Professional Documents
Culture Documents
P/N 000-940039-
Rev 0E
DANGER
Dispensers have both electricity and a hazardous, flammable and potentially explosive liquid. Fail-
ure to follow the below precautions and the Warning and Caution instructions in this manual may
result in serious injury. Follow all rules, codes and laws that apply to your area and installation.
Always make sure ALL power to the dispenser is turned OFF before you open the dispenser cabi-
net for maintenance. Physically lock, restrict access to, or tag the circuit breakers you turn off
when servicing the dispenser. Be sure to trip (close) the emergency valve(s) under the dispenser
BEFORE beginning maintenance.
Make sure that you know how to turn OFF power to the dispenser and submersible pumps in an
emergency. Have all leaks or defects repaired immediately.
Problems with the installation of this kit should be referred to Wayne Technical Support (1-800-
926-3737).
Danger indicates a hazard or unsafe practice which, if not avoided, will result in severe
DANGER injury or possibly death.
Warning indicates a hazard or unsafe practice which, if not avoided, may result in
WARNING severe injury or possibly death.
Caution indicates a hazard or unsafe practice which, if not avoided, may result in minor
CAUTION injury.
Installation/Operation
1 PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 INSTALLATION LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9 REQUIRED TOOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
10 INSTALLATION OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
11 INSTALLATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
11.1 Shutdown the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11.1.1 Sites with Wayne Dispensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11.2 Fusion Forecourt Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11.2.1 Logging on to the Fusion Forecourt Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11.2.2 Clear Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
11.2.3 Apply Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11.2.4 Language Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11.2.5 Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11.3 Payment Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
11.3.1 Payments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.3.2 Service Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.4 Pump Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11.4.1 Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11.4.2 Assign Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11.5 Veeder-Root BIR Installations with EDIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.6 Veeder-Root BIR Installations with CDIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.6.1 Connect the CABs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11.6.2 Connect the Dispensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.6.3 Programming the Fusion Forecourt Controller for Sites with Veeder-Root BIR . 31
11.7 Programming the Fusion Forecourt Controller for 3rd Party POS . . . . . . . . . . . . . . . . . 34
11.7.1 HyperPIB Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11.7.2 PAM Emulation™ Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.7.3 Save the Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
11.8 Connecting to the POS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
11.8.1 VeriFone Ruby, Topaz or Sapphire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
12.1 Fusion Forecourt Controller Rear Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
12.2 Fusion Forecourt Controller Rear Panel - Gilbarco CRIND. . . . . . . . . . . . . . . . . . . . . . . 72
12.3 Fusion Forecourt Controller Rear Panel - Console Configuration. . . . . . . . . . . . . . . . . . 73
12.4 Fusion Forecourt Controller Rear Panel - Tokheim Configuration . . . . . . . . . . . . . . . . . 73
12.5 Serial Port Pin-Outs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2 INTRODUCTION
The Wayne Fusion™ Forecourt Controller is a device capable of supporting existing peripheral devices that are cur-
rently supported through the HyperPIB. This manual explains how to install the Fusion forecourt controller and config-
ure it for use as a Console or with a Ruby Verifone POS or any other supported brand of POS.
NOTE: This kit may require installation of several wiring and hardware assemblies. Any installation or modification
must comply with the requirements of the National Electrical Code (NFPA 70), the Automotive and Marine
Service Station Code (NFPA 30A) and any other applicable codes
NOTE: You must wear a static wrist strap, part number 916962 or equivalent, securely attached to an earth ground,
when handling any circuit board, electronic component or assembly, or when reaching into the site
controller or dispenser computer enclosure. Do not use power tools.
1. Before opening any cartons, count the number of cartons and verify the carton count against the supplied
packing list.
2. Inspect the cartons for damage made during transit.
3. File claim information with the carrier on the bill of lading.
4. Retain cartons suspected of damage for future claim purposes.
NOTE: You must wear an anti-static wrist strap, part number 916962 when removing electronic components from
static packages. Attach the wrist strap securely to an earth grounding point to prevent possible damage
from static electricity.
5. Remove all equipment from the shipping cartons and carefully inspect for visible damage.
NOTE: Any damage should be brought to the attention of the carrier and claims made immediately. Return all
equipment to the respective cartons for protection until actual installation is made. Save all cartons until it is
certain that return shipments are not required.
1. Place electronic components in an anti-static bag and in the original shipping cartons for return shipment
to the factory.
