4/21/2011 60 Hz 480/277 V
Nunavut Government STAR
Arivat RO Water Systems 85.0F
0.0 Ft. A.S.L

417.6 SkVA 150.2 SkW


707.1 SkVA 469.6 SkW
507.8 kVA 453.5 kW 0.89 PF
0.0 RkVA
507.8 kVA 453.5 kW

(1) of C15 455.0 kW / 568.8 kVA


R448, 1:1 slope 0.8 PF
C15DE6X 455.0 kW / 568.8 kVA
Diesel Prime
8,555.0 lbs
148.6in / 43.7in / 82.3in

370 < 5.0 < 5.0 <3


833 < 5.0 6.5 <3
1,429 11.8 9.5 <3
1,795 24.4 20.4 4.4

C15 EPA T2
TA ELEC
INLINE - 6 ATAAC
928 Cubic Inch / 15 Liter 10,066 BTU/min
1800 RPM 5,687 BTU/min
33.4 gph 3,839 BTU/min
0 dBA at 23 ft/7 m 6,483 BTU/min
0 dBA at 23 ft/7 m 25,079 BTU/min
115.7 F 13,933 BTU/min
1,299.6 cfm 922 F
118.4 F 3,528 cfm
29,028.7 cfm 0in
DM8154

2351211 CLASS H
LC / LC6114F 105 C
0.6667 1,478.6 BTU/min
4 *** / 684.4
SE / RANDOM 0.4300

X"d 0.1049 0.0425 T'd0 1.9300


X"q 0.1395 0.0565 T'd 0.1000
X'd 0.1506 0.0610 T"d0 0.0130
Xd 2.9087 1.1783 T"d 0.0100
Xq 1.7448 0.7068 T"q0 0.1250
X2 0.1217 0.0493 T"q 0.0100
X0 0.0091 0.0037 TA 0.0150

* Based on 1/2 inch water (0.12 kPa) external restriction and 1000 ft (300m) altitude.
** Based on instantaneous voltage dip as defined per NEMA MG-1.
*** See your Caterpillar dealer and/or Spec Sheet for technical information.
Maximum voltage distortion due to non-linear load calculated to be within specified limits.
Overall dimensions and weight not to be used for installation. Contact your Caterpillar dealer for specific dimension drawings.

Caterpillar makes no express warranties and disclaims all implied warranties including merchantability and fitness for a particular purpose regarding program. Caterpillar shall have no
liability in law or equity for damages consequential or otherwise arising from use of program and related material or any part thereof. The analysis provided from SpecSizer is only for the
expected results at the generator terminals. Analysis of transient conditions of any device downstream is the responsibility of the system designer.

C
Version: 2.6.0

Data Date: 11/3/2010

4/21/2011 Prime 85 Deg. F


Nunavut Government Diesel 0.0 Ft. A.S.L
Arivat RO Water Systems 60 Hz 480/277 V

Load Transient Resultant Cumulative


Load Description Frequency Voltage Frequency Voltage Running Fdip Vdip 1 Vdip 2
Step Inrush Peak Running
SkVA SkW kVA kW SkVA SkW kVA kW

<5.0% 7.0% <5.0%


1.1 1 40.00 HP - Intake Pump
NEMA, Centrifugal Pump, Across the line, 30% 30% 212.0 82.7 37.7 32.8
Loaded
1.2 1 67.50 kW - Misc Loads
Miscellaneous Load, 3-Phase 30% 30% 75.0 67.5 75.0 67.5

<5.0% <5.0% <5.0%


2.1 1 20.00 HP - System Pressure Pump
NEMA, Centrifugal Pump, Across the line, 30% 30% 106.0 47.7 19.7 16.6
Loaded

<5.0% 10.6% <5.0%


3.1 1 200.00 HP - High Pressure Pump
NEMA, Centrifugal Pump, Soft Starter, 30% 30% 396.6 103.1 176.3 158.7
225% Current Limit
Load Transient Resultant Cumulative
Load Description Frequency Voltage Frequency Voltage Running Fdip Vdip 1 Vdip 2
Step Inrush Peak Running
SkVA SkW kVA kW SkVA SkW kVA kW

<5.0% <5.0% <5.0%


4.1 1 20.00 HP - System Pressure Pump
NEMA, Centrifugal Pump, Across the line, 30% 30% 106.0 47.7 19.7 16.6
Loaded

<5.0% 11.1% <5.0%


5.1 1 200.00 HP - High Pressure Pump
NEMA, Centrifugal Pump, Soft Starter, 30% 30% 396.6 103.1 176.3 158.7
225% Current Limit
5.2 1 3.00 HP - Motor - NEMA
NEMA, Centrifugal Pump, Across the line, 30% 30% 22.6 13.8 3.5 2.7
Loaded

Maximum Step Maximum Peak Final Running


SkVA SkW SkVA SkW kVA kW
417.6 150.2 707.1 469.6 507.8 453.5
Price List: Version: 2.6.0
U.S. Data Date: 11/3/2010

Permitted - 30.0% Permitted - 30.0%


Predicted - <5.0% Predicted - 11.1%
Synchronous (Vdip 1) - 11.1% Frequency Dip
Frequency-induced (Vdip 2) - <5.0%
Voltage Dip

Fdip: Vdip 1: Vdip 2:

<5.0% 11.1% <5.0%

455.0 EkW / 568.8 kVA 60 Hz Prime, 480/277V, C15 ATAAC EPA T2, LC6114F SE LC RANDOM, R448 1:1 slope

< 5.0 < 5.0 <3


< 5.0 6.5 <3
11.8 9.5 <3
24.4 20.4 4.4
Frequency Dip

The selected representative generator set was factory tested in accordance to NFPA Voltage Dip
110 block load step capability and acceptable frequency and voltage response on load
addition and rejection.

0 4.4
Recovery Time (sec)