In case of occurring ghost alarms, you have to tuning the database first as below
procedure. You can do this job on No.1 ACONIS server computer in the engine control
room.
Method
1. Login as supervisor on server No.1.
User ID : aconis2000
Password : aconis2000
2. Click the ACONIS logo at the left upper side on mimic of server no.1, then “SYSTEM
CONFIGURATION” window pops up and click the “DB TUNER” button
3. After step.2, DB Tuner window pops up like below image, and then check “All
servers”, “All Resources” and “Expert Function”
5. The “download is completed” message will be displayed when the job finished.
Click the OK button and close DB Tuner window
After finishing the above job, please check the alarm disappeared or not on the ACONIS
display.