PROFIBUS for AC 700F

Engineering Manual
S700 IO Modules
Freelance
PROFIBUS for AC 700F

Engineering Manual
S700 IO Modules
Version 9.2
NOTICE
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.

In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.

This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.

This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
Voltage Directive 72/23/EEC.

Copyright © 2010 ABB.


All rights reserved.

Release: April 2010


Document number: 2PAA105800R0101

TRADEMARKS
Registrations and trademarks used in this document include:

Windows Registered trademark of Microsoft Corporation.

ActiveX Registered trademark of Microsoft Corporation.

PostScript Registered trademark of Adobe Systems Inc.

Acrobat Reader Registered trademark of Adobe Systems Inc.

Industrial IT Trademark of ABB.


Table of Contents
About This Book
Use of Warning, Caution, Information, and Tip Icons ........................................................... 9
Typographic Conventions ..................................................................................................... 10
Terminology.......................................................................................................................... 10
Related Documentation ........................................................................................................ 10

Section 1 - PROFIBUS setup with S700 IO Modules


General ................................................................................................................................. 11
Setup using S700 IO Modules .............................................................................................. 12
Importing GSD file.................................................................................................... 13
Importing Master Device (GSD) Files ..................................................... 13
Start Import .............................................................................................. 13
Pre defined Template................................................................................ 14
User-defined Tabs..................................................................................... 16
Parameterization of the PROFIBUS Module PROFI_M_772 .................................. 18
Bus Parameter Tab.................................................................................... 18
Memory Configuration Tab...................................................................... 21
Master Configuration tab ......................................................................... 22
Online Information Tab ............................................................................ 23
Module Data: PROFIBUS Master Object, PROFI_M_772 ..................... 24
PROFIBUS Slave Interface ....................................................................................... 26
FBP Interface Module DC 705F .............................................................. 26
Configuration of DC 705F ....................................................................... 26
Tab Module data....................................................................................... 27
Tab User ................................................................................................... 28
Tab DPV1................................................................................................. 30
Tab Force/Substitute................................................................................. 33
Tab PROFIBUS Slave .............................................................................. 34

2PAA105800R0101_Eng_Manual_S700_Modules 1
Table of Contents

Tab IO Module ..........................................................................................35


Tab Info .....................................................................................................36
I/O Editor – Input......................................................................................36
I/O Editor – Output ...................................................................................37
I/O Editor – Diagnosis ..............................................................................39

Section 2 - S700 IO Modules


General ..................................................................................................................................41
Overview of the S700 IO Modules ............................................................................41
Analog input/output module AX 721F ......................................................................42
Tab Module data .......................................................................................42
Tab User ....................................................................................................43
Tab DPV1..................................................................................................47
Tab Force and Substitute Value ................................................................50
Tab Module Parameters ............................................................................51
Tab Inputs 0-3 ...........................................................................................52
Tab Outputs 0-3.........................................................................................53
Tab Info .....................................................................................................54
I/O Editor .................................................................................................54
Tab Input ...................................................................................................55
Tab Output ................................................................................................56
Tab Diagnosis............................................................................................57
Analog input/output module AX 722F ......................................................................59
Tab Module data .......................................................................................59
Tab User ....................................................................................................60
Tab DPV1..................................................................................................61
Tab Force and Substitute Value.................................................................62
Tab Module Parameters ............................................................................63
Tab Inputs (Ch0_Ch3) Parameters............................................................64
Tab Inputs (Ch4-Ch7) Parameters.............................................................65
Tab Outputs (Ch0-Ch3) Parameters..........................................................66
Tab Outputs (Ch4-Ch7) Parameters..........................................................67
Tab Info .....................................................................................................67

2 2PAA105800R0101_Eng_Manual_S700_Modules
Table of Contents

I/O Editor ................................................................................................ 68


Tab Input .................................................................................................. 68
Tab Output................................................................................................ 69
Tab Diagnosis........................................................................................... 70
Analog input/output module AC 722F...................................................................... 71
Tab Module data....................................................................................... 71
Tab User ................................................................................................... 72
Tab DPV1................................................................................................. 73
Tab Force and Substitute Value ................................................................ 74
Tab Module Parameters............................................................................ 75
Tab Inputs (Ch0-Ch3) Parameters............................................................ 76
Tab Inputs (Ch4-Ch7) Parameters............................................................ 77
Tab Outputs (Ch0-Ch3) Parameters ......................................................... 78
Tab Outputs (Ch4-Ch7) Parameters ......................................................... 79
Tab Info .................................................................................................... 79
I/O Editor ................................................................................................ 80
Tab Input .................................................................................................. 80
Tab Output................................................................................................ 81
Tab Diagnosis........................................................................................... 82
Analog input/output module AI 723F ....................................................................... 83
Tab Module data....................................................................................... 83
Tab User ................................................................................................... 84
Tab DPV1................................................................................................. 85
Tab Force and Substitute Value ................................................................ 86
Tab Module Parameters............................................................................ 87
Tab Inputs 0-4........................................................................................... 88
Tab Info .................................................................................................... 88
I/O Editor ................................................................................................ 89
Tab Input .................................................................................................. 89
Tab Diagnosis........................................................................................... 90
Analog input/output module AI 731F ....................................................................... 91
Tab Module data....................................................................................... 91

2PAA105800R0101_Eng_Manual_S700_Modules 3
Table of Contents

Tab User ....................................................................................................92


Tab DPV1 .................................................................................................93
Tab Force and Substitute...........................................................................94
Tab Module Parameters ............................................................................95
I/O Editor .................................................................................................97
Tab Input ...................................................................................................97
Tab Diagnosis............................................................................................98
Analog input/output module AO 723F ......................................................................99
Tab Module data .......................................................................................99
Tab User ..................................................................................................100
Tab DPV1................................................................................................101
Tab Force and Substitute.........................................................................102
Tab Module Parameters ..........................................................................103
Tab Outputs 0-3.......................................................................................104
Tab Info ...................................................................................................104
I/O Editor ...............................................................................................104
Tab Output ..............................................................................................105
Tab Diagnosis..........................................................................................106
Digital input module DX 722F ................................................................................107
Module data ............................................................................................107
Tab Module data .....................................................................................107
Tab User ..................................................................................................108
Tab DPV1................................................................................................111
TAB Force and Substitute Value .............................................................114
Tab IO Parameters...................................................................................115
Tab Info ...................................................................................................115
I/O Editor ...............................................................................................116
Tab Input .................................................................................................116
Tab Output ..............................................................................................117
Tab Diagnosis..........................................................................................118
Digital input/output module DX 731F.....................................................................119
Tab Module data .....................................................................................119

4 2PAA105800R0101_Eng_Manual_S700_Modules
Table of Contents

Tab User ................................................................................................. 120


Tab DPV1............................................................................................... 121
Tab Force and Substitute Value .............................................................. 122
Tab IO Parameters .................................................................................. 123
Tab Info .................................................................................................. 123
I/O Editor .............................................................................................. 123
Tab Input ................................................................................................ 124
Tab Output.............................................................................................. 125
Tab Diagnosis......................................................................................... 126
Digital input/output module DC 722F .................................................................... 127
Tab Module data..................................................................................... 127
Tab User ................................................................................................. 128
Tab DPV1............................................................................................... 129
Tab Force and Substitute Value .............................................................. 130
Tab Module Parameters.......................................................................... 131
Tab Info .................................................................................................. 131
I/O Editor .............................................................................................. 131
Tab Input ................................................................................................ 132
Tab Output.............................................................................................. 133
Tab Diagnosis......................................................................................... 134
Digital input/output module DC 723F .................................................................... 135
Tab Module data..................................................................................... 135
Tab User ................................................................................................. 136
Tab DPV1............................................................................................... 137
Tab Force and Substitute Value .............................................................. 138
Tab Module Parameters ......................................................................... 139
Tab Info .................................................................................................. 139
I/O Editor .............................................................................................. 139
Tab Input ................................................................................................ 140
Tab Output.............................................................................................. 141
Tab Diagnosis......................................................................................... 142
Digital input/output module DC 732F .................................................................... 143

2PAA105800R0101_Eng_Manual_S700_Modules 5
Table of Contents

Tab Module data .....................................................................................143


Tab User ..................................................................................................144
Tab DPV1................................................................................................145
Tab Force and Substitute Value...............................................................146
Tab IO Parameters...................................................................................147
Tab Info ...................................................................................................147
I/O Editor ...............................................................................................147
Tab Input .................................................................................................148
Tab Output ..............................................................................................149
Tab Diagnosis..........................................................................................150
Digital input module DI 724F..................................................................................151
Tab Module data .....................................................................................151
Tab User ..................................................................................................152
Tab DPV1................................................................................................153
Tab Force and Substitute Value...............................................................154
Tab IO Parameters...................................................................................155
Tab Info ...................................................................................................155
I/O Editor ...............................................................................................155
Tab Input .................................................................................................156
Tab Diagnosis..........................................................................................157
Frequency Input Module CD 722F ..........................................................................158
Tab Module data .....................................................................................158
Tab User ..................................................................................................159
Tab DPV1................................................................................................160
Tab Force and Substitute Value...............................................................161
Tab Module Parameters ..........................................................................162
Tab Encoder Input 1................................................................................163
Tab PWM DO .........................................................................................164
Tab Inputs 24VDI ...................................................................................165
Tab Outputs.............................................................................................166
Tab Info ...................................................................................................166
Tab Input .................................................................................................167

6 2PAA105800R0101_Eng_Manual_S700_Modules
Table of Contents

Tab Output.............................................................................................. 168


Tab Diagnosis......................................................................................... 169
Digital Analog input/output module DA 701F........................................................ 170
Tab Module data..................................................................................... 170
Module data............................................................................................ 171
Tab User ................................................................................................ 172
Tab DPV1............................................................................................... 174
Tab Force and Substitute Value .............................................................. 177
Tab Module Parameters.......................................................................... 178
Tab Analog Inputs .................................................................................. 179
TAB Analog Outputs.............................................................................. 180
I/O Editor .............................................................................................. 180
Tab Input ................................................................................................ 181
Tab Output.............................................................................................. 182
Tab Diagnosis......................................................................................... 183

2PAA105800R0101_Eng_Manual_S700_Modules 7
Table of Contents

8 2PAA105800R0101_Eng_Manual_S700_Modules
About This Book

Use of Warning, Caution, Information, and Tip Icons


This publication includes Warning, Caution, and Information where appropriate
to point out safety related or other important information. It also includes Tip to
point out useful hints to the reader. The corresponding symbols should be
interpreted as follows:

Electrical warning icon indicates the presence of a hazard which could result in
electrical shock.

Warning icon indicates the presence of a hazard which could result in personal
injury.

Caution icon indicates important information or warning related to the concept


discussed in the text. It might indicate the presence of a hazard which could
result in corruption of software or damage to equipment/property.

Information icon alerts the reader to pertinent facts and conditions.

Tip icon indicates advice on, for example, how to design your project or how to
use a certain function

Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all Warning and Caution notices.

2PAA105800R0101_Eng_Manual_S700_Modules 9
Typographic Conventions About This Book

Typographic Conventions
All text entries, shortcuts, prompts, system messages, menu items, screen elements
etc. comply with the Microsoft Windows conventions.

Terminology
You will find a complete and comprehensive glossary at the end of the Engineering
Manual System Configuration. This glossary contains terms and abbreviations that
are unique to ABB or have a usage or definition that is different from standard
industry usage. Please make yourself familiar to that.

Related Documentation
The following list gives an overview of the documentation relating to the Freelance
system.

