of the instructions)
Panel in standby = only the current day and time are displayed
DIRECT DIRECT HEATING AND REFRIGERATION On-Off /Cycle / Validation / Modification Programmes
REFRIGERATION
• Set the baking day or the offset (Monday=1, Tuesday=2, etc.) : or then *
• End of programming, start the PROGRAMME: Press , once, the cycle starts.
To stop a Retarder Proofing Cycle in progress: Press once = the panel goes on standby.
CONTROL PANEL
A – Holding temperature
REFRIGERATION thermostat
B – Holding time
HOLDING timer
C – Proofing temperature
PROOFING thermostat
D – On/Off switch
A – REFRIGERATION THERMOSTAT
• Press the key once to display the programmed temperature, the
indicator lamp flashes
• Press the key once to return to normal display or leave the device idle for 15s.
B – HOLDING TIMER
• Stop the countdown of the timer: Press the key once
• Press the key once, the indicator lamp flashes and the h:m
indicator lamp specifies the time units before and after the 2 points.
• Press the key several times or keep it pressed to decrease the duration
• Press the key once to return to the normal display or leave the device idle for 15s, the indicator lamp
goes off
• Press the key once to start the holding phase, the timer counts down the previously programmed
duration. The display becomes green and the two points : flash.
• Press the key once to stop the holding phase. The display becomes red and the two points : are steady.
C – PROOFING THERMOSTAT
• Press the key once to display the programmed temperature, the
indicator lamp flashes
• Press the key once to return to normal display or leave the device idle for 15s.
The indicator lamp lights up, as well as the time unit displayed h: m. These signals indicate that the time
countdown of the HOLDING phase is in progress.
Note: During the last hour of the countdown, the left field switches to minutes and the right field to
seconds. The time unit also displays m: s.
During the countdown of the last minute the display is in seconds and 1/10th of a second. No time unit
is displayed.
At the end of the holding time, the timer returns to its initial colour, the two points at the centre stop flashing and
the indicator lamp goes off.
During a power outage, the current cycle countdown will not be interrupted if the control panel
is operational. When the power is back on, the device will resume its cycle with no
consequences to the program.
• Set the hold temperature on the A cold thermostat: normally 2°C to 3°C are enough for 24 hours of work).
During the proofing phase, the refrigerating unit will start when the set temperature is exceeded by more than
2°C, to guarantee better temperature stability.
• Set the desired humidity level, by adjusting the moisture sensor button situated inside the enclosure when a
simple electronic panel is used
The humidity level setting will be refined according to the type and quality of product obtained.
For direct proofing, the humidity will have to generally be set at 80%.
• Load the equipment with the products and leave enough space in between them to provide excellent air
circulation. Use grille, layer (automatic), mesh or tray type supports.
3.6 – Warning
• Avoid opening the door (unless necessary)as this causes a change in the temperature and ambient
humidity, which can be harmful to the products.
• Avoid provisional storage of loaded supports outside the device. External air currents may cause significant
drying up of products.
• In some cases you may have condensation on walls and floor. This thermal shock phenomenon is normal.
• Avoid extended use under continuous refrigeration (greater than 60 hours) or the evaporator may freeze.
• Use the equipment only for its intended use. Do not try to overload it or use it with inappropriate products.
Ignoring these instructions causes a deterioration in the final quality of the products.
Introduction
The method of proofing during controlled rising is based on the following simple technique: extend dough proving
beyond its normal duration by placing the lumps in an enclosure where the temperature and ambient humidity
level can be controlled at any time.
The device must ensure, under maximum safety conditions, the production of:
We recommend maintaining the dough as it leaves the dough mixer at a temperature of about 22°C, in order to
obtain optimal proofing conditions.
The sum of the temperatures of the pouring water, the flour and the ambient air in the bakery should approach:
(*) The above values are for information purposes and should be adjusted to your process
Controlled rising can be an excellent methodology if applied rigorously while respecting proportioning.
The use of detergents, scouring powder, abrasive products, thinners and all products containing chlorine are
strictly forbidden.
It is essential to use POA – POV certified maintenance products.
