You are on page 1of 32

Project: Balamand University

Hilti Firestop for MEP

Table of Contents

1. Company Profile and Services

2. Firestop System Description

3. Firestop Solutions for MEP Penetrations

- Plastic Pipes less than 3” (UL Systems/Method Statement)


- Plastic Pipes ďŝŐŐĞƌ than 3” (UL Systems/Method Statement)
- Metal Pipes (UL Systems/Method Statement)
- Metal Duct (UL Systems/Method Statement)

4. Technical Data

- FS One Intumescent sealant


- CP 606 Acrylic sealant

5. Material Safety Data Sheet


Company profile

Hilti provides leading-edge technology to the global construction


industry. Hilti products, systems and services offer the
construction professional innovative solutions with outstanding
added value. The headquarters of the Hilti Group are in Schaan in
the Principality of Liechtenstein.
Some 20,000 employees, in more than 120 countries around the
world, enthuse their customers and build a better future. The
corporate culture is founded on integrity, courage, teamwork and
commitment.
Hilti excels through outstanding innovation, top quality, direct
customer relations and effective marketing. Two-thirds of the
employees work directly for the customer in sales organizations
and in engineering, which means a total of more than 200,000
customer contacts every day. Hilti has its own production plants
as well as research and development centers in Europe and Asia.
Founded in 1941, the worldwide Hilti Group evolved from a small
family company. Since 2000, the Martin Hilti Family Trust holds all
shares and, since January 2008, all participation certificates of
Hilti Corporation. This safeguards the further development of the
company founder Martin Hilti’s life’s work in the long term.
Hilti upholds a clear value orientation and pursues a policy of
stakeholder value. Integrating the interests of all the company’s
partners – customers, suppliers and employees – into its strategy
and actively honoring its social and ecological responsibility
creates the foundation of trust that makes possible the long-term
success of the company.

www.hiltiPHFRP
Hilti Lebanon offers the following value-adding services for our dear customers:

• Technical Seminars for consultants and project engineering teams, regarding


various ways of fire protection in buildings, focusing on passive fire prevention
and the regulations / standards followed worldwide.

• Material Estimations for all the firestopping applications at site, based on


penetration table, to help the customer get the most cost-effective, approved
systems.

• Mock-Ups for firestop system installations, to show the customers how the
systems are applied and look like.

• Hands-On Training for all applicators, to ensure proper application of the


firestopping materials.

• Full Technical Support, to back up the numerous UL- & BS-tested & approved
systems.

• UL- & BS-based Engineering Judgments (EJ) by certified Hilti Fire Protection
Engineers, to represent firestop systems that would be expected to pass the
stated ratings and requirements if tested, for those situations where the tested
system is not doable at site.

• Random Inspections by Hilti Field Engineers to assist the customer in verifying


proper installation according to the approved systems, to facilitate the
requirement of the project’s official firestop inspectors.
Firestop System
Description
Firestop Systems for
MEP Penetrations
Plastic Pipes
3inch and below
Plastic Pipes
Bigger than 3inch
Metal Pipes
UL/cUL SYSTEM NO. C-AJ-1372
METAL PIPE THROUGH CONCRETE FLOOR/WALL OR BLOCK WALL
F-RATING = 3-HR.

CAJ1372c.110402
T-RATING = 0-HR.
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT.
L-RATING AT 400° F = 4 CFM/ SQ. FT.
TOP VIEW SECTION A-A

3
5
1 2 6
A A

1. CONCRETE FLOOR OR WALL ASSEMBLY (3-HR. FIRE-RATING) :


A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR WALL (MIN. 4-1/2" THICK).
B. ANY UL/ULC CLASSIFIED CONCRETE BLOCK WALL.
2. OPTIONAL : MAXIMUM 10" NOMINAL DIAMETER STEEL PIPE SLEEVE (SCHEDULE 40 OR HEAVIER).
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING :
A. MAXIMUM 8" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
B. MAXIMUM 8" NOMINAL DIAMETER CAST IRON PIPE.
C. MAXIMUM 4" NOMINAL DIAMETER COPPER PIPE.
D. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT.
E. MAXIMUM 4" NOMINAL DIAMETER EMT.
4. MINIMUM 4-1/4" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY) TIGHTLY PACKED.
5. MINIMUM 1/4 DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT.
6. MINIMUM 1/4" BEAD HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT.