Title Number
Mounting and Installation Instructions, Control IT, AC 800F 3BDD012501Rxxxx
Mounting and Installation Instructions, Control IT, AC 700F 2PAA103858Rxxxx
Mounting and Installation Instructions, Rack-System 3BDD012603Rxxxx
DigiVis, Operators Manual, Operator Station, Conventional Design 3BDD012600Rxxxx
DigiVis, Operators Manual, Operator Station, New Design 3BDD011932Rxxxx
DigiBrowse, Operators Manual 3BDD012601Rxxxx
Getting Started 3BDD012560Rxxxx
New Features History 3BDD011933Rxxxx
Engineering Manual, System Configuration 3BDD012503Rxxxx
Engineering Manual, DigiVis Operator Station Configuration 3BDD012518Rxxxx
Engineering Manual, Process Station - AC 800F 3BDD012505Rxxxx
Engineering Manual, Process Station - AC 700F 2PAA103857Rxxxx

10 2PAA105800R0101_Eng_Manual_S700_Modules
About This Book Related Documentation

Title Number
Engineering Manual, Process-Station - Rack System 3BDD012520Rxxxx
Engineering Manual, S700 Modules 2PAA105800Rxxxx
Engineering Manual, OPC-Server F 3BDD012511Rxxxx
Engineering Manual, Trend-Server 3BDD012527Rxxxx
Engineering Manual, IEC 61131-3 Programming 3BDD012504Rxxxx
Engineering Manual, Integration Process Portal B1 3BDD012521Rxxxx
Engineering Manual, User Access 3BDD012513Rxxxx
Engineering Reference Manual, Functions and Function Blocks 3BDD012514Rxxxx
Engineering Reference Manual, Communication and Fieldbusses 3BDD012515Rxxxx
Engineering Reference Manual, Protronic Remote Control 3BDD012506Rxxxx
Engineering Reference Manual, DDE32 3BDD012507Rxxxx
Engineering Reference Manual, IEC 60870-5 Telecontrol Library 3BDD012509Rxxxx
Engineering Reference Manual, Interbus Blocks 3BDD012510Rxxxx
Engineering Reference Manual, Coupling Sartorius Scales 3BDD012512Rxxxx
Engineering Reference Manual, DMS / API 3BDD012508Rxxxx
Engineering Manual, Freelance Bulk Data Manager 2PAA105801Rxxxx
Engineer IT, Control Builder F, Control Builder F Control Software and 3BDD012544R0101
Tools
Control IT, AC 800F Hardware, Product Guide 3BDD012546R0101

2PAA105800R0101_Eng_Manual_S700_Modules 11
Related Documentation About This Book

12 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO
Modules

General
Freelance System V9.2 supports use of remote S700 I/O modules for PROFIBUS
communication to AC 700F controller in addition to local I/O modules.
The coupler bus module CM 772F for PROFIBUS is used to connect the local I/O
modules to the AC 700F.
PROFIBUS Slave Interface should be used to connect S700 I/O modules to the AC
700F controller. These modules cannot be connected directly to the CM 772F.
For a overview of the setup refer to Setup using S700 IO Modules on page 12.

2PAA105800R0101_Eng_Manual_S700_Modules 11
Setup using S700 IO Modules Section 1 PROFIBUS setup with S700 IO Modules

Setup using S700 IO Modules

2 3 4

AI 731F
1.0 I0- 2.0 I0+ 3.0 I4- 4.0 I4+ 1.0 I0- 1.0 I0 2.0 I8

1.1 I0B 2.1 I0A 3.1 I4B 4.1 I4A 1.1 I1- 1.1 I1 2.1 I9

1.2 I1- 2.2 I1+ 3.2 I5- 4.2 I5+ 1.2 I2- 1.2 I2 2.2 I10

1.3 I1B 2.3 I1A 3.3 I5B 4.3 I5A 1.3 I3- 1.3 I3 2.3 I11

1.4 I2- 2.4 I2+ 3.4 I6- 4.4 I6+ 1.4 I4- 1.4 I4 2.4 I12

1.5 I2B 2.5 I2A 3.5 I6B 4.5 I6A 1.5 I5- 1.5 I5 2.5 I12

1.6 I3- 2.6 I3+ 3.6 I7- 4.6 I7+ 1.6 I6- 1.6 I6 2.6 I14

1.7 I3B - 2.7 I3A 3.7 I7B 4.7 I7A 1.7 I7- 1.7 I7 2.7 I15

1.8 UP 2.8 UP 3.8 UP 4.8 UP 1.8 UP 1.8 UP 2.8 UP

1.9 ZP 2.9 ZP 3.9 ZP 4.9 ZP 1.9 ZP 1.9 ZP 2.9 ZP

CH-ERR2 CH-ERR4 CH-ERR1 CH-ERR2

UP 24V DC 5W 8AI
Analog Input

Power 10 20 30 40 10 20 30 40 10 20 30 40 10 20 30 40 10 20 30 40 10 20 30 40 10 20 30 40

supply 11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
11
12
21
22
31
32
41
42
13 23 33 43 13 23 33 43 13 23 33 43 13 23 33 43 13 23 33 43 13 23 33 43 13 23 33 43

24V DC 14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
14
15
24
25
34
35
44
45
16 26 36 46 16 26 36 46 16 26 36 46 16 26 36 46 16 26 36 46 16 26 36 46 16 26 36 46
17 27 37 47 17 27 37 47 17 27 37 47 17 27 37 47 17 27 37 47 17 27 37 47 17 27 37 47
18 28 38 48 18 28 38 48 18 28 38 48 18 28 38 48 18 28 38 48 18 28 38 48 18 28 38 48
19 29 39 49 19 29 39 49 19 29 39 49 19 29 39 49 19 29 39 49 19 29 39 49 19 29 39 49

DC 705F DC 723F
PWR 1.0 I0 2.0 C8 1.0 24V 2.0 C0 3.0 C8 4.0 C16

FBP 1.1 I1 2.1 C9 1.1 24V 2.1 C1 3.1 C9 4.1 C17

S-ERR 1.2 I2 2.2 C10 1.2 24V 2.2 C2 3.2 C10 4.2 C18

I/O-B us 1.3 I3 2.3 C11 1.3 24V 2.3 C3 3.3 C11 4.3 C19

1.4 I4 2.4 C12 1.4 0V 2.4 C4 3.4 C12 4.4 C20

1.5 I5 2.5 C13 1.5 0V 2.5 C5 3.5 C13 4.5 C21

ADDR 1.6 I6 2.6 C14 1.6 0V 2.6 C6 3.6 C14 4.6 C22
x10
1.7 I7 2.7 C15 1.7 0V 2.7 C7 3.7 C15 4.7 C23

ADDR 1.8 UP 2.8 UP 1.8 UP 2.8 UP 3.8 UP 4.8 UP

x1 1.9 ZP 2.9 ZP 1.9 ZP 2.9 ZP 3.9 ZP 4.9 ZP

CH-ERR1 CH-ERR2 CH-E RR1 CH-ERR2 CH-ERR3 CH-ERR4

FBP 8DI 8DC UP 24V DC 300W 24DC


Input 24V DC Input 24V DC
Output 24V DC 0.5A Output 24V DC 0.5A

1.0 2.0
1.1 2.1
1.2 2.2
1.3 2.3
1.4 2.4
1.5 2.5
1.6 2.6
1.7 2.7
1.8 2.8
1.9 2.9

6 5
8 7

1. Power supply 4. Local IOs 7. Profibus DP Active termination unit PDR 11


2. Profibus Master CM 772F 5. S700 IOs 8. Profibus DP-V1 FieldBus Plug PDP 22
3. CPU PM 783F 6. FBP Interface Module DC 705F 9. Profibus DP Adapter Cable Dsub P9-M12 PDA 11
System_Overview_EN_quer.wmf

CM 772 PROFIBUS Master


PDA11 Adapter cable Dsub9-M12 to the bus master
PDP22-FBP FieldBus Plug
DC 705F FBP Interface Module
S700 Modules remote IO Modules
For a complete list, refer to Section 2, S700 IO Modules on page 41

12 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Importing GSD file

PDR11 Active PROFIBUS termination unit


For data on setting up a PROFIBUS slave refer to 2PAA103857Rxxxx Engineering
Manual, Process Station - AC 700F and 3BDD012515xxx Engineering-Reference
Manual, Communication and Fieldbusses.
For details on Mounting and Installation of the S700 IO Modules refer to
2PAA103858Rxxxx Mounting and Installation Instructions, Control IT, AC 700F.

Importing GSD file

Importing Master Device (GSD) Files


Device specific data for PROFIBUS devices are stored in the master device data file
(GSD file). The PROFIBUS slave object PROFI_S_DEV allows PROFIBUS field
device configuration using a GSD file as the basis. A GSD file is imported into the
PROFIBUS slave object to do this.
PROFIBUS slave objects (PROFI_S_DEV) can only be inserted below the
PROFIBUS master object (PROFI_M_772). The GSD file selection dialog appears
during the Insert command.
> Select PROFIBUS master (PROFI_M_772) > Edit > Insert
> Select PROFIBUS slave object (PROFI_S_DEV) > Free bus address selection
> Select device GSD > Operate Start import button

Start Import
Start Import imports the selected GSD file. Following the Import command, all the
GSD file data is held in the new PROFIBUS slave object. It is no longer possible to
update GSD file data in the PROFIBUS slave object. The GSD file name is
displayed in the PROFIBUS slave object parameter mask.
All the device master data files are displayed in a list in the default device master
data directory. The default device master data directory is: <freelance_installation
_directory>\GSD. The following information is displayed in the list for each device
master data file: vendor, device type, version, path and file name of the device
master data file.

2PAA105800R0101_Eng_Manual_S700_Modules 13
Importing GSD file Section 1 PROFIBUS setup with S700 IO Modules

After importing the device master data, all information on the modular slave
configuration (maximum number of modules, available module types etc.) is
available.
For some device types, the device master data file also includes diagnostic texts.
These texts are also imported. They are used in the Control Builder F
commissioning mode and the DigiVis system display to display diagnostic states.
The device master data file is not a PROFIBUS slave object component. It is only
imported when the object is inserted. i.e. when the device master data file is
updated, the device master data file must again be imported into a new PROFIBUS
slave object.
The device master data file cannot be update in the PROFIBUS slave object.

Following the Insert command, the object appears both in the tree and graphic
views.

Pre defined Template


A pre-defined template has been created for the S700 IO Modules. The template
(S700_Template_US.hwm) is available with the Freelance setup and is located in
the path <freelance_installation _directory>\export after installation.
The template contains the standard tabs and some user defined tabs. The user can
define additional tabs or create a new template as required

14 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Importing GSD file

Import S700 Template


Hardware Manager > Edit > Block import > Browse and select the template
S700_Template_US.hwm from the export folder

Edit_Blk import.bmp

The S700 template is displayed in the Clipboard viewer.

2PAA105800R0101_Eng_Manual_S700_Modules 15
Importing GSD file Section 1 PROFIBUS setup with S700 IO Modules

Clipboard_expand.bmp

Drag the template from the Clipboard viewer directly to the Hardware Manager or
to the Templates window (bottom left pane of the Hardware Manager).

User-defined Tabs
The S700 template has a set of user defined tabs for each of the S700 IO Module.
The user can define additional tabs as required using the Dialog editor.
Select the S700 IO > Right click > Dialog editor

These user defined tabs get appended to the right of the standard tabs.

