Professional Documents
Culture Documents
Accepted Manuscript
DIRECT SHEAR
STRENGTH OF REBAR-
COUPLER ANCHOR
SYSTEMS FOR
STEEL-PLATE
COMPOSITE (SC) WALLS
December 2016
4 ABSTRACT
5 This paper focuses on the direct shear behavior of rebar-coupler anchor systems, and their
6 use for anchorage of steel-plate composite (SC) walls to the concrete basemat of safety-related
7 nuclear facilities. Large-scale rebar-coupler anchor specimens were tested under direct shear
8 loading until failure. The results included the applied load-slip displacement responses of the
9 specimens, the direct shear strength, and the observed failure mode. The American Concrete
10 Institute (ACI) 349 code equation for calculating the direct shear strength of embedded anchors
11 was compared with the direct shear strengths from the tests. The code equation underestimated
12 the direct shear strength of the anchor system, because shear failure was assumed to occur in the
13 rebars, whereas experimental observations indicated that shear fracture failure occurred in the
14 couplers rather than the rebars. The design equation was updated to utilize the net shear area of
15 the couplers instead of the rebars, after which the direct shear strengths from the tests could be
16 calculated with reasonable accuracy. The experimental results were also used to propose an
17 empirical model for the shear force-slip displacement response of rebar-coupler anchor systems.
19 coupler anchor.
20
21
1
Post-Doctoral Research Associate, Idaho National Laboratory, efegkurt@gmail.com
2
Professor, Lyles School of Civil Engineering, Purdue University, ahvarma@gmail.com
3
Assistant Professor, Central Connecticut University at New Britain, CT, sohny@gmail.com
1
22 INTRODUCTION: SC WALLS
23 Steel-plate composite (SC) walls consist of a concrete wall sandwiched between two steel
24 faceplates located on the exterior surfaces. The steel faceplates serve as stay-in-place formwork
25 during concrete casting, and the primary reinforcement for the concrete wall after it sets. No
26 additional rebars (or curtains of orthogonal reinforcing bars) are needed to reinforce the
27 composite SC wall. The concrete infill provides mass, stiffness, damping, and thermal inertia to
28 the composite walls, while delaying the local buckling of the steel faceplates. These steel
29 faceplates are anchored to the concrete infill using steel headed stud anchors (or shear studs), and
30 connected to each other using tie bars or steel shapes. These tie bars provide bracing to the steel
31 faceplates during concrete casting, and also serve as transverse (or out-of-plane shear)
32 reinforcement for the walls. Thus, SC walls optimize the use of both steel and concrete
33 construction materials.
34 The interest in the use of SC walls for safety-related nuclear facilities stems from: (i) their
35 construction schedule economy resulting from the use of stay-in-place formwork and elimination
36 of congested rebar cages (IAEA 2011), (ii) the extensive use of steel modules consisting of
37 faceplates, shear studs and tie bars that can be pre-fabricated in the shop and shipped to site for
38 construction (AISC N690s1, 2015), (iii) better construction quality resulting from reduced rebar
39 congestion and shop fabrication, (iv) structural efficiency resulting from their performance for
40 seismic and accident thermal loading (Sener et al. 2015a, Booth et al. 2015), and (v) significant
41 potential for resistance to missile impact, aircraft impact, and impulsive loading (Bruhl et al.
43 SC walls are being used in nuclear power plants that are being constructed around the world.
44 For example, the AP1000® plants being constructed in Sanmen and Haiyang in China use SC
2
45 walls for the containment internal structure (CIS). The AP1000® plants (DCD 2011) being
46 constructed in V.C. Summer (South Carolina) and Vogtle (Georgia) use SC walls for the CIS and
47 also for the external shield building enhanced for aircraft impact considerations (safeguards
48 information, NEI 2011). Steel-plate composite (SC) walls are also being considered for future
49 power plants and small modular reactors (SMRs). For example, SC walls are being used for the
50 CIS of the US-APWR® (DCD 2013), which was under review for licensing. The Westinghouse
51 SMR and the Generation mPower SMRs are also considering the use of SC walls for safety-
54 Prior research has focused on the behavior and design of SC walls for various force and
55 moment demands, for example, in-plane shear (Ozaki et al. 2004, Seo et al. 2016), out-of-plane
56 flexure (Sener et al. 2015b), out-of-plane shear (Sener and Varma 2014), and axial compression
57 (Zhang et al. 2014). Prior research has also focused on the behavior and design of SC walls for
58 combinations of various in-plane forces and out-of-plane moments (Varma et al. 2014). The
59 results from these and other prior research programs have been used to develop design codes and
60 specification for SC walls in safety-related nuclear facilities, for example, JEAC (2009), KEPIC
62 Recent research has also focused on the seismic behavior and design of SC walls in building
63 structures, for example, Alzeni and Bruneau (2014), Kurt et al. (2016), and Epackachi et al.