NOTE: If original shipping cartons are not available use a sturdy cardboard container and suitable packing
materials such as anti-static polyethylene foam or bubble pack, to ensure the component is firmly packed.
2. Include a Return Parts Tag with the defective component describing the particular problem with the part.
3. Make sure adequate insurance is provided when returning parts to the factory.
WARNING
If the parts or components arrive at our factory in a damaged condition and it is determined that the dam-
age is a direct result of inadequate or improper packaging, the damage will not be covered under the origi-
nal warranty and the customer or distributor will be held responsible for the cost of repairs necessary to
correct or replace the damaged parts.
6 SAFETY INFORMATION
Read NFPA 30A and NFPA 70 (U.S. Installations)
Before installing the equipment, the installer must read, understand and follow this manual, NFPA 30A, NFPA 70, and
applicable federal, state and local codes and regulations. Failure to do so may adversely affect the safe use and
operation of the equipment.
For installation in Canada the installer must read and understand this manual, CSA C22.1 (Canadian Electrical Code)
and applicable federal, provincial and local codes and regulations.
NFPA30A require that an emergency power cutoff be installed. An emergency power cutoff is a single control that
removes AC power from all site fueling equipment and submersible pumps. Make sure the control is accessible,
labeled clearly, and installed away from dispensers. Make sure all station employees know where the Emergency
Power Cutoff is located and how to operate it.
Electrical Circuits
Some of the procedures in this manual involve removal and connection of components during installation or service.
Remove power from the distribution box before executing these procedures.
Low Voltage
Do not be misled by the term "Low Voltage". Voltage potentials as low as 50 volts may cause death under adverse
conditions.
High Voltage
High voltage of 110 volts AC is used for operation of this equipment. Death on contact may result if safety proce-
dures are not followed.
Conduits used must be ¾ in. and the length of each conduit can be up to 330 feet from the Fusion forecourt controller
to the dispenser. Verify that approved wireways and threaded metallic conduit with tight connections are used, that
Data Link wiring is #18 AWG 600 Volt oil and gasoline resistant as a minimum.
Environmental Requirements
Ensure that all cabinets are located in an area that offers easy access for service, and free air space for cooling, 6"
away from other cabinets.
Care should be taken to ensure that the temperature of the cabinets does not exceed the operational ranges of 0°C to
40°C (32°F to 104°F)
Preliminary Wiring
The site wiring must be completed before installation of a Fusion Forecourt Controller.
Two pairs of data link wires must be installed from each dispenser to the location of the Fusion forecourt controller
cabinet. One pair for pump communication and one pair for CAT communication.
Power Wiring
Confirm that all 120VAC to 240VAC wiring for outdoor equipment (line, neutral, relay select, etc.), is #14 AWG mini-
mum (unless local codes call for 12 gauge), stranded, oil and gasoline resistant.
One conduit from the breaker panel to a dedicated outlet located near the Fusion forecourt controller location is
required. The conduit must contain three 14 AWG wires; 110 to 240 VAC, Phase, Neutral and Ground. Do not use
electrical conduit to provide earth ground (earth ground does not exceed 5 ohms) The electrical wiring for the Fusion
forecourt controller dedicated outlet must be run through the Emergency Stop circuit at the site so that all electrical
The circuit powering the Fusion forecourt controller must not power other devices. This circuit must not share a con-
duit with wiring for devices drawing high amperage (compressor, freezer, etc.) or devices that are sources of RFI (TV,
microwave, intercom, etc.)
Data Wiring
Confirm that all data wiring for outdoor equipment (communication lines) is #18 AWG (minimum) stranded, oil and
gasoline resistant. Pump and CAT data wiring that attaches from the wiring trough to the Fusion forecourt controller
needs to be double insulated to satisfy NEC code for commercial use. Wayne recommends the use of the following
cable or equivalent for use as the pump and CAT communication wire for running between the wiring trough and the
Fusion forecourt controller.
Product Construction:
Conductor: 20 or 18 AWG fully-annealed, stranded tinned copper per ASTM B-33
Conductor/Strands: 16/30
Color Code: 1
UPC #: 079407700875
NOTE: Existing wiring that runs from the wiring trough out to the dispensers do not need to be modified since
those wires are protected within the wiring trough or conduit.
Codes
Confirm that all equipment is installed in accordance with the National Electrical Code (NFPA 70), the automotive and
Marine Service Station Code (NFPA 30A), and any other applicable State and local codes.
9 REQUIRED TOOLS
Refer to Table 3 for a list of tools required to install the Fusion forecourt controller.