16 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Importing GSD file

Dialog_editor.bmp

2PAA105800R0101_Eng_Manual_S700_Modules 17
Parameterization of the PROFIBUS Module PROFI_M_772 Section 1 PROFIBUS setup with S700

Parameterization of the PROFIBUS Module PROFI_M_772


The PROFIBUS master object represents the PROFIBUS master in Freelance.
The PROFIBUS master object is used to configure interface and bus parameters for
the PROFIBUS. The PROFIBUS master makes no I/O data available itself, the I/O
data is assigned via the connected slaves.

Bus Parameter Tab

bq008us.bmp

Baud rate Transfer rate 9.6 kBit/s ... 12MBit/s.


Bus address The bus address of the PROFIBUS-DP Master.
Bus timing A set of bus parameters can be calculated depending on the devices
connected. There are two options for specifying the bus times:
Automatic adjustment
All bus times can be changed manually. In connection with the
plausibility check, the set parameters are checked using the
parameters of the connected slaves.
The bus times are calculated using the parameters of the

18 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Parameterization of the PROFIBUS Module

connected slaves. In this case the parameters in the dialog overlay


cannot be changed. During the plausibility check, the bus times are
recalculated using the parameters of the connected slaves.
Although controller redundancy is not possible for AC 700F, cable redundancy
can be configured through Redundancy Link Module (RLM).

Min_Slave_Interval
Time after which a slave can respond again. The largest
Min_Slave_Interval of all connected slaves determines when a
new bus cycle may begin. The value entered is multiplied by 100 µs
in the master.
Data_Control_Time
Monitoring interval for the list of active bus subscribers. The value
entered is multiplied by 10 ms in the master.
TWD > TTR
Data Control Time >= 6 TWD
TWD: Watchdog monitoring time of the slave (slave parameter)
Poll_Timeout Indicates the maximum time which the PROFIBUS-DP master
requires to process a master function.
Max_Retry_Limit
Maximum number of message retries through the FDL (field bus
connection level).
Permissible range: 0 .. 7
GAP-Factor Defines the number of token cycles up to an address gap
maintenance cycle.
Permissible range: 1 .. 100
TSL Slot time is the maximum time which the PROFIBUS-DP master
must wait for a transaction response.
Permissible range: 37 .. 16383 [tBit]
TSL> max TSDR+ TQUI+11+2
TSDR Station Delay Responder. Time which a slave takes to respond

2PAA105800R0101_Eng_Manual_S700_Modules 19
Parameterization of the PROFIBUS Module PROFI_M_772 Section 1 PROFIBUS setup with S700

min TSDR Minimum time which a slave must wait before being permitted to
respond.
Permissible range: 11 .. 1023 [tBit]
max TSDR Time after which a slave must respond at the latest.
Permissible range: 37 .. 216-1 [tBit]

Baud rate min TSDR max TSDR


kBit/s tBit tBit
9.6 11 60
19.2 11 60
45.45 11 400
93.45 11 60
187.5 11 60
500 11 100
1500 11 150
3000 11 250
6000 11 450
12000 11 800

TQUI Quiet Time. This value indicates the bus driver quiet time.
Permissible range: 0 .. 493 [tBit]
TSET Setup Time. Time between an event on the PROFIBUS and the
necessary reaction.
Permissible range: 1 .. 494 - TQUI [tBit]
TTR Token Rotation Time. Time for token relay via all masters of the
PROFIBUS.
Permissible range: 256 .. 224 - 1 [tBit]

20 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Parameterization of the PROFIBUS Module

Memory Configuration Tab

bq009us.bmp

Bus station address


Lowest / Highest bus address
Lowest and highest bus addresses which can be operated by the
PROFIBUS-DP master. A data area is available for data traffic with
all configured slaves. For optimal utilization of this data area, the
length of the input data, output data and diagnostic data per slave
can be specified. In the plausibility check, the data items entered are
checked against each other.
Number of I/O bytes per slave
Max. no of input bytes
Maximum length of the input data [bytes] per slave which can be
processed in the master.
Max. no of output bytes
Maximum length of the output data [bytes] per slave which can be
processed in the master.

2PAA105800R0101_Eng_Manual_S700_Modules 21
Parameterization of the PROFIBUS Module PROFI_M_772 Section 1 PROFIBUS setup with S700

Diagnostic
Number of diagnostic buffer
Maximum number of diagnostic buffers per slave which can be
processed in the master = (Highest bus address - Lowest bus
address) +1.
Maximum diagnostic length per message
Maximum length of the diagnostic data [bytes] of all slaves which
can be processed
The maximum diagnostic data length is not included in the GSD file and
therefore cannot be checked. In the case of values which are too low, some
PROFIBUS slaves may stop cyclic data traffic. The diagnostic data length is
maintained at 100 bytes per slave for AC 700F.

Master Configuration tab

PM_772_Master_Config.bmp

DPV1 Connection Timeout


Connection timeout for the transfer of DPV1 parameter. The value
must be selected according to the slowest slave in the PROFIBUS
line. As the DPV1 Connection Timeout is not included in the GSD

22 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Parameterization of the PROFIBUS Module

file, use the values from the documentation of the slave


manufacturer.
Performance Optimization
Use limited bus cycle
Disables the setting Minimal bus cycle
Enables the setting Minimal bus cycle
Minimal bus cycle
Takes the value between 2 - 25 ms.
The communication between the Master and the Slave is updated at the interval
specified here. This reduces the load on the CPU.

Online Information Tab

bq010us.bmp

The data in this tab are only available in commissioning mode.

2PAA105800R0101_Eng_Manual_S700_Modules 23
Parameterization of the PROFIBUS Module PROFI_M_772 Section 1 PROFIBUS setup with S700

Master Protocol Stack Firmware Version


Firmware version of the PROFIBUS Master protocol stack.
DP cycle time
Average cycle time on the PROFIBUS in the last 4 s.
Number of DP cycles
Number of PROFIBUS cycles since the last PROFIBUS start.

Module Data: PROFIBUS Master Object, PROFI_M_772

Name Data type Conf. Acc. Comment


ModuleID INT no RO Slot number of interface card
Parameterization of Bus Parameter Tab
BAUD INT yes RO Baud rate
0 = 9.6 kbaud
1 = 19.2 kbaud
2 = 45.45 kbaud
3 = 93.75 kbaud
4 = 187.5 kbaud
5 = 500 kbaud
6 = 1.5 Mbaud
7 = 3 Mbaud
8 = 6 Mbaud
9 = 12 Mbaud
BusAdr BYTE yes RO Bus address
MinSlvIv UINT no RO Min_Slave_Interval
DataCtrTime UINT no RO Data_Control_Time
PollTimeout UINT no RO Poll_Timeout
MaxRetries UINT no RO Max Retry Limit
G UINT no RO GAP factor
T_sl UINT no RO TSL
min_T_sdr UINT no RO min TSDR

24 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules Parameterization of the PROFIBUS Module

Name Data type Conf. Acc. Comment


max_T_sdr UINT no RO max TSDR
T_qui UINT no RO TQUI
T_set UINT no RO TSET
T_tr UDINT no RO TTR
Parameterization of Options Tab
LSA BYTE yes RO Lowest bus address
HSA BYTE yes RO Highest bus address
MaxInLen WORD yes RO Max. number of input bytes
0 = 16 bytes, 1 = 32 bytes, 2 = 64 bytes
3 = 96 bytes, 4 = 128 bytes,
5 = 192 bytes, 6 = 244 bytes
MaxOutLen WORD yes RO Max. number of output bytes
0 = 16 bytes, 1 = 32 bytes, 2 = 64 bytes
3 = 96 bytes, 4 = 128 bytes,
5 = 192 bytes, 6 = 244 bytes
NoDiagBuf UINT yes RO Number of diagnostic buffers
MaxDiagLen WORD yes RO Maximum diagnostic length per frame
0 = 16 bytes, 1 = 32 bytes, 2 = 64 bytes
3 = 96 bytes, 4 = 128 bytes,
5 = 192 bytes 6 = 244 bytes
Parameterization Master Configuration Tab
DPVITimeout UINT no RO DPV1 Connection timeout
T_MTO BYTE no RO TMTO(Not available for AC 700F)

Parameterization of Online Info Tab


DPSwRev STRING64 no RO Firmware version
DPTglTime WORD no RO Last redundancy starting-up time

2PAA105800R0101_Eng_Manual_S700_Modules 25
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Name Data type Conf. Acc. Comment


DPCycleTime WORD no RO DP cycle time
DPCycles WORD no RO Number of DP cycles

PROFIBUS Slave Interface

FBP Interface Module DC 705F


DC 705F is used as a decentralized I/O module. The bus connection is performed by
a neutral FieldBusPlug interface, which allows the connection of all existing
FieldBusPlugs
This Module is designed for connecting 8 digital inputs 24V DC, 8 configurable
digital inputs or outputs which is module-wise electrically isolated.

Configuration of DC 705F
Insert the DC 705F object below the PROFI_M_772 object in the Hardware Manager.
General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

26 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

Tab Module data

DC705F_Module_Data.bmp

Data for the module is displayed in this tab.


Input data
Consistency The consistency of the data transfer from the module to the slave is
displayed.
Length The length of the data transferred from the module to the slave is
displayed.
Output data
Consistency The consistency of the data transfer from the slave to the module is
displayed.
Length The length of the data transferred from the slave to the module is
displayed.
Configuration bytes
The sequence of bytes for the configuration of the module specified
in the device master data file.

2PAA105800R0101_Eng_Manual_S700_Modules 27
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Tab User

DC705F_User_Para.bmp

Length Displays the number of bytes used for parameter setting. Generated
by the system and cannot be edited.
Name Name of the user parameter.
Value The cold start value is configured in this column. In commissioning
mode, the current values are displayed in this column.
If an analog input is configured as a digital input, the data type automatically
changes from REAL to BOOL. When changing back a digital input to an analog
input, the data type becomes REAL again.

Error LED/Failsafe Function


Setting for the Error LED and Failsafe function of the PROFIBUS
slave.
Check supply
When this function is activated, the process voltage (supply voltage)
is checked by the module. If the voltage is low or no voltage is

28 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

applied, an alarm is generated.


ON Checking of supply voltage is enabled.
OFF Checking of supply voltage is disabled.
Input delay
With activated supply checking, the input delay for the alarm can be
defined here. The following values can be selected:
0.1 ms for quick processes with frequently changing signal
1 ms for slower processes
8 ms if spikes are to be filtered out reliably
32 ms if low-pass behavior is wanted.
Detect short circ. at outputs
Enable/disable detection of short circuit at the output channels
Behaviour outputs at comm. fault
This module allows configuring the behaviour of outputs at
communication error. The following options are available.
Last value unlimited
Substitute value unlimited
Last value 5 sec
Substitute value 5 sec
Last value 10 sec
Substitute value 10 sec
Substitute value
The configured substitute value is used.

2PAA105800R0101_Eng_Manual_S700_Modules 29
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Tab DPV1

DC705F_DPV1.bmp

Name Name of the DPV1 parameter.


If the DPV1 parameter is described in the device master data file, the name is
taken from the device master data file. The parameter name cannot subsequently
be changed. A parameter defined in the device master data file cannot be deleted.

Value The cold start value is configured in this column. In commissioning


mode, the current values are displayed in this column.
Data type Freelance data type of the component.
Byte, Bit the values for byte and bit describe the position of the Freelance
data type within a structured byte field. For simple data types and
non-structured byte fields, the values for byte and bit should be 0.
Byte Number of the first byte in the structured byte field.
Bit Number of the first bit in the start byte of the structured byte field.