64 (2015). These research studies have been used to develop seismic design provisions for SC walls
65 in steel building structures, where they are referred as composite plate shear walls – concrete
3
67 There are three primary types of connections for SC walls, namely, (i) SC wall-to-concrete
68 basemat anchorage connection, (ii) SC wall-to-wall joint connection, and (iii) SC wall-to-floor
69 slab connection. Limited research has been conducted on the design of these connections for SC
70 walls, for example, Katayama et al. (1999), Varma et al. (2011), Seo (2014) investigated the
71 behavior of connection type (i) wall-to-basemat anchorage. Seo (2014), Seo and Varma (2016),
72 and Hwang et al. (2013) and Lee et al. (2012) have investigated the behavior of connection type
73 (ii), wall-to-wall connections. Kim et al. (2008) and Kim and Choi (2011) have investigated the
75 For connection type (i), namely SC-wall-to-basemat anchorage, there are different potential
76 designs. For example, (a) the steel faceplates of the SC wall can be welded to steel baseplate(s),
77 and steel rebars can be welded to underside of the baseplate(s) and anchored into the concrete
78 basemat, or (b) steel dowel rebars from the concrete basemat can be continued into the SC wall
79 and lap-spliced with the steel plates, or (c) the steel plates of the SC walls can be continued and
80 embedded directly into the concrete basemat using shear studs. These three potential designs are
81 mentioned in JEAC 4618 (2009) and Kurt (2016). Design type (i)(a), i.e., wall-to-basemat
82 anchorage with steel baseplate(s) is of interest because it can be used to design full-strength
83 connections that are stronger than the weaker of the two connected parts.
84 MOTIVATION
86 type (i)(a). The faceplates of the SC wall are welded to a high strength steel baseplate, which
87 extends across the thickness of the wall because it forms part of the continuous pressure
88 boundary within the prestressed concrete containment vessel. Headed shear studs are welded on
89 top of the baseplate and embedded inside the concrete infill of the SC wall to transfer shear
4
90 forces from the concrete infill to the steel baseplate. The transfer of forces between the SC wall
91 and concrete basemat is achieved by rebar anchors that are welded underneath the baseplate
92 using couplers, and embedded into the concrete basemat. An alternate design, where the
93 continuous pressure boundary is not required, uses two baseplates instead of one continuous
94 baseplate across the wall thickness. Each baseplate is welded to the steel faceplate of the SC
95 wall, and force transfer is achieved by rebar anchors that are welded underneath the baseplates
97 This type of connection type (i)(a) shown in Figure 1 is preferred because it can be designed
98 as a full-strength connection, i.e., stronger than the weaker of the two connected parts including
99 the SC wall itself. This is preferred because during beyond design basis or extreme events, the
100 SC wall can undergo inelastic deformations and provide ductility to the system without sudden
101 failure of the associated connections (Sener et al. 2015a). In safety-related nuclear facilities, the
102 behavior and performance of structural walls is governed by their response to in-plane shear
103 forces (Sener et al. 2015a), which can be estimated using AISC N690-12s1 (2015) or Seo et al.
104 (2016). The shear strength of the SC wall-to-basemat anchorage connection depends on the
105 direct shear strength of rebar-coupler system welded underneath the baseplates as mentioned
107 This paper focuses on the direct shear strength of the rebar anchors welded underneath the
108 steel baseplates as they are the primary element governing the behavior, stiffness, and strength of
109 this connection. The paper presents the results of direct shear tests conducted on full-scale rebar-
110 coupler systems welded to high strength steel baseplates. These tests included one on a full-scale
111 #18 rebar-coupler system welded to a 90 mm. thick baseplate, and one on a group of two full-
112 scale #11 rebar-coupler systems welded to a 56 mm. thick baseplate. These sizes are typical and
5
113 representative of nuclear construction. The focus of the tests was to evaluate: (i) the applicability
114 of the ACI code equation for calculating the direct shear strength of embedded anchors, and (ii)
115 to obtain the complete shear force-slip displacement response including stiffness, direct shear
116 strength, slip displacement capacity and failure mode of the full-scale welded rebar-coupler
117 systems. This information is required for designing the basemat anchorage connection, and for
118 evaluating the performance of structures composed of SC wall systems anchored to the basemat.
120 Anchors, located away from concrete edges, have the potential to develop steel rupture
121 failure under direct shear, provided that the anchors are sufficiently embedded to prevent
122 concrete pryout failure mode. ACI 349 (2013) Appendix D.6.1 Equation D-19 proposes the
123 following simple equation for calculating the direct shear strength of steel bolts embedded in
124 concrete;
129 α = 0.6
130 According to ACI 349, the value of futa shall not be taken greater than the smaller of 1.9fya
131 and 860 MPa, where fya is the yield strength of the anchor steel. The value of the coefficient α is
132 specified as 0.6 in ACI 349, but there are different values of coefficient α proposed by some
133 other researchers. For example, Cook and Klinger (1992) recommend 0.5 for cast-in-place
134 anchors and 0.6 for sleeved anchors such as undercut anchors. Anderson and Meiheit (2006)
135 conducted several tests on headed anchors welded to baseplates, and recommended the value of
6
136 1.0 for the coefficient α. Additionally, under direct uniaxial shear, the von Mises yield criterion
!
137 provides shear yield stress equal to or 0.57 times the tensile yield stress. This relationship is
"
!
138 typically assumed to hold for the shear fracture stress to be equal to or 0.57 times the tensile
"
140 If the anchors are ductile, and welded in a regular pattern that is parallel to the direction of
141 the applied shear load, then the applied (shear) load is resisted uniformly by the anchors,
142 particularly at the ultimate load level. The direct shear strength of such an anchor group can be
143 calculated as the direct shear strength of each anchor multiplied by the number (n) of anchors in
146 The rebar anchors need to be developed and embedded sufficiently in the concrete basemat to
147 prevent any pullout or pryout failure modes. ACI 349 has direct recommendations for the
148 development lengths of rebars under tension or compression, but not for the development length
149 of a rebar under shear. However, shear-friction methodology can be used for understanding the
150 force transfer mechanism for a rebar subjected to shear and embedded in the concrete basemat.
