You are on page 1of 1

Date

Company
Attention
PT. Kruger Ventilation Indonesia
Project TFJ CIANJUR Jl Teuku Umar No 20 Karawaci
Reference TF-L1.OZ.1 Tangerang 15115
txtnotes 4500 CFM - 0.3 INWG
Tel: +021 5512288 fax: +021 5513502
email: mktg@krugerindo.co.id
Fan Type Bifurcated Fan Fan Absorbed Power
Unit TDB560-12AA-5-5 / 22° 1.5

Operating Conditions Long Cased / Dir B / Type D 1.2

Air Volume 4500 cfm 0.9

Static Pressure 0.30 inwg 0.6

Velocity Pressure 0.18 inwg 0.3

Total Pressure 0.48 inwg 0


Static Pressure in inwg
Outlet Velocity 8.63 m/s 0.8
Fan Total Efficiency 44%
Fan Static Efficiency 28% 0.6

Fan Speed 1450 rpm


Air Temperature 20 °C 0.4

Altitude 0m
0.2
Fan Absorbed Power 0.57 kW 12° 16°
20°
Motor Power D80 (0.75 kW) 24°
0 28°
Motor Speed 1450 rpm 32°36°
Total Efficiency %
100
80
60
40
20
0
0 2000 4000 6000 8000 10k
Air Volume in cfm

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lw (Lin) 76 83 79 78 76 73 70 67 87 dB
Lw (A) 50 67 70 75 76 74 71 66 81 dB(A)
Lp (A) 30 47 50 54 54 53 50 45 60 dB(A)
* Sound pressure level @ distance 3m, Free Field
D
N° X Ø
ØC
ØA
ØB

A B C D N°xØ

560 605 660 480-65012x10

Version 11.2a.355 printed 3/19/2020 at 10:24:04 AM Copyright Kruger Ventilation Ind. Pte. Ltd and Paramet Limited