30 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

Length Length of the DPV1 parameter.For simple data types the length is
stated in bits, while for BYTE Arrays and UserDS bytes are used
The length of BYTE Arrays and UserDS is stated in bytes. The fields for entering
the length of BYTE Arrays are therefore highlighted in color.

Slot, Index The values for slot and index are used to address the DPV1
parameter in the device. For further information, please see the
device manual of the respective vendor.
Slot Slot number for addressing a slot in the PROFIBUS device
Permissible range: 0 .. 254 (255 = Reserved.)
Index Index for addressing the desired data within a slot.
Permissible range: 0 .. 254 (255 = Reserved.)
Access The value specifies the access to the DPV1 parameter on the
PROFIBUS device.
R/W Read and write access to the parameter.
R Read access only to the parameter.
W Write access only to the parameter.
W Addressing is configured and loaded in the device.
R Addressing is first read from the device object directory in
commissioning mode and then used for all further device accesses.
This addressing is only possible if the device supports reading from
the object directory. For further information, please see the vendor's
manual.
Load The value specifies whether the parameter is loaded with Load all
DPV1 Parameters or not.
A DPV1 parameter which cannot be written cannot be loaded wit Load all DPV1
Parameters either.
Parameters which have been defined as structured data types or BYTE Arrays
can only be written if no gaps were left during definition of the data type.

Load-Seq. The value specifies the sequence in which the DPV1 parameters are
loaded with Load all DPV1 Parameters.

2PAA105800R0101_Eng_Manual_S700_Modules 31
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or Radio-Button can
be configured in the dialog editor.
After the DPV1 parameters have been defined, individual
parameterization tabs can be created with the dialog editor.
Read Elem. Used to configure HART commands.
Module Name of the associated module.
DPV1 parameter can be accessed via OPC. The name of the DPV1 parameter is
used as an OPC name. If the name contains space characters or special characters, it
is recommended that an alias be defined. Some OPC clients cannot resolve names
with space characters or special characters.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

32 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

Tab Force/Substitute

DC705F_force.bmp

Component
Name of the component for which force values and default values
are specified.
Type
Data type of the component for which force values and default
values are specified.
Hold last value
This option can be selected for analog inputs, only.
In the event of a fault the last valid value is held.
The last value is not used.

2PAA105800R0101_Eng_Manual_S700_Modules 33
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Substitute valueThis option can be selected for analog inputs, only.


In the event of a fault, the substitute value entered here is further
processed.
If both Hold last value is checked and a Substitute value is also given, then in the
event of a fault the last value is held.

Force active Specifies whether the configured force value is used.

Forcing is enabled.
Forcing is disabled.
Force value The value entered here is further processed when forcing is on.

Tab PROFIBUS Slave

DC705F_PROFIBUS_Slave.bmp

This tab allows the user to set the parameters for the PROFIBUS Slave.

34 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

Slave Parameters
Error LED/Failsafe Function
Setting for the Error LED and Failsafe function of the PROFIBUS
slave.

Tab IO Module

DC705F_IO_Module.bmp

This tab allows the user to set the parameters for the Digital I/Os in the module.
IO Parameters
Check Supply
Enable/disable supervision of power supply
Input Delay
Delay for the Digital Input channels
Detect short circ. at outputs

2PAA105800R0101_Eng_Manual_S700_Modules 35
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Enable/disable detection of short circuit at the output channels


Behaviour outputs at comm.fault
Set the behaviour of output channels on PROFIBUS
communication failure
E.g. Last value or Substitute value
Substitute value outputs
Set the value for the outputs in case of communication failure

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor – Input

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. For details refer 3BDD012503Rxxxx Engineering
Manual, System Configuration, Section 3, Hardware Structure.

36 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

Input.bmp

Component Output (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

I/O Editor – Output

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

2PAA105800R0101_Eng_Manual_S700_Modules 37
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

Output.bmp

Component Output (O0 to O7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

38 2PAA105800R0101_Eng_Manual_S700_Modules
Section 1 PROFIBUS setup with S700 IO Modules PROFIBUS Slave Interface

I/O Editor – Diagnosis

Diagnosis.bmp

Component: Name of the channel error type.


Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

2PAA105800R0101_Eng_Manual_S700_Modules 39
PROFIBUS Slave Interface Section 1 PROFIBUS setup with S700 IO Modules

40 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules

General
Overview of the S700 IO Modules
Abbreviation Object description
AX 721F Analog input/output module
AX 722F Analog input/output module
AC 722F Analog input/output module
AI 723F Analog input module
AI 731F Analog input module
AO 723F Analog output module
DX 722F Digital input/output module
DX 731F Digital input/output module
DC 722F Digital input/output module
DC 723F Digital input/output module
DC 732F Digital input/output module
DI 724F Digital input module
CD 722F Frequency Input Module
DA 701F Digital/Analog input/output module
The modules above will be available in the Hardware Manager of the Control
Builder F after import of the GSD file.

2PAA105800R0101_Eng_Manual_S700_Modules 41
Analog input/output module AX 721F Section 2 S700 IO Modules

Analog input/output module AX 721F


The analog input/output module AX 721F provides 4 configurable analog inputs
and 4 configurable analog outputs.

AX721_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: Free text of up to 12 characters can be entered here
Long text: Free text of up to 30 characters can be entered here.

Tab Module data


Data for the module is displayed in this tab.
Input data
Consistency The consistency of the data transfer from the module to the slave is
displayed.

42 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Length The length of the data transferred from the module to the slave is
displayed.
Output data
Consistency The consistency of the data transfer from the slave to the module is
displayed.
Length The length of the data transferred from the slave to the module is
displayed.
Configuration bytes
The sequence of bytes for the configuration of the module specified
in the device master data file.

Tab User

AX721_user.bmp

Length Displays the number of bytes used for parameter setting. Generated
by the system and cannot be edited.

2PAA105800R0101_Eng_Manual_S700_Modules 43
Analog input/output module AX 721F Section 2 S700 IO Modules

Name Name of the user parameter.


Value The cold start value is configured in this column. In commissioning
mode, the current values are displayed in this column.
If an analog input is configured as a digital input, the data type automatically
changes from REAL to BOOL. When changing back a digital input to an analog
input, the data type becomes REAL again.

Check supply
When this function is activated, the process voltage (supply voltage)
is checked by the module. If the voltage is low or no voltage is
applied, an alarm is generated.
ON Checking of supply voltage is enabled.
OFF Checking of supply voltage is disabled.
Behaviour outputs at comm. fault
This module allows configuring the behaviour of outputs at
communication error. The following options are available.
Last value unlimited
Substitute value unlimited
Last value 5 sec
Substitute value 5 sec
Last value 10 sec
Substitute value 10 sec
Substitute value
The configured substitute value is used.

If one of the Last value options are selected for Behaviour outputs at comm. fault
then the substitute value for OutChannel 0 Substitute value should be zero for
channel 0.

44 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Range The range that can be selected for the corresponding input. The
following ranges are available:

Type Value ranges


Not used 0
Analog Input 0...20mA
4...20mA
Analog U 0...10V
-10V...+10V
Analog Pt100(2w) or -50C...+70C
Pt100(3w) -50C...+400C
Analog Pt1000 -50C...+400C
Analog Ni1000 -50C...+150C
Digital input –

The value of an unused channel is automatically set to 0. The Force/Substitute tab


only displays those channels that are configured here.

Wire The wiring type or operating mode of the channel.


2 Connection in 2-wire technique
3 Connection in 3-wire technique
Differential input
Differential input can be selected for analog voltage inputs (Analog
U), only.
Data type Freelance data type of the component.
For data which is described as a bit field (for example
"Reaction_to_PRO.."), Freelance data types such as BYTE or
WORD are used. The PROFIBUS data type bit is changed to the
Freelance data type BOOL.

2PAA105800R0101_Eng_Manual_S700_Modules 45
Analog input/output module AX 721F Section 2 S700 IO Modules

Byte,Bit,Length
The values for Byte, Bit and Length describe the position of the
Freelance data type in the parameter block. The bit fields
defined in this way always start at bit 0 in the Freelance data
type.
Byte Number of the first byte in the parameter block.
Bit Number of the first bit in the start byte of the parameter block.
Length Length of the bit field in the parameter block.
Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or radio button can be
configured in the dialog editor.After the user parameters have been
defined, individual parameterization tabs can be created with the
dialog editor.
Comments Comments on the description of the component. The allocation of
comments is optional.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

46 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Tab DPV1

AX721_DPV1.bmp

Name Name of the DPV1 parameter.


If the DPV1 parameter is described in the device master data file, the name is
taken from the device master data file. The parameter name cannot subsequently
be changed. A parameter defined in the device master data file cannot be deleted.

Value The cold start value is configured in this column. In commissioning


mode, the current values are displayed in this column.
Data type Freelance data type of the component.
Byte, Bit the values for byte and bit describe the position of the Freelance
data type within a structured byte field. For simple data types and
non-structured byte fields, the values for byte and bit should be 0.
Byte Number of the first byte in the structured byte field.

2PAA105800R0101_Eng_Manual_S700_Modules 47
Analog input/output module AX 721F Section 2 S700 IO Modules

Bit Number of the first bit in the start byte of the structured byte field.
Length Length of the DPV1 parameter.For simple data types the length is
stated in bits, while for BYTE Arrays and UserDS bytes are used
The length of BYTE Arrays and UserDS is stated in bytes. The fields for entering
the length of BYTE Arrays are therefore highlighted in color.

Slot, Index The values for slot and index are used to address the DPV1
parameter in the device. For further information, please see the
device manual of the respective vendor.
Slot Slot number for addressing a slot in the PROFIBUS device
Permissible range: 0 .. 254 (255 = Reserved.)
Index Index for addressing the desired data within a slot.
Permissible range: 0 .. 254 (255 = Reserved.)
Access The value specifies the access to the DPV1 parameter on the
PROFIBUS device.
R/W Read and write access to the parameter.
R Read access only to the parameter.
W Write access only to the parameter.
W Addressing is configured and loaded in the device.
R Addressing is first read from the device object directory in
commissioning mode and then used for all further device accesses.
This addressing is only possible if the device supports reading from
the object directory. For further information, please see the vendor's
manual.
Load The value specifies whether the parameter is loaded with Load all
DPV1 Parameters or not.
A DPV1 parameter which cannot be written cannot be loaded wit Load all DPV1
Parameters either.
Parameters which have been defined as structured data types or BYTE Arrays
can only be written if no gaps were left during definition of the data type.

Load-Seq. The value specifies the sequence in which the DPV1 parameters are
loaded with Load all DPV1 Parameters.

48 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or Radio-Button can
be configured in the dialog editor.
After the DPV1 parameters have been defined, individual
parameterization tabs can be created with the dialog editor.
Read Elem. Used to configure HART commands.
Module Name of the associated module.
DPV1 parameter can be accessed via OPC. The name of the DPV1 parameter is
used as an OPC name. If the name contains space characters or special characters, it
is recommended that an alias be defined. Some OPC clients cannot resolve names
with space characters or special characters.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

2PAA105800R0101_Eng_Manual_S700_Modules 49
Analog input/output module AX 721F Section 2 S700 IO Modules

Tab Force and Substitute Value

AX721_force.bmp

Component
Name of the component for which force values and default values
are specified.
Type
Data type of the component for which force values and default
values are specified.
Hold last value
This option can be selected for analog inputs, only.
In the event of a fault the last valid value is held.
The last value is not used.
Substitute valueThis option can be selected for analog inputs, only.
In the event of a fault, the substitute value entered here is further
processed.
If both Hold last value is checked and a Substitute value is also given, then in the
event of a fault the last value is held.

50 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Force active Specifies whether the configured force value is used.