151 Shear-friction assumes that the rebars are extending across a joint or shear plane, and shear
152 transfer occurs across two planes via friction between the surfaces. The friction force is a result
153 of the clamping forces created by the rebars keeping the two surfaces together. ACI 349 Ch.11
154 covers the shear-friction method, and it requires the shear-friction reinforcement to be anchored
155 to develop fy by embedment, hooks or welding to special devices. Therefore, the development
156 lengths of the rebars for the tests were calculated using ACI 349 Ch.12.
157 ACI 349 Ch.12 specifies the development length detailing of straight rebars in tension or
158 compression and hooked rebars in tension. The average bond stresses over the length of the
7
159 embedment of the rebar are the basis for the design equations in ACI 349, and they are functions
160 of the uniaxial compressive strength. The general design equation for development length of
3 f y yt y e y s
ld = db
40 f c' ( cb + Ktr )
162 db Eq-2
0.02 f y db
ldh =
164 f c' Eq-3
165 The constants, ψt, ψe, and ψs, are related to the location, material and geometric properties of
166 the rebars being developed. These constants are defined in ACI349-13. The following minimum
167 development lengths of the rebars used in the tests were calculated using Eq-2 and Eq-3 in
169 • #18 rebar development length (fy = 410 MPa, f’c = 41 MPa, ψt = 1.3, ψe = 1.0, ψs = 1.0):
3 f ya yt y e y s
170 ld 18 = ( )d #18 = 1700 mm ( straight bar )
40 f c' ( cb + Ktr )
d #18
0.02 f ya d #18
171 ldh18 = = 890 mm (hooked bar )
f c'
172 • #11 rebar development length (fy = 410 MPa, f’c = 41 MPa, ψt = 1.3, ψe = 1.0, ψs = 1.0):
3 f y yt y e y s
173 ld 11 = ( )d #11 = 1100 mm ( straight bar )
40 f c' ( cb + Ktr )
d #11
174 The development length of #18 rebar anchor was calculated as 1700 mm and 890 mm for
175 straight and hooked bars, respectively. In the design of the test specimen, the hooked
8
176 configuration was preferred (over straight bars) for the #18 rebar anchor due to issues related to
177 the size and expanse of the specimen. The development length of the #11 rebar anchor was
178 calculated as 1100 mm. for straight bars. The actual embedment lengths (implemented in the
179 specimens) were longer than the corresponding calculated development lengths. Figure 2 shows
182 Two full-scale direct shear tests were conducted. One of these anchor tests was conducted on
183 a full-scale #18 rebar-coupler system welded to a 90 mm. thick baseplate. This specimen is
184 referred as DSS1 in the paper. The second test was conducted on a group of two #11 rebar-
185 coupler anchor systems welded to a 56 mm thick baseplate. This specimen is referred as DSS2 in
187 The nominal ares of the #18 rebar in DSS1 was equal to 2580 mm2, and the nominal area of
188 the #11 rebar in DSS2 was equal to 1005 mm2. The total area of the group of two #11 rebars in
189 DSS2 was equal to 2010 mm2. Both the #18 and #11 rebars were made from ASTM A706 steel
190 with specified minimum yield strength of 410 MPa and ultimate strength of 550 MPa,
191 respectively (ASTM, 2014). The ACI code equation (Eq-1) used along with these nominal
192 material properties results in design shear strengths of approximately 845 kN and 670 kN for the
194 Two reinforced concrete blocks were constructed to provide the base blocks in which the
195 rebars could be embedded for testing. These concrete blocks were 2300 x 1850 mm in plan, and
196 2160 mm high in elevation. Figure 3 shows a picture and schematic view of the concrete blocks.
197 The concrete blocks were cast within wood formwork designed to be stiff enough to prevent
198 appreciable deflections during and after casting the concrete. The reinforcement for the concrete
9
199 blocks was designed and detailed to resist the applied forces and resulting internal forces (shear,
200 moment etc.) without undergoing significant stresses. Additionally, this reinforcement was
201 placed inside the concrete blocks such as to minimize its contributions to the strength of the rebar
202 anchors. The concrete block was designed to prevent concrete breakout failure of the test
203 specimens by following the recommendations in ACI 349 (2013) Appendix D.6. The concrete
204 blocks were post-tensioned to the laboratory strong floor using 38 mm diameter bars that were
206 Self-consolidating concrete with a specified minimum strength of 41 MPa was used in the
207 construction of the concrete blocks. Several concrete cylinders were cast, and tested (later on the
208 day of testing the specimens) as per the ASTM C39 standard. The average compressive strength
209 of the concrete cylinders was equal to 50 MPa and 46 MPa for the single-anchor (DSS1) and
211 The thicknesses of the baseplates for the DSS1 and DSS2 specimens were equal to 90 mm
212 and 56 mm respectively. The spacing between the two #11 rebar anchors in the DSS2 specimen
213 was 190 mm, which also conforms to the minimum spacing requirements recommended by ACI
214 349 (ACI, 2013). Table 1 summarizes the measured material properties of the steel rebar anchors
215 and baseplates. The baseplates used in the tests had nominal yield strength of 345 MPa and
216 ultimate strength of 540 MPa. The measured average yield strength of #18 rebar was 540 MPa
217 and the tensile strength was 690 MPa, while these values were 470 MPa and 700 MPa for #11
218 rebars.