Quantity Description
1 Small Channel Lock pliers
1 Wire Cutters
1 Wire Strippers
16 to 32 Wire Nuts
1 Volt Meter
1 Diagonal Cutters
1 Drill
10 INSTALLATION OVERVIEW
1 4”
1
F u sio n B o x
Earth Ground at
Electrical Panel
"
A C O u tle t
wired to Serial C a b l e t o P O S (pumps)
Emergency
Stop button
Serial C a b l e t o P O S (CATs) optional
A C P o w e r w irin g fo r F u sio n
Double Shielded
AC Pow er B r i c k Communications Wires
11 INSTALLATION PROCEDURE
When possible, mount the Fusion Forecourt Controller at a location on the back wall near where there is access to
the wiring trough where the dispenser comm wires are located. If the Fusion forecourt controller is going to be a
HyperPIB replacement then the location will be where the HyperPIB EC was located. The previous diagram shows a
typical placement of the Fusion forecourt controller.
NOTE: If mounting the Fusion forecourt controller to a concrete wall, you will need concrete bits and appropriate
mounting hardware.
NOTE: CAT data wires may have been bundled together in parallel within the wiring trough. Un-bundle the wire
pairs and splice extensions if needed so that each discrete CAT wire pair reaches the location of the Fusion
forecourt controller. Use double insulated wire specified in Section 8 for all exposed wiring from the wiring
trough to the Fusion forecourt controller.
Mounting
pins
Mounting
slots
Mounting
stud
Fusion mounting
bracket
NOTE: The green GRIB connectors for the Pumps (Current Loop) are located on the right-hand row of connectors
while the black GRIB connector for the Wayne CATs (RS485/422) is located on the left-hand row of
connectors. See Figure 12-1.
____ 5. Insert the green current loop GRIB plugs into the appropriate GRIB sockets on the rear panel of the Fusion
forecourt controller beginning with the plug for Pump #1, #2, #3 and #4. See Figure 12-10.
____ 6. Insert the black CAT GRIB plug into the GRIB socket on the rear panel of the Fusion forecourt controller.
See Figure 12-9.
NOTE: Make a note of where all of the pumps and CATs are connected.
NOTE: The Fusion forecourt controller units ship pre-configured for BIR functionality. BIR communication is
through the 4th port of the Current Loop GRIB. If BIR functionality is not needed then remove the resistor
from the GRIB plug that is in the 4th port.
____ 7. Connect CAT serial communications cable from the existing POS into the DB9 connector on the Serial-485
CAT GRIB. See Figure 12-8.
NOTE: The cable length for serial communications @ 9600 baud is officially 50 feet. However, tests have shown
that lengths 150 or 200 feet have been known to work.
____ 8. Connect pump serial communications cable from the Ruby system into the bottom Serial port on the back
of the Fusion forecourt controller [the CUPS board]. See Figure 12-8.
____ 9. Complete the wiring, secure the conduit, etc.
____ 10. Plug the power brick into the dedicated120VAC power outlet which has been wired into the Emergency
Stop button, then plug the other end into the transformer input of the Fusion forecourt controller.
11.2.5 Wizard
The Wizard is used to automatically set the most common pump programming settings when configuring a
Fusion forecourt controller. The Wizard will ask for equipment and site layout information and configure the
Fusion forecourt controller based on this input.
NOTE: When entering the Physical ID above you can optionally leave the value at zero, then use Learning Mode to
physically lift each nozzle of the dispensers one at a time to “learn” the ID and automatically enter the
value.
____ 14. Once all the hoses have been programmed click the Next button to continue, and the following window
will be displayed.
____ c. Select the Reboot Fusion button and the system will display:
The system will stop Fusion forecourt controller processes, shutdown the operating system and then reboot.
11.3.1 Payments
Log into the Web UI, Using Internet Explorer and navigate to Configuration > Generic > Payments.
11.4.1 Groups
Existing entry
Port 1
Port 2
Port 3
- Pin 4
Pin 3
BIR
+
Click Configuration
then select Generic
IMPORTANT: If the "Second Port" is not used, then the "Second Port Pump" MUST be set to '0'
then
____ 11. Select the Reboot Fusion button and the Fusion forecourt controller will display:
11.7 Programming the Fusion Forecourt Controller for 3rd Party POS
To access the Fusion forecourt controller programming screen, open an Internet Explorer session using a
laptop connected to the ethernet port.
____ 1. Change the IP address of the laptop to match the IP scheme on the Fusion forecourt controller so that a
connection can be made.