Forcing is enabled.
Forcing is disabled.
Force value The value entered here is further processed when forcing is on.

Tab Module Parameters

AX721_ud1.bmp

Check Supply
Enable/disable supervision of power supply
Analog data format
Data format for the analog values

2PAA105800R0101_Eng_Manual_S700_Modules 51
Analog input/output module AX 721F Section 2 S700 IO Modules

Behaviour outputs at comm. fault


Set the behaviour of output channels on PROFIBUS
communication failure
E.g. Last value or Substitute value
Channel O0 Substitute Value
OutChannel 0 Substitute value
Set the value for the output 0 in case of communication failure

Tab Inputs 0-3

Channel X
InChannel x configuration
Type of the Input measurement (voltage, current, RTD)

52 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

InChannel x checks
Enable Plausibility check for cut wire, short circuit

x is the channel number for the input channels

Tab Outputs 0-3

Channel X
OutChannel x configuration
Type of the Input measurement (voltage, current, RTD)
OutChannel x checks
Enable Plausibility check for cut wire, short circuit

2PAA105800R0101_Eng_Manual_S700_Modules 53
Analog input/output module AX 721F Section 2 S700 IO Modules

x is the channel number for the input channels

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

54 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Tab Input

AX721_IOEditor_input.bmp

Component Output (I0 to I3) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

2PAA105800R0101_Eng_Manual_S700_Modules 55
Analog input/output module AX 721F Section 2 S700 IO Modules

Tab Output

AX721_IOEditor_output.bmp

Component Output (O0 to O3) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

56 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 721F

Tab Diagnosis

AX721_IOEditor_diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component (see table).
Variable: The variable name.
Comment: Comment on the component diagnosis.

2PAA105800R0101_Eng_Manual_S700_Modules 57
Analog input/output module AX 721F Section 2 S700 IO Modules

Object data: Analog input/output module AX 721F

Ac-
Name Data type Conf. Comment
cess
Parameter definition mask
CheckSupply BOOL
EASid INT no RO Module location
SrvNO STRING8 no RO Firmware version
HrvNo STRING8 no RO Module hardware version
Ident STRING8 no RO ID number of the module type
ModName STRING8 no RO Name of the module type
Diagnostic data
STA UDINT no RO Bit-coded state
CHSTA UDINT no RO CHannel STAte, i.e. the state (over-
flow, underflow or short-circuit) of the
respective channel
NDR BOOL no RO New Data Ready, module is active, cy-
clic data transfer is in progress
ERR BOOL no RO Module defective
STI0 -ST3 INT no RO Stands for STatus Input
I0 - I3 REAL no RO
O0 - O3 REAL no RO

58 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Analog input/output module AX 722F


The analog input/output module AX 722F provides 8 configurable analog inputs
and 8 configurable analog outputs module wise electrically isolated.

AX722_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

Tab Module data


For further details refer to Tab Module data on page 42.

2PAA105800R0101_Eng_Manual_S700_Modules 59
Analog input/output module AX 722F Section 2 S700 IO Modules

Tab User

AX722_user.bmp

For further details refer Tab User on page 43.


Name Name of the input/output channel (I0 to I7) or (O0 to O7)
Value Type of input/output.
From O0 to O3 both current and voltage outputs are possible
From O4 to O7 only voltage outputs are possible

60 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Tab DPV1

AX722_DPV1.bmp

For further details refer Tab DPV1 on page 47.

2PAA105800R0101_Eng_Manual_S700_Modules 61
Analog input/output module AX 722F Section 2 S700 IO Modules

Tab Force and Substitute Value

AX722_Force_Sub.bmp

For further details refer Tab Force and Substitute Value on page 50.

62 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Tab Module Parameters

For further details refer Tab Module Parameters on page 51

2PAA105800R0101_Eng_Manual_S700_Modules 63
Analog input/output module AX 722F Section 2 S700 IO Modules

Tab Inputs (Ch0_Ch3) Parameters

For further details refer Tab Inputs 0-3 on page 52

64 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Tab Inputs (Ch4-Ch7) Parameters

For further details refer Tab Inputs 0-3 on page 52

2PAA105800R0101_Eng_Manual_S700_Modules 65
Analog input/output module AX 722F Section 2 S700 IO Modules

Tab Outputs (Ch0-Ch3) Parameters

For further details refer Tab Outputs 0-3 on page 53

66 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Tab Outputs (Ch4-Ch7) Parameters

For further details refer Tab Outputs 0-3 on page 53

Tab Info
This tab displays information on the version of the GSD and the S700 Template.

2PAA105800R0101_Eng_Manual_S700_Modules 67
Analog input/output module AX 722F Section 2 S700 IO Modules

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

Tab Input

AX722_IOEditor_Input.bmp

Component Output (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

68 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AX 722F

Tab Output

AX722_IOEditor_Output.bmp

Component Output (O0 to O7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 69
Analog input/output module AX 722F Section 2 S700 IO Modules

Tab Diagnosis

AX722_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

70 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Analog input/output module AC 722F


The analog input/output module AC 722F provides 8 configurable analog inputs or
outputs module wise electrically isolated.

AC722_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

Tab Module data


For further details refer Tab Module data on page 42.

2PAA105800R0101_Eng_Manual_S700_Modules 71
Analog input/output module AC 722F Section 2 S700 IO Modules

Tab User

AC722_User.bmp

For further details refer Tab User on page 43.


Name Name of the input/output channel (I0 to I7) or (O0 to O7)
Value Type of input/output.
From O0 to O3 both current and voltage outputs are possible
From O4 to O7 only voltage outputs are possible

72 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Tab DPV1

AC722_DPV1.bmp

For further details refer Tab DPV1 on page 47.

2PAA105800R0101_Eng_Manual_S700_Modules 73
Analog input/output module AC 722F Section 2 S700 IO Modules

Tab Force and Substitute Value

AC722_Force_Sub.bmp

For further details refer Tab Force and Substitute Value on page 50.

74 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Tab Module Parameters

AC722_ud1.bmp

For further details refer Tab Module Parameters on page 51.

2PAA105800R0101_Eng_Manual_S700_Modules 75
Analog input/output module AC 722F Section 2 S700 IO Modules

Tab Inputs (Ch0-Ch3) Parameters

AC722_ud2.bmp

For further details refer Tab Inputs 0-3 on page 52.

76 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Tab Inputs (Ch4-Ch7) Parameters

AC722_ud3.bmp

For further details refer Tab Inputs 0-3 on page 52.

2PAA105800R0101_Eng_Manual_S700_Modules 77
Analog input/output module AC 722F Section 2 S700 IO Modules

Tab Outputs (Ch0-Ch3) Parameters

AC722_ud4.bmp

For further details refer Tab Outputs 0-3 on page 53.

78 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Tab Outputs (Ch4-Ch7) Parameters

AC722_ud5.bmp

For further details refer Tab Inputs 0-3 on page 52.

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

2PAA105800R0101_Eng_Manual_S700_Modules 79
Analog input/output module AC 722F Section 2 S700 IO Modules

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

Tab Input

AC722_IOEdit_Input.bmp

Component Output (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

80 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AC 722F

Tab Output

AC722_IOEdit_Output.bmp

Component Output (O0 to O7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 81
Analog input/output module AC 722F Section 2 S700 IO Modules

Tab Diagnosis

AC722_IOEdit_Diag.bmp

Component: Name of the channel error type.Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

82 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 723F

Analog input/output module AI 723F


The analog input/output module AI 723F provides 16 configurable analog inputs
module wise electrically isolated.

AI723_Mod_Data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: Free text of up to 12 characters.
Long text: Free text of up to 30 characters.

Tab Module data


For further details refer Tab Module data on page 42.

2PAA105800R0101_Eng_Manual_S700_Modules 83
Analog input/output module AI 723F Section 2 S700 IO Modules

Tab User

AI723_User.bmp

For further details refer Tab User on page 43.


Name Name of the input channel (I0 to I15)
Value Type of input.

84 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 723F

Tab DPV1

AI723_DPV1.bmp

For further details refer Tab DPV1 on page 47.

2PAA105800R0101_Eng_Manual_S700_Modules 85
Analog input/output module AI 723F Section 2 S700 IO Modules

Tab Force and Substitute Value

AI723_Force.bmp

For further details refer Tab Force and Substitute Value on page 50.

86 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 723F

Tab Module Parameters

AI723_ud1.bmp

For further details refer to Tab Module Parameters on page 51.

2PAA105800R0101_Eng_Manual_S700_Modules 87
Analog input/output module AI 723F Section 2 S700 IO Modules

Tab Inputs 0-4

AI723_ud2.bmp

For further details refer to Tab Inputs 0-3 on page 52.


Tab Inputs 4-7, Tab Inputs 8-11 and Tab Inputs12-15 are similar to Tab Inputs
0-4.

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

88 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 723F

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

Tab Input

AI723_IOEditor_input.bmp

Component Output (I0 to I15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 89
Analog input/output module AI 723F Section 2 S700 IO Modules

Tab Diagnosis

AI723_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

90 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 731F

Analog input/output module AI 731F


The analog input/output module AI 731F provides 8 configurable analog inputs
module wise electrically isolated.

AI731_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

Tab Module data


For further details Tab Module data on page 42.

2PAA105800R0101_Eng_Manual_S700_Modules 91
Analog input/output module AI 731F Section 2 S700 IO Modules

Tab User

AI731_User_parm.bmp

For further details Tab User on page 43.


Name Name of the input channel (I0 to I7)
Value Type of input.
Noise rejection The options available are
50 Hz
60 Hz
none
Compensation The options available are
Internal Compensation
External with temperature value
An external temperature value is transferred via the IO bus to the module (output
value). It can be used by every TC channel for compensation purpose.

92 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 731F

The following values are possible

Channel Compensation Default


0 1,2,3,E,I internal
1 0,2,3,E,I internal
2 0,1,3,E,I internal
3 0,1,2,E,I internal
4 5,6,7,E,I internal
5 4,6,7,E,I internal
6 4,5,7,E,I internal
7 4,5,6,E,I internal

Tab DPV1

AI731_DPV1.bmp

2PAA105800R0101_Eng_Manual_S700_Modules 93
Analog input/output module AI 731F Section 2 S700 IO Modules

For further details refer Tab DPV1 on page 47.

Tab Force and Substitute

AI731_Force_Sub.bmp

For further details refer Tab Force and Substitute Value on page 50.

94 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 731F

Tab Module Parameters

AI731_ud1.bmp

For further details refer Tab Module Parameters on page 51.

2PAA105800R0101_Eng_Manual_S700_Modules 95
Analog input/output module AI 731F Section 2 S700 IO Modules

Tab Inputs 0-1

AI731_ud1.bmp

Input channel x configuration


Type of input channel (Voltage, Current, RTD, Thermocouple,
Resistance)
Input channel x checks

Compensation channel x
Type of compensation for thermocouple inputs (External, Internal,
other channel within same group)
Noise rejection Channel x
Setting for noise rejection filter for analog input

Tab Inputs 2-3, Inputs 4-5, Inputs 6-7 are similar to the Tab Inputs 0-1.

96 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AI 731F

Tab Info
This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

Tab Input

AI731_IOEditor_Input.bmp

Component Output (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.

2PAA105800R0101_Eng_Manual_S700_Modules 97
Analog input/output module AI 731F Section 2 S700 IO Modules

Comment: Comment for the component.

Tab Diagnosis

AI731_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

98 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AO 723F

Analog input/output module AO 723F


The analog output module AO 723F provides 16 configurable analog outputs
module wise electrically isolated.