220 The specimens were tested using a hydraulic cylinder with maximum push capacity of 2560
221 kN, and pull capacity of 1070 kN. The hydraulic cylinder was positioned, as shown in Figure 3,
10
222 to apply vertical push force to the baseplate through bearing. Vsa,m was the shear strength of test
223 specimens calculated using Eq-1 using the measured ultimate strength ( f ut , m ) of the rebar
224 anchors listed in Table1. Vsa,m was calculated as 1060 kN and 845 kN for Specimens DSS1 and
225 DSS2, respectively. Table 2 provides the calculated shear strengths (Vsa,m) of test specimens
226 along with measured material properties presented in Table 2, and the design shear strengths,
227 ∅Vsa,m, where ∅ is the strength reduction factor. The ASTM A706 rebars are classified as ductile
228 steel elements by Section D.1 of ACI 349 (2013), and the corresponding strength reduction
229 factor, ∅, is specified as 0.75 in Section D.4.5. The push capacity of the hydraulic cylinder was
230 approximately 240% greater than the calculated shear strengths of the specimens.
231 The instrumentation used in the tests included string potentiometers and displacement
232 transducers. Figure 4 shows a view of the instrumentation layout around the specimens. All of
233 the sensors were calibrated and checked before the tests, and monitored during testing. The
234 instrumentation surrounding the specimens was used to measure and record the horizontal and
235 vertical displacements of the baseplate and the concrete block, and their relative displacement
236 with respect to each other. This relative displacement is refereed as slip in later sections of the
237 paper. Strain gages were attached (bonded) to the couplers and rebar anchors to measure the
238 longitudinal strains along the coupler and rebar anchor height. Figure 5 shows the layout of the
239 strain gages. The locations were ground smooth, and the strain gages were waterproofed and
241 An initial load of approximately 445 kN was applied and the corresponding measurements
242 from the string potentiometers, displacement transducers and strain gages were recorded. The
243 specimen was unloaded. Following this initial loading cycle, the specimens were loaded
244 monotonically to: (a) their calculated design shear strength, ∅Vsa,m, (b) shear strength Vsa,m, and
11
245 (c) 1.25 of Vsa,m. Loads were applied in increments varying from 40 to 80 kN in the early stages
246 of the tests, and in smaller increments of 20 to 40 kN during the later stages. The specimen was
247 subjected to monotonically increasing loading beyond 1.25 Vsa,m up to fracture failure in the final
250 The results of the tests are presented in the following sections in tabulated and graphical
251 formats. The relative displacement at the anchor points, i.e., slip displacement, was calculated by
252 subtracting the vertical displacement measured at the baseplate from the measured vertical
253 displacements of the concrete block. The movement of the concrete block was extremely small,
254 within 1%, compared to the displacements measured for the baseplate at the early stages of
255 loading.
257 This test evaluated the performance of the full-size #18 rebar-coupler anchor system under
258 direct shear. The complete load-slip displacement response of Specimen DSS1 is shown later in
259 Figure 11, and discussed step-by-step in this section. The initial applied load, 480 kN, was used
260 to identify any unresponsive strain gages or displacement sensors. The measured values in this
261 initial load step confirmed that two strain gages on the rebar anchor were not functioning
262 properly. They were disconnected from the data acquisition system. The remaining strain gages
263 showed that both the coupler and the anchor rebar remained elastic at the applied load of 480 kN.
264 The recorded slip between the concrete block and the steel baseplate, which was the
265 displacement at the anchor point, was approximately 0.56 mm. The vertical movement, uplift, of
266 the concrete block during at the early stages of the test was so small that the recorded slip values
267 were close to the vertical displacement of the baseplate. However, the slip at the anchor points
12
268 were calculated by subtracting the displacement of the concrete block from the displacement of
270 The specimen was unloaded, and then reloaded up to (∅Vsa,m) 797 kN for the second loading
271 cycle. At this load level, there were no visible cracks or damage of the concrete block. The yield
272 strain of the #18 rebar was 2620 microstrain based on the measured yield stress of the rebar. The
273 maximum recorded axial strain on the rebar (strain gage 14B) was approximately 995
274 microstrain reflecting that the rebar was still in the linear range of response. Figure 6 shows the
275 applied force vs. measured strain response on the rebar for DSS1. The measured displacement at
276 the anchor point and the slip displacement was approximately equal to 0.89 mm. As there were
277 no sign of failure, the specimen was unloaded, and then reloaded up to (Vsa,m) 1070 kN. There
278 were still no visible cracks or damage of the specimen. The maximum recorded strain on the
279 rebar (14B) was approximately 2380 microstrain showing that the rebar was still in the elastic
280 range. The maximum measured slip displacement was approximately equal to 2 mm at the
281 applied load of 1150 kN. Small concrete cracks were observed around the anchor point at this
282 load level. The test was considered successful when the specimen showed no failure at the load
283 value of 1070 kN ( Vsa ,m ). However, the applied loading was increased up to (1.25 Vsa ,m ) 1330
284 kN to further evaluate the direct shear behavior of the rebar-coupler anchorage system. The
285 measured strains on the rebar (12B, 13B, and 14B) were higher than the yield strain. Although
286 the anchor rebar was experiencing inelastic deformations, there were no signs of significant
287 distress or failure of the specimen even at this load level. There was some creep (increasing
288 displacement) when the applied loading was sustained at this load level (1330 kN). The
289 maximum recorded slip displacement was approximately 3.6 mm, and the residual slip-
290 displacement was equal to 1.8 mm when the specimen was unloaded.