Use lukewarm soap water or any inert organic product with bactericidal properties.
The following limitations must be respected when cleaning PVC coated panels:
• Water pressure: maximum 1 bar
• Temperature: 25°C
Do not use highly aggressive degreasing additives. Do not use phosphoric acid based products. We
recommend:
• Ammonia: 10% solution
• Ethyl alcohol: 48% solution
• Phenolic derivative: 0.5% solution
Finally, whatever the product used for local and frequent cleaning, do not exceed 30 minutes of contact time and
follow up with fresh water rinsing.
The refrigerating unit: The airflow must be allowed to circulate freely around the refrigeration unit and through the
condenser. This should be checked on a monthly basis. The condenser must be permanently clean for
maximum equipment output.
Each month, you should dust off the condenser and rid it of all obstructions with a vacuum cleaner, a brush or a
flexible paintbrush.
When the equipment reaches ambient room temperature, clean it fully as indicated above.
Breakdowns
5.1 – Troubleshooting
WHAT TO DO IF POSSIBLE CAUSE REMEDIAL ACTION
the device does not start
The control panel does not Local power shortage. Check the circuit breaker
work Check the head end line
protection
The device does not cool
anymore
Bubbles in the fluid indicator, Fluid shortage Fill up with Freon and find the
cool condenser leak
Frozen evaporator Extended cold operation De-freeze by hot running
Warm condenser Blocked condenser Clean the condenser, water
condenser: check the output
The device does not heat Burnt resistance Change the resistance
anymore
Ventilator out of order Change the ventilator
Product is crusty Bad mixing Use soft and fresh dough
Bad humidity Increase the humidity setting
(equipment dependent).
Check the humidifier operation.
Operation time too long See The device does not cool
anymore
Product is blistered Inadequate dough hold Use fresh dough
Reduce hold temperature
Baking defect Reduce oven steam
Product sticks Dough is too soft. Use stiffer dough
Excess humidity Reduce the humidity setting
(equipment dependent).
The temperature regulator Defective connection or probe, Check the connections, change
displays: “PR1” parameter P0 the probe, modify the value P0
Automatic control system plate Defective connection or Check connections, change
displays AL1 temperature probe probe
Automatic control system plate Defective hot safety thermostat Check the set temperature
displays AL2 Check plate parameters
Automatic control system plate Defective connection or 4- Check connections, change
displays AL 20mA humidity probe probe
Day and time display flashing Power shortage in excess of
Press the key and check the
15 minutes during a proofing
products
cycle
To select a parameter
• Press either the or key to scroll through the parameter titles.
To modify a parameter
• Press the key once to display the parameter value
• Press either the or key to modify the parameter value
• Press the key once to return to the parameter title.
Note: The equipment will go back to its normal operational state if the keys are not used for 15 seconds.
To select a parameter
• Press either or once to scroll through the parameter titles.
To modify a parameter
• Press the key once to display the parameter value
• Press either or once to modify the parameter value
• Press the key once to return to the parameter title.
Note: The equipment will go back to its normal operational state if the keys are not used for 15 seconds.
To select a parameter
• Press either or once to scroll through the parameter titles.
To modify a parameter
• Press the key once to display the parameter value
• Press either or once to modify the parameter value
• Press the key once to return to the parameter title.
Note: The equipment will go back to its normal operational state if the keys are not used for 15 seconds.