AO723_Mod_data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

Tab Module data


For further details Tab Module data on page 42.

2PAA105800R0101_Eng_Manual_S700_Modules 99
Analog input/output module AO 723F Section 2 S700 IO Modules

Tab User

AO723_User_para1.bmp

For further details refer Tab User on page 43.


Name Name of the output channel (O0 to O15)
Value Type of output.
From O0 to O3 both current and voltage outputs are possible
From O4 to O7 only voltage outputs are possible
If one of the Last value options are selected for Behaviour outputs at comm. fault
then the substitute value for Channel 0 and Channel 8 should be zero.

100 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AO 723F

Tab DPV1

AO723_DPV1.bmp

For further details refer Tab DPV1 on page 47.

2PAA105800R0101_Eng_Manual_S700_Modules 101
Analog input/output module AO 723F Section 2 S700 IO Modules

Tab Force and Substitute

AO723_Force_Sub.bmp

For further details refer Tab Force and Substitute Value on page 50.

102 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AO 723F

Tab Module Parameters

AO723_ud1.bmp

For further details refer Tab Module Parameters on page 51.

2PAA105800R0101_Eng_Manual_S700_Modules 103
Analog input/output module AO 723F Section 2 S700 IO Modules

Tab Outputs 0-3

AO723_ud2.bmp

For further details refer Tab Outputs 0-3 on page 53


Tab Outputs 4-7, Tab Outputs 8-11 and Tab Outputs 12-15 are similar to Tab
Outputs 0-3.

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

104 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Analog input/output module AO 723F

Tab Output

AO723_IOEditor_Output.bmp

Component Output (O0 to O15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 105
Analog input/output module AO 723F Section 2 S700 IO Modules

Tab Diagnosis

AO723_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

106 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Digital input module DX 722F


The digital input/output module DX 722F is designed for connecting 8 digital inputs
24V DC, module wise electrically isolated and 8 relay output signals.

Module data

DX722_Module_data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: Free text of up to 12 characters can be entered.
Long text: Free text of up to 30 characters can be entered.

Tab Module data


Data for the module is displayed in this tab.

2PAA105800R0101_Eng_Manual_S700_Modules 107
Digital input module DX 722F Section 2 S700 IO Modules

Input data
Consistency The consistency of the data transfer from the module to the slave is
displayed.
Length The length of the data transferred from the module to the slave is
displayed.
Output data
Consistency The consistency of the data transfer from the slave to the module is
displayed.
Length The length of the data transferred from the slave to the module is
displayed.
Configuration bytes
The sequence of bytes for the configuration of the module specified
in the device master data file.

Tab User

DX722_User_Param.bmp

108 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Length Displays the number of bytes used for parameter setting. Is


generated by the system and cannot be edited.
Name Name of the user parameter.
Value The cold start value is configured in this column. In commissioning
mode, the current values are displayed in this column.
Check supply
When this function is activated, the process voltage (supply voltage)
is checked by the module. If the voltage is low or no voltage is
applied, an alarm is generated.
ON Checking of supply voltage is enabled.
OFF Checking of supply voltage is disabled.
Input delay
With activated supply checking, the input delay for the alarm can be
defined here. The following values can be selected:
0.1 ms for quick processes with frequently changing signal
1 ms for slower processes
8 ms if spikes are to be filtered out reliably
32 ms if low-pass behavior is wanted.
Behaviour outputs at comm. fault
This module allows configuring the behaviour of outputs at
communication error
Substitute value
The configured substitute value is used.
Data type Freelance data type of the component.
For data which is described as a bit field (for example
"Reaction_to_PRO.."), Freelance data types such as BYTE or
WORD are used. The PROFIBUS data type bit is changed to the
Freelance data type BOOL.
Byte,Bit,Length
The values for Byte, Bit and Length describe the position of the
Freelance data type in the parameter block. The bit fields

2PAA105800R0101_Eng_Manual_S700_Modules 109
Digital input module DX 722F Section 2 S700 IO Modules

defined in this way always start at bit 0 in the Freelance data


type.
Byte Number of the first byte in the parameter block.
Bit Number of the first bit in the start byte of the parameter block.
Length Length of the bit field in the parameter block.
Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or radio button can be
configured in the dialog editor.After the user parameters have been
defined, individual parameterization tabs can be created with the
dialog editor.
Comments Comments on the description of the component. The allocation of
comments is optional.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

110 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Tab DPV1

DX722_DPV1.bmp

Name Name of the DPV1 parameter.


If the DPV1 parameter is described in the device master data file, the name is
taken from the device master data file. The parameter name cannot subsequently
be changed. A parameter defined in the device master data file cannot be deleted.

Value The cold start value is configured in this column. In commissioning


mode, the current values are displayed in this column.
Data type Freelance data type of the component.
Byte, Bit the values for byte and bit describe the position of the Freelance
data type within a structured byte field. For simple data types and
non-structured byte fields, the values for byte and bit should be 0.
Byte Number of the first byte in the structured byte field.
Bit Number of the first bit in the start byte of the structured byte field.

2PAA105800R0101_Eng_Manual_S700_Modules 111
Digital input module DX 722F Section 2 S700 IO Modules

Length Length of the DPV1 parameter. For simple data types the length is
stated in bits, while for BYTE Arrays and UserDS bytes are used
The length of BYTE Arrays and UserDS is stated in bytes. The fields for entering
the length of BYTE Arrays are therefore highlighted in color.

Slot, Index The values for slot and index are used to address the DPV1
parameter in the device. For further information, please see the
device manual of the respective vendor.
Slot Slot number for addressing a slot in the PROFIBUS device
Permissible range: 0 .. 254 (255 = Reserved.)
Index Index for addressing the desired data within a slot.
Permissible range: 0 .. 254 (255 = Reserved.)
Access The value specifies the access to the DPV1 parameter on the
PROFIBUS device.
R/W Read and write access to the parameter.
R Read access only to the parameter.
W Write access only to the parameter.
W Addressing is configured and loaded in the device.
R Addressing is first read from the device object directory in
commissioning mode and then used for all further device accesses.
This addressing is only possible if the device supports reading from
the object directory. For further information, please see the vendor's
manual.
Load The value specifies whether the parameter is loaded with Load all
DPV1 Parameters or not.
A DPV1 parameter which cannot be written cannot be loaded wit Load all DPV1
Parameters either.
Parameters which have been defined as structured data types or BYTE Arrays
can only be written if no gaps were left during definition of the data type.

Load-Seq. The value specifies the sequence in which the DPV1 parameters are
loaded with Load all DPV1 Parameters.

112 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or Radio-Button can
be configured in the dialog editor.
After the DPV1 parameters have been defined, individual
parameterization tabs can be created with the dialog editor.
Read Elem. Used to configure HART commands.
Module Name of the associated module.
DPV1 parameter can be accessed via OPC. The name of the DPV1 parameter is
used as an OPC name. If the name contains space characters or special characters, it
is recommended that an alias be defined. Some OPC clients cannot resolve names
with space characters or special characters.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

2PAA105800R0101_Eng_Manual_S700_Modules 113
Digital input module DX 722F Section 2 S700 IO Modules

TAB Force and Substitute Value

DX722_Force_Sub.bmp

Component Name of the component for which force values and default values
are specified.
Type Data type of the component for which force values and default
values are specified.
Hold last value
This option can be selected for analog inputs, only.
In the event of a fault the last valid value is held.
The last value is not used.
Substitute valueThis option can be selected for analog inputs, only.
In the event of a fault, the substitute value entered here is further
processed.
If both Hold last value is checked and a Substitute value is also given, then in the
event of a fault the last value is held.

114 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Force active Specifies whether the configured force value is used.

Forcing is enabled.
Forcing is disabled.
Force value The value entered here is further processed when forcing is on.

Tab IO Parameters

Input Delay Delay for the Digital Input channels


Check Supply Enable/disable supervision of power supply

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

2PAA105800R0101_Eng_Manual_S700_Modules 115
Digital input module DX 722F Section 2 S700 IO Modules

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

Tab Input

DX722_IOEditor_Input.bmp

Component Input (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

116 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DX 722F

Tab Output

DX722_IOEditor_Output.bmp

Component Output (O0 to O7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 117
Digital input module DX 722F Section 2 S700 IO Modules

Tab Diagnosis

DX722_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

118 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DX 731F

Digital input/output module DX 731F


The digital input/output module DX 731F is designed for connecting 8 digital inputs
120/230V AC, module wise electrically isolated and 4 relay output signals.

Tab Module data

DX731_Mod_data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.
For further details refer Tab Module data on page 107.

2PAA105800R0101_Eng_Manual_S700_Modules 119
Digital input/output module DX 731F Section 2 S700 IO Modules

Tab User

DX731_User_Para.bmp

For further details refer Tab User on page 108.

120 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DX 731F

Tab DPV1

DX731_DPV1.bmp

For further details refer Tab DPV1 on page 111.

2PAA105800R0101_Eng_Manual_S700_Modules 121
Digital input/output module DX 731F Section 2 S700 IO Modules

Tab Force and Substitute Value

DX731_Force_Sub.bmp

For further details refer TAB Force and Substitute Value on page 114.

122 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DX 731F

Tab IO Parameters

DX731_ud1.bmp

For further details refer Tab IO Parameters on page 115

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

2PAA105800R0101_Eng_Manual_S700_Modules 123
Digital input/output module DX 731F Section 2 S700 IO Modules

Tab Input

DX731_IOEditor_Input.bmp

Component Input (I0 to I7) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

124 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DX 731F

Tab Output

DX731_IOEditor_Output.bmp

Component Output (O0 to O3) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 125
Digital input/output module DX 731F Section 2 S700 IO Modules

Tab Diagnosis

DX731_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

126 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 722F

Digital input/output module DC 722F


The digital input/output module DC 722F is designed for connecting 16
configurable 24 V DC input/output signals.

Tab Module data

DC722_Mod_Data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.
For further details refer Tab Module data on page 107.

2PAA105800R0101_Eng_Manual_S700_Modules 127
Digital input/output module DC 722F Section 2 S700 IO Modules

Tab User

DC722_User_Para.bmp

For further details refer Tab User on page 108.

128 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 722F

Tab DPV1

DC722_DPV1.bmp

For further details refer Tab DPV1 on page 111.

2PAA105800R0101_Eng_Manual_S700_Modules 129
Digital input/output module DC 722F Section 2 S700 IO Modules

Tab Force and Substitute Value

DC722_Force_Sub.bmp

For further details refer TAB Force and Substitute Value on page 114.

130 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 722F

Tab Module Parameters

DC722_ud1.bmp

For further details refer Tab IO Parameters on page 115

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

2PAA105800R0101_Eng_Manual_S700_Modules 131
Digital input/output module DC 722F Section 2 S700 IO Modules

Tab Input

DC722_IOEditor_input.bmp

Component Input (I0 to I15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

132 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 722F

Tab Output

DC722_IOEditor_output.bmp

Component Output (O0 to O15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 133
Digital input/output module DC 722F Section 2 S700 IO Modules

Tab Diagnosis

DC722_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

134 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 723F

Digital input/output module DC 723F


The digital input/output module DC 723F is designed for connecting 24
configurable 24 V DC input/output signals.

Tab Module data

DC723_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

For further details refer Tab Module data on page 107.

2PAA105800R0101_Eng_Manual_S700_Modules 135
Digital input/output module DC 723F Section 2 S700 IO Modules

Tab User

DC723_User_Para.bmp

For further details refer Tab User on page 108.

136 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 723F

Tab DPV1

DC723_DPV1.bmp

For further details refer Tab DPV1 on page 111.