13
291 GROUP ANCHOR SPECIMEN (DSS2)
292 This test evaluated the performance of the group of two #11 rebar-coupler anchor systems
293 under direct shear. The complete load-slip displacement response of Specimen DSS2 is shown
294 later in Figure 12, and discussed step-by-step in this section. The initial applied load, 445 kN,
295 was used to identify unresponsive strain gages or displacement sensors. The measured values
296 confirmed that two strain gages were not functioning properly, and they were therefore
297 disconnected from the data acquisition system. The maximum recorded slip displacement at the
298 anchor point was approximately 0.75 mm. Maximum strain on the rebars was close to 920
299 microstrain (212B). After the specimen was unloaded, the measured displacements around the
300 specimen returned back to their initial unloaded values without any residual displacements.
301 Figure 7 shows the applied force vs. measured strain response on the rebar anchors for DSS2.
302 The loading was increased to fVsa ,m = 620 kN . There were no signs of any damage on the
303 specimen. The measured slip displacement at the anchor location was approximately 1.5 mm.
304 The measured maximum strain increased to 1580 microstrain. When the specimen was unloaded,
305 the residual slip was approximately equal to 0.90 mm. The specimen was reloaded up to Vsa,m
306 equal to 890 kN. The corresponding slip displacement was measured as 3 mm. The maximum
307 recorded strain was equal to 1820 microstrain, which indicates that the rebars were still within
308 their elastic range of response. As there was still no signs of damage, the load was increased up
309 to 1.25 Vsa,m (1110kN). There were some visible inclined surface cracks originating around the
310 anchor points at loading equal to 980 kN. The strain gages stopped functioning properly when
311 the applied load reached to 1000 kN. The measured maximum slip displacement was equal to 4.3
312 mm at 1110 kN. The group anchor rebar-coupler system did not show significant distress or
14
313 failure at load level of1.25 Vsa,m (1110kN). After the specimen was unloaded, the residual slip
316 Both of the specimens (DSS1 and DSS2) could resist applied loads that were greater than
317 1.25 times the calculated direct shear strength Vsa,m without significant distress or failure.
318 Therefore, the applied loading was increased monotonically (in small increments of 20 kN) up to
319 complete fracture failure. The test setup and instrumentation layout were the same as before. The
320 strain gages were disconnected from the data acquisition system because they had been damaged
321 by the earlier loading cycles. The hydraulic setup including actuator, pump, and pressure
323 The complete load-slip displacement response of Specimen DSS1 up to failure is shown in
324 Figure 11. As shown the maximum measured slip displacement (at failure) was equal to 7 mm.
325 Shear fracture failure of the welded coupler occurred at 1548 kN. Figure 8 shows photographs of
326 the fractured coupler surfaces (a) inside the concrete block, and (b) on the baseplate surface.
327 Figure 8 indicates that shear fracture failure occurred through the coupler wall thickness near the
329 The complete load-slip displacement response of Specimen DSS2 up to failure is shown in
330 Figure 12. As shown the maximum measured slip displacement (at failure) was equal to 6 mm.
331 Shear fracture failure of the welded coupler occurred at 1263 kN. Figure 9 shows photographs of
332 the fractured coupler surfaces (a) inside the concrete block, and (b) on the baseplate surface.
333 Figure 9 indicates that shear fracture failure occurred through both the coupler wall thicknesses
15
336 As discussed in the previous section, and shown in Figures 11 and 12, in the early stages of
337 loading, the slip displacements were relatively proportional to the applied loading. The applied
338 load-slip displacement curves did not show appreciable deviation from linear-elastic behavior up
339 to at least one-fourth (25%) of the maximum applied load. The applied load-slip displacement
340 responses demonstrated significant nonlinearity with increasing loading. At the final stages of
341 loading, i.e., close to the failure, applied load-slip displacement responses demonstrated plastic
342 flow, i.e., slip displacements increased significantly with little to no increase in loading.
343 The specimens were subjected to loads significantly greater than design shear strengths,
344 fVsa ,m , and complete failure occurred at applied loads of 1548 kN and 1263 kN for Specimens
345 DSS1 and DSS2, respectively. Figures 8 and 9 show photographs of the fracture failures that
346 occurred in the couplers. These photographs indicate that shear fracture failures occurred in the
347 net section of the coupler after the end of the rebar anchor that was threaded into it. Figure 10
348 identifies the location of this shear fracture failure plane in the net area of the rebar-coupler
350 The experimental results and observations of the shear fracture failure surfaces (and
351 locations) indicate that the direct shear strength of the rebar-coupler anchor system is governed
352 by the shear fracture failure of the net section in the coupler, not the shear fracture failure of the
353 rebar anchor as assumed earlier in Eq.-1. Therefore, Eq-1 was modified to utilize the net shear
354 area of the coupler as shown in Figure 10. The updated equation for calculating the direct shear
355 strength (Vrb-cp) of the rebar-coupler systems is shown in Eq-4, which is still based on and
356 consistent with the format of the original ACI 349 design equation.
16
359 futc,m = measured tensile strength of steel coupler, MPa
362 α = 0.6
363 Table 3 shows the geometric properties, provided by the manufacturer, of the steel couplers.
364 Figure 10 shows a noticeable feature of the couplers that the inner diameter of the coupler where
365 the rebar starts to engage with the coupler decreases almost linearly from ϕG, engagement
366 diameter, to ϕG, inner diameter, until the attached length of the rebar is terminated inside the
367 coupler. This makes the net area of the rebar-coupler anchor system to be governed by the inner
368 diameter, ϕG1, of the coupler. Thus the net area of the coupler is the difference in the areas
369 calculated using the outer diameter ϕA, and ϕG1. Direct shear strengths of the specimens using
𝜋
373 𝐴%&,()* (#11) = ∅𝐴2∅!! − ∅𝐺12∅!! = 1477𝑚𝑚2
4
375 Table 4 shows the comparison of the calculated direct shear strengths with the measured
376 failure loads in the experiments. As shown, the direct shear strengths of the rebar-coupler anchor
377 systems calculated using Eq-4 were within 1% difference of the failure loads observed in the
378 tests.