Page 24
02.2008 - 01429782.1 - AFV . AFB series
6.4 – REFRIGERATION regulator parameters of the simple electronic control panel
Reference Mini. Maxi. Unit Factory Description – EVK211 - Proofing
SP r1 r2 °C/°F (1) 02.0 Set point
Reference Mini. Maxi. Unit Factory Set point – EVK211 - Proofing
CA1 -25 25 °C/°F 0.0 Probe calibration
P0 0 1 - 1 Probe type: 0=PTC, 1=NTC
P1 0 1 - 1 Display of one decimal: 0=NO, 1=YES
P2 0 0 - 0 Measurement unit: 0=°Celsius, 1=°Fahrenheit (2)
P5 0 1 - 0 Quantity viewed: 0=T° inside, 1=Set point
Reference Mini. Maxi. Unit Factory Regulator - EVK211 - Proofing
r0 0.1 15 °C/°F 2.0 Set point differential
r1 -99.0 r2 °C/°F -6.0 Minimum set point
r2 r1 99.0 °C/°F 40 Maximum set point
r3 0 1 °C/°F 0 Locking of the set point modification: 1=YES, “Keyboard locking and unlocking
procedure”
Reference Mini. Maxi. Unit Factory Compressor protection – EVK211 - Proofing
C0 0 240 min 0 Delay of the compressor on starting the device
C1 0 240 min 0 Minimum time between two activations of the compressor and delay after probe
fault (3)
C2 0 240 min 2 Minimum compressor shut-down time
C3 0 240 s 0 Minimum compressor operating time
C4 0 240 min 15 Compressor stoppage time during probe fault
C5 0 240 min 5 Compressor operating time during probe fault
Reference Mini. Maxi. Unit Factory Defrosting – EVK211 - Proofing
d0 0 99 H 0 Defrosting interval: 0=WITHOUT defrosting (see d8) (5)
d3 0 99 min 30 Defrosting duration
d4 0 1 - 0 Defrosting after starting the device: 1=YES
d5 0 99 min 0 Defrosting delay at start-up only if d4=1
d6 0 1 - 1 Display during defrosting: 0=Device temperature, 1=if the device temperature is
less than the “set point +r0”: display of the set point +r0 – if the temperature is
above the “set point +r0”: Display of the device temperature on activation of
defrosting. (6)
d8 0 1 - 0 Type of counting of the defrosting interval d0: 0=operating time of the device,
1=operating time of the compressor.
Reference Mini. Maxi. Unit Factory Temperature alarms – EVK211 - Proofing
A1 -99.0 99.0 °C/°F -1.0 Value of the low temperature alarm
A2 0 2 - 0 Type of low temperature alarm: 0=WITHOUT, 1=set point –A1, 2=value of A1
(4)
A4 -99.0 99.0 °C/°F 15.0 Value of the high temperature alarm see A5 (4)
A5 0 2 - 0 Type of high temperature alarm: 0=WITHOUT, 1=set point +A4, 2=value of A4
A6 0 240 min 120 Delay of the high temperature alarm on device start-up
A7 0 240 min 30 Delay of the temperature alarm
A8 0 240 min 30 Delay of the high temperature alarm after defrosting (7)
Reference Mini. Maxi. Unit Factory Serial Network (MODBUS) – EVK211 - Proofing
LA 1 247 - 247 Device address
Lb 0 3 - 2 Baud Rate 0=2.400 – 1=4.800 – 2=9.600 – 3=19.200 baud
LP 0 2 - 2 Parity 0=none, 1=odd, 2=even
Reference Mini. Maxi. Unit Factory Reserved – EVK211 - Proofing
E9 0 1 - 1 Reserved
Page 25
02.2008 - 01429782.1 - AFV . AFB series
6.5 – Parameters of the Holding timer of the simple electronic control panel
Reference Mini. Maxi. Unit Factory Timer – EVK712 - PROOFING cabinet and room
t1 00:00 (1) (2) 00:00 Duration of the first time t1
t2 00:00 (1) (3) 00:00 Duration of the second time t2 (not visible if device code = 3 or 4)
t3 00:00 (1) (4) 00:00 Duration of the third time t3 (not visible if the device code = 1, 2, 3, 4 or 10)
t4 00:00 (1) (5) 00:00 Duration of the fourth time t4 (visible if device code = 7 or 8)
t5 00:00 99:59 min:s 00:00 Buzzer activation duration (not visible if device code = 4 or 9)
t6 00:00 99:59 min:s 00:00 Time between buzzer activation and stopping of the last load (not visible if the device
code = 3, 4 or 9)
t7 0 2 - 2 Time base duration t1 (0 = s:ds, 1 = min:s, 2 = h:min) (6)
t8 0 2 - 2 Time base duration t2 (not visible if device code = 3 or 4) (0=s:ds, 1=min:s, 2=h:min)
(6)
t9 0 2 - 2 Time base duration t3 (not visible if device code = 1, 2, 3, 4 or 10) (0=s:ds, 1=min:s,
