'ĞŶĞƌĂƚŽƌZĂƟŶŐ 300 MW
neutral grounding transformer to limit the stator earth Terminal Voltage 20 KV
fault current within 5 to 10 Amps. When single-phase
earth fault occurs close to the generator neutral, the ƌŽŬĞŶĞůƚĂWdZĂƟŽ ¥/ (.11/3) kV
driving voltage will be low, and hence the value of E'dƌĂƟŽ 20 /0.220 kV
fault current will also be extremely less. For faults in EdZĂƟŽ 5/5 Amp
the last 5% of the winding from star point, the earth
fault current is too low that it cannot be detected by Load Resistor 0.45 ohm
protective relay and hence it is YHU\ GLIÀFXOW WR GHWHFW Table-1
stator earth fault through current based protection.
Therefore single-phase earth fault of stator winding Stator Earth Fault Current in Solidly Grounded System-
can be protected by using voltage-based protections The earth fault current value depends on voltage level and
(Residual over voltage or Neutral voltage displacement) fault resistance. For example 20kV generator is solidly
or by third harmonic voltage protection function. There grounded, and if single-phase earth fault occurred, then
are different philosophies used for detecting earth fault fault current will be-
in stator winding. In this paper we are showing most
common used philosophies, its setting calculation and Vph
If
interlock. R
June 2020 67
TechSpace
Z1 = 3719.0 Ohm
Ie = 3.10 Amp
So, when there is earth fault at 5% of the winding, this
current will be extremely less and hence stator earth Figure-2. Vector Diagram Of Normal And Faulted System
fault is detected by using voltage-based concept.
Note – Table -1 data is used for setting calculation of all Operation Criteria for relay -
philosophies. Relay will give trip command when neutral displacement
voltage is greater than setting value.
Philosophy - 1 V0 > Setting Value
Where,
Residual Voltage of Generator Neutral Point- V0 is the measured neutral displacement voltage.
20kV
Vng
3
Vng 11.55kV
Considering 95 % of the winding to be protect, then
Figure-1. Connection Diagram for Residual Voltage of voltage appeared across 5 % of the winding from
Generator Neutral Point neutral point will be-
On a healthy three-phase power system, the addition
5 % of Vng = 0.5775 kV
of each of the three-phase to earth voltage is nominally
zero, as it is the vector addition of three balanced As relay is measuring voltage across NGT secondary
vectors at 120° to one another.
However, when an earth fault occurs on the primary 20kV 0.5775kV
220 V sec.
68 June 2020
TechSpace
Setting Calculation-
Please refer Table -1 Data
We know that, Figure-5. Trip logic for philosophy-3
When there is earth fault occur on terminal of winding, Setting Values-
then Generator Zero Sequence Voltage at Terminal is
V0 - 6.0 Volts
equal to Generator Neutral point Voltage and voltage
developed across open delta VT will be hence 3 times Ǽ9 – 5.0 Volts
the zero sequence voltage. Note - Setting Calculation has been already done in
So, according to above statement- philosophy -1 & 2.
Vng = Vo
Philosophy-4
Ǽ9 9R 9QJ
N9
Residual Voltage of Generator Terminal Point and
Ǽ9 N9 neutral point current
As per the setting consideration for 95 % of winding to When generator is directly connected to bus bar, it
be protect, open delta voltage will be- VHHPV GLIÀFXOW WR GLVWLQJXLVK EHWZHHQ D JULG HDUWK
RIN9 N9 fault and a generator earth fault by only measuring
June 2020 69
TechSpace
Philosophy-5
Third Harmonics voltage ratio measurement of
Generator Neutral & Terminal point
Generator during normal running operation naturally
generates third harmonic currents due to imperfection
Figure-6. Connection Diagram for Combination of Residual in stator windings, pitch of the stator windings and
Voltage & Earth Fault Current YDULDWLRQ LQ DPRXQW RI ÀHOG H[FLWDWLRQ 7KH YROWDJHV
developed due to third harmonic currents are used in
Operation criteria for relay- protection of stator winding earth fault.
7KLUGKDUPRQLFYROWDJHSURÀOHLQKHDOWK\FRQGLWLRQDQG
fault condition are shown below-
Setting Values-
IE Setting - 155 mA
Ǽ96HWWLQJ9%URNHQ'HOWDYROWDJH
Setting Calculation-
70 June 2020
TechSpace
backup to 100% stator earth fault. Figure-11. Trip Logic for Post Sync Condition
Relay will generate alarm when the ratio of third Also 3rd harmonic voltage ratio can be club along with
harmonics voltage at neutral point to generator terminal any philosophy, which provides additional backup to
is greater than its Pre Sync or Post Sync ratio setting. 95% or 100% of stator earth fault protection.
Note- Pre Sync/Post Sync setting can be made active REFERENCE
by taking GCB position contact feedback.
1 Dr K Rajamani and Bina Mitra, (May 2013, IEEMA
Pre Sync Condition-
Journal, Page 76 to 80) stator earth fault protection
of large generator (95%)- part I
Vo
6 User Manual & Trouble shooting guide for
(3rd Harmonic
Content) Vo
>