NOTES : 1. MAXIMUM DIAMETER OF OPENING = 10-1/2".


2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1-7/8".
3. MINIMUM 1/4" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT
IS REQUIRED ON BOTH SIDES OF A WALL ASSEMBLY.

Sheet 1 of 1 Drawing No.


HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000
Scale 5/32" = 1" CAJ
Date
Nov. 4, 2002 1372c
Metal Pipes
with insulation
Metal Ducts
Technical Data
Product Information

FS-ONE
High performance Intumescent
firestop sealant
Product description
Intumescent (expands when exposed to fire) firestop
sealant that helps protect combustible and non-
combustible penetrations for up to 4 hours fire rating.
Areas of application
Steel (<30”), copper (<6”), cast iron (<30”) and EMT pipes.
Insulated steel and copper pipes.
Cable bundles.
Closed or vented plastic pipes.
HVAC penetrations.
Base Materials
Concrete, masonry, drywall and wood floor assemblies.
Wall and floor assemblies rated up to 4 hours.
Product Features
System advantages / customer benefits
Expanding in fire protection pipes and cable penetrations.
Smoke, gas and water tight. Protects more than 95% of all typical firestop application.
Halogen and solvent free. Easy to work with and fast cleanup.
Odourless, water based, easy to clean. Can be repenetrated when laying new cables.
High fire rating properties. Can be painted.
Sealing around compushible and non-compushible Meets LEEDTM requirements for indoor
penetration in fire-rated construction. environmental quality credit

Approvals Internationally tested and approved

Other tests include : UL 1479 : ASTM E 814 : ASTM E 84 : ASTM E 90-97

FS-ONE
High Performance Intumescent firestop sealant
Ordering Color Packaging Volume Item no.
designation contents

FS-ONE, tube red (300 ml) 18 in3


259579
FS-ONE, foil red (600 ml) 36 in3 311387

Manual dispenser CS 201 - P1 (310ml) 225555


Manual dispenser CS 270 - P1 (600ml) 24669

"%
Installation Instructions

Opening Technical data


1. Clean the opening. Surfaces to which FS-ONE will be applied FS-ONE
should be cleaned of loose debris, dirt, oil, moisture, frost and Intumescent firestop mastic
wax. Structures supporting penetrating items must be installed in Chemical basis: water-based intumescent
compliance with local building and electrical standards. acrylate
Application of firestop sealant Density: 1.5 g/cm3
2. Install the prescribed backfilling material type and depth to obtain Colour: red
the desired rating (if required). Leave sufficient depth for applying Curing time:
approx. 4mm/3days
FS-ONE. at 23°C/50% relative humidity
3. Application of firestop sealant: Apply FS-ONE to the required Movement capacity: ± 5%
depth in order to obtain the desired fire rating. Make sure FS- Intumescent: Yes
ONE contacts all surfaces to provide maximum adhesion. For Application temperature: +5°C to 40°C
application of FS-ONE use a standard caulking gun, foil pack
gun, bulk loader and bulk gun. With FS-ONE buckets, Graco type Shelf time:
9 months
sealant pumps may be used. (Contact pump manufacturer for at 23°C/50% relative humidity
proper selection).
4. Smoothing of firestop sealant: To complete the seal, tool
immediately to give a smooth appearance. Excess sealant, prior
to curing, can be cleaned away from adjacent surfaces and tools Safety precautions
with water.
5. Leave completed seal undisturbed for 48 hours. Before handling, read the product and Material Safety Data Sheet
6. For maintenance reasons, a penetration seal should be for detailed use and health information.
permanently marked with an identification plate and fastened in a Keep out of the reach of children.
visible position next to the seal. Wear suitable gloves and eye protection.
Notice about approvals
Check that the penetration has been sealed according to the Storage
specified drawing in the UL Fire Resistance Directory or Hilti
Store only in the original packaging in a location protected from
North American Firestop Manual. For further advice, please
moisture at temperatures between 45°F (5°C) and 86°F (30°C).
contact Hilti customer service. Refer to Hilti product literature and
Observe expiration date on the packaging.
UL Fire Resistance Directory for specific application details.
Not for use...
High movement expansion joints.
Underwater.
On materials where oil, plasticizers or solvents may bleed i.e.
impregnated wood, oil based seals, green or partially vulcanized
rubber.
In any penetration other than those specifically described in this
manual or the test reports.