2=h:min) (6)
t10 0 2 - 2 Time base duration t4 (visible if device code = 7 or 8) (0=s:ds, 1=min:s, 2=h:min) (6)
t11 0 2 - 0 Event that causes starting of the counting (not visible if device code = 3), 0=pressing the
START key or activating the start input
1=pressing the START key, 2=activating the start input
t12 0 2 - 0 Event that causes stopping of the counting (not visible if device code = 3 or 10) (8)
0=pressing the STOP key or activating the stop input, 1=pressing the STOP key,
2=activating the stop input
t13 0 2 - 0 Start input contact type (0=NO (input activated with contact closed), 1=NF (input
activated with contact open)
t14 0 2 - 0 Stop input contact type (0=NO (input activated with contact closed), 1=NF (input
activated with contact open)
t15 0 2 - 0 Counting type, 0=countdown - 1=counting
t16 0 3 - 3 Display colour (0=green, 1=red, 2=green when the loads are off and red when the loads
are illuminated, 3=red when the loads are off and green when the loads are illuminated)
t17 0 2 - 0 Action caused by events established with parameters t11 and t12 when the counting is in
progress (not visible if device code = 3)
0=the event established parameter t12 will suspend the counting and the event
established parameter t11 will reinitialise it, 1=the event established parameter t12 will
suspend the counting and the event established parameter t11 will reinitialise it
2=the event established parameter t12 will suspend the counting and the event
established parameter t11 will resume
t18 0 1 - 0 Cyclic operation (visible if device code = 2, 5 or 8) (1=yes)
t19 00:00 (1) (7) 00:00 Duration between activation of load 2 and stopping of load 1 (visible if device code = 5 or
6)
t20 0 1 - 0 Holding of the modification of parameter t1 (with the indicated procedure paragraph
4.3), 1=yes
t21 0 1 - 0 Holding of the modification of parameter t2 (with the indicated procedure paragraph 4.3;
not visible if device code = 3 or 4), 1=yes
t22 0 1 - 0 Holding of the modification of parameter t3 (with the indicated procedure paragraph 4.3;
not visible if device code = 1, 2, 3 or 4), 1=yes
t23 0 1 - 0 Holding of the modification of parameter t4 (with the indicated procedure paragraph 4.3;
visible if device code = 7 or 8), 1=yes
t24 0 1 - 1 Load state 1 during a counting suspension, counting that is executed when the load is
active (not visible if device code = 3 or 4) 0=off – 1=on
t25 0 1 - 1 Load state 2 during a counting suspension that is executed when the load is on (not
visible if device code = 1, 2, 3, 4 or 9) 0=off – 1=on
t26 0 1 - 3 Operation of the device when the power returns after an interruption that occurs when
the counting is in progress
0=the counting will be interrupted, 1=the counting will be interrupted, the display will
flash and the buzzer will be activated, 2=the counting will resume at the end of the time
during which the power supply interruption has occurred, the display will flash and the
buzzer will be activated (9)
3=the counting will resume from the moment when the power supply interruption
occurred (with a maximum error of 10 min), the display will flash and the buzzer will be
activated (9) (10)
t27 --:-- 15:00 min:s 00:01 Buzzer on restoration of power after power shut-down during countdown
-- :-- = continuously except if pressing the key, 00:01 to 15:00 = rings from 1s to 15min
t28 00:00 99:59 min:s 00:10 Activation time of output 2, linked to parameters t29, t30 and t31. (visible only if
CFG=10)
t29 00:00 99:59 min:s 00:40 Idle time of the load output 2, linked to parameters t28, t30 and t31. (visible only if
CFG=10)
t30 0 1 - 1 Dependence between the status of the load output 1 and the operation of the load output
2; linked to parameters t28, t29 and t31 (visible only if CFG=10).