379
380
17
381 LOAD-SLIP CURVE
382 Rebar-coupler anchor systems are typically designed and analyzed with the assumption that
383 there is no slip between the anchor system and the concrete, i.e. fixed-base boundary condition
384 with no translation. Unfortunately, this fixed-base boundary condition assumption also neglects
385 the potential stress relief associated with the flexibility (displacements) of couplers to
386 accommodate thermal deformations induced during accidental thermal events. This flexibility
387 due to the load vs. slip displacement behavior of the rebar-coupler anchor system can relieve
388 large internal forces (axial and shear forces) calculated in the SC walls assuming fixed-base
389 boundary conditions. This section proposes a simple empirical model for the load-slip
390 displacement behavior of rebar-coupler anchors based on existing knowledge and the limited test
391 data presented in this paper. Additional research is needed to further evaluate and develop
392 appropriate models for the load-slip behavior of rebar-coupler anchor systems.
393 Several researchers have developed load-slip relationships for steel headed stud anchors (also
394 referred as shear studs) embedded inside concrete as an outcome of push-out tests. The research
395 conducted by Ollgaard et al. (1971) is the most cited among all previous studies in the U.S. for
396 load-slip relationship of shear studs. It also serves as the source for stud strength identified in
397 AISC and AASHTO specifications. The load-slip relationship proposed by Ollgaard et al is:
399 In Eq-5, Qu is an empirical function representing the direct shear strength of stud anchors, and Δ
401 The load-slip relationship for the rebar-coupler anchor system can be modeled (empirically)
402 using the mathematical relationship proposed by Ollgaard et al., with the exception that Qu
403 should be replaced with Vrb-cp, which is the direct shear strength of the rebar-coupler anchor
18
404 system. For example, Figures 11 and 12 include the load-slip relationships predicted for
405 Specimens DSS1 and DSS2 using Eq-5, while using Vrb-cp instead of Qu in the empirical
406 relationship proposed by Ollgaard et al. Comparisons with the corresponding experimental
407 results in Figures 11 and 12 indicate that this empirical model over estimates the initial stiffness
408 and secant stiffness of the rebar-coupler anchor systems. This is because Eq-5 inherently results
409 in infinite slope at zero load, which corresponds to perfect bond between the anchors and
410 concrete as assumed by Ollgard et al. (and valid for shear studs only). The couplers of rebar-
411 coupler anchor systems act similar to shear lugs with some crushing of the concrete around the
412 coupler due to high bearing stresses. This results in softening of the initial stiffness of load-slip
413 curves. The load-slip relationship proposed by Ollgaard et al. was therefore modified to Eq-6 to
414 effectively model the relatively lower initial stiffness of rebar-coupler anchor systems:
416 Figures 11 and 12 include the load-slip (V- Δ) relationships calculated using Eq-6 for the two
417 specimens DSS1 and DSS2, respectively. Comparisons with the corresponding experimental
418 results indicate that this empirical model (Eq-6) models the load-slip relationship of the rebar-
419 coupler anchor systems with reasonable accuracy. As mentioned earlier, this is a simple
420 empirical model based on existing knowledge and the limited test data presented in this paper.
421 Additional research is needed to develop better models for the load-slip behavior of rebar-
423 CONCLUSIONS
424 This paper presented the results from direct shear tests of large-scale rebar-coupler anchor
425 systems. The applied load vs. slip displacement responses of the specimens were discussed along
426 with the final failure mechanism of the anchor system. The experimental results were used to
19
427 develop a simple equation for calculating the direct shear strength of rebar-coupler anchor
428 systems. The experimental results were also used to propose a simple empirical model for the
429 load-slip relationship of the rebar-coupler anchor systems. The experimental results presented in
430 the paper are extremely useful as there are very few full-scale tests available in the literature. The
432 1. The applied load vs. slip displacement response of the rebar-coupler anchor systems was
433 relatively linear up to about 25% of the shear strength. The load-slip responses had
434 significant nonlinearity with increasing loading. At the final stages of loading, i.e., close to
435 the failure, the load-slip response had plastic flow, i.e., slip increased with little to no
437 2. The initial design assumption was that the direct shear strength of the rebar-coupler anchor
438 system would be governed by the shear fracture of the rebar (area). The ACI 349 code
439 equation for estimating the direct shear strength of steel elements (bolts) embedded in
440 concrete was used to calculate the design shear strength ( fVsa ,m ) of the tested specimens.
441 3. Experimental results indicated that large-scale specimens could resist applied loads more
442 than 125% of the (initially) calculated design shear strength ( 1.25Vsa ,m ) without any signs of
444 4. The direct shear strength of the rebar-coupler anchor systems was governed by the shear
445 fracture failure of the net section area of the coupler, not the shear fracture of the rebar
446 anchor. This net section area was located just after the end of the rebar anchor threaded into
447 the coupler. The experimental results indicated significant (95-100%) over strength of the
448 specimens with respect to the initially calculated design shear strengths.
20
449 5. The direct shear strength equations were updated to utilize the net section area of the
450 couplers (rather than the area of the rebars). The direct shear strengths calculated using the
451 updated equation were within 1% of the corresponding failure loads from the tests.
452 6. The load-slip relationships measured from the tested specimens could be modeled
453 empirically using a modified version of the empirical model proposed by Ollgaard et al.