2PAA105800R0101_Eng_Manual_S700_Modules 137
Digital input/output module DC 723F Section 2 S700 IO Modules

Tab Force and Substitute Value

DC723_Force_Sub.bmp

For further details refer TAB Force and Substitute Value on page 114.

138 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 723F

Tab Module Parameters

DC723_ud1.bmp

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

2PAA105800R0101_Eng_Manual_S700_Modules 139
Digital input/output module DC 723F Section 2 S700 IO Modules

Tab Input

DC723_IOEditor_input.bmp

Component Input (I0 to I23) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

140 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 723F

Tab Output

DC723_IOEditor_output.bmp

Component Output (O0 to O23) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 141
Digital input/output module DC 723F Section 2 S700 IO Modules

Tab Diagnosis

DC723_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

142 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 732F

Digital input/output module DC 732F


The digital input/output module DC 732F is designed for connecting 16 digital
inputs 24 V DC, 16 configurable digital inputs/outputs, module wise electrically
isolated.

Tab Module data

DC732_Mod_data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.
For further details refer Tab Module data on page 107.

2PAA105800R0101_Eng_Manual_S700_Modules 143
Digital input/output module DC 732F Section 2 S700 IO Modules

Tab User

DC732_User_Para.bmp

For further details refer Tab User on page 108.

144 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 732F

Tab DPV1

DC732_DPV1.bmp

For further details refer Tab DPV1 on page 111.

2PAA105800R0101_Eng_Manual_S700_Modules 145
Digital input/output module DC 732F Section 2 S700 IO Modules

Tab Force and Substitute Value

DC732_Force.bmp

For further details refer TAB Force and Substitute Value on page 114.

146 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 732F

Tab IO Parameters

DC732_ud1.bmp

For further details refer Tab IO Parameters on page 115

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

2PAA105800R0101_Eng_Manual_S700_Modules 147
Digital input/output module DC 732F Section 2 S700 IO Modules

Tab Input

DC732_IOEditor_Input.bmp

Component Input (I0 to I15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

148 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input/output module DC 732F

Tab Output

DC732_IOEditor_Output.bmp

Component Output (O0 to O15) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 149
Digital input/output module DC 732F Section 2 S700 IO Modules

Tab Diagnosis

DC732_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

150 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DI 724F

Digital input module DI 724F


The digital input module DI 724F is designed for connecting 32 binary 24 V DC
input signals, module wise electrically isolated.

Tab Module data

DI724_Mod_Data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.
For further details refer Tab Module data on page 107.

2PAA105800R0101_Eng_Manual_S700_Modules 151
Digital input module DI 724F Section 2 S700 IO Modules

Tab User

DI724_User_Para.bmp

For further details refer Tab User on page 108.

152 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DI 724F

Tab DPV1

DI724_DPV1.bmp

For further details refer Tab DPV1 on page 111.

2PAA105800R0101_Eng_Manual_S700_Modules 153
Digital input module DI 724F Section 2 S700 IO Modules

Tab Force and Substitute Value

DI724_force.bmp

For further details refer TAB Force and Substitute Value on page 114.

154 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DI 724F

Tab IO Parameters

DI724_ud1.bmp

For further details refer Tab IO Parameters on page 115

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data. See also 3BDD012503Rxxxx Engineering Manual,
System Configuration, Section 3, Hardware Structure.

2PAA105800R0101_Eng_Manual_S700_Modules 155
Digital input module DI 724F Section 2 S700 IO Modules

Tab Input

DI724_IOEditor_input.bmp

Component Input (I0 to I31) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

156 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital input module DI 724F

Tab Diagnosis

DI724_IOEditor_diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

2PAA105800R0101_Eng_Manual_S700_Modules 157
Frequency Input Module CD 722F Section 2 S700 IO Modules

Frequency Input Module CD 722F


The Frequency Input Module CD 722F is designed for connecting 2 encoder inputs
with 2 integrated 5-V-Power supplies for the encoders, 2 PWM outputs, 2 digital
inputs 24V DC, 8 configurable digital inputs/outputs 24V DC, module-wise
electrically isolated.

Tab Module data

CD722_mod.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.
For further details refer Tab Module data on page 107.

158 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

Tab User

CD722_User_Para.bmp

For further details refer Tab User on page 108.

2PAA105800R0101_Eng_Manual_S700_Modules 159
Frequency Input Module CD 722F Section 2 S700 IO Modules

Tab DPV1

CD722_DPV1.bmp

For further details refer Tab DPV1 on page 111.

160 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

Tab Force and Substitute Value

CD722_force.bmp

For further details refer TAB Force and Substitute Value on page 114.

2PAA105800R0101_Eng_Manual_S700_Modules 161
Frequency Input Module CD 722F Section 2 S700 IO Modules

Tab Module Parameters

CD722_ud1.bmp

For further details refer Tab Module Parameters on page 51.


Input Delay

Detection SC and sensors

162 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

Tab Encoder Input 1

This tab allows the user to configure the settings for the encoder channels (2
channels)
5V sensor 0 supply
Enable/disable the 5V Power Supply for the sensor
Freq Limit FC0
Frequency setting for the filter
Input Level FC0
Input voltage type (0-24VDC, 0-5VDC, differential, Sine 1vPP)
Mode Counter 0
Select the type of counter (1-1 Up/down counter, Incremental
encoder etc.)
SSI 0 code type

2PAA105800R0101_Eng_Manual_S700_Modules 163
Frequency Input Module CD 722F Section 2 S700 IO Modules

Binary code type


SSI 0 frequency
Setting for input Frequency (200 kHz, 1MHz)
SSI 0 Polling Time
Setting for Polling time
SSI 0 resolution bit
Number of bits resolution (e.g.16)
Tab Encoder Input 2 is similar to Tab Encoder Input 1.

Tab PWM DO

This tab allows the user to configure the 2 PWM digital output channels.
Channel confg Output O0 and O1

164 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

Type of the output channel (Digital output, Pulse output or PWM


Output)

Tab Inputs 24VDI

This tab allows the user to configure the 2 digital input channels and 8 channels
configurable as digital input channels.
Channel Config Input Ix
Type of digial input (eg. Touch, reset, SET, RPI etc.)
x = 3,11,4,5,67,12,13,14,15

2PAA105800R0101_Eng_Manual_S700_Modules 165
Frequency Input Module CD 722F Section 2 S700 IO Modules

Tab Outputs

This tab allows the user to configure the 8 configurable digital channels as output
channels
Channel Config Output Cx
Type of digial output (ENDV)
x = 4,5,6,7,12,13,14,15

Tab Info

This tab displays information on the version of the GSD and the S700 Template.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,

166 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

outputs and diagnostic data.

Tab Input

CD722_IOEditor_Input.bmp

Component Output (I0 to I1) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 167
Frequency Input Module CD 722F Section 2 S700 IO Modules

Tab Output

CD722_IOEditor_Ouput.bmp

Component Output (O0 to O7)that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

168 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Frequency Input Module CD 722F

Tab Diagnosis

CD722_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component.
Variable: The variable name.
Comment: Comment on the component diagnosis.

2PAA105800R0101_Eng_Manual_S700_Modules 169
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Digital Analog input/output module DA 701F


The Digital analog input/output module DA 701F provides 4 configurable analog
inputs and 2 configurable analog outputs module wise electrically isolated.

Tab Module data

DA701_Mod_Data.bmp

General data
Name: Full name of the module. The name is taken over from the tree
structure.
Short text: You can enter free text of up to 12 characters.
Long text: You can enter free text of up to 30 characters.

170 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Module data
Data for the module is displayed in this tab.
Input data
Consistency The consistency of the data transfer from the module to the slave is
displayed.
Length The length of the data transferred from the module to the slave is
displayed.
Output data
Consistency The consistency of the data transfer from the slave to the module is
displayed.
Length The length of the data transferred from the slave to the module is
displayed.
Configuration bytes
The sequence of bytes for the configuration of the module specified
in the device master data file.

2PAA105800R0101_Eng_Manual_S700_Modules 171
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Tab User

DA701_User_Para.bmp

Length Displays the number of bytes used for parameter setting. Is


generated by the system and cannot be edited.
Name Name of the user parameter.
Value The cold start value is configured in this column. In commissioning
mode, the current values are displayed in this column.
Check supply
When this function is activated, the process voltage (supply voltage)
is checked by the module. If the voltage is low or no voltage is
applied, an alarm is generated.
ON Checking of supply voltage is enabled.
OFF Checking of supply voltage is disabled.
Input delay
With activated supply checking, the input delay for the alarm can be
defined here. The following values can be selected:
0.1 ms for quick processes with frequently changing signal

172 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

1 ms for slower processes


8 ms if spikes are to be filtered out reliably
32 ms if low-pass behavior is wanted.
Behaviour outputs at comm. fault
This module allows configuring the behaviour of outputs at
communication error
Substitute value
The configured substitute value is used.
Data type Freelance data type of the component.
For data which is described as a bit field (for example
"Reaction_to_PRO.."), Freelance data types such as BYTE or
WORD are used. The PROFIBUS data type bit is changed to the
Freelance data type BOOL.
Byte,Bit,Length
The values for Byte, Bit and Length describe the position of the
Freelance data type in the parameter block. The bit fields
defined in this way always start at bit 0 in the Freelance data
type.
Byte Number of the first byte in the parameter block.
Bit Number of the first bit in the start byte of the parameter block.
Length Length of the bit field in the parameter block.
Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or radio button can be
configured in the dialog editor.After the user parameters have been
defined, individual parameterization tabs can be created with the
dialog editor.
Comments Comments on the description of the component. The allocation of
comments is optional.

2PAA105800R0101_Eng_Manual_S700_Modules 173
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

OPC Access The user parameter can be accessed via OPC.


OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

Tab DPV1

DA701_DPV1.bmp

Name Name of the DPV1 parameter.


If the DPV1 parameter is described in the device master data file, the name is
taken from the device master data file. The parameter name cannot subsequently
be changed. A parameter defined in the device master data file cannot be deleted.

Value The cold start value is configured in this column. In commissioning


mode, the current values are displayed in this column.
Data type Freelance data type of the component.

174 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Byte, Bit the values for byte and bit describe the position of the Freelance
data type within a structured byte field. For simple data types and
non-structured byte fields, the values for byte and bit should be 0.
Byte Number of the first byte in the structured byte field.
Bit Number of the first bit in the start byte of the structured byte field.
Length Length of the DPV1 parameter.For simple data types the length is
stated in bits, while for BYTE Arrays and UserDS bytes are used
The length of BYTE Arrays and UserDS is stated in bytes. The fields for entering
the length of BYTE Arrays are therefore highlighted in color.

Slot, Index The values for slot and index are used to address the DPV1
parameter in the device. For further information, please see the
device manual of the respective vendor.
Slot Slot number for addressing a slot in the PROFIBUS device
Permissible range: 0 .. 254 (255 = Reserved.)
Index Index for addressing the desired data within a slot.
Permissible range: 0 .. 254 (255 = Reserved.)
Access The value specifies the access to the DPV1 parameter on the
PROFIBUS device.
R/W Read and write access to the parameter.
R Read access only to the parameter.
W Write access only to the parameter.
W Addressing is configured and loaded in the device.
R Addressing is first read from the device object directory in
commissioning mode and then used for all further device accesses.
This addressing is only possible if the device supports reading from
the object directory. For further information, please see the vendor's
manual.

2PAA105800R0101_Eng_Manual_S700_Modules 175
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Load The value specifies whether the parameter is loaded with Load all
DPV1 Parameters or not.
A DPV1 parameter which cannot be written cannot be loaded wit Load all DPV1
Parameters either.
Parameters which have been defined as structured data types or BYTE Arrays
can only be written if no gaps were left during definition of the data type.