0=no dependence: The load output 2 flashes as soon as the timer is powered on only if
the stop input is activated.
1=slaved: The load output 2 flashes as soon as the timer is powered on only if the load
output 1 is deactivated and if the stop input is activated.
t31 0 1 - 1 Activation of the flashing of load output 2, linked to parameters t28, t29 and t30. (visible
only if CFG=10); 1=YES, make the flashing of load output 2 active.
Reference Mini. Maxi. Unit Factory Serial Network (MODBUS) - EVK712 - PROOFING cabinet and room
LA 1 247 - 247 Device address
Lb 0 3 - 2 Baud Rate 0=2.400 – 1=4.800 – 2=9.600 – 3=19.200 baud
LP 0 2 - 2 Parity 0=none, 1=odd, 2=even
Reference Mini. Maxi. Unit Factory Reserved- EVK712 - PROOFING cabinet and room
E9 0 1 - 1 Reserved
Reference Mini. Maxi. Unit Factory Operation - EVK712 - PROOFING cabinet and room
CFG 1 (11) - 10 Operating code of the device (13)
Page 26
02.2008 - 01429782.1 - AFV . AFB series
6.6 – HEATING regulator parameters of the simple electronic control panel
Reference Mini. Maxi. Unit Factory Description – EVK412 - Proofing
SP1 r1 r2 °C/°F (1) 18 First set point
SP2 r7 r8 °C/°F (1) 0.0 Second set point – If CFG = 1: offset of the load output 2 with respect to the
first set point
Reference Mini. Maxi. Unit Factory Set point – EVK412 - Proofing
CA1 -25 25 °C/°F 0.0 Probe calibration
P0 0 1 - 1 Probe type: 0=PTC, 1=NTC
P1 0 1 - 1 Display of one decimal: 0=NO, 1=YES
P2 0 0 - 0 Measurement unit: 0=°Celsius, 1=°Fahrenheit (2)
P5 0 1 - 0 Quantity viewed: 0=Probe temperature, 1=Set point
Reference Mini. Maxi. Unit Factory Regulator – EVK412 - Proofing
r0 0.1 99.0 °C/°F (1) 2.0 If CFG = 1 or 2, first set point differential
If CFG = 3, differential of the load that operates in refrigeration (load 1)
r1 -99.0 r2 °C/°F (1) 1.0 Minimum programming of the first set point
r2 r1 (3) °C/°F (1) 40.0 Maximum programming of the first set point
r3 0 1 - 0 Holding of the first set point modification: 1=YES, 0=NO “Keyboard locking and
unlocking procedure”
r5 0 1 - 1 If CFG = 1 or 2, operation for refrigeration or for heating of the load1 output
If CFG = 3, operation for refrigeration or for heating of load1 and load2
outputs
0=for refrigeration, 1=for heating
r6 0.1 99.0 °C/°F (1) 2.0 If CFG = 1 or 2, second set point differential
If CFG = 3, differential of the output that operates in heating
r7 -99.0 r8 °C/°F (1) 1.0 Minimum programming of the second set point
r8 r7 (3) °C/°F (1) 40.0 Maximum programming of the second set point
r9 0 1 - 0 Holding the modification of the second set point:1=YES, “Keyboard locking and
unlocking procedure”
r10 0 1 - 0 If CFG = 1 or 2, operation for refrigeration or for heating of the load2 output,
0=for refrigeration, 1=for heating
r11 1.0 (3) °C/°F (1) 1.0 If CFG = 3, value of the neutral zone distributed on each side of the set point
If CFG = 4, value of two levels
Reference Mini. Maxi. Unit Factory Protection of outputs – EVK412 - Proofing
C1 0 240 min 0 Minimum time between two activations of the load1 output and delay after a
probe fault (3)
C2 0 240 min 0 Minimum stopping duration of the load1 output and delay upon powering on of
the load1 output
C3 0 240 s 0 Minimum operating duration of the load1 output
C6 0 1 - 0 Activate the load1 output during a probe fault, 0=no, 1=yes
