U.S. Data Date: 11/3/2010
4/21/2011 60 Hz 480/277 V
Nunavut Government STAR
Arivat RO Water Systems 85.0F
0.0 Ft. A.S.L
C15 EPA T2
TA ELEC
INLINE - 6 ATAAC
928 Cubic Inch / 15 Liter 10,066 BTU/min
1800 RPM 5,687 BTU/min
33.4 gph 3,839 BTU/min
0 dBA at 23 ft/7 m 6,483 BTU/min
0 dBA at 23 ft/7 m 25,079 BTU/min
115.7 F 13,933 BTU/min
1,299.6 cfm 922 F
118.4 F 3,528 cfm
29,028.7 cfm 0in
DM8154
2351211 CLASS H
LC / LC6114F 105 C
0.6667 1,478.6 BTU/min
4 *** / 684.4
SE / RANDOM 0.4300
* Based on 1/2 inch water (0.12 kPa) external restriction and 1000 ft (300m) altitude.
** Based on instantaneous voltage dip as defined per NEMA MG-1.
*** See your Caterpillar dealer and/or Spec Sheet for technical information.
Maximum voltage distortion due to non-linear load calculated to be within specified limits.
Overall dimensions and weight not to be used for installation. Contact your Caterpillar dealer for specific dimension drawings.
Caterpillar makes no express warranties and disclaims all implied warranties including merchantability and fitness for a particular purpose regarding program. Caterpillar shall have no
liability in law or equity for damages consequential or otherwise arising from use of program and related material or any part thereof. The analysis provided from SpecSizer is only for the
expected results at the generator terminals. Analysis of transient conditions of any device downstream is the responsibility of the system designer.
C
Version: 2.6.0
455.0 EkW / 568.8 kVA 60 Hz Prime, 480/277V, C15 ATAAC EPA T2, LC6114F SE LC RANDOM, R448 1:1 slope
The selected representative generator set was factory tested in accordance to NFPA Voltage Dip
110 block load step capability and acceptable frequency and voltage response on load
addition and rejection.
0 4.4
Recovery Time (sec)