____ 2. Change your Subnet Mask to 255.255.255.0
____ 3. Start an Internet Explorer session.
____ 4. In the Explorer Address bar, type in 192.168.1.20 and press <enter>. The following Screen will then be
displayed.
Click Configuration
then select Generic
Click Search
NOTE: When configuring the Fusion forecourt controller in Console mode without connecting a 3rd pary POS, be
sure to disable both the HyperPIB module (see step 2 on page 35) and the PAM Emulation module (see step
2 on page 37). Skip to Section 11.7.3 on page 38 and complete the Fusion forecourt controller configuration.
Enabled
Serial Port
Baud Rate
Authorization
Timeout
POS
Configuration
NOTE: When setting up the HyperPIB Configuration then set the value for the PAM™ (Pump Access Module)
Emulator Communication Type to blank. See step 2 on page 37.
Submit button
Param Value
Submit button
Param Value
Submit button
Param Value
Submit button
Param Value
Submit button
Param Value
Figure 11-53 HyperPIB Programming Screen 5
____ 7. Skip to Section 11.7.3 to complete the configuration changes.
Communication
Type
Baud Rate
POS
Configuration
NOTE: When setting up the PAM Emulator be sure to set the HyperPIB Enabled option to 0-DISABLED. See step 2
on page 35
Submit button
Param Value
Figure 11-55 PAM Programming Screen 1
____ 3. Click Baud Rate to open the following window where you use the Param Value pull-down to set the baud
rate to match your POS. Click the Submit button to save. See the following window.
Submit button
Param Value
Param Value
Figure 11-57 PAM Programming Screen 3
Retries for
auth/preset
Param Value
then
NOTE: If the Fusion forecourt controller Console is used as a backup when the Ruby system is down, you must
disconnect the Ruby to Fusion forecourt controller communications cable so that sales don’t get sent to the
Ruby system.
____ 1. Connect a Null Modem cable from the POS pump communication port to the Fusion forecourt controller
HyperPIB POS connection.
____ 2. Connect a straight-though serial cable from the POS card reader communication port to the Fusion
forecourt controller Serial IN port on the CAT GRIB.
Define as
Tokheim-US
____ 1. Make sure all the Gilbarco pumps are isolated on their own channel.
NOTE: If you are connecting a BIR, then you must use the EDIM solution since the CDIM solution will not work with
this configuration.
____ 2. Program the pumps at the POS as if they were all Wayne pumps.
____ 3. After you have created your configuration with the option of “POS Config = YES”, then turn the setting off
( set to “NO” ).
____ 4. Next, from the Web UI, delete the Wayne pumps that are going to be the replaced with Gilbarco pumps.
NOTE: Pumps cannot be removed from the middle of the list. The Gilbarco pumps will need to be added/replaced
at the end of the list.
____ 1. Program the pumps from the Web UI as Gilbarco or Wayne pumps.
____ 2. Gilbarco physical fueling point addresses are limited to 16 unique addresses (typically ranging from 1-16).
Therefore, the first 16 Gilbarco fueling point addresses are connected to the first GRIB board. The
remainder of the Gilbarco fueling point addresses restart the numbering and are connected to the second
GRIB.
NOTE: When connecting up the dispensers to the GRIB boards, be sure that no two identical physical fueling point
addresses are connected to any one GRIB board.
____ 3. Wayne physical fueling point addresses range from 1-24. Therefore, the physical fueling point addresses
can go from 1-24 then repeat 1-8 for the 25th through the 32nd pump. This means that the Wayne
physical fueling points can cover 4 ports of the first GRIB board and 2 ports of the second GRIB board
before the addressing repeats.
____ 4. From the Web UI, the Gilbarco Pumps are addressed as 1-16 then start over again with 1-16.
____ 5. From the Web UI, the Wayne Pumps are addressed as 1-24 and then start over again with 1-8.
____ 6. Apply the Configuration.
• Create printer
• Configure Printer parameters
• Assigning the new printer to default POS (which has pos ID 0)
• Configuring Receipt layout
• Assigning Receipt Layout
• Apply the entire configuration to the Fusion forecourt controller
• Test configured printer from Fusion forecourt controller console.
11.12.6 Apply the Entire Configuration to the Fusion Forecourt Controller System
This is Final step in the process.
1. Go to POS > Configuration > Maintenance > Apply Configuration this will open a pop up window with
status.