Installation instructions for FS-ONE


Cable installation

1. Clean opening 2. Pack mineral 3. Apply FS-ONE 4. Smooth 5. Leave completed 6. Fasten
wool. (if required) FS-ONE seal undisturbed for identification plate
48 hours (if required)
Pipe installation

1. Clean opening 2. Pack mineral 3. Apply FS-ONE 4. Smooth 5. Leave completed 6. Fasten
wool. (if required) FS-ONE seal undisturbed for identification plate
48 hours (if required)

"'
Product Information

CP 606
Fire resistant joint filler
Product description
An acrylic based firestop mastic that offers movement
capabilities and excellent acoustic rating in fire rated joint
applications. Provides up to 4hrs integrity in various
applications when tested to BS476 Part 20.

Areas of application
Sealing header joints
Sealing drywall partition connections
Sealing joints to CP670 firestop safety board
Metal pipes
Rigid and low movement joints
Tested on metal pipes in walls, floors and drywall.

Product features
Silicone free System advantages/customer benefits
Halogen and solvent free Paintable
UV resistant Simple use and application
Smoke, gas and water tight
Base materials
Easy clean up with water
Concrete, Masonry, Drywall
Approved for infinite linear gap lengths
Steel, Porous concrete
Meets LEEDTM requirements for indoor
(Wall and floor thickness from 100mm)
environmental quality credit
(Joint widths from 6-100mm)

Approvals Internationally tested and approved

British Standard
BS 476
Other tests include : UL 2079 : ASTM E 1399 : UL 1479 : ASTM E 814 : ASTM E 84

Recommendations
Can be used in conjunction with a suitable backing material:
– Non flammable mineral wool (min. 100kg/m 3 per BS).
– Hilti CF125-50 fire rated backing foam for construction joints only*
*Please note fire rating will be reduced.
Storage
Store only in the original packaging in a location protected
from moisture at a temperature of 5˚C to 25˚C.
Observe expiry date on top of cartridge.

CP 606
Fire resistant joint filler
Description Ordering Item no.
designation 310 ml catridge 580 ml foil
Fire resistant joint filler, white CP 606 (310ml) 209625
Fire resistant joint filler, gray CP 606 (310ml) 209630
Fire resistant joint filler, gray CP 606 (580ml) 214050
Fire resistant joint filler, white CP 606 (580ml) 209632
Manual dispenser CS 201-P1 225555 310 ml 600 ml
Manual dispenser CS 270 P1 24669

1(
Installation Instructions

CP 606
Fire resistant joint filler
Technical Data
CP 606
Density 1.58 g/cm³
Application Temperature 5°C - 40°C
Range
Skin forming time (at 15 min
23°C/50% r.H)
Cure Time (at 23°C/50% r.H) approx. 3 mm/ 3 days
Volume shrinkage <20 %
Movement ±10 %
Temperature resistance tem - -30°C - 100°C
perature range
Shelf life (@73°F/23°C and 50% 24 months
relative humidity)
Chemical basis Acrylic

Application Dimensions
Joint sides must be sound, dry and free from dust, oil or grease. The following dimensions must be observed when using CP 606
Check whether a primer is required for adhesion to the substrate. fire resistant joint filler.
In walls apply CP 606 to both sides of the joint.
Insert backfill of non-flammable mineral wool (at least a b
100 kg/m3 + melting point > 1000OC), Hilti CF 125-50 foam or b a
PE backing rod.
Smooth firestop sealant with water before the skin forms.
Remove CP 606 firestop sealant before it cures using water
Once cured, it can only be removed mechanically. Floor Wall

Joint side material/primer recommendations Consumption guide


To improve adhesion of firestop sealant if the substrate is porous Consumption guide values are given as joint length in meters
and absorptive, mix CP 606 with water and apply as a primer on per cartridge.
base material. b = Joint depth a = Joint width (mm)
The compatibility of the sealant with any encountered paints must 6 10 20 30
always be checked. In particular, this concerns dispersion paint 6 mm 8.6 5.2
systems and alkyd resin systems that can be diluted in water. 10 mm 1.6
Checks of compatibility must be repeated at reasonable intervals 15 mm 0.7
because the chemical composition of paint systems may change.