454 (1971) for the behavior of shear studs embedded in concrete. The Ollgaard et al. model had
455 to modified to account for the softening of the load-slip relationship due to the shear lug type
456 behavior of the coupler embedded in concrete, and the crushing of concrete around it due to
458 7. The proposed design equation and empirical load-slip model are preliminary, and additional
459 research is needed to improve these models and to further investigate the effects of different
461 NOTATION
463 Acp,net = Effective cross sectional area of the steel coupler, in.2
464 Ase = Effective cross sectional area of the rebar anchors, in.2
471 ϕVsa = Design shear strength of the anchor with nominal material properties, kN
21
472 ϕVsa,m = Design shear strength of the anchor with measured material properties, kN
482 Vsa = Shear strength of the anchor with nominal material properties, kN
483 Vsa,m = Shear strength of the anchor with measured material properties, kN
484 REFERENCES
485 ACI (American Concrete Institute). (2013). “Code requirements for Nuclear Safety-Related
486 Concrete Structures and Commentary.” ACI 349, Farmington Hills, 958 MI.
487 AISC 341 (2016) “Seismic Provisions for Structural Steel Buildings.” American Institute of
489 AISC N690-12s1. (2015). “Specification for Safety-Related Steel Structures for Nuclear
491 Alzeni, Y., and Burneau, M. (2014). “Cyclic Inelastic Behavior of Concrete Filled Sandwich
492 Panel Walls Sujected to In-Plane Flexure.” Technical Report MCEER 14-0009, Univ. at
494 http://www.mceer.buffalo.edu/pdf/report/14-0009.pdf
22
495 Anderson, N.S. and Meinheit, D.F. (2006). “Design Criteria of Headed Stud Groups in Shear:
496 Final Report.” Wiss., Janney, Elstner Associates, Inc., Northbrook, IL.
497 ASCE / SEI 7 (2010). “Minimum Design Loads for Buildings and Other Structures.” ASCE,
499 Booth, P.N., Varma, A.H., Sener, K., and Malushte, S. (2015a). “Flexural Behavior and Design
500 of Steel-Plate Composite (SC) Walls for Accident Thermal Loading.” Nuclear
501 Engineering and Design, Volume 295, Pages 817-828, Elsevier Science,
502 http://dx.doi.org/10.1016/j.nucengdes.2015.07.036
503 Bruhl, J., Varma, A.H., Johnson, W.H. (2015). “Design of Composite SC Walls to Prevent
504 Perforation from Missile Impact.” International Journal of Impact Engineering, Vol. 75,
506 Bruhl, J., and Varma, A.H. (2015). “Summary of Blast Tests on Steel-Plate Reinforced Concrete
507 Walls.” Proceedings of the Structures Congress, April 2015, pp. 151-59, ASCE, Reston,
509 Cook, R.A., and Klinger, R.E. (1992). “Ductile multiple-anchor steel-to-concrete connections.”
511 DCD (2011). “Design Control Document for the AP1000.” U.S. Nuclear Regulatory
513 cert/ap1000.html
514 DCD (2013). “Design control document for the US-APWR.” Nuclear Regulatory Commission,
516 cert/apwr/dcd.html
23
517 Epackachi, S., Whittaker, A., Varma, A.H., and Kurt, E. (2015). “Finite Element Modeling of
518 Steel-Plate Concrete Composite Wall Piers.” Engineering Structures, Elsevier Science,
520 Hwang, K.M., Lee, K.J., Yang, H.J., and Kim, W.K. (2013). "An Experimental Study on the
521 Flexural and Shear Behavior of Steel Plate Concrete-Reinforced Concrete Connected
522 Structures." Nuclear Engineering and Design, Vol. 257, pp. 88-99.
523 IAEA (2011). “Construction Technologies for Nuclear Power Plants.” International Atomic
524 Energy Agency, IAEA Nuclear Energy Series No. NP-T-2.5, Vienna
525 JEAC (2009). “Technical Code for Seismic Design of Steel Plate Reinforced Concrete
526 Structures: Buildings and Structures.” JEAC-4618, Japanese Electric Association Nuclear
527 Standards Committee, Tokyo, Japan. Translated from Japanese by Obayashi Company
529 Katayama, S., Fujita, F., Furuwada M., Shohara, R., Takeuchi, M., and Matsumoto, R. (1999).
530 “Experimental study on a steel plate reinforced concrete structure (part #33). Pull-out
532 Meeting, Architectural Institute of Japan, B-2, Structures II, Structural Dynamics Nuclear
534 KEPIC-SNG (2010). “Specification for safety-related steel plate concrete structures for nuclear
535 facilities.” Board of KEPIC Policy, Structural Committee, Korea Electric Association;
536 Kim, H.G., Kim, W.B., Kim, W.K. (2008). "Behavior and Strength of Wall-Slab Connection in
537 SC Structure." J. Korean Soc. Steel Constr., Vol. 20, No. 2, pp. 347-354.
24
538 Kim, W.B., and Choi, B.J. (2011). "Shear Strength of Connections Between Open and Closed
539 Steel-Concrete Composite Sandwich Structures." Steel and Composite Structures, Vol.
541 Kurt, E.G. (2016). “Steel-Plate Composite (SC) Walls and Their Basemat Connections: Seismic
542 Behavior, Analysis and Design” Ph.D. Dissertation, Purdue University, West Lafayette,
543 IN 47906
544 Kurt, E.G., Varma, A.H., Booth, P.N., and Whittaker, A., (2016). "In-plane Behavior and Design
545 of Rectangular SC Wall Piers Without Boundary Elements." ASCE Journal of Structural