• Site Number
• Site Name
• Site Address
• Country
• Currency
• Currency (Abbrev)
• Date Format
Pin 1 is
upper right
hand pin of
2x4 pin header
Pin 1 of ribbon
cable is the red
wire
BIR/EDIM DSM/GSM
Connection
CUPS
Board
DSM
Cable
Connect to DSM
BIR
Connection
Power USB
button ports HyperPIB Serial IN
POS Connection RS422/RS232
Transformer Requires Null Modem Requires Serial cable
Ethernet
input PN WU002402-0001 PN WU002401-0001
port
for POS Comm for CAT Comm
HyperPIB DB9
POS Connector Serial IN RS422/232
RCV LED CH 2
RCV LED CH 4
XMIT LED
RCV LED
OR
XMIT LED
RCV LED
CAT 1&2 CAT 3&4 CAT 5&6 CAT 7&8 CAT 9&10 CAT 11&12 CAT 13&14 CAT 15&16
-
Pump #1
+ Pin 1
Figure 12-12 GRIB Plug - Single Pump (Dispenser) Per Plug Configuration
- Pin 4
Pump #2
+
Pin 1
-
Pump #1
+
Figure 12-13 GRIB Plug - Two Pumps (Dispensers) Per Plug Configuration
- Pin 4
BIR
+
Pin 1
23
(OT .EUTRAL %ARTH
TO
$#"S
WU001421
WU001421
WU002708-0001
WU001274
WU001266 10P COM2
WU001258
10P COM3
WU001307
J17
Pwr
PS Section +5V LED
10P
CUPS PCB ASSY
C C
Battery
+24V LED
WU000995
USB1
BAT EN LED
Charger
PF LED
J13
4P 3P
J5 J7
USB AUX PWR
WU001269
SBC
J11
9P
J5
Reset
GRIB Current Loop
J16 LED1 Charge LED J21 Wayne/Gil 30/40 ma
WU001259
6P ACT DC IN 10P
COM1
J8
+24V LED
5P
J23
B
OUT 10P WU001259 2 DISPENSERS/CHNL B
J9 5P COM2
+24V 2-WIRE DSM/MSM/GSM
May 2016
2AMP +24V J6-J7 Ethernet J15 J1 J2 J3 J4
J6 2P
1-4 5-8 9-12 13-16
J10
Box
PWR TO +24V USB 6 USB 5 COM 2 COM 1
SW/LED GRN External OPTION OPTION
To POS
Not on PCB Supply
GSM
To Dispensers 1-16
Rev. 0E
TWO DISPENERS EACH
or
DSM/MSM
TO TOK 67 BOX
OR SECONDARY POS
LAN
OR Gil "G" BOX CAT 5 WIRE
P/N 000-940039
A A
Title
FUSION T/AA1Z0/x/x
Size Document Number R ev
B WU00***** X4
FUSION SYSTEM Date: Thursday, January 13, 2011 Sheet 1 of 1
5 4 3 2 1
84
5 4 3 2 1
KB1 6P J8 10P
WU001817 J7 10P LED2 LED1
8P USB5 & USB6 KYBD&Mouse Audio Activity Pwr
VGA
Top Bot
8P USB3 & USB4
(Heart
Beat)
8P
USB1 & USB2
D
SINGLE BOARD COMPUTER D
CN2 LINUX OS
RJ45 LAN2 2P 4P SATA2 EBX FORM FACTOR
NOVA ADAM
WU001261 WU001585
RJ45 LAN1
J2
WU002111 COOLER
10P COM1 CN1 2P 4P SATA1 PWR 4P
WU002708-0001
WU001266 10P COM2
10P COM3
10P 8P 10P
WU001421
WU001421
2P 3P 3P 3P 3P COM4
WU001274
J2 2P
7P
J3
J18 J19 J20 J22 J24 F_PANEL1 DIO1
WU001258
+24V
WU001307
+5V ,5AMP
Pwr
J17
C PS Section +5V LED C
+5V Out
10P
+24V LED
Battery
WU002192-0001
2P
J12
BAT EN LED
WU000995
Charger
USB1
PF LED
2P
J13
3P 2P 4P 3P
J7 J8 J5 J7
PWR DSM/MSM USB AUX PWR
WU001269
SBC
PWR C/10 LED Reset WU001850 WU000813
4P
9P
J11
J5
GRIB RS485, USB GRIB Current Loop
J16 LED1 Charge LED J21 (Serial GRIB) Wayne/Gil 30/40 ma
WU001259
6P ACT DC IN 10P
+24V LED COM1 4 CHNL
5P
J8
LED GIL/TOK 2 DISPENSERS/CHNL
OUT
2P
J23
B J14 10P WU001259 4 CHNL B
J9 5P COM2
+24V 2-WIRE DSM/MSM/GSM
2AMP +24V J6-J7 Ethernet J15 J1 J2 J3 J4
WU001265 J15 CH1 CH2 CH3 CH4 1-4 5-8 9-12 13-16
WU001229
DB9 J1 2P-Jack J4 2P USB USB RJ45 DB9 DB9
J10
PINS SKT DB9
J6 2P
DSM or MSM J6 16P 4P 4P 4P 4P