Chemical resistance Backfilling per BS


Normally, there is no need for resistance to chemicals with the Max. joint Base material Backfilling Fire rating per BS476
applications recommended by Hilti. width Warres N° 69754/G
Unprotected acrylic sealants have only slight resistance to chemicals. Insulation Integrity
Please contact the Technical Advisory Service or your local Fire 6 mm Gas concrete Mineral wool 4H 4H
15 mm Gas concrete Mineral wool 4H 4H
Protection Specialist or the nearest Hilti center if special
20 mm Gas concrete PE 24 mm 130 min. 4 H
requirements for chemical resistance have to be met.
20 mm Gas concrete PU foam CF 125-50 208 min. 4 H
Safety precautions 30 mm Gas concrete Mineral wool 216 min. 4 H
Please refer to MSDS data sheet available as a download from the 30 mm Steel-steel Mineral wool 36 min. 4H
Technical Library on the Hilti web site at 65mm Dry wall/ Mineral wool 136 min. 136 min
concrete
www.hilti.co.uk / www.us.hilti.com (Top of wall)

The above applications are not exhaustive.


For further details please contact your local Hilti representative

1)
Firestop Collars, Wraps and Bandages

Firestop wrap strip CP 648-E (endless)

Applications Technical data


■ An intumescent, flexible firestop wrap strip for combustible pipe Expansion temperature 210 °C
penetrations (approx.)
■ Concrete, masonry floor and gypsum wall assemblies Expansion ratio (unrestricted, 1:19
■ Can be used with pipes at right angles and at 45° up to)
Building material class (ac- B2
Advantages cording to DIN 4102)
■ Quick and easy closure without need for tools LEED VOC 3.1 g/l
■ Easy to cut
Colour Grey, printed foil
■ Fast installation
■ Ideal for very tight installations Height 5 mm

■ Maximum flexibility

Ordering designation Sales pack Item number


quantity
CP 648-E 1” x 33’ 1 pc 304308
CP 648-E 1,75” x 33’ 1 pc 304309

Related products on page


Consumables 405, 412-413, 415, 423

www.hilti.com
424
Material Safety
Data Sheet
Page 1/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

* 1 Identification of substance:

· Product details:
· Trade name: FS-ONE - CP 612
· Application of the substance / the preparation Acrylic sealant
· Manufacturer/Supplier:
Hilti AG
FL-9494 Schaan
· Informing department: see section 16
· Emergency information:
Tel.: 00423 / 234 - 2111
Fax.: 00423 / 234 - 2965
Schweizerisches Toxikologisches Informationszentrum - 24 h Service
Tel.: 0041 / 1 251 51 51 (international)

* 2 Composition/Data on components:

· Chemical characterization
· Description: Watery, acrylate dispersion with filler
· Dangerous components:
CAS: 107-21-1 ethane-1,2-diol Xn; R 22 <2,5%
EINECS: 203-473-3
CAS: 65997-17-3 Fiberglas Xi; R 36/37/38 <2,5%
· Additional information For the wording of the listed risk phrases refer to section 16.

* 3 Hazards identification

· Hazard designation: void


· Information pertaining to particular dangers for man and environment void
· Classification system
The classification is in line with current EC lists. It has been expanded, however, by information from technical literature, by information furnished
by suppliers and by national regulations which have to be observed in chapter 15.

* 4 First aid measures

· General information No special measures required.


· After inhalation Take affected persons into the open air and position comfortably
· After skin contact Instantly wash with water and soap and rinse thoroughly.
· After eye contact Rinse opened eye for several minutes under running water. Then consult doctor.
· After swallowing Seek immediate medical advice.

* 5 Fire fighting measures

· Suitable extinguishing agents CO2, extinguishing powder or water jet. Fight larger fires with water jet or alcohol-resistant foam.
· Special hazards caused by the material, its products of combustion or resulting gases:
Can be released in case of fire
Carbon monoxide (CO)
Carbon dioxide (CO2)
· Protective equipment: Do not inhale explosion gases or combustion gases.

