Air System Sizing Summary For UE
Air System Sizing Summary For UE
Calculation Months .................................... Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ....................................................... 15.6 Tons Load occurs at ................................................. Jan 1300
Total coil load ..................................................... 187.1 MBH OA DB / WB ................................................... 84.7 / 74.7 °F
Sensible coil load ................................................ 121.9 MBH Entering DB / WB ........................................... 78.2 / 68.3 °F
Coil CFM at Jan 1300 .......................................... 6032 CFM Leaving DB / WB ............................................ 59.5 / 58.6 °F
Max block CFM ................................................... 6032 CFM Coil ADP .................................................................. 57.4 °F
Sum of peak zone CFM ....................................... 6032 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.651 Resulting RH ............................................................... 59 %
ft²/Ton ................................................................. 165.5 Design supply temp. ................................................. 58.0 °F
BTU/(hr-ft²) ........................................................... 72.5 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ................................... 37.45 gpm Max zone temperature deviation ................................ 0.0 °F
Actual max CFM .................................................. 6032 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ..................................................... 6023 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 2.34 CFM/ft² Fan static ................................................................. 0.00 in wg
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2P-201 SALA SACRAMENTAL '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 2581 ft² 38103 - 2581 ft² 11741 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 2581 ft² 0 - 2581 ft² 0 -
Partitions 1300 ft² 9 - 1300 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2878 W 9818 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 265 60949 31800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 110586 31800 - 11741 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2P-201 SALA SACRAMENTAL '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
H EXPOSURE
ROOF 2581 0.350 - 38103 - 11741