To 2nd bot top Top bot SKT
OPTION
Box
PWR USB 6 USB 5 COM 2 COM 1
SW/LED GRN OPTION OPTION
TO +24V
COM 3
Not on PCB External TO POS
GSM
Supply or
DSM/MSM
P/N 000-940039
SECONDARY POS
LAN
RS232
Third Party POS
Rev. 0E
FUSION T/AA1D1/x/x
May 2016
85
5 4 3 2 1
KB1 6P J8 10P LED1
WU001817 J7 10P LED2
8P USB5 & USB6 KYBD&Mouse Activity Pwr
Audio
WU002192-0001
10P PWR 4P
WU001421
WU001421
CN1 2P 4P SATA1 WU002708-0001
WU001274
WU001258
10P COM2
10P COM3
WU001307
J17
Pwr
PS Section +5V LED
10P
CUPS PCB ASSY
C C
Battery
+24V LED
WU000995
USB1
BAT EN LED
USB2
Charger
PF LED
J13
3P 2P 4P 3P 4P 3P
J7 J8 J5 J7 J5 J7
PWR DSM/MSM USB AUX PWR USB AUX PWR
WU001269
SBC
J11
9P
J5
Reset
GRIB RS485, USB GRIB Current Loop GRIB Current Loop
J16 LED1 Charge LED J21 (Serial GRIB) Wayne/Gil 30/40 ma Wayne/Gil 30/40 ma
WU001259
6P ACT DC IN 10P
COM1
J8
OUT
May 2016
B J14 10P WU001259 4 CHNL B
J9 5P COM2
+24V 2-WIRE DSM/MSM/GSM
2AMP +24V J6-J7 Ethernet J15 J1 J2 J3 J4 J1 J2 J3 J4
J6 2P
J15 CH1 CH2 CH3 CH4 1-4 5-8 9-12 13-16 1-4 5-8 9-12 13-16
J10
To FP 1-16
Rev. 0E
Not on PCB
To FP 17-32
External To POS System
Supply
RS232
LAN
P/N 000-940039
CAT 5 WIRE
A A
TOK 67 BOX
OR SECONDARY POS Connections for TWO CATS/CH
SIX CATS LOAD MAX/CH Title
FUSION T/AA2D1/x/x
NOTE: FP Numbers are based on IGEM or DUPLEX Size Document Number R ev
B 89XXXXX-XXX X4
PUMP Computers in Dispensers (2 FP per IGEM or DUPLEX)
FUSION SYSTEM Date: Monday, January 17, 2011 Sheet 1 of 1
5 4 3 2 1
86 P/N 000-940039 Rev. 0E May 2016
INSTALLATION/OPERATION
This manual and any software described herein are furnished under the terms of sale or other applicable contract in-
cluding any license, and may be used or copied only in accordance with those terms.
No part of this publication may be electronically or mechanically reproduced, stored in a retrieval system, or transmitted,
in any form or by any means, except as permitted by such terms. Translation of this material to another language with-
out express written permission from Wayne Fueling Systems is prohibited.
This publication is intended for informational purposes only and this material is subject to change without notice. Wayne
Fueling Systems has not made, and does not make, any representations or warranties of any kind, expressed or im-
plied, with respect to any information in the publication, including any warranty as to the accuracy, correctness, or com-
pleteness of any of the information. Wayne Fueling Systems shall not be responsible or liable for any damages or losses
that occur as a result of the receipt and/or use of the information contained herein.
Wayne, the Wayne logo, iX Pay, Ovation, and combinations thereof are trademarks or registered trademarks of Wayne
Fueling Systems, in the United States and other countries. EMV is a registered trademark of EMVCo, LLC. NAMOS is
a trademark of Wincor Nixdorf. Other names are for informational purposes and may be trademarks of their respective
owners.