* 6 Accidental release measures

· Person-related safety precautions:


Ensure adequate ventilation
Wear protective clothing.
Particular danger of slipping on leaked/spilled product.
· Measures for environmental protection: Do not allow product to reach sewage system or water bodies.
· Measures for cleaning/collecting:
Collect mechanically.
Dispose of contaminated material as waste according to item 13.

7 Handling and storage

· Handling
· Information for safe handling: No special measures required.
· Information about protection against explosions and fires: No special measures required.
· Storage
· Requirements to be met by storerooms and containers: Keep containers securely closed and dry, store at 5 - 25°C.
· Information about storage in one common storage facility: Not required.
(Contd. on page 2)
FLE

DR
Page 2/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

Trade name: FS-ONE - CP 612

(Contd. of page 1)
· Further information about storage conditions: None.

* 8 Exposure controls and personal protection

· Additional information about design of technical systems: No further data; see item 7.
· Components with limit values that require monitoring at the workplace:
107-21-1 ethane-1,2-diol (d 2,5%)
MAK 26 mg/m3, 10 ml/m3
· Additional information: The lists that were valid during the compilation were used as basis.
· Personal protective equipment
· General protective and hygienic measures The usual precautionary measures should be adhered to general rules for handling chemicals.
· Breathing equipment: Not necessary if room is well-ventilated.
· Protection of hands: Protective gloves.
· Material of gloves Synthetic gloves
· Penetration time of glove material
The exact break trough time has to be found out by the manufacturer of the protective gloves and has to be observed.
· Eye protection: Safety glasses
· Body protection: Protective work clothing.

* 9 Physical and chemical properties:

· General Information
Form: Pasty
Colour: Red
Odour: Characteristic
· Change in condition
Melting point/Melting range: Not determined
Boiling point/Boiling range: Not determined
· Flash point: Not applicable
· Self-inflammability: Product is not selfigniting.
· Danger of explosion: Product is not explosive.
· Density at 20°C 1,5 g/cm³ (DIN 51757)
· Solubility in / Miscibility with
Water: Slightly soluble

10 Stability and reactivity

· Thermal decomposition / conditions to be avoided: No decomposition if used according to specifications.


· Dangerous reactions No dangerous reactions known
· Dangerous products of decomposition: No dangerous decomposition products known

* 11 Toxicological information

· Acute toxicity:
· LD/LC50 values that are relevant for classification:
107-21-1 ethane-1,2-diol
Oral LD50 5840 mg/kg (ratte)
Dermal LD50 9530 mg/kg (rbt)
· Primary irritant effect:
· on the skin: No irritant effect.
· on the eye: No irritant effect.
· Sensitization: No sensitizing effect known.
· Additional toxicological information:
When used and handled according to specifications, the product does not have any harmful effects according to our experience and the information
provided to us.

* 12 Ecological information:

· General notes:
Water hazard class 1 (German Regulation) (Self-assessment): slightly hazardous for water.
Do not allow undiluted product or large quantities of it to reach ground water, water bodies or sewage system.
FLE
(Contd. on page 3)

DR
Page 3/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

Trade name: FS-ONE - CP 612


(Contd. of page 2)

* 13 Disposal considerations

· Product:
· Recommendation For disposal, local regulations issued by the authorities must be observed.
· European waste catalogue
08 00 00 WASTES FROM THE MANUFACTURE, FORMULATION, SUPPLY AND USE (MFSU) OF COATINGS (PAINTS, VARNISHES
AND VITREOUS ENAMELS), ADHESIVES, SEALANTS AND PRINTING INKS
08 04 00 wastes from MFSU of adhesives and sealants (including waterproofing products)
08 04 10 waste adhesives and sealants other than those mentioned in 08 04 09
· Uncleaned packagings:
· Recommendation: Disposal must be made according to official regulations.

* 14 Transport information

· Land transport ADR/RID (cross-border)


· ADR/RID-GGVS/E Class: -
· Maritime transport IMDG:
· IMDG Class: -
· Marine pollutant: No
· Air transport ICAO-TI and IATA-DGR:
· ICAO/IATA Class: -

· Transport/Additional information: Not dangerous according to the above specifications.