C7 0 240 min 2 Minimum time between two consecutive start-ups of the load2 output and delay
of the out 2 output after end of ambiance probe error (4)
C8 0 240 min 0 Minimum time for load 2 stopping; delay as well
load 2 after starting the device
C9 0 240 s 0 Minimum operating duration of the load2 output
C10 0 1 - 0 Activity of the load2 output during the ambiance probe error
0=no (off), 1=yes (on)
Reference Mini. Maxi. Unit Factory Temperature alarms – EVK412 - Proofing
A1 -99.0 (3) °C/°F (1) 0.0 Value of the 1st temperature alarm see A3 (5)
st
A2 0 240 min 0 Delay of the 1 temperature alarm
st
A3 0 4 - 0 Type of the 1 temperature alarm: 0=WITHOUT alarm, 1=low(=A1),
2=high(=A1), 3=1st set point–A1, 4=1st set point+A1
A4 0 240 min 0 Temperature alarms delay after modification of an independent set point
A5 -99.0 (3) °C/°F (1) 45.0 Value of the 2nd temperature alarm see A7 (5)
A6 0 240 min 15 Delay of the 2nd temperature alarm
A7 0 4 min 2 Type of the 2nd temperature alarm: 0=WITHOUT alarm, 1=low(=A5),
nd nd
2=high(=A5), 3=2 set point–A5, 4=2 set point+A5
Reference Mini. Maxi. Unit Factory Serial Network (MODBUS) – EVK412 - Proofing
LA 1 247 - 247 Device address
Lb 0 3 - 2 Baud Rate 0=2.400 – 1=4.800 – 2=9.600 – 3=19.200 baud
LP 0 2 - 2 Parity 0=none, 1=odd, 2=even
Reference Mini. Maxi. Unit Factory Reserved – EVK412 - Proofing
E9 0 1 - 1 Reserved
Reference Mini. Maxi. Unit Factory Operation – EVK412 - Proofing
CFG 1 4 - 1 Operation: 1=the 1st set point is independent
and the 2nd one is relative to the 1st, 2=two independent set points, 3=neutral
zone, 4=two levels
Page 27
02.2008 - 01429782.1 - AFV . AFB series
6.7 – Control panel, automatic control system board
The electronic plate is parameterizable. Only qualified or authorised persons may access this menu.
Upon commissioning, the automatic control system plate lights up completely (initialisation) and beeps. It is
going in idle state: it only displays the current day and time (standby).
Press and keep depressed for 10 seconds the and keys: The name of the parameter appears on the
"hot” temperature display and its value appears on the minutes display.
P1 as well as its
value are
displayed.
To modify a parameter
To select a parameter
• To go to the next parameter press the key once below the Px display.
• To go to the previous parameter press the key once below the Px display.
Note: The device returns to its normal operational state if no keys are pressed for more than 2 minutes.
Page 28
02.2008 - 01429782.1 - AFV . AFB series
6.8 – Parameters of the automatic control system control panel
UNIT Mini. Maxi. Reference Factory Description
None 0 1 P1 0 Temperature unit: 0=°Celsius / 1=°Fahrenheit
None 0 1 P7 0 Cold group ventilation control during a complete programmed cycle (only during the
hold phase): 0=NO - 1=YES
None 0 1 P8 0 Heat resistance ventilation control during a complete programmed cycle (only during
the proofing phase): 0=NO - 1=YES
°C / °F 0 50 P9 2 Set point and cold switching differential (hold phase)
Second 0 300 P 13 0 Compressor stop delay between ON / OFF at the compressor stop
None 0 1 P 20 0 Water injection activation only if resistances line 10 are activated:: 0=NO - 1=YES
Second 0 31 P 24 0 HR probe default “AL3” activation: 0=deactivated – (1…240min) alarm “AL3” after 1
to 240 minutes.