547 04016026
548 Lee, K.J., Hwang, K.M., Hahm, K.W., and Kim, W.B. (2012). "An Experimental Study on
549 Flexural/Shear Load Properties of SC (steel plate concrete) Structure with Reinforced
550 Concrete Join." J. Korean Soc. Steel Constr., Vol. 24, No. 2, pp. 137-147.
551 Nuclear Energy Institute. (2011). “Methodology for performing aircraft impact assessment for
552 new plant designs.” NEI 07-13, Draft Rev 8, prepared by ERIN Engineering & Research,
554 Ollgaard, J.G., Slutter, and R.G., Fisher, J.W., (1971). “Shear strength of stud connectors in
555 lightweight and normal-weight concrete.” Engineering Journal, Issue: April 1971, pp. 55–
557 Ozaki, M., Akita, S., Oosuga, H., Nakayama, T., Adachi, N. (2004). “Study on Steel Plate
558 Reinforced Concrete Panels Subjected to Cyclic In-Plane Shear.” Nuclear Eng. and
25
560 Sener, K., and Varma, A.H. (2014). “Steel-Plate Composite SC Walls: Experimental Database
561 and Design for Out-of-Plane Shear.” Journal of Constructional Steel Research, Elsevier
563 Sener, K., Varma, A.H., Booth, P.N., and Fujimoto, R. (2015a). “Seismic Behavior of a
566 http://dx.doi.org/10.1016/j.nucengdes.2015.07.038
567 Sener, K., Varma, A.H., and Ayhan, D. (2015b). “Steel-Plate Composite SC Walls: Experimental
568 Database and Design for Out-of-Plane Flexure.” Journal of Constructional Steel
570 http://dx.doi.org/10.1016/j.jcsr.2015.02.002
571
572 Seo, J. (2014). “Design of steel concrete composite wall-to-wall joints for safety-related nuclear
574 http://docs.lib.purdue.edu/dissertations/AAI3636512/
575 Seo, J., and Varma, A.H. (2015). "Behaviour and Design of Corner or L-Joints in SC Walls."
576 Transactions of SMiRT 23 in Manchester, UK, Paper ID 695, IASMIRT, North Carolina
578 Seo, J., Varma, A.H., Sener, K., and Ayhan, D. (2016). "Steel-Plate Composite (SC) Walls: In-
579 Plane Shear Behavior, Database, and Design." Journal of Constructional Steel Research,
581 http://dx.doi.org/10.1016/j.jcsr.2015.12.013
582 Varma, A.H., Malushte, S., Sener, K., and Lai, Z., (2014). “Steel-Plate Composite (SC) Walls for
583 Safety Related Nuclear Facilities: Design for In-Plane Force and Out-of-Plane
26
584 Moments.” Nuclear Engineering and Design, Special Issue on SMiRT-21 Conference,
586 http://dx.doi.org/10.1016/j.nucengdes.2013.09.019
587 Varma, A.H., Seo, J., Chi, H., and Baker, T., (2011). “Behavior of SC Wall Lap Splice
589 in Reactor Technology (SMiRT 21), New Delhi, India, Paper ID 765, IASMiRT, North
591 Varma, A.H., Seo, J., Chi, H., and Baker, T., (2011). “Behavior of SC Wall Lap Splice
592 Anchorages.” Transactions of SMiRT 21, New Delhi, India, Paper ID 765, IASMiRT,
594 http://engineering.purdue.edu/~ahvarma/Publications/p765.pdf
595 Zhang, K., Varma, A.H., Malushte, S., and Gallocher, S. (2014). “Effects of Shear Connectors
596 on the Local Buckling and Composite Action in Steel Concrete Composite Walls.”
597 Nuclear Engineering and Design, Special Issue on SMiRT-21 Conference, Vol. 269, pp.
599
27
600 Table 1. Measured material properties of rebar anchors and baseplates.
Measure Measure
d yield d Tensile
strength Strength
(MPa) (MPa)
#18 Rebar anchor rods (DSS1) 540 690
#11 Rebar anchor rods (DSS2) 470 700
Baseplate (DSS1) – 90 mm 340 530
Baseplate (DSS2) – 55 mm 350 545
601
602 Table 2. Calculated design shear strengths of the test specimens with measured material
603 properties, Vsa ,m , and their comparison to the experimentally observed shear strength, Vexp .
607
608
609
610
611
28
612 Table 4. Comparison of direct shear strength calculated using the updated design equation,
615
29
616
617
619
620
621
622 Figure 2. Rebar anchor development length for specimens DSS1 and DSS2. (dimensions in
623 mm)
30
624
(a) Picture at the test day of (b) Detailed sketch of the test setup
DSS2
625
626 Figure 3. Test setup; (a) Photo on day of test for DSS2, and (b) Detailed sketch
627
31
629
631 Figure 5 . Strain gage layout on the couplers and rebar anchors for (a) DSS1 and (b) DSS2
632
633 Figure 6. Applied force- measured strain on the rebar anchor for DSS1
32
634
635 Figure 7. Applied force - measured strain on the rebar anchor for DSS2
637
638 Figure 8. Photographs of fractured coupler of DSS1 (#18 rebar); (a) inside the concrete
33
640
641
642 Figure 9. Photographs of the fractured couplers of DSS2 (#11 rebars); (a) inside the concrete
644
646 (https://www.erico.com/category.asp?category=R80)
34
647
648 Figure 11. Comparison of applied load-slip displacement behavior of (i) DSS1 Specimen, (ii)
650
651 Figure 12. Comparison of applied load-slip displacement behavior of (i) DSS2 Specimen, (ii)
35