* 15 Regulatory information

· Designation according to EC guidelines:


The product is not subject to classification according to the calculation methods of the "General Classification Guideline for Preparations of the
EC" as issued in the last version.
Observe the normal safety regulations when handling chemicals.
· Hazard-determining components of labelling:
Solvent naphtha (petroleum), light arom.
Naphtha (petroleum), hydrodesulfurized heavy
· Special designation of certain preparations:
Safety data sheet available for professional user on request.
· National regulations
· Technical instructions (air):
Class Share in %
Wasser 10-25
III <2,5
NK 2-5

· Water hazard class: Water hazard class 1 (Self-assessment): slightly hazardous for water.

* 16 Other information:
These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not
establish a legally valid contractual relationship.
Changes made since last issue dated 15.02.2002 at the following points: *
· Relevent R-phrases
22 Harmful if swallowed.
36/37/38 Irritating to eyes, respiratory system and skin.
· Department issuing data specification sheet:
Hilti Corp.
BU Chemicals
Quality/Safety/Environment

Hilti Entwicklungsgesellschaft mbH


Hiltistrasse 26
D-86916 Kaufering
Tel: +49 8191 90 6494
Fax: +49 8191 90 17 6494
· Contact: Michael Kaindl
· * Data compared to the previous version altered.
FLE

DR
Page 1/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

1 Identification of substance:

· Product details:
· Trade name: CP 606
· Application of the substance / the preparation Acrylic sealant
· Manufacturer/Supplier:
Hilti AG
FL-9494 Schaan
· Informing department: see section 16
· Emergency information:
Tel.: 00423 / 234 - 2111
Fax.: 00423 / 234 - 2965
Schweizerisches Toxikologisches Informationszentrum - 24 h Service
Tel.: 0041 / 1 251 51 51 (international)

2 Composition/Data on components:

· Chemical characterization
· Description: Watery, acrylate dispersion with filler
· Dangerous components:
CAS: 107-21-1 ethane-1,2-diol Xn; R 22 2-5%
EINECS: 203-473-3
· Additional information For the wording of the listed risk phrases refer to section 16.

3 Hazards identification

· Hazard designation: void


· Information pertaining to particular dangers for man and environment void
· Classification system
The classification is in line with current EC lists. It has been expanded, however, by information from technical literature, by information furnished
by suppliers and by national regulations which have to be observed in chapter 15.

4 First aid measures

· General information No special measures required.


· After inhalation Take affected persons into the open air and position comfortably
· After skin contact Instantly wash with water and soap and rinse thoroughly.
· After eye contact Rinse opened eye for several minutes under running water. Then consult doctor.
· After swallowing Seek immediate medical advice.

5 Fire fighting measures

· Suitable extinguishing agents CO2, extinguishing powder or water jet. Fight larger fires with water jet or alcohol-resistant foam.
· For safety reasons unsuitable extinguishing agents Water with a full water jet.
· Special hazards caused by the material, its products of combustion or resulting gases:
Can be released in case of fire
Carbon monoxide (CO)
Carbon dioxide (CO2)
· Protective equipment: Do not inhale explosion gases or combustion gases.

6 Accidental release measures

· Person-related safety precautions:


Ensure adequate ventilation
Wear protective clothing.
Particular danger of slipping on leaked/spilled product.
· Measures for environmental protection: Do not allow product to reach sewage system or water bodies.
· Measures for cleaning/collecting:
Collect mechanically.
Dispose of contaminated material as waste according to item 13.

7 Handling and storage

· Handling
· Information for safe handling: No special measures required.
· Information about protection against explosions and fires: No special measures required.
· Storage
· Requirements to be met by storerooms and containers: Keep containers securely closed and dry, store at 5 - 25°C.
· Information about storage in one common storage facility: Not required.
(Contd. on page 2)
FLE

DR
Page 2/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

Trade name: CP 606

(Contd. of page 1)
· Further information about storage conditions: None.