°C / °F - 50 150 P 25 0 Minimum Proofing Temperature
°C / °F - 50 150 P 29 2 Minimum temperature measured by the probe before blocking the humidity system
(line 10 and 8)
Second 0 120 P 30 10 Line 10 activation time when the moisture sensor is activated – electro-valve water
supply
Minute 0 99 P 31 20 Line 10 idle time when the moisture sensor is activated – electro-valve water supply
None 0 1 P 35 1 Allow humidification in hold phase during a programmed cycle: 0=NO - 1=YES
None 0 1 P 40 0 Ventilation operation in constant low speed as per P 19: 0=NO - 1=YES
None 0 3 P 44 1 Auto. Baking day advance: P44=0(deactivated) – P44=1(activated for all programs)
– P44=2(activated only for P1+P2+P3) – P44=3(activated only for prg 4 arrows)
Page 29
02.2008 - 01429782.1 - AFV . AFB series
Warranty
Our full warranty (parts and labour) covers a period of one year from the date of availability of the material. It is
strictly limited to the replacement of original parts, found to be defective because of components or
manufacturing defects.
Consumable equipment, windows, light bulbs, fluorescent lamps, layer cloth and all accessories in general are
excluded from the present warranty.
The warranty does not cover the consequences of bad foundations work, or adaptation of the premises, or
connections (water, electricity, heating fluid, earth connection), or consequences of any error of handling or
monitoring of the equipment.
Finally, it is formally mentioned that it becomes completely void and in all cases where modifications have been
introduced after installation and outside the company or when work has been done on the equipment under the
same conditions.
In case of incident with the warranty in effect, do not dismantle anything. Consult your retailer, mentioning the
type and serial number of the concerned equipment.
Any intervention that could prevent an inspection by our inspection departments or those of our suppliers, can
release us of all responsibility.
Indeed, rising dust during flour handling is one of the causes of the different forms of rhinitis or even worse,
different types of asthma.
Below are some recommendations to limit flour dust creation as much as possible in the bakery:
There are other dusty substances that can be harmful or dangerous to the operator health; consult the raw
material supplier information to this effect.
Page 30
02.2008 - 01429782.1 - AFV . AFB series
Declaration of conformity
• Acoustic characteristics:
• Food hygiene:
- The device is built with materials complying with guides of CNEVA/ LERPAC – food hygiene
The surfaces of the food areas are smooth and easily cleanable. Use cleaning products that have been
approved for food hygiene and follow their operating instructions as well as the cleaning instructions in these
instructions.
In accordance with the regulations in force, this symbol indicates that the product must not be
discarded with domestic waste.
The device will have to be placed at a suitable collection point for its treatment, reprocessing and recycling. This
gesture for the environment will contribute to the preservation of natural resources and protection of health.
Page 31
02.2008 - 01429782.1 - AFV . AFB series
Wiring diagrams
Page 32
02.2008 - 01429782.1 - AFV . AFB series
10.1.1 – Electromechanical Control panel, Connection principle
Page 33
02.2008 - 01429782.1 - AFV . AFB series
10.2 – Automatic control system control panel, Developed diagram
Page 34
02.2008 - 01429782.1 - AFV . AFB series
10.2.1 – Automatic control system Control panel, Connection principle
Page 35
02.2008 - 01429782.1 - AFV . AFB series
Nomenclatures – Exploded views
Number of parts
Code Article
Item code
01428778
01427563
01427565
01428806
01428805
W0002006
W0000261
W0001428 01428870
Page 37
02.2008 - 01429782.1 - AFV . AFB series
11.2.1 – Refrigerating platform references
Page 38
02.2008 - 01429782.1 - AFV . AFB series
11.3 – Accessories, generic overview
Item code
D
E
01414616
01414615
01428522
Page 39
02.2008 - 01429782.1 - AFV . AFB series
11.3.1 – Accessory references, generic overview
Page 40
02.2008 - 01429782.1 - AFV . AFB series
11.4 – Electro mechanical control panel
Number of parts
Page 41
02.2008 - 01429782.1 - AFV . AFB series
11.5 – Automatic control system Control panel
Number of parts
Notes
Page 42
02.2008 - 01429782.1 - AFV . AFB series
Notes
Page 43
02.2008 - 01429782.1 - AFV . AFB series
02.2008 - 01429782.1 - AFV . AFB series
02.2008 - 01429782.1 - AFV . AFB series