Load-Seq. The value specifies the sequence in which the DPV1 parameters are
loaded with Load all DPV1 Parameters.
Min / Max The "Min" and "Max" columns are required for input in the dialog
editor. Thus input elements such as combobox or Radio-Button can
be configured in the dialog editor.
After the DPV1 parameters have been defined, individual
parameterization tabs can be created with the dialog editor.
Read Elem. Used to configure HART commands.
Module Name of the associated module.
DPV1 parameter can be accessed via OPC. The name of the DPV1 parameter is
used as an OPC name. If the name contains space characters or special characters, it
is recommended that an alias be defined. Some OPC clients cannot resolve names
with space characters or special characters.
OPC Access The user parameter can be accessed via OPC.
OPC Shortname
Alias of the user parameter if it is accessible on the OPC server.

176 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Tab Force and Substitute Value

AX722_Force_Sub.bmp

Component Name of the component for which force values and default values
are specified.
Type Data type of the component for which force values and default
values are specified.
Hold last value
This option can be selected for analog inputs, only.
In the event of a fault the last valid value is held.
The last value is not used.
Substitute value
This option can be selected for analog inputs, only.
In the event of a fault, the substitute value entered here is further
processed.
If both Hold last value is checked and a Substitute value is also given, then in the
event of a fault the last value is held.

2PAA105800R0101_Eng_Manual_S700_Modules 177
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Force active Specifies whether the configured force value is used.

Forcing is enabled.
Forcing is disabled.
Force value The value entered here is further processed when forcing is on.

Tab Module Parameters

This tab allows the user to set the parameters for the Digital I/Os in the module.
IO Parameters
Check Supply
Enable/disable supervision of power supply
Behaviour outputs at comm.fault

178 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Set the behaviour of output channels on PROFIBUS


communication failure
E.g. Last value or Substitute value
Analog data format

Detect short circ. at outputs


Enable/disable detection of short circuit at the output channels
Input Delay
Delay for the Digital Input channels

Tab Analog Inputs

DA701_ud2.bmp

For further details refer Tab Inputs 0-3 on page 52.

2PAA105800R0101_Eng_Manual_S700_Modules 179
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

TAB Analog Outputs

DA701_ud2.bmp

For further details refer Tab Outputs 0-3 on page 53.

I/O Editor

In Configuration mode, right-click on the module > I/O editor

With the I/O editor, it is possible to define the individual components for inputs,
outputs and diagnostic data.

180 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Tab Input

DA701_IOEditor_Input.bmp

Component Output (I0 to I3) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

2PAA105800R0101_Eng_Manual_S700_Modules 181
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Tab Output

DA701_IOEditor_Output.bmp

Component Output (O0 to O1) that is to be edited.


Data type: The data type (REAL or BOOL) of the component.
Variable: The variable name.
Comment: Comment for the component.

182 2PAA105800R0101_Eng_Manual_S700_Modules
Section 2 S700 IO Modules Digital Analog input/output module DA 701F

Tab Diagnosis

DA701_IOEditor_Diag.bmp

Component: Name of the channel error type. Diagnostic components are


available from Channel 0 to 63.
Data type: The data type of the component (see table).
Variable: The variable name.
Comment: Comment on the component diagnosis.

2PAA105800R0101_Eng_Manual_S700_Modules 183
Digital Analog input/output module DA 701F Section 2 S700 IO Modules

Ac-
Name Data type Conf. Comment
cess
Parameter definition mask
CheckSupply BOOL
EASid INT no RO Module location
SrvNO STRING8 no RO Firmware version
HrvNo STRING8 no RO Module hardware version
Ident STRING8 no RO ID number of the module type
ModName STRING8 no RO Name of the module type
Diagnostic data
STA UDINT no RO Bit-coded state
CHSTA UDINT no RO CHannel STAte, i.e. the state (overflow,
underflow or short-circuit) of the re-
spective channel
NDR BOOL no RO New Data Ready, module is active, cy-
clic data transfer is in progress
ERR BOOL no RO Module defective
STI0 -STI23 INT no RO Stands for STatus Input
I0 - I23 REAL no RO
O0 - O23 REAL no RO

184 2PAA105800R0101_Eng_Manual_S700_Modules
Index

A CM 772F 11
AC 722F 41, 71 Configuration
Active PROFIBUS termination unit AX 722F 183
PDR11 13 DC 705F 30
Adapter cable Dsub9-M12 to the bus master
PDA11 12 D
AI 723F 41, 83 DA 701F 41, 170
AI 731F 41, 91 DC 705F 12
Analog input module DC 722F 41, 127
AI 723F 41 DC 723F 41, 135
AI 731F 41 DC 732F 41, 143
Analog input/output module DI 724F 41, 151
AC 722F 41, 71 Diagnosis
AI 723F 83 AC 722F 82
AI 731F 91 AI 723F 90
AO 723F 99 AI 731F 98
AX 721F 41, 42 AO 723F 106
AX 722F 41, 59 AX 721F 57
Analog Inputs AX 722F 70
DA 701F 179 CD 722F 169
Analog output module DA 701F 183
AO 723F 41 DC 722F 134
Analog Outputs DC 723F 142
DA 701F 180 DC 732F 150
AO 723F 41, 99 DI 724F 157
AX 721F 41, 42 DX 722F 118
AX 721F Tab Module Data 42 DX 731F 126
AX 722F 41, 59 Digital Analog input/output module
DA 701F 170
C Digital input module
CD 722F 41, 158 DI 724F 41, 151
Clipboard viewer 15 DX 722F 107
CM 772 12 Digital input/output module

2PAA105800R0101_Eng_Manual_S700_Modules 185
Index

DC 722F 41, 127 AO 723F 102


DC 723F 41, 135 AX 722F 62
DC 732F 41, 143 Force and Substitute Value
DX 722F 41 AC 722F 74
DX 731F 41, 119 AI 723F 86
Digital/Analog input/output module CD 722F 161
DA 701F 41 DA 701F 177
DPV1 DC 722F 130
AC 722F 73 DC 723F 138
AI 723F 85 DC 732F 146
AI 731F 93 DI 724F 154
AO 723F 101 DX 722F 114
AX 722F 61 DX 731F 122
CD 722F 160 Force/Substitute
DA 701F 174 AX 721F 50
DC 722F 129 AX 722F 79, 104, 183
DC 723F 137 DC 705F 33
DC 732F 145 Frequency Input Module
DI 724F 153 CD 722F 41, 158
DX 722F 111
DX 731F 121 I
DPV1 Parameters I/O Editor
AX 721F 47 AC 722F 80
DC 705F 30 AI 723F 89
DX 722F 41, 107 AI 731F 97
DX 731F 41, 119 AO 723F 104
AX 721F 54
E AX 722F 68
Encoder Input 1 CD 722F 166
CD 722F 163 DA 701F 180
DC 722F 131
F DC 723F 139
FBP Interface Module DC 732F 147
DC 705F 12 DI 724F 155
FBP Interface Module DC 705F 26 DX 722F 116
Configuration 26 DX 731F 123
FieldBus Plug Import S700 Template 15
PDP22-FBP 12 Importing GSD file 13
Force and Substitute Info
AI 731F 94 AC 722F 79

2PAA105800R0101_Eng_Manual_S700_Modules 186
Index

AI 723F 88 AI 723F 88
AI 731F 97 Inputs 24VDI
AO 723F 104 CD 722F 165
AX 721F 54 Inputs 4-5
AX 722F 67 AI 731F 96
CD 722F 166 Inputs 6-7
DC 705F 36 AI 731F 96
DC 722F 131 IO Module
DC 723F 139 DC 705F 35
DC 732F 147 IO Parameters
DI 724F 155 DC 732F 147
DX 722F 115 DI 724F 155
DX 731F 123 DX 722F 115
Input DX 731F 123
AC 722F 80
AI 723F 89 M
AI 731F 97 Module Configuration
AX 721F 55 DC 722F 127
AX 722F 68 DC 723F 135
CD 722F 167 DC 732F 143
DA 701F 181 Module configuration
DC 722F 132
DC 723F 140 CD 722F 158
DC 732F 148 DX 722F 107
DI 724F 156 AC 722F 71
DX 722F 116 AI 723F 83
DX 731F 124 AI 731F 91
Inputs (Ch0_Ch3) Parameters AO 723F 99
AX 721F 42
AX 722F 64 AX 722F 59, 170, 171
Inputs (Ch0-Ch3) Parameters DA 701F 170
AC 722F 76 DC 705F 27
Inputs (Ch4-Ch7) Parameters DI 724F 151
AC 722F 77 DX 722F 107
AX 722F 65 DX 731F 119
Inputs 0-1 Module Parameters
AI 731F 96 AC 722F 75
Inputs 0-3 AI 723F 87
AX 721F 52 AI 731F 95
Inputs 0-4 AO 723F 103

2PAA105800R0101_Eng_Manual_S700_Modules 187
Stichwortverzeichnis

AX 721F 51 Profibus
AX 722F 63 master object 18
CD 722F 162 PROFIBUS Master
DA 701F 178 CM 772 12
DC 722F 131 PROFIBUS Module PROFI_M_772
DC 723F 139 Bus Parameter Tab 18
Master Configuration tab 22
O Memory Configuration Tab 21
Object data Object data 24
AX 721F 58 Online Information Tab 23
Output Parameterization 18
AC 722F 81 PROFIBUS Setup
AO 723F 105 Overview 12
AX 721F 56 Profibus setup
AX 722F 69 S700 IO Modules 11
CD 722F 168 PROFIBUS Slave
DA 701F 182 DC 705F 34
DC 722F 133 PROFIBUS Slave Interface 11, 26
DC 723F 141 PWM DO
DC 732F 149 CD 722F 164
DX 722F 117
DX 731F 125 S
Outputs S700 Template 14
CD 722F 166
Outputs (Ch0-Ch3) Parameters T
Tab Encoder Input 2
AX 722F 66 CD 722F 164
AC 722F 78 Tab Inputs 2-3
Outputs (Ch4-Ch7) Parameters AI 731F 96
AC 722F 79 Tab Inputs 4-7 88
AX 722F 67 Tab Inputs 8-11 88
Outputs 0-3 Tab Inputs12-15 88
AO 723F 104 Tab Outputs 12-15
AX 721F 53 AO 723F 104
Tab Outputs 4-7
P AO 723F 104
PDA11 12 Tab Outputs 8-11
PDP22-FBP 12 AO 723F 104
PDR11 13
Pre defined Template 14

188 2PAA105800R0101_Eng_Manual_S700_Modules
Index

U
User
AC 722F 72
AI 723F 84
AI 731F 92
AO 723F 100
AX 722F 60
CD 722F 159
DA 701F 172
DC 722F 128
DC 723F 136
DC 732F 144
DI 724F 152
DX 731F 120
User Parameters
AX 721F 43
DC 705F 28
User-defined Tabs 16

2PAA105800R0101_Eng_Manual_S700_Modules 189
Stichwortverzeichnis

190 2PAA105800R0101_Eng_Manual_S700_Modules
Printed in Germany April 2010
Copyright © 2010 ABB, All Rights Reserved
® Registered Trademark of ABB
™ Trademark of ABB

http://www.abb.com/control

Automation Technology Products Automation Technology Products Automation Technology Products


Wickliffe, Ohio, USA Västerås, Sweden Mannheim, Germany
www.abb.com/processautomation www.abb.com/processautomation www.abb.de/processautomation