8 Exposure controls and personal protection

· Additional information about design of technical systems: No further data; see item 7.
· Components with limit values that require monitoring at the workplace:
107-21-1 ethane-1,2-diol (2-5%)
TLV (European Union) Short-term value: 104 mg/m³, 40 ml/m³
Long-term value: 52 mg/m³, 20 ml/m³
Skin
· Additional information: The lists that were valid during the compilation were used as basis.
· Personal protective equipment
· General protective and hygienic measures The usual precautionary measures should be adhered to general rules for handling chemicals.
· Breathing equipment: Not necessary if room is well-ventilated.
· Protection of hands: Protective gloves.
· Material of gloves Synthetic gloves
· Penetration time of glove material
The exact break trough time has to be found out by the manufacturer of the protective gloves and has to be observed.
· Eye protection: Safety glasses
· Body protection: Protective work clothing.

9 Physical and chemical properties:

· General Information
Form: Pasty
Colour: Various colours
Odour: Characteristic
· Change in condition
Melting point/Melting range: Not determined
Boiling point/Boiling range: Not determined
· Flash point: Not applicable
· Ignition temperature: Not applicable
· Danger of explosion: Product is not explosive.
· Vapour pressure at 20°C: ca. 23 hPa
· Density at 20°C ca. 1,55 g/cm3 (DIN 51757)
· Solubility in / Miscibility with
Water: Fully miscible

10 Stability and reactivity

· Thermal decomposition / conditions to be avoided: No decomposition if used according to specifications.


· Dangerous reactions No dangerous reactions known
· Dangerous products of decomposition: No dangerous decomposition products known

* 11 Toxicological information

· Acute toxicity:
· LD/LC50 values that are relevant for classification:
107-21-1 ethane-1,2-diol
Oral LD50 5840 mg/kg (ratte)
Dermal LD50 9530 mg/kg (rbt)
· Primary irritant effect:
· on the skin: No irritant effect.
· on the eye: No irritant effect.
· Sensitization: No sensitizing effect known.
· Additional toxicological information:
When used and handled according to specifications, the product does not have any harmful effects according to our experience and the information
provided to us.

12 Ecological information:

· Ecotoxical effects: Not determined


· General notes:
Water hazard class 1 (German Regulation) (Self-assessment): slightly hazardous for water.
(Contd. on page 3)
FLE

DR
Page 3/3
Material Safety Data Sheet
According to 91/155 EEC
Printing date 15.03.2004 Reviewed on 15.03.2004

Trade name: CP 606

(Contd. of page 2)
Do not allow undiluted product or large quantities of it to reach ground water, water bodies or sewage system.

13 Disposal considerations

· Product:
· Recommendation For disposal, local regulations issued by the authorities must be observed.
· European waste catalogue
08 00 00 WASTES FROM THE MANUFACTURE, FORMULATION, SUPPLY AND USE (MFSU) OF COATINGS (PAINTS, VARNISHES
AND VITREOUS ENAMELS), ADHESIVES, SEALANTS AND PRINTING INKS
08 04 00 wastes from MFSU of adhesives and sealants (including waterproofing products)
08 04 10 waste adhesives and sealants other than those mentioned in 08 04 09
· Uncleaned packagings:
· Recommendation: Disposal must be made according to official regulations.

14 Transport information

· Land transport ADR/RID (cross-border)


· ADR/RID-GGVS/E Class: -
· Maritime transport IMDG:
· IMDG Class: -
· Air transport ICAO-TI and IATA-DGR:
· ICAO/IATA Class: -

· Transport/Additional information: Not dangerous according to the above specifications.

15 Regulatory information

· Designation according to EC guidelines:


The product is not subject to classification according to the calculation methods of the "General Classification Guideline for Preparations of the
EC" as issued in the last version.
Observe the normal safety regulations when handling chemicals.
· Special designation of certain preparations:
Safety data sheet available for professional user on request.
· National regulations
· Technical instructions (air):
Class Share in %
Wasser 10-25
NK 2-5

· Water hazard class: Water hazard class 1 (Self-assessment): slightly hazardous for water.

* 16 Other information:
These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not
establish a legally valid contractual relationship.
Changes made since last issue dated 20.10.2003 at the following points: *
· Relevent R-phrases
22 Harmful if swallowed.
· Department issuing data specification sheet:
Hilti Corp.
BU Chemicals
Quality/Safety/Environment

Hilti Entwicklungsgesellschaft mbH


Hiltistrasse 26
D-86916 Kaufering
Tel: +49 8191 90 6494
Fax: +49 8191 90 17 6494
· Contact: Michael Kaindl